INSTALLATION &

OPERATION GUIDE

VERT-I-PAK® A-SERIES

SINGLE PACKAGE

VERTICAL AIR

CONDITIONING SYSTEM

9,000 - 18,000 BTU/h

920-075-08(10-06)

920-075-08

 

 

Table of Contents

I.

General Specifications

 

 

Installation Recommendations ..........................................................................................................................................

3

 

Model Number Identification Guide ...................................................................................................................................

4

 

VERT-I-PAKChassis Specifications....................................................................................................................................

4

II.Installation

1.

Utility Closet Dimensions ...................................................................................................................................................

5

2.

Wall Plenum & Architectural Louver Installation ................................................................................................................

6

3.

Electrical Information......................................................................................................................................................

7-9

4.

Indoor Return Air Grille Installation ..................................................................................................................................

10

5.

Ductwork Preparation and CFM .......................................................................................................................................

11

6.

Chassis Installation..........................................................................................................................................................

11

7. Chassis Final Connections (Electrical, Duct, Drain & Wall Thermostat)............................................................................

12

8.

Final Installation Checklist...............................................................................................................................................

12

III.Chassis Operation

9.

Thermostat Control ..........................................................................................................................................................

13

10.

Low Ambient Protection for Compressor & Fan................................................................................................................

13

11.

Heating Defrost (Heat Pump Models only)........................................................................................................................

13

12.

Fresh Air Door...................................................................................................................................................................

13

13.

Condensate Disposal System ..........................................................................................................................................

13

IV.

Service & Warranty

 

14.

Servicing / Chassis Quick Changeouts.............................................................................................................................

13

15.

Warranty...........................................................................................................................................................................

14

V.

Vert-I-PakAccessories ....................................................................................................................................................

15

Please read this manual thoroughly prior to equipment installation or operation. It is the installer’s responsibility to properly apply and install the equipment. Installation must be in conformance with the NFPA 70-2002National Electric Code or current edition and Universal Mechanical Code current edition and applicable local or national codes.

Proper installation is not difficult but it is essential.

2

920-075-08

Vert-I-PakInstallation Recommendations

For proper unit performance and maximum operating life please refer to the minimum installation clearances below.

Figure 1

VERT-I-PAK® units must be installed on an outside wall. Confined spaces and/or covered areas should be avoided. Units should be installed no closer than 12" apart when two units are side by side. If three of more units are to operate next to one another allow a minimum of 60" between units or pairs of units. Also, a vertical clearance of 60" should be maintained between units. Units installed on the bottom floor should be mounted at least 6" off of the ground.

6"

 

B

 

 

60" 60"

A

 

 

SMALL RECESS OK

LARGER RECESS OK. IF A> 5xB

60"

60"

 

 

60"

 

 

60"

 

 

 

 

 

60"

60"

 

60"

 

 

 

 

 

60"

60"

 

 

 

6"

6"

 

 

12"

 

 

 

 

Figure 2

Any time obstructions are present use the following guidelines for proper spacing from the VERT-I-PAKlouver:

For minor obstructions such as lamp poles or small shrubbery a clearance of 24" from the outdoor louver should be maintained.

For major obstructions such as a solid fence, wall or other heat rejecting device like a condensing unit, a minimum distance of 72" should be kept.

BUILDING

60"

24"

 

VPAK

12" VPAK

VPAK

24"

SHRUB

POLE

OUTDOOR

72"

CONDENSING

 

UNIT

FENCE

 

 

MAJOR OBSTRUCTION

The above suggestions are for reference only and do not represent all possible installations. Please contact the factory for information regarding affects of other installation arrangements.

By following these simple recommendations you can be confident that your Friedrich Vert-I-Pak® will provide years ofworry-freeoperation.

