Friedrich M33TYF User Manual

Size:
271.66 Kb
Download

Ductless Split Systems

Wall mounted, Tri-zoneheat pump

PURCHASER

 

 

P.O. #

 

DATE

 

 

 

 

 

 

 

 

 

PROJECT

 

 

LOCATION

 

 

 

 

 

 

 

 

 

 

 

ENGINEER

 

 

ARCHITECT

 

 

 

 

 

 

 

 

 

 

 

SUBMITTED BY

 

 

FOR APPROVAL

 

FOR REFERENCE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ITEM

PLAN DESIGNATION

QUANTITY

 

COOLING BTU/H

VOLTAGE

FRIEDRICH MODEL

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Features

LCD remote for each indoor unit

24-hourtimer and sleep timer

Auto/cool/dry/fan/heat modes

Four fan speeds heating or cooling: high/medium/low/quiet, plus auto-fan

Continuous ‘Air Sweep’ UP/DOWN

Auto-restartafter power interruptions

Auto-shutflaps close when unit is off for a sleeker appearance

Washable, reusable air filters

Removable front grille

Auto-changeover(heat pump models)

Secured remote control holder

Four different transmitter codes to prevent unintentional interference with nearby units

M27TYF, M30TYF, M36TYF

All Inverter line

M33TYF

Ductless_Tri_Zone_Heat Pump_Submittal_11

Ductless Split Systems

Wall mounted, Tri-zoneheat pump

Specifications

PERFORMANCE RATINGS

SYSTEM MODEL NO.

 

M27TYF

M30TYF

M33TYF

M36TYF1

M36TYF2

INDOOR MODEL

 

3 x MW09Y3FM

2 x MW09Y3FM

 

MW12Y3FM

MW09Y3FM

2 x MW12Y3FM

2 x MW09Y3FM

 

MW18Y3FM

3 x MW12Y3FM

OUTDOOR MODEL

 

MR36TQY3F

MR36TQY3F

MR36TQY3F

MR36TQY3F

MR36TQY3F

 

 

 

 

 

 

 

 

 

 

Capacity Cooling

Btu

9200 ea.

9300 ea.

 

11800

9400

11800 ea.

9100 ea.

 

17000

11700 ea.

Capacity Cooling Min - Max

Btu

5100-11300ea.

5100-11300ea.

 

5100-13600ea

5100-11300ea.

5100-13600ea

5100-11300ea.

 

6100-19000ea.

5100-13600ea

 

 

 

 

 

 

 

 

 

 

 

 

Sensible Heat Ratio

 

0.71

0.71

 

0.71

0.71

0.71

0.71

 

0.71

0.71

Capacity Heating @ 47°F

Btu

11200 ea.

11000 ea.

 

14000

10700

13600 ea.

9800 ea.

 

18400

12700 ea.

Capacity Heating Min - Max

Btu

5100-13000ea.

5100-13000ea.

 

5100-15400ea.

5100-13000ea.

5100-15400ea.

5100-13000ea.

 

5500-23000ea

5100-15400ea.

 

 

 

 

 

 

 

 

 

 

 

 

Capacity Heating @ 17°F

Btu

8300 ea.

7700 ea.

 

9800

7200

9200 ea.

6700 ea.

 

12500

8600 ea.

HSPF

 

9.0

9.0

9.0

 

9.0

 

9.0

 

 

 

 

 

 

 

SEER

 

15.0

15.0

15.0

15.0

15.0

EER

 

10.0

9.2

8.8

 

8.8

 

8.8

Moisture Removal

Pts/h

2.9 ea.

2.9 ea.

 

3.7

2.9

3.7 ea.

2.9 ea.

 

5.7

3.7 ea.

 

 

 

 

 

 

 

 

 

 

 

 

Airflow (Quiet, Low, Med, High)

CFM

185,220,260,295

185,220,260,295

 

215,250,305,355

185,220,260,295

215,250,305,355

185,220,260,295

 

240,290,355,415

215,250,305,355

Sound Rating - Indoor

dB-A

27,29,33,37

27,29,33,37

 

30,34,39,42

27,29,33,37

30,34,39,42

27,29,33,37

 

33,39,42,46

30,34,39,42

 

 

 

 

 

 

 

 

 

 

 

Sound Rating - Outdoor

dB-A

52

52

52

 

52

 

52

Operationg Range (heating)

°F

0 - 115 (14 - 75)

