Greenheck Fan SFD, SWB, SFB User Manual

0 (0)

Centrifugal Utility Fans

Model SFD, SFB and SWB

Direct and Belt Drive

November

2011

Greenheck Fan SFD, SWB, SFB User Manual

Models SFD, SFB and SWB

Utility Fans

Contents

 

 

 

Standard Construction Features.......................

4-5

Discharge Position and Dimensional Data...

12-13

Severe Duty Options............................................

6

Fan Identification/Model Selection....................

14

Temperature Options..........................................

7

SFD Performance and Dimensions..................

15

Options and Accessories................................

8-9

SFB Performance and Dimensions............

16-25

Engineering Data...............................................

10

SWB Performance and Dimensions...........

26-61

Typical Installations...........................................

11

Typical Specifications.................................

62-63

 

 

 

 

Greenheck Fan Corporation certifies that the model SFD, SFB and SWB, fans shown herein are licensed to bear the AMCA Seal. The ratings shown are based on tests and procedures performed in accordance with AMCA Publication 211 and comply with the requirements of the AMCA Certified Ratings Program. The certified ratings for Model SFD, SFB and SWB are shown on pages 15-61.

SFD, SFB and SWB Series 100, 200 and 300 models are listed for electrical (UL/cUL 705)

File no. E40001

SWB Series 200 and 300 models are listed for grease removal (UL/cUL 762) File no. MH11745

SWB Series 200 and 300 models are listed for Emergency Smoke Control Systems File No. MH17511

Greenheck Fan Corporation certifies that the model SWB Series 300 AF, fans shown herein are licensed to bear the AMCA Seal. The ratings shown are based on tests and procedures performed in accordance with AMCA Publication 211 and AMCA Publication 311 and comply with the requirements of the AMCA Certified Ratings Program. The certified ratings for Model SWB Series 300 AF are shown on pages 49-61.

High Wind Certification

Seismic Certification

Miami-DADE Notice of Acceptance (NOA)

OSHPD - Office of Statewide Health Planning

09-0303.31 for high wind and hurricane zones

and Development - OSP-0113-10

Florida Product Approval Number - FL12680

IBC 2006 and 2009 - International Building Code

2

Models SFD, SFB and SWB

Utility Fans

Model Comparison

 

Location

 

Mounting

 

 

Airflow

 

 

 

Application

 

 

Drive

Impeller

Performance

 

 

 

 

 

 

 

 

 

 

Type

 

Type

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CostRelative

Model

Outdoor

Indoor

CurbRoof

Base/Floor

Hanging

Wall

MountedCeiling

Exhaust

Supply

Reversible

Recirculate

General/CleanAir

ContaminatedAir

ResistantSpark

762)(ULGrease

ControlSmoke(UL)

(150WindHighmph)

(aboveTempHigh200°F )

Belt

Direct

Centrifugal

Propeller/Axial

 

FlowMixed

VolumeMaximum (cfm)

StaticMaximumPressure wg)(in.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SFD

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2,600

2.5

$

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SFB

 

 

 

 

 

 

 

 

 

 

 

 

 

 

25,200

3.5

$$

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SWB

 

 

 

 

 

 

 

 

 

 

54,000

5

$$

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Models SFD and SFB

Greenheck models SFD and SFB forward-curved utility fans have been designed for supply, exhaust and return

air applications requiring low to medium air volumes and pressures. You will receive the following benefits with these fans:

SFD fans are available in four sizes (6, 7.5, 9 and 10) with different rpm motors. Capacities range from 300 to 2,600 cfm (510 to 4,600 m3/hr) with static pressures to 2.5 in. wg (623 Pa).

SFB fans are available in ten sizes (9 through 30) with capacities ranging from 360 to 25,200 cfm (610 to 42,800 m3/hr) and static pressures to

3.5 in. wg (872 Pa).

Greenheck utility fans are designed, engineered and tested prior to shipment to provide years of smooth, vibration-free operation with minimal maintenance.

The fan may be mounted indoors or outdoors.

All fan sizes are tested in our AMCA accredited laboratory to ensure complete and accurate performance ratings. All models are licensed to bear the AMCA Air Performance seal. Performance as cataloged is assured.

Model SWB

Greenheck’s backwardinclined utility fans have many advantages; higher operating efficiencies, non-overloading horsepower curves

and higher pressure capabilities. You will also receive

the following benefits with these fans:

SWB Series 100 in ten sizes (106 through 124) with capacities from 70 to 11,000 cfm

(120 to 18,700 m3/hr) and static pressures to

3.0in. wg (747 Pa).

SWB Series 200 in twelve sizes (206 through 224) with capacities from 70 to 13,700 cfm

(120 to 23,300 m3/hr) and static pressures to

5.0in. wg (1250 Pa).

SWB Series 300 in seven sizes (327 through 349) with capacities from 4,600 to 54,000 cfm

(7,700 to 91,700 m3/hr) and static pressures to

5.0in. wg (1250 Pa).

Three different series of construction will meet your exact needs in the most efficient manner.

Greenheck utility fans are designed, engineered and tested prior to shipment to provide years of smooth, vibration-free operation with minimal maintenance.

Fans are tested in our AMCA accredited laboratory to ensure complete and accurate performance ratings. All models are licensed to bear the AMCA Air Performance seal. SWB 300 Series AF fans are licensed to bear the AMCA Sound and Air Performance seal. Performance as cataloged is assured.

3

Standard Construction Features

Standard Construction Features

1

Wheel

SFD and SFB fans have forward-curved centrifugal wheels constructed of

 

 

die formed steel with blades securely riveted to a steel backplate and rim.

 

 

Each wheel is statically and dynamically balanced to precise tolerances.

 

 

SWB Series 100 and 200 through size 210 have backward-inclined non-

 

 

overloading centrifugal wheels constructed of aluminum. Series 200, sizes

 

 

212 and larger and Series 300 wheels are constructed of steel or aluminum.

 

 

Backward-inclined wheels are made of a heavy-gauge material with single-

 

 

thickness blades securely riveted or welded to a heavy-gauge backplate

 

 

and wheel cone. SWB Series 300 fans are available with aluminum airfoil

 

 

wheels. Each wheel is statically and dynamically balanced to precise

 

 

tolerances.

2

Finish

All structural steel parts are phosphate treated and coated with

 

 

Greenheck’s Permatector™ for a long lasting finish. Galvanized

 

 

construction remains unpainted.

 

 

See housing and drive frame information for specific material and coating.

3

Housing

SFD and SWB Series 100 housings are constructed of galvanized steel.

 

 

SFB and SWB Series 200 and 300 housings are constructed of steel

 

 

and coated with Permatector™. Both are available in clockwise or

 

 

counterclockwise rotation and are field rotatable to the eight standard

 

 

discharge positions. Housing sides are bonded to the fan scroll with an

 

 

airtight lock seam. Fully welded scrolls are available on SFB and SWB

 

 

Series 200 and 300 models.

4

Housing

Housing supports are constructed of heavy gauge-steel with formed

 

Supports

flanges for extra strength.

5

Mounting

Base rails have prepunched mounting holes which allow for easy

 

Holes

installation.

6

Drive

Series 100 and 200 drive frames are constructed of rugged, welded

 

Frame

and coated steel members (Series 300 drive frames are constructed of

 

 

reinforced heavy gauge galvanized steel) supporting the shaft and bearings

 

 

to provide rigid reinforcement for the housing. SFD drive frames are

 

 

constructed of galvanized steel, bolted and available in arrangement 4.

 

 

SFB and SWB are arrangement 10.

7

Fasteners

Corrosion-resistant fasteners are used to secure unit base and blower

 

 

scroll assembly.

8

Motor

Heavy-duty ball bearing motors are carefully matched to the fan load. Open

 

 

drip proof, totally enclosed and explosion resistant enclosures are available.

9

Inlet Cone

Streamlined inlet cone design provides for low turbulence air intake,

 

 

reducing intake losses and sound levels.

 

 

 

Belt Drive Only Features

SFD SFB

 

SWB

 

 

 

 

100

200

300

Forward Curved

Forward Curved

Backward Inclined

Backward Inclined

Backward Inclined or Airfoil

— — — —

Galvanized

Painted Steel

Galvanized

Painted Steel or Aluminum

Painted Steel

Galvanized

Painted Steel

Painted Steel

Painted Steel

Galvanized

10

Motor

A pivoting motor plate with adjusting screws make belt tensioning a quick

 

 

Plate

and easy operation.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

11

Drive

Machined, cast iron pulleys are factory set to the required RPM and are

 

 

Assembly

adjustable for final system balancing for applications with 10 hp or less

 

 

 

motors. Sized for a minimum of 150% of driven horsepower.

 

 

 

 

 

12

Fan Shaft

Precision turned, ground and polished solid steel shafts are sized so the

 

 

 

first critical speed is at least 25% over the maximum operating speed.

 

 

 

Stainless steel shafts are available on SWB Series 200 and 300 fans.

 

 

 

 

 

 

 

 

 

 

 

 

 

13

Bearings

Heavy-duty, self-aligning pillow block ball bearings are selected for a

 

 

 

minimum L10 life in excess of 100,000 hours (L50 average life of 500,000

 

 

 

hours) at maximum cataloged operating conditions.

 

 

 

 

 

4

Standard Construction Features

 

 

2

 

 

7

3

1

3

 

 

 

13

12

8

 

 

 

 

 

13

11

8

4

 

 

5

10

6

SFD

5

SFB and SWB 200 Series

 

 

3

 

 

3

 

 

7

7

 

2

 

 

 

2

13

 

 

12 11

11 13 12

6

8

4

4

 

 

8

10 6

10

5

5

 

SWB 100 Series SWB 300 Series

5

Severe Duty Options

High Wind and Hurricane

Greenheck is leading the high wind standard for roof top fans and ventilators. Forceful winds and windborne debris are

the cause of most hurricane damage. Hurricane winds start at 75 mph. At speeds over 150 mph, wind can exert a force of 75 pounds per square foot of pressure or over 900 pounds on a fan. Forceful winds are not the only problem, wind-borne debris can also cause detrimental effects to objects and structures. High winds and extreme forces are the cause of most storm damage. By analyzing calculations, computer simulations and actual testing—Greenheck developed the High Wind Standard.