3

920-075-08

Section I. General Specifications

Vert-I-Pak® Model Identification Guide

MODEL NUMBER

V

E

A

09

K

 

34

RT

H

 

 

 

SERIES

 

 

 

 

 

 

 

 

 

 

ENGINEERING CODE

V=Vertical Series

 

 

 

 

 

 

 

 

 

OPTIONS

 

 

 

 

 

 

 

 

 

 

 

E =Cooling with electric heat

 

 

 

 

 

 

 

 

 

RT = Standard Remote Operation

H =Heat Pump

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ELECTRIC HEATER SIZE

 

 

 

 

 

 

 

 

 

DESIGN SERIES

 

 

 

 

 

 

 

 

 

 

 

 

 

A Series

A = 32"/47" Cabinet

 

 

 

 

 

 

25 =

2.5 KW

 

 

 

 

 

 

 

 

34 =

3.4 KW

NOMINAL CAPACITY

 

 

 

 

 

 

 

 

 

 

 

 

50 =

5.0 KW*

A Series (Btu/h)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

75 =

7.5 KW**

09 = 9,000

18 = 18,000

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

12 = 12,000

24 = 24,000

 

 

 

 

 

 

 

Refer to electrical data chart for heater/unit compatibility.

 

 

 

 

 

 

 

 

 

* Not available on 9000 BTU models.

VOLTAGE

 

 

 

 

 

 

 

 

K = 208/230V-1Ph-60Hz

 

 

 

 

 

 

 

** 24000 BTU only.

Vert-I-Pak® Chassis Specifications

MODEL:

V(E,H)A09

V(E,H)A12

V(E,H)A18

Voltage (V)

230 / 208

230 / 208

230 / 208

Refrigerant

R-22

R-22

R-22

Chassis Width

23.125"

23.125"

23.125"

Chassis Depth

23.125"

23.125"

23.125"

Chassis Height **

32.25"

32.25"

32.25"

Shipping W x D x H

26.00" x 28.50" x 35.00"

26.00" x 28.50" x 35.00"

26.00" x 28.50" x 35.00"

Supply Duct Collar ***

10"

10"

10"

Drain Connection

3/4" FPT

3/4" FPT

3/4" FPT

Min. Circuit Amps

 

See Chassis Nameplate

 

CFM Indoor

 

See Charts 2 & 3 (Page 10)

 

Max. Duct ESP

.3 in. water

.3 in. water

.3 in. water

NOTES:

**Height includes 2" duct collar & isolators under unit.

***Factory collar accepts 10" flex duct.

4

920-075-08

II. Installation

1) Utility Closet Dimensions

Recommended utility closet dimensions and a typical indoor installation are illustrated in Figure 3. Three inches minimum clearance on three sides of the unit must be allowed for return airflow, installation access and service access. See Figures 3 and 4 for clearances and reference dimensions.

Figure 3

Typical Utility Closet

 

Chassis Shown in Closet, on Optional Platform

25" x 20" Filter

Rigid Ductwork

(Field Supplied)

Electrical

 

 

Connection

 

Exterior Wall

 

Thermostat

VPRG4 Access Panel and

Wiring

 

Return Air Filter Grille

Power

See Figure 8, Page 10

Disconnect

for return air options

 

Vert-I-PakChassis dimensions:

23 1/8" wide x 231/8" deep x 321/4" high.

VPAWP1-8/1-14Wall Plenumcut-outdimensions 245/8" wide x 307/8" high.

VPRG4 Access Panel cutout dimensions: 27" wide by 55 3/4" high.

See Figure 9 (Pg 11) for proper chassis installation.

Optional field installed dran pan (refer to local codes)

Optional

Platform

Flexible Ductwork

VPAWP1-8/1-14

Wall Plenum

Plenum Divider

3/4" FPT Drain

Connection

Chassis installs 2 3/8" into Plenum

3" Clearance on all three sides minimum for service and installation.

Figure 4

Top View

Outside Wall

5

920-075-08

2) Wall Plenum and Architectural Louver Installation

A. Install the wall plenum (VPAWP1-8/1-14)components in accordance with the installation instructions provided with each accessory.

