Friedrich C24YF User Manual

Size:
272.79 Kb
Download

Ductless Split Systems

Ceiling and floor installed heat pumps

PURCHASER

 

 

P.O. #

 

DATE

 

 

 

 

 

 

 

 

 

PROJECT

 

 

LOCATION

 

 

 

 

 

 

 

 

 

 

 

ENGINEER

 

 

ARCHITECT

 

 

 

 

 

 

 

 

 

 

 

SUBMITTED BY

 

 

FOR APPROVAL

 

FOR REFERENCE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ITEM

PLAN DESIGNATION

QUANTITY

 

COOLING BTU/H

VOLTAGE

FRIEDRICH MODEL

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Features

• LCD remote for each indoor unit

 

 

24-hourtimer and sleep timer

 

 

• Auto/cool/dry/fan/heat modes

 

 

• Four fan speeds heating or cooling:

 

 

high/medium/low/quiet, plus auto-fan

 

 

• Continuous ‘Air Sweep’ UP/DOWN

 

 

Auto-restartafter power interruptions

 

 

Auto-shutflaps close when unit is off

 

 

for a sleeker appearance

 

 

• Washable, reusable air filters

 

 

• Removable front grille

 

 

Auto-changeover(heat pump models)

S24YF

C24YF

• Secured remote control holder

 

 

Four different transmitter codes to prevent unintentional interference with nearby units

All Inverter line

S36YF

Ductless_Ceiling_Flloor_Heat Pumps_Submittal_11

Ductless Split Systems

Ceiling and floor installed heat pumps

Specifications

PERFORMANCE RATINGS

SYSTEM MODEL NO.

 

S24YF

S36YF

C24YF

INDOOR MODEL

 

MS24Y3F

MS36Y3F

MC24Y3F

OUTDOOR MODEL

 

MR24UY3F

MR36Y3F

MR24UY3F

 

 

 

 

 

Capacity Cooling

Btu

22200

34100

22200

Capacity Cooling Min - Max

Btu

5000-27300

8500-36000

5000-27300

 

 

 

 

 

Sensible Heat Ratio

 

0.62

0.67

0.64

Capacity Heating @ 47°F

Btu

24,200

38,200

24,200

Capacity Heating Min - Max

Btu

5000-29000

9200-42700

5000-29000

 

 

 

 

 

Capacity Heating @ 17°F

Btu

20,100

27,100

20,100

HSPF

 

8.5

8.5

8.5

 

 

 

 

 

SEER

 

15

14

15

EER

 

9.8

8.1

10.6

Moisture Removal

Pts/h

7.4

7.4

6.4

 

 

 

 

 

Airflow (Low, Med, High)

CFM

371, 436, 518

842, 977, 1089

436, 536, 618

Sound Rating - Indoor

dB-A

38, 43, 47

41, 45, 48

38, 43, 45

 

 

 

 

 

Sound Rating - Outdoor

dB-A

53

54

53

Operationg Range (heating)

°F

0 - 115 (14 - 75)

0 - 115 (14 - 75)

0 - 115 (14 - 75)

Est. Yearly Operating Cost

 

$180

$337

$168

 

 

 

 

 

ELECTRICAL DATA

 

 

 

 

Power Source

 

230/208-60-1

230/208-60-1

230/208-60-1

 

 

 

 

 

Min. Ampacity

A

15.5

23

15.5

Cooling Watts

W

2250

4220

2100

Max. TD Fuse/Breaker

A

20

30

20

 

 

 

 

 

REFRIGERATION SYSTEM

 

 

 

 

Refrigerant

 

R410A

R410A

R410A

 

 

 

 

 

Compressor Type

 

Inverter (Twin Rotary)

Inverter (Twin Rotary)

Inverter (Twin Rotary)

Connections

 

Flare

Flare

Flare

Liquid Line O.D.

in

3/8"

3/8"

3/8"

 

 

 

 

 

Suction Line O.D.

in

5/8"

5/8"

5/8"

Factory Precharge

ft

50'

50'

50'

 

 

 

 

 

Max. Line Length

ft

165'

165'

165'

Max. Height Difference

ft

66'

98'

66'

DIMENSIONS & WEIGHT

 

 

 

 

 

 

 

 

 

Indoor Unit

 

 

 

 

W x H x D

in

39" x 7 7/8" x 25 3/4"

65 3/8" x 9 1/2" x 27 1/2"

32 5/8" x 9 5/8" x 32 5/8"

 

 

 

 

 

Net Weight

lbs

62

106

75

Shipping Weight

lbs

82

134

97

Outdoor Unit

 

 

 

 

 

 

 

 

 

W x H x D

in

35 3/8" x 32 5/8" x 13"

35 3/8" x 32 5/8" x 13"

35 3/8" x 32 5/8" x 13"

Net Weight

lbs

141

141

141

 

 

 

 

 

Shipping Weight

lbs

154

154

154

NOTE: All models have low ambient capabilities built-in.Capacity is reduced as 0 degrees Fahrenheit is approached.

NOTE: All R410A models have 1/2˝ UNF 20 thread per inch charging and vacuuming ports. An adapter must be used for 1/4˝ gauges. Adapter part number 67270018 is available through Friedrich parts distributors.

Due to continuing research in new energy-savingtechnology,

specifications are subject to change without notice.

Refrigeration line sets

USED WITH:

LENGTH-FT.

LIQUID

SUCTION

KIT#

 

 

 

 

 

S24YF, S36YF

15'

3/8”

5/8”

T53150

 

 

 

 

and C24YF

35'

3/8”

5/8”

T53350

systems

 

 

 

 

 

Insulated line sets are available for all Friedrich split systems in 15 ft. and 35 ft. lengths. Each line set is equipped with flare nuts on both ends. Both liquid and suction lines are insulated. Line sets can be joined together with field supplied double female connectors. Each system requires one line set for each indoor unit installed. On multi-zonesystems, line sets should be ordered based on individual indoor unit capacities not total system capacity. For example, a M18DYF uses 2 line sets for 9,000 Btu units, not 1 for the 18,000 Btu product.

Ductless_Ceiling_Floor_Heat_Pumps_Submittal_11