Protocols designed to protect against wind borne debris and severe wind loads:

Greenheck worked with Miami-Dade County to outline a high velocity hurricane zone standard for rooftop fans. The SFD, SFB and SWB Series 100 and 200 have

Miami-Dade been certified by an independent third County Test party to the ASTM E-330 Static Pressure

Protocols Difference Standard, Florida Building Code Test Protocol TAS-201 (large missile

impact), 202 (static pressure difference) and 203 (cyclic pressure) Static Pressure Difference. NOA #09-0303.31

 

Florida Product Approval ensures that

 

products which have been approved can

Florida

be used anywhere in the State of Florida

which are not governed by the Miami-

Product

Dade County high wind regulations. More

Approval

information can be found on the Florida

 

 

Building Code website. Florida Product

 

Approval FL12680

 

 

 

 

Seismic

Protocols designed for seismic standards:

 

 

 

 

 

All Greenheck seismically certified models

 

With changes in

 

have been tested using the most severe

 

building codes

 

seismic event that is found on the Spectral

 

 

Response Map per IBC Figures 1613.5

 

and standards,

 

 

Seismic

(1-2). Because our testing is performed

 

more equipment

under the worst case scenario, using the

 

Testing

 

is required to

highest mapped seismic load, highest level

 

Criteria

 

be seismically

occupancy category, worst case site class,

 

 

 

certified in areas

 

and highest code mandated importance

 

 

factor, this allows Greenheck seismically

 

of the country not

 

 

 

certified fans to be used anywhere in the

 

commonly thought of

 

United States under any conditions.

 

as being in seismically active zones.

 

 

 

 

The California Office of Statewide Health

 

 

 

 

The International Building Code (IBC) is designed

 

Planning and Development (OSHPD)

 

to provide model code regulations that safeguard

 

requires all certified models be shake table

 

public health and safety in all U.S. communities.

 

tested in accordance with ICC ES AC-156,

 

California

in which the fans are physically subjected

 

The IBC 2009 is the latest version adopted on state

 

to the same or greater forces than they

 

or local levels. With this code, the standards are

OSHPD Test

will see during a seismic event. Subjecting

 

Protocols

 

intended to improve the performance and design of

Greenheck models SWB, SFD and SFB fans

 

 

 

non-structural systems subject to seismic events.

 

to this type of testing ensures the fans will

 

 

operate without problems after a seismic

 

The State of California, one of the most active

 

 

 

event. (OSP-0113-10 - SWB Series 100 and

 

seismic areas in the United States, has the Office

 

200 SFB, SFD)

 

of Statewide Health Planning and Development

 

 

 

 

All Greenheck seismically certified fan

 

(OSHPD). OSHPD regulates the design and

 

 

 

models have gone through extensive

 

construction of healthcare facilities to ensure they

Certified

testing procedures. Greenheck models

 

are safe and capable of providing services to the

SWB, SFD and SFB have been certified to

 

Independent

 

IBC 2006, 2009, ASCE 7-05 and California

 

public after a seismic event. OSHPD developed

Third-Party

 

OSHPD standards through both engineering

 

their own unique certification process to incorporate

Testing

 

calculations and shake table testing by

 

the IBC and ASCE testing standards to ensure

 

independent third party engineering firms.

 

equipment remains operable after a seismic event.

 

(SWB Series 100 and 200, SFB and SFD)

 

 

 

 

 

6

Temperature Options

Testing

High temperature testing was conducted at Greenheck’s Research and Development facility with airstream temperatures in excess of 1000°F (538°C). Temperatures were monitored at the following critical locations throughout the tests: bearings, bearing compartment, motor, motor compartment, airstream and fan housing.

Operating Temperatures

Utility set fans are suitable for applications with elevated temperature airstreams. Refer to the chart at the right for operation temperature guidelines and optional accessories.

High Temperature/Emergency Smoke Control

The SWB Series 200 sizes 212 to 224 and Series 300 may be equipped for emergency smoke removal applications by specifying a high temperature option. The table below right indicates the construction features included in the high temperature options enabling exhaust of heat and smoke at 500°F (260°C) for a minimum of 4 hours or 1000°F (538°C) for a minimum of 15 minutes.

High Temperature Option SWB Series 200 & 300

500°F (260°C) for a minimum of 4 hours

1000°F (538°C) for a minimum of 15 minutes

Temperature ratings tested in accordance to UL smoke control systems.

Emergency Smoke Control - UL Listed SWB Series 200 & 300

500°F (260°C) for a minimum of 4 hours

1000°F (538°C) for a minimum of 15 minutes

Testing for Emergency Smoke Temperature and Time Guidelines

Code

 

Class

 

 

Tested Temperature

 

 

Time

 

 

 

 

 

 

(Hours)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

IRI

 

 

 

 

 

500°F

(260°C)

 

 

4.00

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SBCCI

 

 

 

 

 

1000°F (538°C)

 

 

0.25

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

BSI

 

Class A

 

 

302°F (150°C)

 

 

5.00

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Class B

 

 

482°F (250°C)

 

 

2.00

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Class C

 

 

572°F (300°C)

 

 

0.50

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Class D

 

 

572°F (300°C)

 

 

1.00

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Class E

 

 

752°F (400°C)

 

 

2.00

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SWB

SWB

 

SWB

 

 

 

Operating

 

Series

Series

 

Series

SFD, SFB

Temperatures

 

100

 

200

 

300

 

 

 

and Construction

Galvanized

Painted

Aluminum

 

Steel

SFD

 

SFB

 

 

 

 

 

 

 

 

 

 

 

Steel

Airstream

 

 

 

 

 

 

-20° to 200°F

 

 

 

 

 

(-29° to 93°C)

 

 

 

 

 

Standard

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

201° to 300°F

 

 

 

 

 

 

 

(94° to 149°C)

 

 

 

 

 

 

 

Heat Slinger/Shaft Seal

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

301° to 400°F

 

 

 

 

 

 

 

 

 

 

(149° to 204°C)

 

 

 

 

 

 

 

 

 

 

Heat Slinger/Shaft Seal

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

The maximum continuous operating temperature on the SWB is 400°F. For continuous operating temperatures between 401° and 1000°F use an Arrangement 1, 9 or 10, backward-inclined centrifugal fan model BISW.

High Temperature SWB Features

High

High

Temperature

Temperature

Series 200 & 300

Option

Option with UL

 

 

 

 

Steel Construction

 

 

 

Shaft Seal

 

 

 

Heat Slinger

 

 

 

Weatherhood

 

 

 

 

UL Label (Power ventilators for smoke

 

control systems)

 

 

 

 

Spark-Resistant Construction Options

The following AMCA Standards apply to fan applications that may involve the handling of potentially explosive or flammable particles, fumes or vapors.

AMCA Type A - All parts in contact with the airstream are constructed of nonferrous material (aluminum). Model SWB does not meet AMCA Type A spark resistant construction because the fan shaft is steel.

AMCA Type B - The fan wheel is constructed of nonferrous material (aluminum). A nonferrous

(aluminum) rub ring surrounds the fan shaft where

it passes through the fan housing. Available on all SWB sizes with an aluminum wheel and rub ring.

AMCA Type C - The inlet cone is constructed of nonferrous material (aluminum). A nonferrous

(aluminum) rub ring surrounds the fan shaft where it passes through the fan housing.

The constructions listed minimize the potential of ferrous components making contact with each other that may produce sparks. However, they do not guarantee against the potential of producing sparks. The installer must electrically ground all fan and system components.

7

Options and Accessories

UL/cUL 762 - SWB Series 200 and 300 models are listed for grease removal (UL/cUL 762). The UL/cUL 762 option includes a weatherhood, threaded drain connection and access door. Indoor mounting requires the fan to have welded scroll construction.

Weatherhood - Available to completely cover the motor and drive compartments; protecting the shaft, bearings, motor and drive components from moisture and other adverse weather conditions. Weatherhoods are vented to provide sufficient motor cooling, designed to meet OSHA guidelines and are easily removed for service access. Series 300 includes an access door.

Drain Connection - Threaded drain connections can be provided to drain moisture from the bottom of the fan housing.

Grease Trap (SWB Only) - Aluminum trap is designed to collect grease residue and avoid drainage onto roof surface. Disposable grease absorbents are available for easy maintenance.

Access Doors - Access doors provide access for inspection and cleaning. Either bolted or hinged, quick opening access doors are available on all models except SFD. (Series 100—bolted option only)

Welded Scroll Construction - Welded scroll construction is available on SWB Series 200 and 300.

Aluminum Construction - Aluminum airstream option is available on SWB Series 200.

Dampers - Gravity or motorized parallel blade backdraft dampers feature sturdy galvanized frames with prepunched mounting holes, aluminum blades with felt edges and balanced design for minimal resistance to airflow. Backdraft dampers are not suitable for downblast or bottom

angular downblast discharge positions. The fan must be supplied with a flanged outlet to install a backdraft damper directly to the fan. Heavy-duty dampers are available for high pressure applications on fans with motors equal to or greater than 712 horsepower.

Disconnect Switches - A wide selection of NEMA rated switches are available

for positive electrical shutoff and safety, including: dust-tight, rainproof and corrosion-resistant.

Wiring Pigtail - Allows direct hookup to the power supply eliminating field wiring to the fan.

Extended Lube Lines - Lubrication lines with grease fittings are extended from shaft bearings to the base of the drive frame panel or weatherhood for easy bearing lubrication.

8

Inlet and Outlet Guards - Constructed of expanded metal mounted in a steel frame to provide protection for non-ducted installations. The guards can be easily

removed for fan maintenance or inspection.

Flanged Inlet and Outlet - Flanges are available for damper mounting or flanged duct connections. Inlet flanges have prepunched mounting holes. Outlet flanges are bolted on standard; welded for UL 762 applications

Companion Flange - Connects to the inlet flange and then attaches to the ductwork. Recommended for slip-fit duct connections.

Inlet Vane Dampers (SWB only) - External inlet vane dampers are available on model SWB fans, sizes 112– 124 and 212–224. External vanes are mounted on the inlet flange. Inlet vane dampers feature

zinc-plated steel blade axles, stainless steel washers and bearings. Vanes can be used for either manual or automatic operation, with controls furnished

by others. Maximum operating temperature is 200°F (93°C).

Coatings - A wide variety of coatings and

colors are available for decorative to acidic applications on SFB and SWB Series 200 and 300. All Greenheck coatings can be found in the Performance Coatings for Commercial and Industrial Fans publication.

