READ BEFORE INSTALLING UNIT

MSII Window Mounting (5,000~8,000 BTU)

INSTALLATION WARNINGS AND CAUTION

The unit is for window mounting only.

Carefully read the installation manual before beginning.

Follow each step as shown.

Observe all local, state, and national electrical codes and by qualified, licensed, authorized personnel only.

Pay attention to danger and safety notices.

To avoid risk of personal injury, property damage, or product damage due to the weight of this device and sharp edges that may be exposed:

Air conditioners covered in this manual pose an excessive weight hazard. Two or more people are needed to move and install the unit. Wear protective gloves whenever lifting or carrying the unit. AVOID the sharp metal fins of front and rear coils. To prevent injury or strain, use proper lifting and carrying techniques when moving unit.

Carefully inspect location where air conditioner will be installed. Be sure it will support the weight of the unit overan extended period of time.

Handle air conditioner with care.

Make sure air conditioner does not fall during installation.

NOTE:

SAVE CARTON and these INSTALLATION INSTRUCTIONS for future reference. The carton is the best way to store unit during winter, or when not in use.

DO NOT USE ANY SCREWS OTHER THAN THOSE SPECIFIED HERE.

FOR SAFETY REASONS, THE TOP RAIL MUST BE SECURELY FASTENED WITH ALL FOUR (4) SCREWS.

Some assembly is required. Please read these instructions carefully.

 

 

 

 

 

 

Mounting Hardware

Qty.

 

 

 

 

 

 

Ǝ VFUHZV

7

 

 

 

 

 

 

lock frame

2

 

 

 

 

 

 

 

 

 

 

 

 

(For Wooden windows)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

lock frame

2

 

 

 

 

 

 

(For Vinyl-Cladwindows)

 

 

 

 

 

 

 

sash lock

1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

weather seals

5

 

 

 

 

 

 

Ǝ; Ǝ; Ǝ

 

 

 

 

 

 

 

window sash seal foam

1

 

 

 

 

 

 

 

 

Top Rail Hardware

Qty.

TOOLS NEEDED

 

 

 

 

Ǝ 6FUHZ

4

 

Philips Screwdriver

 

 

 

 

Top Rail

1

 

Drill (If pilot holes are needed)

 

 

 

 

Before installing, the top rail must be assembled on the unit.

A.Remove the air conditioner from the carton and place on a flat surface.

B.Remove top rail from the rear of the packaging material as shown in Fig. A

C.Align the hole in the top rail with those on the top of the unit as shown in Fig. B

' 6HFXUH WKH WRS UDLO WR WKH XQLW ZLWK WKH Ǝ 6FUHZV DV VKRZQ LQ )LJ &

Fig. A

Fig. B

Fig. C

Packaging

Top Rail

2020211A1446

 

1

HowInstallationto ll

LEFT + RIGHT FILLER PANEL ASSEMBLY

NOTE: Top Rail and Side Panels at each side are offset to provide the proper pitch to the rear of (5/16”). This is necessary for proper condensed water utilization and drainage. If you are not using the Side Panels for any reason, this pitch to the rear must be maintained!

Place unit on floor, a bench or a table. There is a Left and Right side Filler Panels - be sure to use the proper panel for each side. When installed, the flange for securing the panel in place to the window sill will be facing into the room.

A.Hold the side Panel in one hand and gently pull back the center to free the open end. See FIG. 1.

B.Slide the free end “I” section of the panel directly into the cabinet as shown in FIG. 2. Slide the panel down. Be sure to leave enough space to slip the top and bottom of the frame into the rails on the cabinet.

C.Once the panel has been installed on the side of the cabinet, make sure it sits securely inside the frame channel by

making slight adjustments. Slide the top and bottom ends of the frame into the top and bottom rails of the cabinet. See FIG. 3.

D. Slide the panel all the way in and repeat on the other side.

 

FIG. 1

FIG. 2 “I” section

FIG. 3 Top Rail

Bottom Rail

Your air conditioner is designed to install in standard double hung windows with opening widths of 23 to 36 inches (584 mm to 914 mm) (FIG. 4A , FIG. 4B).

Lower sash must open sufficiently to allow a clear vertical opening of 14 inches (356 mm ). Side louvers and the rear of the air conditioner must have clear air space to allow enough airflow through the condenser, for heat removal. The rear of the unit must be outdoors, not inside a building or garage.

