Model FSD-211 |
|
APPLICATION |
Combination FIRE SMOKE DAMPERS |
|||
Model FSD-211 is a combination fire smoke damper with 3V style |
|
Steel 3-V Blades |
||
blades. The FSD-211 has been qualified to 2000 fpm (10.2 m/s) and |
|
UL 555S Leakage Class I |
||
4 in. wg (1 kPa) for operation and dynamic closure in emergency fire |
|
UL555 11⁄2 Hour Fire Resistance Rating |
||
smoke situations. Model FSD-211 may be installed vertically (with |
|
|||
|
|
|||
blades running horizontal) or horizontally and is rated for airflow and |
Model FSD-211 meets the requirements for fire |
|||
leakage in either direction. |
|
|||
|
dampers, smoke dampers and combination fire |
|||
|
|
|||
Ratings |
|
smoke dampers established by: |
||
UL 555 Fire Resistance Rating |
National Fire Protection Association |
|||
Fire Rating: |
11⁄2 Hours |
NFPA Standards 80, 90A, 92A, 92B, 101 & 105 |
||
Dynamic Closure Rating: Actual ratings are size dependent |
IBC |
International Building Codes |
||
Maximum Velocity: |
2000 fpm (10.2 m/s) |
|||
ICBO Uniform Building Codes |
||||
Maximum Pressure: |
4 in. wg (1 kPa) |
|||
CSFM California State Fire Marshal |
||||
Maximum Temperature: 350ºF (177°C) -- Depending on |
||||
|
actuator |
Fire Damper Listing (#3225-0981:103) |
||
UL 555S Leakage Rating |
|
Leakage (Smoke) Damper Listing (#3230-0981:104) |
||
|
New York City (MEA listing #260-91-M) |
|||
Leakage Class: |
I |
|||
Operational Rating: |
Actual ratings are actuator dependent |
|
|
|
Maximum Velocity: |
2000 fpm (10.2 m/s) |
|
|
|
Maximum Pressure: |
4 in. wg (1 kPa) |
“UL CLASSIFIED (see complete marking on |
||
Maximum Temperature: 350ºF (177°C) - Depending on |
||||
|
actuator |
product)” |
||
|
|
“UL CLASSIFIED to Canadian safety standards |
||
Standard Construction |
(see complete marking on product)” |
|||
Frame: |
5 in. x 1 in. (127mm x 25mm) |
|
Standard 555 & 555S (Listing #R13317) |
|
|
galvanized steel hat channel with |
|
|
|
|
reinforced corners. A low profile head |
|
Greenheck Fan Corporation certifies that the |
|
|
and sill are used on sizes less than |
|
model FSD-211 shown herein is licensed to bear |
|
|
17 in. (432mm) high to maximize free |
|
the AMCA Seal. The ratings shown are based on |
|
|
area and performance. |
|
tests and procedures performed in accordance |
|
Blades: |
|
with AMCA Publication 511 and comply with |
||
16 ga. (1.5mm) galvanized steel, |
|
|||
|
the requirements of the AMCA Certified Ratings |
|||
|
reinforced with 3 longitudinal |
R |
||
|
|
Programs. The AMCA Certified Ratings Seal |
||
|
structurally designed vee’s. |
|
||
Seals: |
|
applies to air performance ratings only. |
||
Extruded silicone rubber blade seals |
|
|
||
Jamb Seals: |
Flexible stainless steel jamb seals |
|
|
|
Linkage: |
Concealed in jamb. |
|
|
|
Closure Device: |
UL listed 165°F (74°C) RRL |
|
|
|
Axles: |
1⁄2 in. (13mm) dia. plated steel |
|
|
|
Bearings: |
Bronze sleeve type |
|
W* |
|
|
|
|
||
Size Limitations: |
|
|
|
|
Minimum Size: |
8 in. W x 6 in. H (203mm W x 152mm H) |
|
|
|
Maximum Size: |
Single Section: 32 in. W x 50 in. H |
|
|
|
|
(813mm W x 1270mm H) |
|
|
|
|
36 in. W x 48 in. H |
|
|
|
|
(914mm x 1219mm) |
|
|
|
|
Multiple Section: |
|
RH |
|
|
Horizontal: 144 in. W x 96 in. H |
|
|
|
|
(3658mm W x 2438mm H) |
|
|
|
|
Vertical: 128 in. W x 100 in. H |
|
|
|
|
(3251mm W x 2540mm H) |
H* |
||
Optional Features: |
||||
|
|
•RRL/OCI (Open closed indication switches)
•Electric or pneumatic actuators
•POC retaining angles
•Smoke detectors
• Momentary switch |
LH |
|
• Pneumatic Relief Valve (PRV) |
||
|
||
• Security bars |
*W&H dimensions furnished approximately ¼in. (6mm) undersize. |
|
• TOR (remote override of 165ºF (74°C) or 212ºF (100°C) closure |
||
(Add sleeve thickness for overall sleeved damper dimension) |
||
allows damper to perform smoke management functions during a |
||
Right hand drive is shown. Left hand drive is available upon request. |
||
fire emergency) |
|
• 165ºF (74°C), 212°F (100°C), 250ºF (121°C), and 350ºF (177°C)
RRL's available. |
Installation installations available at www.greenheck.com |
|
• Sealed transitions and sleeves |
||
|
Pressure Drop Data |
FSD-211 |
This pressure drop testing was conducted in accordance with AMCA Standard 500-D using the three configurations shown. All data has been corrected to represent standard air at a density of .075 lb/ft3 (1.201 kg/m3).