Permatector™ is our standard coating. Typically used for applications that require corrosion resistance in indoor and outdoor environments.

Hi-Pro™ Polyester is resistant to salt water, chemical fumes and moisture in more corrosive atmospheres. Typically used for applications requiring superior chemical resistance, excellent abrasion and outdoor UV protection. This coating exceeds protective qualities of Air Dried Heresite and Air Dry Phenolic.

Baked Enamel Decorative Coatings are heat cured enamels applied as electrostatic powders. Customers can choose from 16 standard decorative colors or color match any color.

Heat Slinger and Shaft Seal (all belt models) - Heat slinger is an aluminum cooling disc mounted on

the fan shaft between the inboard bearing and the fan housing. The disc dissipates heat conducted along the fan shaft.

The shaft seal with an aluminum rub ring is available for applications where

contaminated or high temperature air is being handled.

Mounting Options

Vibration Isolators

Base-mounted neoprene or spring isolators are available to lessen mechanical vibration and assure quiet operation. Free-standing, restrained and housed spring isolators are also available. Isolators are sized to match the weight of each fan.

Free-Standing Open Spring Mounts -

Type 3, 1-inch Deflection

Free-standing spring isolators are unhoused laterally stable steel springs. They provide a minimum horizontal stiffness of 0.8 times the rated vertical

stiffness and provide an additional 50% overload capacity. These isolators are equipped with a top-mounted adjusting bolt and an acoustical non-skid base. Springs are color coded to indicate load capacity.

Housed Spring Mounts

Type 4B, 1-inch Deflection

Housed spring isolators consist of steel springs assembled into a telescoping housing with a top-mounted adjusting bolt and an acoustical non-skid base. Housed spring isolators

include resilient inserts to prevent metal-to-metal contact and provide snubbing for side loads. Springs provide an additional 50% overload capacity and are color coded to indicate load capacity.

Rubber Mounts -

Type 2, ¼-inch and

½-inch Deflection

Neoprene mountings consist of a steel top plate and base plate completely embedded in colored (oilresistant) neoprene for easy

identification of capacity. Neoprene mountings are furnished with a tapped hole in the center. This enables the equipment to be bolted securely to the rubber mount.

Restrained Spring Mounts -

Type 4A, 1-inch Deflection

Restrained spring isolators consist of laterally stable, free-standing springs assembled into a steel housing. These assemblies

are designed for vertical and horizontal motion restraint. Restrained spring isolators can be used for blocking during equipment installation and are provided with leveling bolts. Springs provide 50%

overload capacity and are color coded or identified to indicate load capacity. Restrained spring mounts are recommended for equipment subject to wind loading or large torquing forces.

Direct Mount - Type A

No base required. Isolators are attached directly to equipment. Direct isolation can be used if equipment is unitary and rigid without the use of additional support. If there is

any doubt whether or not equipment can be

supported directly on isolators,

use rails, bases or consult the factory.

Equipment Supports

Models GESS and GESR equipment supports are available for roof mounting of utility fans up to size 36. Equipment supports are available in a number of lengths, widths, heights,

and can also be built for a pitched roof.

Mounting Rails with Isolators

Isolation mounting rails are available with either rubber mount, free-standing open or restrained spring

isolators. The isolators are mounted between aluminum rails that run the length of the

fan base. Isolation rails provide easy installation on isolated systems,

and are ideal for applications where

there is a large overhung load. Mounting rails are available for fans up to size 36.

9

Engineering Data

Selection

The first consideration in any fan selection is the amount of air to be moved and the resistance to this air movement. Air volume requirements are established through specific codes or accepted industry standards. Once the air volume is known, system resistance can be determined by summing up the losses through the system components. Duct layout, duct size, coils, filters, dampers, and fan accessories all affect system resistance. ASHRAE Guide and Data Books and manufacturer’s data on individual system components are

common sources of information available to the system designer.

In most applications, several fans may meet the required airflow and system resistance conditions. An optimum fan selection requires evaluation of alternative fan types and fan sizes, as they relate

to initial cost, operating cost, available space, and allowable sound levels. The relative importance of these facts varies with each system.

Two types of wheels are available:

1.Backward-inclined or airfoil wheels turn at twice the speed of forwardcurved fans and feature:

Higher operating efficiencies

A non-overloading horsepower curve which reaches a peak near the middle of the normal operation range

Stronger wheel design allowing for operation at higher static pressures

2.Forward-curved wheels typically have lower performance capabilities compared to the backward inclined and contain:

Overloading type wheel (meaning that changes in performance can result in significant brake horsepower changes)

Forward-curved wheels have lower sound levels

Comprehensive air performance data for these utility fans can be found in the fan tables and fan curves section, starting on page 15.

10

Effects of Installation on Performance

Fan ratings presented in the performance tables and curves of this catalog are in accordance with AMCA Standard 210 “Laboratory Methods of Testing Fans for Aerodynamic

Performance Rating.” The AMCA test procedure utilizes an open inlet and a straight outlet duct to assure maximum static regain.

Any installation with inlet or discharge configurations that deviate from this standard may result in reduced fan performance. Restricted or unstable flow at the fan inlet can cause pre rotation of incoming air or uneven loading of the fan wheel yielding large system losses and increased sound levels. Free discharge or turbulent flow in the discharge ductwork will also result in system effect losses.

The examples below show system layouts and inlet and discharge configurations which can affect fan performance.

 

 

7o MAX.

POOR

FAIR

GOOD

POOR

POOR

FAIR

 

Turning

One

 

Impeller

 

Varies

 

Dia.

 

 

 

 

Should be at least

 

 

1/2 Impeller Dia.

POOR

FAIR

GOOD

POOR

FAIR

GOOD

 

 

Not Greater than

 

 

60o Including Angle

POOR

POOR

FAIR

Typical Installations

General Clean Air or Fume Hood (Non–Grease)

The SFD, SFB and SWB are designed for applications ranging from clean air to contaminated air. Typical installations are shown below. Installations must include a means for inspecting, cleaning and servicing the exhaust fan.

Flex

Flex

3 Wheel

Diameters

SWB, Commercial Kitchen (Grease)

Greenheck’s SWB Series 200 and 300 are designed to meet restaurant and foodservice applications. These fans are UL and cUL Listed for grease removal and have been tested under elevated temperature conditions.

Due to high temperatures and grease-laden airstreams in commercial kitchen ventilation, system designers must be aware of governing codes and guidelines. The National Fire Protection Association (NFPA) is the primary source used by many local codes for commercial kitchen ventilation systems. Local code authorities should be consulted before proceeding with any kitchen ventilation project.

Upblast Discharge

Optional

Companion

Flange

**40 in.

Weatherhood

(1016 mm)

3 Wheel

 

Diameters

Installation must include a means for inspecting, cleaning and servicing the exhaust fan.

Fans selected for grease removal must include a weatherhood, access door and 1 inch (25 mm) drain connection. For grease applications where the fan is mounted indoors, the welded scroll option must be selected. An outlet guard is strongly recommended when the fan discharge is accessible. When an outlet guard is not ordered with the fan, it must be provided by the installer. An upblast discharge is recommended. No dampers are to be used in

the system.

The fan discharge must be a minimum of 40 inches (1016 mm) above the roof line and the exhaust

duct must be fully welded to a minimum distance of 18 inches (457 mm) above the roof surface.

SWB Series 200 and 300 models are listed for grease removal (UL/cUL 762).

File no. MH11745

*18 in.

(457 mm)

**Per NFPA 96 the fan discharge must be a minumum distance of 40 in. (1016 mm) above the roof surface.

Duct

From *Per NFPA 96 the duct must Kitchen be all welded construction Hood to a minumum distance of

18 in. (457 mm) above the roof surface.

11

SFD and SFB Discharge

Positions and Dimensional Data

CW BAU

CCW BAU

B

C

C

B

D

 

 

D

A

 

 

A

H

 

 

H

CW UB

CCW UB

I

G

G

I

J

 

 

J

H

 

 

H

CW TAU

CCW TAU

E

D

D

E

 

A

A

 

B

 

 

B

H

 

 

H

CW TH

CCW TH

F

J

J

F

I

 

 

I

H

 

 

H

CW TAD

CCW TAD

C

B

B

C

E

 

 

E

 

 

A

 

H

 

 

H

CW DB

CCW DB

G

I

I

G

SFD Dimensions

Unit Size

A

B

C

D

E

F

G

H

I

J

SFD-6

1116

8716

5916

434

612

6116

5316

9

7

514

(27)

(214)

(141)

(121)

(165)

(154)

(132)

(230)

(178)

(133)

 

 

 

 

 

 

 

 

 

 

 

 

SFD-7.5

114

1014

61316

51316

734

714

614

923

812

634

(32)

(260)

(173)

(148)

(197)

(184)

(159)

(245)

(216)

(171)

 

 

 

 

 

 

 

 

 

 

 

 

SFD-9

1516

111316

734

612

81516

8516

7316

1079

912

712

(33)

(300)

(197)

(165)

(227)

(211)

(183)

(274)

(241)

(191)

 

 

 

 

 

 

 

 

 

 

 

 

SFD-10

11516

14

914

71316

1034

10116

812

1234

1112

812

(49)

(356)

(235)

(198)

(273)

(256)

(216)

(324)

(292)

(216)

 

 

 

 

 

 

 

 

 

 

 

 

All dimensions in inches (millimeters).