0 - 115 (14 - 75)

0 - 115 (14 - 75)

0 - 115 (14 - 75)

0 - 115 (14 - 75)

Est. Yearly Operating Cost

 

$216

$254

 

$254

$296

$296

$320

 

$320

$318

 

 

 

 

 

 

 

 

 

 

ELECTRICAL DATA (all indoor units receive power from outdoor unit; values listed are total)

 

 

 

 

 

 

Power Source

 

230/(208)-60-1

230/(208)-60-1

230/(208)-60-1

230/(208)-60-1

230/(208)-60-1

 

 

 

 

 

 

 

Min. Ampacity

A

22.5

22.5

22.5

22.5

22.5

Cooling Watts

W

2710

3180

3710

4000

3980

Max. TD Fuse/Breaker

A

30

30

30

 

30

 

30

 

 

 

 

 

 

 

 

 

 

 

 

REFRIGERATION SYSTEM

 

 

 

 

 

 

 

 

 

 

 

Refrigerant

 

R410A

R410A

R410A

R410A

R410A

 

 

 

 

 

 

 

Compressor Type

 

Inverter

Inverter

Inverter

Inverter

Inverter

Connections

 

Flare

Flare

Flare

Flare

Flare

Liquid Line O.D.

in

1/4"

1/4"

1/4"

1/4"

 

1/4"

1/4"

 

 

 

 

 

 

 

 

 

Suction Line O.D.

in

3/8"

3/8"

3/8"

3/8"

 

1/2"

3/8"

Factory Precharge

ft

165'

165'

165'

165'

165'

 

 

 

 

 

 

 

 

 

 

Max. Line Length

ft

Each unit:82 Total:230

Each unit:82

Total:230

Each unit:82

Total:230

Each unit:82

Total:230

Each unit:82Total:230

Max. Height Difference

ft

49'

49'

49'

 

49'

 

49'

DIMENSIONS & WEIGHT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Indoor Unit

 

 

 

 

 

 

 

 

 

 

 

W x H x D

in

31 1/8" x 10 7/8" x 8 1/2" ea.

31 1/8" x 10 7/8" x 8 1/2" ea.

31 1/8" x 10 7/8" x 8 1/2"

31 1/8" x 10 7/8" x 8 1/2"

31 1/8" x 10 7/8" x 8 1/2"

 

 

 

 

 

 

 

 

 

 

Net Weight

lbs

21 ea.

21 ea.

 

21

21

21 ea.

21 ea.

 

21

21 ea.

Shipping Weight

lbs

26 ea.

26 ea.

 

26

26

26 ea.

26 ea.

 

26

26 ea.

Outdoor Unit

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

W x H x D

in

35 3/8" x 32 5/8" x 13"

35 3/8" x 32 5/8" x 13"

35 3/8" x 32 5/8" x 13"

35 3/8" x 32 5/8" x 13"

35 3/8" x 32 5/8" x 13"

Net Weight

lbs

149

149

149

 

149

149

 

 

 

 

 

 

 

 

Shipping Weight

lbs

167

167

167

 

167

167

NOTE: All models have low ambient capabilities built-in.Capacity is reduced as 0 degrees Fahrenheit is approached.

NOTE: All R410A models have 1/2˝ UNF 20 thread per inch charging and vacuuming ports. An adapter must be used for 1/4˝ gauges. Adapter part number 67270018 is available through Friedrich parts distributors.

Due to continuing research in new energy-savingtechnology, specifications are subject to change without notice.

Refrigeration line sets

USED WITH:

LENGTH-FT.

LIQUID

SUCTION

KIT#

 

 

 

 

 

All 9000 and

15'

1/4”

3/8”

T32150

12000 Btu

 

 

 

 

35'

1/4”

3/8”

T32350

indoor units

MW18Y3FM

15'

1/4”

1/2”

T42150

indoor units

35'

1/4”

1/2”

T42350

Insulated line sets are available for all Friedrich split systems in 15 ft. and 35 ft. lengths. Each line set is equipped with flare nuts on both ends. Both liquid and suction lines are insulated. Line sets can be joined together with field supplied double female connectors. Each system requires one line set for each indoor unit installed. On multi-zonesystems, line sets should be ordered based on individual indoor unit capacities not total system capacity. For example, a M18DYF uses 2 line sets for 9,000 Btu units, not 1 for the 18,000 Btu product.