Actual pressure drop found in any HVAC system is a combination of many factors. This pressure drop information along with an analysis of other system influences should be used to estimate actual pressure losses for a damper installed in a given HVAC system.
AMCA Test Figures
Figure 5.3 Illustrates a fully ducted damper. This configuration has the lowest pressure drop of the three test configurations because entrance and exit losses are minimized by straight duct runs upstream and downstream of the damper.
Figure 5.2 Illustrates a ducted damper exhausting air into an open area. This configuration has a lower pressure drop than Figure 5.5 because entrance losses are minimized by a straight duct run upstream of the damper.
Figure 5.5 Illustrates a plenum mounted damper. This configuration has the highest pressure drop because of extremely high entrance and exit losses due to the sudden changes of area in the system.
5D |
|
|
|
|
|
|
|
6D |
|
|
|
|
|||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
5D
D |
4 (W) (H) |
|
3.14 |
AMCA 5.2 Pressure Drop |
|
|
|
FSD-211 |
||
|
|
|
|
|
|
|
|
|
|
5D |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Figure 5.2
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
48 in. x 12 in. (1219mm x 305mm) |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||
12 in. x 12 in. (305mm x 305mm) |
|
24 in. x 24 in. (610mm x 610mm) |
|
36 in. x 36 in. (914mm x 914mm) |
|
12 in. x 48 in. (305mm x 1219mm) |
|
|||||||||
Velocity (fpm) |
Pressure Drop |
|
Velocity (fpm) |
Pressure Drop |
|
Velocity (fpm) |
Pressure Drop |
|
|
Velocity (fpm) |
Pressure Drop |
|
Velocity (fpm) |
Pressure Drop |
||
(in. wg) |
|
(in. wg) |
|
|
(in. wg) |
|
|
(in. wg) |
|
(in. wg) |
||||||
500 |
0.04 |
|
500 |
0.02 |
|
500 |
0.01 |
|
|
500 |
0.01 |
|
500 |
0.03 |
||
1000 |
0.14 |
|
1000 |
0.07 |
|
1000 |
0.04 |
|
|
1000 |
0.06 |
|
1000 |
0.10 |
||
1500 |
0.31 |
|
1500 |
0.16 |
|
1500 |
0.09 |
|
|
1500 |
0.13 |
|
1500 |
0.23 |
||
2000 |
0.55 |
|
2000 |
0.29 |
|
2000 |
0.16 |
|
|
2000 |
0.23 |
|
2000 |
0.41 |
||
2500 |
0.86 |
|
2500 |
0.45 |
|
2500 |
0.25 |
|
|
2500 |
0.36 |
|
2500 |
0.63 |
||
3000 |
1.24 |
|
3000 |
0.65 |
|
3000 |
0.36 |
|
|
3000 |
0.52 |
|
3000 |
0.91 |
||
3500 |
1.69 |
|
3500 |
0.89 |
|
3500 |
0.49 |
|
|
3500 |
0.70 |
|
3500 |
1.24 |
||
4000 |
2.20 |
|
4000 |
1.16 |
|
4000 |
0.64 |
|
|
4000 |
0.92 |
|
4000 |
1.62 |
Greenheck Fan Corporation certifies that the model FSD-211 shown herein is licensed to bear the AMCA Seal. The ratings shown are based on tests and procedures performed in accordance with AMCA Publication 511 and comply with the requirements of the AMCA Certified Ratings Programs. The AMCA Certified Ratings Seal applies to air performance ratings only.