SFB Dimensions

Unit Size

A

B

C

D

E

F

G

H

I

J

SFB-9

138

121116

814

7

912

81516

758

1345

1014

8

(35)

(322)

(210)

(178)

(241)

(227)

(194)

(350)

(260)

(203)

 

 

 

 

 

 

 

 

 

 

 

 

SFB-10

1716

1412

9516

71316

1034

10116

8916

1516

1112

914

(37)

(368)

(237)

(198)

(273)

(256)

(217)

(385)

(292)

(235)

 

 

 

 

 

 

 

 

 

 

 

 

SFB-12

214

16

101116

9116

1238

11916

978

1516

1314

934

(57)

(406)

(271)

(230)

(314)

(294)

(251)

(385)

(337)

(248)

 

 

 

 

 

 

 

 

 

 

 

 

SFB-15

21116

17916

111316

91516

131116

121116

1078

1634

1458

1058

(68)

(446)

(300)

(252)

(348)

(322)

(276)

(426)

(371)

(270)

 

 

 

 

 

 

 

 

 

 

 

 

SFB-18

4116

2338

151316

1314

18516

1718

1458

2213

1958

1334

(103)

(594)

(402)

(337)

(465)

(435)

(371)

(567)

(498)

(349)

 

 

 

 

 

 

 

 

 

 

 

 

SFB-20

4916

2512

1714

1412

20116

1834

16116

2449

2112

1478

(116)

(648)

(438)

(368)

(510)

(476)

(408)

(621)

(546)

(378)

 

 

 

 

 

 

 

 

 

 

 

 

SFB-22

5516

28

19116

16

2218

2034

171116

2849

2334

16

(135)

(711)

(484)

(406)

(562)

(527)

(449)

(723)

(603)

(406)

 

 

 

 

 

 

 

 

 

 

 

 

SFB-25

6116

301116

21116

1734

24716

2278

19916

3135

2614

1712

(154)

(779)

(535)

(451)

(621)

(581)

(497)

(803)

(667)

(445)

 

 

 

 

 

 

 

 

 

 

 

 

SFB-27

5

34

22

19

2612

2412

2078

33

2834

1878

(127)

(864)

(559)

(483)

(673)

(622)

(530)

(838)

(730)

(479)

 

 

 

 

 

 

 

 

 

 

 

 

SFB-30

658

3818

25

2118

29

2714

2314

3635

3158

21

(168)

(968)

(635)

(537)

(737)

(692)

(591)

(930)

(803)

(533)

 

 

 

 

 

 

 

 

 

 

 

 

All dimensions in inches (millimeters).

F

 

 

F

H

 

 

H

CW BAD

CCW BAD

D

E

E

D

C

 

 

C

H

 

 

H

 

A

A

 

CW BH

CCW BH

J

F

F

J

G

 

 

G

H

 

 

H

Images are viewed from the drive side of fan.

12

SWB Discharge

Positions and Dimensional Data

CW BAU

CCW BAU

B

C

C

B

D

 

 

D

A

 

 

A

H

 

 

H

CW UB

CCW UB

I

G

G

I

J

 

 

J

H

 

 

H

CW TAU

CCW TAU

E

D

D

E

 

A

A

 

B

 

 

B

H

 

 

H

CW TH

CCW TH

F

J

J

F

I

 

 

I

H

 

 

H

CW TAD

CCW TAD

C

B

B

C

E

 

 

E

 

 

A

 

H

 

 

H

CW DB

CCW DB

G

I

I

G

F

 

 

F

H

 

 

H

CW BAD

CCW BAD

D

E

E

D

C

 

 

C

H

 

 

H

 

A

A

 

CW BH

CCW BH

J

F

F

J

G

 

 

G

H

 

 

H

Images are viewed from the drive side of fan.

SWB Dimensions

Size

A

B

C

D

E

F

G

H

I

J

106

11516

1418

914

71316

1034

1018

858

1518

1112

858

(49)

(359)

(235)

(198)

(273)

(257)

(219)

(384)

(292)

(219)

 

 

 

 

 

 

 

 

 

 

 

 

107

11516

1418

91/4

71316

1034

1018

858

1518

1112

858

(49)

(359)

(235)

(198)

(273)

(257)

(219)

(384)

(292)

(219)

 

 

 

 

 

 

 

 

 

 

 

 

108

11516

1418

914

71316

1034

1018

858

1518

1112

858

(49)

(359)

(235)

(198)

(273)

(257)

(219)

(384)

(292)

(219)

 

 

 

 

 

 

 

 

 

 

 

 

110

11516

1418

914

71316

1034

1018

858

1518

1112

858

(49)

(359)

(235)

(198)

(273)

(257)

(219)

(384)

(292)

(219)

 

 

 

 

 

 

 

 

 

 

 

 

113

21116

1758

1134

978

1358

1234

1078

1658

1458

1058

(68)

(448)

(298)

(251)

(346)

(324)

(276)

(422)

(371)

(270)

 

 

 

 

 

 

 

 

 

 

 

 

115

318

1912

13116

11

1518

1418

1218

1812

1614

1158

(79)

(495)

(332)

(279)

(384)

(359)

(308)

(470)

(413)

(295)

 

 

 

 

 

 

 

 

 

 

 

 

116

312

2114

14515

12

16916

1512

1314

2038

1734

1212

(89)

(540)

(364)

(305)

(406)

(394)

(337)

(518)

(451)

(318)

 

 

 

 

 

 

 

 

 

 

 

 

118

4116

2338

151316

1314

18516

1718

1458

2238

1958

1334

(103)

(594)

(402)

(337)

(465)

(435)

(371)

(568)

(498)

(349)

 

 

 

 

 

 

 

 

 

 

 

 

120

4916

2512

1714

1412

20116

1834

1618

2412

2112

1478

(116)

(648)

(438)

(368)

(510)

(476)

(410)

(622)

(546)

(378)

 

 

 

 

 

 

 

 

 

 

 

 

124

51316

301516

21116

1734

24716

2278

19916

3112

2614

1734

(402)

(786)

(535)

(451)

(621)

(581)

(497)

(800)

(667)

(451)

 

 

 

 

 

 

 

 

 

 

 

 

206

11516

1418

914

71316

1034

1018

858

1518

1112

858

(49)

(359)

(235)

(198)

(273)

(257)

(219)

(384)

(292)

(219)

 

 

 

 

 

 

 

 

 

 

 

 

207

11516

1418

914

71316

1034

1018

858

1518

1112

858

(49)

(359)

(235)

(198)

(273)

(257)

(219)

(384)

(292)

(219)

 

 

 

 

 

 

 

 

 

 

 

 

208

11516

1418

914

71316

1034

1018

858

1518

1112

858

(49)

(359)

(235)

(198)

(273)

(257)

(219)

(384)

(292)

(219)

 

 

 

 

 

 

 

 

 

 

 

 

210

11516

1418

914

71316

1034

1018

858

1518

1112

858

(49)

(359)

(235)

(198)

(273)

(257)

(219)

(384)

(292)

(219)

 

 

 

 

 

 

 

 

 

 

 

 

212

2516

1618

101116

9

1238

1158

91516

1518

1314

934

(59)

(410)

(271)

(229)

(314)

(295)

(252)

(384)

(337)

(248)

 

 

 

 

 

 

 

 

 

 

 

 

213

21116

1758

1134

978

1358

1234

1078

1658

1458

1058

(68)

(448)

(298)

(251)

(346)

(324)

(276)

(422)

(371)

(270)

 

 

 

 

 

 

 

 

 

 

 

 

215

318

1912

13116

11

1518

1418

1218

1812

1614

1158

(79)

(495)

(332)

(279)

(384)

(359)

(308)

(470)

(413)

(295)

 

 

 

 

 

 

 

 

 

 

 

 

216

312

2114

14515

12

16916

1512

1314

2038

1734

1212

(89)

(540)

(364)

(305)

(406)

(394)

(337)

(518)

(451)

(318)

 

 

 

 

 

 

 

 

 

 

 

 

218

4116

2338

151316

1314

18516

1718

1458

2238

1958

1334

(103)

(594)

(402)

(337)

(465)

(435)

(371)

(568)

(498)

(349)

 

 

 

 

 

 

 

 

 

 

 

 

220

4916

2512

1714

1412

20116

1834

1618

2412

2112

1478

(116)

(648)

(438)

(368)

(510)

(476)

(410)

(622)

(546)

(378)

 

 

 

 

 

 

 

 

 

 

 

 

222

5316

28116

19116

16

2218

2058

171116

2834

2334

1614

(132)

(713)

(484)

(406)

(562)

(524)

(449)

(730)

(603)

(413)

 

 

 

 

 

 

 

 

 

 

 

 

224

51316

301516

21116

1734

24716

2278

19916

3112

2614

1734

(402)

(786)

(535)

(451)

(621)

(581)

(497)

(800)

(667)

(451)

 

 

 

 

 

 

 

 

 

 

 

 

327

518

35

2314

1958

2678

25

2112

33

2834

2114

(130)

(889)

(591)

(498)

(683)

(635)

(546)

(838)

(730)

(540)

 

 

 

 

 

 

 

 

 

 

 

 

330

534

3838

2558

2158

2934

2758

2334

3658

3158

2318

(146)

(975)

(651)

(549)

(756)

(702)

(603)

(930)

(803)

(587)

 

 

 

 

 

 

 

 

 

 

 

 

333

634

4218

2838

231316

321316

30916

26116

40

34 916

25

(171)

(1070)

(721)

(605)

(833)

(776)

(662)

(1016)

(878)

(635)

 

 

 

 

 

 

 

 

 

 

 

 

336

71316

46516

31516

26516

36316

3334

281316

4412

3814

2714

(198)

(1176)

(795)

(668)

(919)

(857)

(732)

(1130)

(972)

(692)

 

 

 

 

 

 

 

 

 

 

 

 

340

878

5034

34716

281516

391516

37316

311116

47

42316

2958

(225)

(1289)

(875)

(735)

(1014)

(953)

(805)

(1194)

(1072)

(752)

 

 

 

 

 

 

 

 

 

 

 

 

344

1018

551316

38

311516

44116

41116

35

52

4658

32516

(257)

(1418)

(965)

(811)

(1119)

(1043)

(889)

(1321)

(1184)

(821)

 

 

 

 

 

 

 

 

 

 

 

 

349

1138

61316

411316

3518

48716

4518

38716

57

51516

35316

(289)

(1554)

(1062)

(892)

(1230)

(1146)

(976)

(1448)

(1303)

(894)

 

 

 

 

 

 

 

 

 

 

 

 

All dimensions in inches (millimeters).

13

Fan Identification

Model Number Code

The model number code is designed to completely identify the fan. The correct code letters must be specified to designate the correct construction. The remainder of the model number is determined by the size and performance.