IMPORTANT REMINDER: FRIEDRICH WALL PLENUM IS NOT DESIGNED TO CARRY STRUCTURAL LOADS. PROPER WALL HEADER CONSTRUCTION IS REQUIRED. THE PLENUM REQUIRES PROPER FLASHING, SHIM AND CAULK FOR A WEATHER RESISTANT INSTALLATION.

B. Ensure that the divider is adjusted properly for the depth of the wall in accordance with the accessory installation manual.

Figure 5

Wall Plenum & Outdoor Louver Installation

Proper Header

Caulk all 8

 

flange corners

Proper Flashing

Proper Caulking

Inside Wall Plenum

(Part B)

Outside Wall

Proper Caulking

 

Architectural louver VPAL2 mounted

 

on the outside wall plenum (Part A)

Proper Flashing

 

Rough opening dimension 24 5/8" wide x 307/8" high.

Ensure that the bottom of the plenum is 3/4" from the floor of the closet.

For proper airflow, maintain a minimum distance of 12" between Vert-I-Pakunits (see Figure 1, page 3). Consult the factory for any installation or application questions.

6

920-075-08

3) Electrical Data

Electrical Data

Model

V(E,H)A09K25V(E,H)A09K34V(E,H)09K50V(E,H)A12K25V(E,H)A12K34V(E,H,)A12K50V(E,H)A18K25V(E,H)A18K34V(E,H)A18K50

 

Voltage ( V)

230/208

230/208

230/208

230/208 230/208 230/208 230/208 230/208 230/208

LRA - Comp. (A)

21

21

21

24.0

24.0

24.0

47

47

47

Cooling Current (A)

4.4/4. 9

4.4/4. 9

4.4/4.9

5.5/6.1

5.5/6.1

5.5/6.1

9.2/10.2

9.2/10.2

9.2/10.2

MIN. Ckt. Amps (A)

15

20

30

15

20

30

15

20

30

Power Connection

HARD WIRED

HARD WIRED

HARD WIRED

Sample Nameplate (see your chassis nameplate)

FRIEDRICH AIR CONDITIONING CO.

 

WARNING

120524

MODEL NO 1

 

 

 

LISTED

SERIAL NO *

 

 

 

 

SAN ANTONIO, TEXAS

 

 

HEATING AND

 

 

VOLTS: 24,33,34

 

 

ELECTRICAL SHOCK AND

COOLING EQUIPMENT

VOLTAGE RANGE: 255-197

 

REFRIG CHARGE: 7 OZS. R22

 

 

 

MOVING PARTS HAZARD

APPLICABLE PATENTS:

DESIGN PRESSURE: 575 PSIG HS / 150 PSIG LS

COOLING: BTU/HR 8

 

CAN CAUSE INJURY OR

US 6,065,296

SEER: 10

COP: 16

 

NY MEA NO.: 295-00-E

HEAT PUMP BTU/HR: 14

 

DEATH

TOTAL COOLING AMPS: 9

 

USE ONE OF THE

TOTAL ELEC. HEAT AMPS: 15

 

PULL OUT DISCONNECT

FOLLOWING ITEMS

ELECTRIC HEAT WATTS: 18

 

FROM EACH CATEGORY

FOR PERMANENTLY CONNECTED UNITS ONLY:

HE D LOCATED ON THE

TO COMPLETE THE

COMP'. PLA 11 LRA 12

 

FRONT OF THIS UNIT TO

ASSEMBLY

MOTOR: FLA 13 HP 19

 

WALL PLENUM:

HEATER AMPS: 17

 

DIS BLE POWER BEFORE

MIN. CKT AMP ~0 USE ~1 MAX. TIME DELAY FU

VPAWP1 -8

 

 

 

SERVICING.

VPAWP1 -14

OR HACR TYPE CIRCUIT BREAKER.