Fig. 4A

Fig. 4B

 

 

 

Ǝ PLQ

 

 

 

 

 

 

 

 

 

 

 

Ǝ PLQ

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

WINDOW SILL

 

 

356 mm

 

 

 

 

 

INNER

 

 

 

356 mm

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

WINDOW SILL

 

 

 

 

INTERIOR

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

WALL

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Wooden Windows

 

 

 

 

 

 

 

 

 

 

 

Vinyl-CladWindows

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Storm Window:

If the air conditoner is blocked by Storm Window, add wood as shown in FIG. 5, or remove storm window before air conditioner is installed.

If Storm Window Frame must remain, be sure the drain holes or slots are not caulked or painted shut. Accumulated Rain Water or Condensation must be allowed to drain out.

 

 

 

SASH

FIG. 5

Storm window

 

 

 

 

 

 

 

 

Board

1-1/2”min

thickness as

frame or other

required, for

(38 mm)

obstruction.

proper pitch to

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

rear, along

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

entire sill.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Fasten with

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

nails or screws.

2

How to Install

Installation

Keep a firm grip on the air conditioner, carefully place the unit into the window opening so the bottom of the air conditioner frame is against the window sill (FIG. 6A & FIG. 6B). Carefully close the window behind the top rail of the unit.

FIG. 6A

FIG. 6B

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

INSIDE

 

OUTSIDE

INSIDE

 

 

 

OUTSIDE

 

 

 

 

 

Wooden Windows

 

 

 

Vinyl-CladWindows

Extend the side panels out against the window frame (FIG. 7A for wooden windows), (FIG. 7B for Vinyl-Cladwindows).

FIG. 7A

FIG. 7B

window frame

Place the frame lock between the frame extensions and the window sill as shown (FIG. 8A for wooden windows), (FIG. 8B for Vinyl-Cladwindows).

FIG. 8A

FIG. 8B

wooden windows:

Vinyl-Cladwindows:

Drive locking screws:

 

A: For wooden windows:

 

'ULYH Ǝ PP ORFNLQJ VFUHZV WKURXJK WKH IUDPH ORFN DQG LQWR WKH VLOO ),* $ NOTE:To prevent ZLQGRZ VLOO IURP VSOLWWLQJ GULOO Ǝ PP SLORW KROHV EHIRUH GULYLQJ VFUHZV 'ULYH Ǝ PP ORFNLQJ VFUHZV WKURXJK IUDPH KROHV LQWR ZLQGRZ VDVK ),* %

B: For Vinyl-Cladwindows:

'ULYH Ǝ PP ORFNLQJ VFUHZV WKURXJK WKH IUDPH ORFN DQG LQWR WKH ZLQGRZ VDVK ),* % NOTE: Before driving the screws, use a drill to drill 5 holes through the holes in the frame lock and frame extensions

LQWR WKH ZLQGRZV VDVK DV VKRZQ ),* %

),*$

),* %

3

Installation

7R VHFXUH ORZHU VDVK LQ SODFH DWWDFK ULJKW DQJOH VDVK ORFN ZLWK Ǝ PP VFUHZ DV VKRZQ ),*

NOTE: It is difficult to lock the windows with the sash lock forVinyl-Cladwindows, so you can use lock by window itself.

Cut foam window seal and insert it into the space between the upper and lower sashes (FIG. 11).

FIG. 10

FIG. 11

FOAM SEAL

After the completion of the installation, please check the machine’s lean as shown (FIG. 12A & FIG. 12B). It’s necessary for proper condensed water utilization and drainage.

FIG. 12A

FIG. 12B

 

H

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

H

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

INSIDE

OUTSIDE

 

INSIDE

 

 

 

 

 

 

 

 

 

 

 

 

OUTSIDE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Bottom Rail

 

 

 

H=H1-H2DERXW Ǝa Ǝ

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

H

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Bottom Rail

 

 

 

 

 

 

 

 

 

 

 

 

 

H1

 

 

 

 

H2

 

 

 

 

 

 

 

 

 

 

 

about

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Ǝa Ǝ

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Wooden Window

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Vinyl-CladWindow

Trim the weather seal Ǝ; Ǝ; Ǝ with a proper length,

peel off the protective backing and plug any gaps if needed ),*

DV VKRZQ ),*

Removing the air conditioner From Window

Turn the air conditioner off, and disconnect power cord.

Remove sash seal from between windows, and unscrew sash lock. Remove screws installed through frame and framelock.

Close (slide) side panels into frame.

Keeping a firm grip on air conditioner, raise sash and carefully remove.

Be careful not to spill any condensate water while lifting unit from window. Store parts WITH air conditioner.

4