SW

 

B

-

1

10 -

AF

-

3

 

-

CW

-

TH

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Drive

 

 

 

Fan Size

 

 

 

 

 

 

 

 

 

 

Wheel Rotation

 

 

 

 

 

 

 

 

 

B - Belt

 

 

 

06 through 49

 

 

 

 

 

 

 

 

 

CW - Clockwise

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Wheel Type

 

 

 

D - Direct

 

 

 

 

 

 

 

AF - Airfoil Wheel

 

 

 

 

CCW - Counterclockwise

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SW - Backward-Incline

 

 

 

 

 

 

 

 

 

 

 

 

(backward inclined

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

wheel is standard)

 

 

 

 

 

 

 

 

 

SF - Forward-Curved

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Discharge Position

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Series (SWB Only)

 

 

 

 

 

 

Motor HP

 

 

 

 

 

 

 

UB - Upblast

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

100 - Galvanized Construction

 

 

 

 

4 = 1/4

15

= 112

100 = 10

 

 

TAU - Top Angular Upblast

 

 

 

 

 

 

 

 

TH - Top Horizontal

 

 

200 - PermatectorTM Coated

 

 

 

 

3 = 1/3

20

= 2

150 = 15

 

 

 

 

 

 

 

Steel Construction

 

 

 

 

 

 

5 = 1/2

30

= 3

200 = 20

 

 

TAD - Top Angular Downblast

 

 

300 - Galvanized and Permatector

7 = 3/4

50

= 5

300 = 30

 

 

DB - Downblast

 

 

 

 

 

 

 

 

Coated Steel Construction

10 = 1

75

= 712

400 = 40

 

 

BAD - Backward Angular Downblast

BH - Backward Horizontal

BAU - Backward Angular Upblast

14

SFD Direct Drive

 

 

 

N

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

P

 

 

 

 

B

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

K

 

 

 

 

 

 

 

C

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Motor RPM (Direct Drive only)

 

 

 

 

M

 

 

 

 

 

 

 

 

A = 1725

D = 1550

 

 

 

 

 

 

J

 

 

 

 

 

 

 

B = 1140

E = 1050

 

 

 

 

 

 

 

 

 

 

 

L

 

 

C = 860

G = 1300

 

 

 

 

 

 

 

H

 

H

 

 

 

 

International

 

 

 

E

 

 

 

E

 

 

 

 

 

(See CAPS for performance)

 

 

 

 

 

G

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

K = 950 RPM

J = 1475 RPM

 

 

 

D

 

 

 

 

F

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

DIMENSIONAL DATA

 

 

 

 

 

 

Model

A

B

C

D

E

F

G

H

J

K

L

M

N

P

Max. Motor

*Unit

SFD

Frame Size Weight

 

 

 

 

 

 

 

 

 

 

 

 

 

 

6

738

514

16

11

5/8

141116

8316

1116

9116

6

114

7/8

1114

5316

56

30

(187)

(133)

(406)

(279)

(16)

(373)

(208)

(27)

(230)

(152)

(32)

(22)

(286)

(132)

(14)

 

 

7.5

9

514

18116

1214

5/8

14516

818

1116

958

8

114

118

131116

638

56

40

(229)

(133)

(459)

(311)

(16)

(364)

(206)

(27)

(244)

(203

(32)

(29)

(348)

(162)

(18)

 

 

9

1018

614

20516

1334

5/8

1778

1038

1116

1034

10

114

138

151316

7716

145T

75

(257)

(159)

(516)

(349)

(16)

(454)

(264)

(27)

(273)

(254)

(32)

(35)

(402)

(189)

(34)

 

 

10

1218

634

24516

1614

9/16

1938

1138

1116

1234

12

114

138

1858

812

184T

113

(308)

(171)

(618)

(413)

(14)

(492)

(289)

(27)

(324)

(305)

(32)

(35)

(473)

(216)

(51)

 

 

All dimensions in inches (millimeters) and weight in pounds (kilograms). *Approximate unit weight with largest frame size motor (60 Hz).

Model

Motor

Fan

 

 

 

 

Static Pressure in Inches wg

 

 

 

Number

HP

RPM

 

0.125

0.25

0.375

0.5

0.75

1

1.25

1.5

2

2.5

 

 

 

CFM

407

338

232

 

 

 

 

 

 

 

SFD-6-6B

1/6

1140

BHP

0.06

0.05

0.03

 

 

 

 

 

 

 

 

 

 

Sones

6.7

6.0

4.7

 

 

 

 

 

 

 

 

 

 

CFM

667

628

585

541

424

 

 

 

 

 

SFD-6-4A

1/4

1725

BHP

0.24

0.22

0.20

0.17

0.13

 

 

 

 

 

 

 

 

Sones

13.6

12.8

12.3

11.7

10.5

 

 

 

 

 

 

 

 

CFM

672

612

549

467

 

 

 

 

 

 

SFD-7.5-6B

1/6

1140

BHP

0.16

0.14

0.13

0.10

 

 

 

 

 

 

 

 

 

Sones

10.6

9.8

9.4

8.6

 

 

 

 

 

 

 

 

 

CFM

1062

1028

988

949

869

775

636

 

 

 

SFD-7.5-5A

1/2

1725

BHP

0.59

0.56

0.53

0.50

0.46

0.38

0.30

 

 

 

 

 

 

Sones

20

18.6

16.8

15.8

14.1

12.7

11.3

 

 

 

 

 

 

CFM

839

748

645

487

 

 

 

 

 

 

SFD-9-4C

1/4

860

BHP

0.18

0.15

0.12

0.09

 

 

 

 

 

 

 

 

 

Sones

9.2

7.8

7.0

6.6

 

 

 

 

 

 

 

 

 

CFM

1159

1097

1028

957

782

 

 

 

 

 

SFD-9-5B

1/2

1140

BHP

0.46

0.42

0.38

0.34

0.26

 

 

 

 

 

 

 

 

Sones

16.1

14.9

14.3

13.6

12.3

 

 

 

 

 

 

 

 

CFM

1806

1765

1725

1683

1595

1502

1407

1298

989

 

SFD-9-15A

112

1725

BHP

1.64

1.59

1.54

1.48

1.36

1.24

1.13

1.01

0.70

 

 

 

 

Sones

31

29

28

27

25

22

21

21

19.3

 

 

 

 

CFM

1259

1176

1085

965

 

 

 

 

 

 

SFD-10-3C

1/3

860

BHP

0.36

0.32

0.29

0.25

 

 

 

 

 

 

 

 

 

Sones

12.3

11.3

10.0

9.2

 

 

 

 

 

 

 

 

 

CFM

1713

1653

1592

1528

1378

1163

 

 

 

 

SFD-10-7B

3/4

1140

BHP

0.86

0.82

0.77

0.72

0.64

0.52

 

 

 

 

 

 

 

Sones

19.4

18.5

17.6

17.0

15.7

13.9

 

 

 

 

 

 

 

CFM

2641

2603

2564

2525

2444

2362

2275

2179

1942

1621

SFD-10-30A

3

1725

BHP

3.03

2.98

2.93

2.87

2.73

2.60

2.44

2.32

2.01

1.62

 

 

 

Sones

39

37

36

35

33

31

30

29

27

25

Performance certified is for installation Type B - Free inlet, Ducted outlet. Performance ratings do not include the effects of appurtenances (accessories). The AMCA

Certified Ratings Seal applies to air performance only.

15

SFB-9 - Belt Drive

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1678

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(429)

 

8

 

 

 

 

 

 

1512

 

 

 

 

658

 

 

 

 

2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(203)

 

 

 

 

 

 

(394)

 

 

 

 

(168)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(51)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1014

1018

 

(260)

(257)

 

24

 

10

(610)

1978

(254)

1334

158 (505)

 

(41)

 

(349)

 

 

1312 (343)

 

11516

1414 (362)

 

(287)

 

20 (508)

 

 

Wheel Diameter = 912 (241)

Shaft Diameter = 3/4 (19)

Outlet Area = 0.454 ft2 (0.042 m2) ^Approximate Unit Weight = 120 lb. (54 kg)

 

 

 

 

 

 

 

 

 

 

 

e

 

 

 

 

 

 

 

 

 

 

 

v

 

 

 

 

 

 

 

 

 

 

 

r

 

 

 

 

 

 

 

 

 

 

 

u

 

 

 

 

 

 

 

 

 

 

 

c

 

 

 

 

 

 

 

 

 

 

 

m

 

 

 

 

 

 

 

 

 

 

 

e

 

 

 

 

 

 

 

 

 

 

 

t

 

 

 

 

 

 

 

 

 

 

 

s

 

 

 

 

 

 

 

 

 

 

 

y

 

 

 

 

 

 

 

 

 

 

 

s

 

 

 

 

 

 

 

 

 

 

 

s

 

 

 

 

 

 

 

 

 

 

 

i

 

 

 

 

 

 

 

 

 

 

 

h

 

 

 

 

 

 

 

 

 

 

 

t

 

 

 

 

 

 

 

 

 

 

 

f

 

 

 

 

 

 

 

 

 

 

 

o

 

 

 

 

 

 

 

 

 

 

 

t

 

 

 

 

 

 

 

 

 

 

 

f

 

 

 

 

 

 

 

 

 

 

 

e

 

 

 

 

 

 

 

 

 

 

l

 

 

 

 

 

 

 

 

 

 

e

 

 

 

 

 

 

 

 

 

 

h

 

 

 

 

 

 

 

 

 

o

t

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

c

t

t

 

 

 

 

 

 

 

 

l e

 

 

 

 

 

 

 

 

e

 

 

 

 

 

 

 

 

s

 

 

 

 

 

 

 

 

t

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

o

 

 

 

 

 

 

 

 

 

n

 

 

 

 

 

 

 

 

 

 

o

 

 

 

 

 

 

 

 

 

 

 

D

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

cfm

All dimensions in inches (millimeters)

For additional discharge positions see page 12

^Weight shown is largest cataloged Open Drip Proof motor

Maximum BHP at given RPM = (RPM/1747)3

(Maximum KW at a given RPM = (RPM/1926)3)

Maximum RPM = 2000 and Minimum RPM = 450 Tip Speed (ft/min.) = RPM x 2.49

SFB-9

 

 

 

 

 

 

 

 

(Tip Speed (m/s) = RPM x 0.0126)

 

 

 

 

 

 

 

 

 

 

Maximum Motor Frame Size = 145T

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CFM

 

OV

 

 

 

 

 

Static Pressure in Inches wg

 

 

 

 

 

 

 

0.25

0.5

0.75

1

 

1.25

1.5

 

1.75

2

 

2.25

2.5

 

 

 

 

 

 

 

 

 

 

RPM

644

 

 

 

 

 

 

 

 

 

 

 

 

360

 

792

BHP

0.03

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Sones

6.3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

RPM

681

891

 

 

 

 

 

 

 

 

 

 

 

460

 

1013

BHP

0.05

0.08

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Sones

6.8

11.0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

RPM

728

930

1090

1225

 