 

SAMPLE

GENERAL UNIT INFORMATION:

 

OUTDOOR GRILLE

 

 

VPAL2

MAX OUTLET AIR TEMPERATURE: 2OO'F

 

 

INDOOR GRILLE

MAX EXTERNAL STATIC PRESSURE ELECTRIC

 

HEAT'..5 IN. WATER

 

 

VPRG1

"O" CLEARANCE TO COMBUSTIBLE MATERIAL

 

VPRG2

USE ON SINGLE OUTLET CIRCUIT ONLY

 

VPRG5

 

 

 

 

 

 

 

Important: all 208/230v chassis must be hard wired with properly sized breaker. See nameplate for specific chassis electrical requirements. See page 8 - Figure 5 for unit wiring and wall thermostat wiring. See page 8 for wire size. Use HACR type breakers to avoid nuisance trips. All field wiring must be done in accordance with nec and local codes.

7

920-075-08

3) Electrical Data (continued)

Figure 6

Electrical Requirements

Note: All field wiring must comply with NEC and local codes. It is the responsibility of the installer to insure that the electrical codes are met.

 

Wire Size

Use ONLY wiring size recommended for single

 

outlet branch circuit.

 

 

 

 

 

 

 

Use ONLY type and size fuse or HACR circuit

 

Fuse/Circuit

breaker indicated on unit's rating plate (See sample

 

Breaker

on page 6). Proper current protection to the unit is

 

 

the responsibility of the owner.

 

 

 

 

 

Unit MUST be grounded from branch circuit to

 

Grounding

unit, or through separate ground wire provided on

 

permanently connected units. Be sure that branch

 

 

 

 

circuit or general purpose outlet is grounded.

 

 

 

 

 

Use recommended wire size given in tables and

 

Wire Sizing

install a single branch circuit. All wiring must comply

 

with local and national codes. NOTE: Use copper

 

 

 

 

conductors only.

 

 

 

Electrical Rating Tables

NOTE: Use copper conductors ONLY. Wire sizes are per NEC. Check local codes for overseas applications

Recommended branch circuit wire sizes*

Nameplate

AWG Wire size**

maximum circuit

 

breaker size

 

 

 

15A

14

20A

12

30A

10

AWG — American Wire Gauge

*Single circuit from main box

**Based on copper wire, single insulated conductor at 60°C

CAUTION

Electric shock hazard.

Turn OFF electric power before service or installation.

All electrical connections and wiring MUST be installed by a qualified electrician and conformtotheNationalElectricalCodeand all local codes which have jurisdiction.

Failure to do so can result in property damage, personal injury and/or death.

8

920-075-08

3) Electrical Data (continued)

Figure 7

Electrical & Thermostat Wiring Diagrams

208V 240V

RT4

THERMOSTAT (FRONT)

Note: the diagram above illustrates the typical thermostat wiring and 208 volt transformer wiring. See the unit control panel for the actual unit wiring diagram and schematic.

9

920-075-08

4) Indoor Return Air Grille Installation

There are two Indoor Return Air Grille options as shown in Figure 8. Choose the option that best suits your needs. Use the installation instructions provided with accessories for installation details.

Figure 8

Return Air Grille Options

Option 1

VPRG4

Return Air Grille with Access Panel

A field-supplied(25" x 20") filter is mounted inside the hinged access door.

Option 2

Field Supplied

Return Air Grille

Must have a minumum of 220 square inches of free area.

All Vert-I-Pakchassis are shipped with a 14 x 20 filter installed. If an accessory filter holder is to be used, you MUST remove the factory shipped filter from the chassis. Do NOT use two filters

Notes:

A.These are the Friedrich recommended return air grille / filter / access panel arrangements. Consult the factory on other arrangements. Improper return air arrangements will cause performance problems.

B.Return air arrangements are shown from the front, but can also be installed from the right or left side of the unit.

10