 

 

 

 

 

 

 

 

560

 

1233

BHP

0.07

0.11

0.15

0.19

 

 

 

 

 

 

 

 

 

 

 

 

Sones

7.5

10.8

10.1

10.3

 

 

 

 

 

 

 

 

 

 

 

 

RPM

780

966

1129

1264

 

1382

 

 

 

 

 

 

 

660

 

1453

BHP

0.09

0.14

0.18

0.23

 

0.28

 

 

 

 

 

 

 

 

 

 

Sones

8.5

10.7

10.3

10.6

 

11.0

 

 

 

 

 

 

 

 

 

 

RPM

838

1013

1166

1303

 

1422

1528

 

1628

 

 

 

 

760

 

1674

BHP

0.13

0.18

0.23

0.28

 

0.34

0.39

 

0.44

 

 

 

 

 

 

 

Sones

9.8

10.6

10.7

11.0

 

11.8

13.2

 

14.5

 

 

 

 

 

 

 

RPM

909

1064

1207

1340

 

1461

1568

 

1667

1758

 

1845

 

860

 

1894

BHP

0.17

0.23

0.28

0.34

 

0.40

0.46

 

0.52

0.58

 

0.64

 

 

 

 

Sones

11.1

10.9

11.1

11.4

 

12.6

14.0

 

15.4

17.0

 

18.6

 

 

 

 

RPM

983

1118

1256

1378

 

1498

1608

 

1706

1798

 

1883

1965

960

 

2114

BHP

0.23

0.28

0.34

0.40

 

0.47

0.54

 

0.61

0.68

 

0.75

0.82

 

 

 

Sones

11.1

11.5

11.8

12.1

 

13.4

14.9

 

16.4

18.0

 

19.7

21

 

 

 

RPM

1059

1174

1306

1426

 

1534

1644

 

1745

1837

 

1923

 

1060

 

2334

BHP

0.30

0.35

0.42

0.49

 

0.55

0.63

 

0.71

0.78

 

0.86

 

 

 

 

Sones

12.0

12.2

12.6

13.2

 

14.3

15.8

 

17.5

19.1

 

21

 

 

 

 

RPM

1216

1318

1417

1528

 

1631

1728

 

1818

1911

 

1999

 

1260

 

2775

BHP

0.48

0.54

0.61

0.69

 

0.77

0.84

 

0.92

1.01

 

1.10

 

 

 

 

Sones

14.2

14.3

14.6

15.7

 

16.8

18.1

 

19.5

21

 

23

 

 

 

 

RPM

1297

1392

1482

1583

 

1682

1777

 

1866

1949

 

 

 

1360

 

2995

BHP

0.59

0.66

0.72

0.81

 

0.89

0.98

 

1.06

1.14

 

 

 

 

 

 

Sones

15.7

15.7

16.1

17.0

 

18.1

19.5

 

21

22

 

 

 

 

 

 

RPM

1378

1468

1554

1639

 

1736

1827

 

1915

1998

 

 

 

1460

 

3215

BHP

0.71

0.79

0.86

0.94

 

1.03

1.13

 

1.22

1.31

 

 

 

 

 

 

Sones

17.3

17.2

17.6

18.3

 

19.6

21

 

22

24

 

 

 

Performance certified is for installation Type B - Free inlet, Ducted outlet. Power rating (Bhp) does not include transmission losses. Performance ratings do not include the effects of appurtenances (accessories). The AMCA Certified Ratings Seal applies to air performance only.

16

SFB-10 - Belt Drive

1938

 

 

 

 

 

 

(492)

914

 

 

 

1512

812

 

 

 

 

 

(235)

 

 

 

(394)

(216)

1112

 

1134

 

 

(292)

 

(298)

 

 

 

 

 

 

2658

 

 

 

 

 

 

(676)

 

 

 

 

2214

 

 

 

 

 

 

 

1518

 

2

1

4

(565)

 

 

 

 

 

(384)

 

(57)

 

 

 

 

 

 

 

 

16 (406)

 

 

 

12 (305)

 

1678 (429)

 

 

 

 

2038 (518)

 

 

 

 

 

 

22 (559)

Wheel Diameter = 1058 (270) Shaft Diameter = 3/4 (19)

Outlet Area = 0.705 ft2 (0.065 m2) ^Approximate Unit Weight = 130 lb. (59 kg)

2

 

 

 

 

 

 

 

 

 

 

 

 

(51)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

e

 

 

 

 

 

 

 

 

 

 

 

 

v

 

 

 

 

 

 

 

 

 

 

 

 

r

 

 

 

 

 

 

 

 

 

 

 

 

u

 

 

 

 

 

 

 

 

 

 

 

 

c

 

 

 

 

 

 

 

 

 

 

 

 

m

 

 

 

 

 

 

 

 

 

 

 

 

e

11

 

 

 

 

 

 

 

 

 

 

 

t

 

 

 

 

 

 

 

 

 

 

 

s

 

 

 

 

 

 

 

 

 

 

 

 

y

(279)

 

 

 

 

 

 

 

 

 

 

 

s

 

 

 

 

 

 

 

 

 

 

 

s

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

i

 

 

 

 

 

 

 

 

 

 

 

 

h

 

 

 

 

 

 

 

 

 

 

 

 

t

 

 

 

 

 

 

 

 

 

 

 

 

f

 

 

 

 

 

 

 

 

 

 

 

 

o

 

 

 

 

 

 

 

 

 

 

 

t

 

 

 

 

 

 

 

 

 

 

 

f

 

 

 

 

 

 

 

 

 

 

 

e

 

 

 

 

 

 

 

 

 

h

e

l

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

t

o

t

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

le

t

 

 

 

 

 

 

 

 

 

s

e

 

 

 

 

 

 

 

 

 

t

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

o

 

 

 

 

 

 

 

 

 

 

 

n

 

 

 

 

 

 

 

 

 

 

 

 

o

 

 

 

 

 

 

 

 

 

 

 

 

D

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

cfm

All dimensions in inches (millimeters)

For additional discharge positions see page 12

^Weight shown is largest cataloged Open Drip Proof motor

Maximum BHP at given RPM = (RPM/1310)3

(Maximum KW at a given RPM = (RPM/1444)3)

Maximum RPM = 1650 and Minimum RPM = 400 Tip Speed (ft/min.) = RPM x 2.78

SFB-10

 

 

 

 

 

 

 

(Tip Speed (m/s) = RPM x 0.0141)

 

 

 

 

 

 

 

 

 

Maximum Motor Frame Size = 145T

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CFM

OV

 

 

 

 

 

Static Pressure in Inches wg

 

 

 

 

 

 

0.25

0.5

0.75

1

 

1.25

1.5

 

1.75

2

 

2.25

2.5

 

 

 

 

 

 

 

 

RPM

526

 

 

 

 

 

 

 

 

 

 

 

 

600

851

BHP

0.05

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Sones

5.6

 

 

 

 

 

 

 

 

 

 

 

 

 

 

RPM

575

730

 

 

 

 

 

 

 

 

 

 

 

790

1121

BHP

0.08

0.12

 

 

 

 

 

 

 

 

 

 

 

 

 

Sones

6.2

9.1

 

 

 

 

 

 

 

 

 

 

 

 

 

RPM

633

777

897

1013

 

 

 

 

 

 

 

 

 

980

1390

BHP

0.13

0.18

0.23

0.30

 

 

 

 

 

 

 

 

 

 

 

Sones

7.1

10.3

10.3

10.2

 

 

 

 

 

 

 

 

 

 

 

RPM

693

828

944

1045

 

1144

 

 

 

 

 

 

 

1170

1660

BHP

0.19

0.25

0.32

0.38

 

0.45

 

 

 

 

 

 

 

 

 

Sones

8.3

10.7

10.3

10.6

 

10.9

 

 

 

 

 

 

 

 

 

RPM

760

887

994

1092

 

1181

1263

 

1349

1430

 

 

 

1360

1930

BHP

0.27

0.35

0.42

0.50

 

0.57

0.64

 

0.73

0.81

 

 

 

 

 

Sones

9.9

10.7

10.7

11.0

 

11.3

12.0

 

13.3

14.7

 

 

 

 

 

RPM

828

946

1049

1142

 

1229

1309

 

1383

1456

 

1531

1603

1550

2199

BHP

0.37

0.46

0.54

0.63

 

0.73

0.81

 

0.89

0.97

 

1.02

1.17

 

 

Sones

11.1

11.0

11.3

11.6

 

12.0

13.0

 

14.2

15.5

 

17.0

18.7

 

 

RPM

898

1009

1109

1196

 

1279

1357

 

1430

1499

 

1564

1629

1740

2469

BHP

0.50

0.60

0.70

0.79

 

0.89

1.00

 

1.09

1.18

 

1.27

1.37

 

 

Sones

11.4

11.7

12.1

12.4

 

13.1

14.2

 

15.5

16.8

 

18.1

19.9

 

 

RPM

973

1077

1169

1256

 

1332

1407

 

1479

1546

 

1611

 

1930

2739

BHP

0.66

0.77

0.87

0.99

 

1.08

1.20

 

1.32

1.43

 

1.53

 

 

 

Sones

12.4

12.7

13.0

13.6

 

14.5

15.6

 

16.8

18.1

 

19.8

 

 

 

RPM

1050

1145

1232

1316

 

1393

1461

 

1529

1596

 

 

 

2120

3008

BHP

0.85

0.97

1.09

1.21

 

1.33

1.43

 

1.56

1.69

 

 

 

 

 

Sones

13.8

13.9

14.1

15.0

 

16.0

17.1

 

18.3

19.8

 

 

 

 

 

RPM

1128

1214

1299

1376

 

1452

1522

 

1585

1647

 

 

 

2310

3278

BHP

1.08

1.21

1.34

1.46

 

1.59

1.72

 

1.84

1.97

 

 

 

 

 

Sones

15.3

15.2

15.6

16.5

 

17.6

18.8

 

20

22

 

 

 

 

 

RPM

1207

1285

1368

1441

 

1512

1581

 

1645

 

 

 

 

2500

3548

BHP

1.36

1.48

1.63

1.76

 

1.90

2.04

 

2.18

 

 

 

 

 

 

Sones

17.1

16.9

17.4

18.3

 

19.4

21

 

22

 

 

 

 

Performance certified is for installation Type B - Free inlet, Ducted outlet. Power rating (Bhp) does not include transmission losses. Performance ratings do not include the effects of appurtenances (accessories). The AMCA Certified Ratings Seal applies to air performance only.

17

SFB-12 - Belt Drive

 

 

 

 

2138

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(543)

934

 

 

 

 

1512

 

 

9

2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(248)

 

 

 

 

(394)

 

 

(229)

(51)

 

 

 

 

 

 

 

 

 

 

 

 

13

1

4

 

13 ⁄8

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

e

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

r

 

 

 

 

5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

v

(337)

 

(346)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

u

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

c

3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

m

 

 

 

 

 

 

 

 

 

 

 

 

 

13

 

 

 

 

 

 

 

 

 

 

 

e

28 ⁄8

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

t

(721)

 

 

 

 

 

 

 

 

1

 

 

 

 

(330)

 

 

 

 

 

 

 

 

 

 

 

s

 

 

 

 

 

 

 

22

4

 

 

 

 

 

 

 

 

 

 

 

 

 

 

y

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

s

 

 

 

 

 

 

 

1

(565)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

s

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

i

 

 

1

 

 

1 ⁄2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

h

15

8

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

t

 

 

 

(38)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

f

(384)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

o

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

t

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

f

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

e

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

e

l

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

o

t

h

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

t

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

16 (406)

 

 

12 (305)

7

 

 

 

 

 

 

le c

t

 

 

 

 

 

 

 

 

 

 

 

7

 

 

 

 

20 ⁄8

(530)

 

 

 

 

s

e

 

 

 

 

 

 

 

 

 

 

 

16 ⁄8 (429)

 

 

 

 

 

 

 

 

 

 

 

t

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

22

1

2

(572)

 

 

o

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

n

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

o

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

D

 

 

 

 

 

 

 

 

 

 

 

Wheel Diameter = 1258 (321)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

cfm

Shaft Diameter = 3/4 (19)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Outlet Area = 0.856 ft2 (0.08 m2)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

^Approximate Unit Weight = 147 lb. (67 kg)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

All dimensions in inches (millimeters)

For additional discharge positions see page 12

^Weight shown is largest cataloged Open Drip Proof motor

Maximum BHP at given RPM = (RPM/1111)3

(Maximum KW at a given RPM = (RPM/1225)3)

Maximum RPM = 1400 and Minimum RPM = 370 Tip Speed (ft/min.) = RPM x 3.30

SFB-12

 

 

 

 

 

 

 

(Tip Speed (m/s) = RPM x 0.0168)

 

 

 

 

 

 

 

 

 

Maximum Motor Frame Size = 145T

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CFM

OV

 

 

 

 

 

Static Pressure in Inches wg

 

 

 

 

 

 

0.25

0.5

0.75

1

 

1.25

1.5

 

1.75

2

 

2.25

2.5

 

 

 

 

 

 

 

 

RPM

455

 

 

 

 

 

 

 

 

 

 

 

 

825

964

BHP

0.07

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Sones

5.7

 

 

 

 

 

 

 

 

 

 

 

 

 

 

RPM

493

631

 

 

 

 

 

 

 

 

 

 

 

1065

1244

BHP

0.12

0.18

 

 

 

 

 

 

 

 

 

 

 

 

 

Sones

6.3

9.3

 

 

 

 

 

 

 

 

 

 

 

 

 

RPM

533

665

773

871

 

 

 

 

 

 

 

 

 

1305

1525

BHP

0.18

0.25

0.33

0.40

 

 

 

 

 

 

 

 

 

 

 

Sones

7.1

10.2

10.3

10.5

 

 

 

 

 

 

 

 

 

 

 

RPM

580

703

806

897

 

983

1061

 

 

 

 

 

 

1545

1805

BHP

0.26

0.35

0.43

0.52

 

0.62

0.71

 

 

 

 

 

 

 

 

Sones

8.2

10.5

10.6

11.0

 

11.3

12.0

 

 

 

 

 

 

 

 

RPM

632

743

844

931

 

1010

1087

 

1158

1225

 

 

 

1785

2086

BHP

0.36

0.47

0.57

0.67

 

0.77

0.88

 

0.99

1.09

 

 

 

 

 

Sones

9.6

10.7

11.1

11.5

 

11.8

13.0

 

14.4

16.0

 

 

 

 

 

RPM

686

789

883

969

 

1045

1116

 

1185

1251

 

1313

1373

2025

2367

BHP

0.49

0.61

0.74

0.85

 

0.96

1.07

 

1.19

1.32

 

1.44

1.56

 

 

Sones

11.0

11.4

11.8

12.2

 

12.7

14.0

 

15.5

17.0

 

18.6

20

 

 

RPM

747

837

925

1008

 

1083

1152

 

1217

1278

 

1340

1399

2265

2647

BHP

0.67

0.79

0.93

1.06

 

1.19

1.31

 

1.44

1.56

 

1.70

1.84

 

 

Sones

11.8

12.2

12.6

12.9

 

13.9

15.2

 

16.6

18.1

 

19.8

22

 

 

RPM

809

889

971

1048

 

1122

1190

 

1254

1314

 

1370

 

2505

2928

BHP

0.88

1.00

1.15

1.30

 

1.45

1.59

 

1.73

1.87

 

2.00

 

 

 

Sones

13.0

13.2

13.5

14.1

 

15.3

16.6

 

17.9

19.5

 

21

 

 

 

RPM

873

943

1019

1093

 

1162

1230

 

1292

 

 

 

 

2745

3208

BHP

1.13

1.26

1.41

1.58

 

1.75

1.91

 

2.06

 

 

 

 

 

 

Sones

14.5

14.4

14.6

15.6

 

16.7

18.0

 

19.5

 

 

 

 

 

 

RPM

937

1001

1071

1140

 

1205

 

 

 

 

 

 

 

2985

3489

BHP

1.43

1.56

1.72

1.90

 

2.08

 

 

 

 

 

 

 

 

 

Sones

16.1

15.8

16.2

17.1

 

18.2

 

 

 

 

 

 

 

 

 

RPM

1002

1062

1124

 

 

 

 

 

 

 

 

 

 

3225

3769

BHP

1.77

1.92

2.08

 

 

 

 

 

 

 

 

 

 

 

 

Sones

17.8

17.4

17.8

 

 

 

 

 

 

 

 

 

 

Performance certified is for installation Type B - Free inlet, Ducted outlet. Power rating (Bhp) does not include transmission losses. Performance ratings do not include the effects of appurtenances (accessories). The AMCA Certified Ratings Seal applies to air performance only.

18

SFB-15 - Belt Drive

Note: New dimensions on this model

2338

 

 

 

(594)

1058

2134

1234

 

(270)

(552)

(324)

1458

 

16

 

(371)

 

(406)

 

3114

 

 

 

(371)

 

2434

 

5

 

112 (629)

 

16 ⁄8

 

(38)

 

(422)

 

 

 

 

 

1758 (448)

13 (330)

 

1878 (479)

 

30 (762)

 

 

3258 (829)

Wheel Diameter = 15 (381) Shaft Diameter = 1 (25)

Outlet Area = 1.39 ft2 (0.129 m2) Mounting Hole Size = 1/2 (13)

^Approximate Unit Weight = 214 lb. (97 kg)

All dimensions in inches (millimeters)

For additional discharge positions see page 12

^Weight shown is largest cataloged Open Drip Proof motor

2

 

 

 

 

 

 

 

 

 

 

(51)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

e

 

 

 

 

 

 

 

 

 

 

v

 

 

 

 

 

 

 

 

 

 

r

 

 

 

 

 

 

 

 

 

 

u

 

 

 

 

 

 

 

 

 

 

c

 

 

 

 

 

 

 

 

 

 

m

 

 

 

 

 

 

 

 

 

 

e

3

 

 

 

 

 

 

 

 

 

t

 

 

 

 

 

 

 

 

 

s

15 ⁄8

 

 

 

 

 

 

 

 

 

y

(391)

 

 

 

 

 

 

 

 

 

s

 

 

 

 

 

 

 

 

 

s

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

i

 

 

 

 

 

 

 

 

 

 

h

 

 

 

 

 

 

 

 

 

 

t

 

 

 

 

 

 

 

 

 

 

f

 

 

 

 

 

 

 

 

 

 

o

 

 

 

 

 

 

 

 

 

 

t

 

 

 

 

 

 

 

 

 

 

f

 

 

 

 

 

 

 

 

 

 

e

 

 

 

 

 

 

 

 

 

 

l

 

 

 

 

 

 

 

 

 

 

e

 

 

 

 

 

 

 

 

 

 

h

 

 

 

 

 

 

 

 

 

t

 

 

 

 

 

 

 

 

 

o

 

 

 

 

 

 

 

 

 

t

 

 

 

 

 

 

 

 

t

 

 

 

 

 

 

 

e

le

c

 

 

 

 

 

 

 

s

 

 

 

 

 

 

 

t

 

 

 

 

 

 

 

o

 

 

 

 

 

 

 

n

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

o

 

 

 

 

 

 

 

 

 

 

D

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

cfm

Maximum BHP at given RPM = (RPM/720)3

(Maximum KW at a given RPM = (RPM/794)3)

Maximum RPM = 1200 and Minimum RPM = 380 Tip Speed (ft/min.) = RPM x 3.93

SFB-15

 

 

 

 

 

 

 

(Tip Speed (m/s) = RPM x 0.0200)

 

 

 

 

 

 

 

 

 

Maximum Motor Frame Size = 184T

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CFM

OV

 

 

 

 

 

Static Pressure in Inches wg

 

 

 

 

 

 

0.25

0.5

0.75

1

 

1.25

1.5

 

1.75

2

 

2.5

2.75

 

 

 

 

 

 

 

 

RPM

395

508

 

 

 

 

 

 

 

 

 

 

 

1560

1125

BHP

0.16

0.25

 

 

 

 

 

 

 

 

 

 

 

 

 

Sones

6.0

8.1

 

 

 

 

 

 

 

 

 

 

 

 

 

RPM

421

529

619

 

 

 

 

 

 

 

 

 

 

1860

1342

BHP

0.23

0.33

0.43

 

 

 

 

 

 

 

 

 

 

 

 

Sones

7.5

8.8

9.4

 

 

 

 

 

 

 

 

 

 

 

 

RPM

450

554

638

716

 

 

 

 

 

 

 

 

 

2160

1558

BHP

0.32

0.44

0.55

0.67

 

 

 

 

 

 

 

 

 

 

 

Sones

9.9

9.6

10.3

11.2

 

 

 

 

 

 

 

 

 

 

 

RPM

481

580

663

734

 

803

865

 

 

 

 

 

 

2460

1775

BHP

0.42

0.56

0.70

0.83

 

0.97

1.09

 

 

 

 

 

 

 

 

Sones

10.9

10.6

11.4

12.0

 

13.4

15.2

 

 

 

 

 

 

 

 

RPM

514

608

688

759

 

822

884

 

941

 

 

 

 

2760

1991

BHP

0.56

0.71

0.87

1.03

 

1.17

1.32

 

1.47

 

 

 

 

 

 

Sones

11.5

11.9

12.3

12.8

 

14.0

15.6

 

17.2

 

 

 

 

 

 

RPM

549

637

715

784

 

846

903

 

959

1013

 

 

 

3060

2208

BHP

0.72

0.89

1.07

1.24

 

1.41

1.57

 

1.74

1.90

 

 

 

 

 

Sones

12.7

13.5

13.2

13.5

 

14.6

16.0

 

17.5

19.0

 

 

 

 

 

RPM

585

668

742

810

 

871

928

 

980

1031

 

1128

1174

3360

2424

BHP

0.91

1.11

1.29

1.49

 

1.68

1.87

 

2.04

2.22

 

2.58

2.75

 

 

Sones

14.1

14.9

14.0

14.1

 

15.0

16.5

 

17.9

19.4

 

22

24

 

 

RPM

623

701

772

837

 

897

953

 

1005

1053

 

1147

1192

3660

2641

BHP

1.14

1.35

1.56

1.76

 

1.98

2.18

 

2.39

2.58

 

2.98

3.17

 

 

Sones

15.9

16.0

14.7

14.7

 

15.4

17.0

 

18.6

20

 

23

24

 

 

RPM

662

734

802

865

 

924

979

 

1030

1078

 

1166

 

3960

2857

BHP

1.41

1.63

1.86

2.07

 

2.31

2.54

 

2.76

2.98

 

3.40

 

 

 

Sones

17.8

17.3

15.9

15.4

 

16.3

17.7

 

19.3

21

 

23

 

 

 

RPM

701

768

834

895

 

951

1005

 

1056

1103

 

1191

 

4260

3074

BHP

1.71

1.95

2.20

2.44

 

2.67

2.93

 

3.17

3.41

 

3.88

 

 

 

Sones

18.9

18.6

17.2

16.6

 

17.6

18.9

 

20

22

 

24

 

 

 

RPM

742

804

867

925

 

980

1032

 

1082

1129

 

 

 

4560

3290

BHP

2.06

2.32

2.59

2.85

 

3.09

3.35

 

3.63

3.89

 

 

 

 

 

Sones

20

19.8

18.8

18.4

 

19.2

20

 

22

23

 

 

 

Performance certified is for installation Type B - Free inlet, Ducted outlet. Power rating (Bhp) does not include transmission losses. Performance ratings do not include the effects of appurtenances (accessories). The AMCA Certified Ratings Seal applies to air performance only.

19

SFB-18 - Belt Drive

3078

 

 

 

(784)

1334

22

1734

 

 

(349)

(559)

(451)

1958

 

1938

 

(498)

 

(492)

 

42

 

 

 

(1067)

 

3314

 

2238

 

112 (845)

 

 

(38)

 

(568)

 

 

 

2338 (594)

18 (457)

35 (889)

2518 (638)

 

 

 

 

3678 (937)

Wheel Diameter = 1818 (460) Shaft Diameter = 1 (25)

Outlet Area = 2.29 ft2 (0.213 m2) Mounting Hole Size = 1/2 (13)

^Approximate Unit Weight = 265 lb. (120 kg)

All dimensions in inches (millimeters)

For additional discharge positions see page 12

^Weight shown is largest cataloged Open Drip Proof motor

2

 

 

 

 

 

 

 

 

 

 

 

 

 

(51)

 

 

 

 

 

 

 

 

 

 

 

 

e

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

v

 

 

 

 

 

 

 

 

 

 

 

 

 

r

 

 

 

 

 

 

 

 

 

 

 

 

 

u

 

 

 

 

 

 

 

 

 

 

 

 

 

c

 

 

 

 

 

 

 

 

 

 

 

 

 

m

 

 

 

 

 

 

 

 

 

 

 

 

 

e

 

 

 

 

 

 

 

 

 

 

 

 

 

t

1

 

 

 

 

 

 

 

 

 

 

 

 

s

 

 

 

 

 

 

 

 

 

 

 

 

y

19 ⁄4

 

 

 

 

 

 

 

 

 

 

 

 

s

(489)

 

 

 

 

 

 

 

 

 

 

 

 

s

 

 

 

 

 

 

 

 

 

 

 

 

i

 

 

 

 

 

 

 

 

 

 

 

 

 

h

 

 

 

 

 

 

 

 

 

 

 

 

 

t

 

 

 

 

 

 

 

 

 

 

 

 

 

f

 

 

 

 

 

 

 

 

 

 

 

 

 

o

 

 

 

 

 

 

 

 

 

 

 

 

 

t

 

 

 

 

 

 

 

 

 

 

 

 

 

f

 

 

 

 

 

 

 

 

 

 

 

 

 

e

 

 

 

 

 

 

 

 

 

 

 

 

l

 

 

 

 

 

 

 

 

 

 

 

 

e

 

 

 

 

 

 

 

 

 

 

 

 

h

 

 

 

 

 

 

 

 

 

 

t

o

t

 

 

 

 

 

 

 

 

 

c

t

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

l e

 

 

 

 

 

 

 

 

 

 

e

 

 

 

 

 

 

 

 

 

 

s

 

 

 

 

 

 

 

 

 

 

t

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

o

 

 

 

 

 

 

 

 

 

 

 

n

 

 

 

 

 

 

 

 

 

 

 

 

o

 

 

 

 

 

 

 

 

 

 

 

 

 

D

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

cfm

Maximum BHP at given RPM = (RPM/614)3

(Maximum KW at a given RPM = (RPM/677)3)

Maximum RPM = 1050 and Minimum RPM = 310 Tip Speed (ft/min.) = RPM x 4.75

SFB-18

 

 

 

 

 

 

 

(Tip Speed (m/s) = RPM x 0.0241)

 

 

 

 

 

 

 

 

 

Maximum Motor Frame Size = 184T

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CFM

OV

 

 

 

 

 

Static Pressure in Inches wg

 

 

 

 

 

 

0.25

0.5

0.75

1

 

1.25

1.5

 

1.75

2

 

2.25

2.5

 

 

 

 

 

 

 

 

RPM

364

464

550

 

 

 

 

 

 

 

 

 

 

2725

1188

BHP

0.29

0.44

0.60

 

 

 

 

 

 

 

 

 

 

 

 

Sones

8.4

9.2

10.2

 

 

 

 

 

 

 

 

 

 

 

 

RPM

388

481

563

635

 

 

 

 

 

 

 

 

 

3150

1374

BHP

0.39

0.56

0.74

0.93

 

 

 

 

 

 

 

 

 

 

 

Sones

10.3

10.1

11.2

12.6

 

 

 

 

 

 

 

 

 

 

 

RPM

415

500

578

648

 

712

 

 

 

 

 

 

 

3575

1559

BHP

0.52

0.70

0.90

1.11

 

1.33

 

 

 

 

 

 

 

 

 

Sones

11.1

11.3

12.2

13.4

 

15.5

 

 

 

 

 

 

 

 

 

RPM

444

524

596

662

 

725

782

 

836

 

 

 

 

4000

1744

BHP

0.68

0.89

1.10

1.32

 

1.56

1.80

 

2.03

 

 

 

 

 

 

Sones

12.0

13.1

13.1

14.0

 

15.8

17.7

 

19.5

 

 

 

 

 

 

RPM

473

548

615

680

 

738

795

 

848

898

 

943

 

4425

1930

BHP

0.87

1.09

1.32

1.57

 

1.81

2.08

 

2.34

2.60

 

2.86

 

 

 

Sones

13.6

14.7

14.0

14.4

 

15.9

17.8

 

19.7

21

 

23

 

 

 

RPM

503

573

638

698

 

756

809

 

861

910

 

957

1001

4850

2115

BHP

1.09

1.34

1.59

1.85

 

2.12

2.38

 

2.68

2.97

 

3.26

3.54

 

 

Sones

15.5

15.8

14.8

14.8

 

16.2

18.1

 

20

22

 

24

25

 

 

RPM

534

601

662

719

 

774

826

 

875

923

 

970

1013

5275

2300

BHP

1.36

1.63

1.90

2.17

 

2.46

2.75

 

3.04

3.35

 

3.67

3.99

 

 

Sones

17.7

17.1

15.6

15.6

 

16.7

18.7

 

20

22

 

24

26

 

 

RPM

566

630

687

743

 

793

844

 

893

938

 

982

1026

5700

2486

BHP

1.67

1.96

2.24

2.55

 

2.83

3.15

 

3.47

3.78

 

4.11

4.46

 

 

Sones

19.2

18.6

16.9

16.6

 

17.9

19.5

 

21

23

 

25

26

 

 

RPM

599

660

714

767

 

817

863

 

911

956

 

998

1039

6125

2671

BHP

2.03

2.34

2.64

2.96

 

3.28

3.58

 

3.94

4.28

 

4.61

4.95

 

 

Sones

20

20

18.5

18.0

 

19.4

21

 

22

24

 

26

27

 

 

RPM

631

689

743

791

 

840

886

 

929

974

 

1016

 

6550

2857

BHP

2.43

2.76

3.09

3.41

 

3.77

4.10

 

4.43

4.81

 

5.18

 

 

 

Sones

22

21

20

20

 

21

22

 

24

26

 

27

 

 

 

RPM

664

720

771

818

 

865

909

 

951

992

 

1034

 

6975

3042

BHP

2.88

3.23

3.60

3.93

 

4.30

4.67

 

5.02

5.38

 

5.78

 

 

 

Sones

24

23

23

22

 

23

24

 

26

27

 

29

 

Performance certified is for installation Type B - Free inlet, Ducted outlet. Power rating (Bhp) does not include transmission losses. Performance ratings do not include the effects of appurtenances (accessories). The AMCA Certified Ratings Seal applies to air performance only.

20