Vert-I-Pak®

Single Package Vertical Air Conditioning System

A-Series

24,000 BTU/h

Installation&OperationManual

920-159-01(10-03)

 

 

920-159-01(10-03)

 

 

TableofContents

InstallationRecommendations.........................................................................................................................................................

3

I.

GeneralSpecifications

 

 

ModelNumberIdentificationGuide...................................................................................................................................

4

 

VERT-I-PAKChassisSpecifications...................................................................................................................................

4

II.Installation

1.

UtilityClosetDimensions...................................................................................................................................................

5

2.

WallPlenum&ArchitecturalLouverInstallation ................................................................................................................

6

3.

ElectricalInformation .....................................................................................................................................................

7-9

4.

IndoorReturnAirGrilleInstallation..................................................................................................................................

10

5.

DuctworkPreparationandCFM.......................................................................................................................................

11

6.

ChassisInstallation..........................................................................................................................................................

11

7. ChassisFinalConnections(Electrical,Duct,Drain&WallThermostat)............................................................................

12

8.

FinalInstallationChecklist...............................................................................................................................................

12

III.ChassisOperation

9.

ThermostatControl..........................................................................................................................................................

12

10.

LowAmbientProtectionforCompressor&Fan................................................................................................................

12

11.

HeatingDefrost(HeatPumpModelsonly)........................................................................................................................

12

12.

FreshAirDoor...................................................................................................................................................................

13

13.

CondensateDisposalSystem ..........................................................................................................................................

13

IV.

Service,Maintenance&Warranty

 

14.

Servicing/ChassisQuickChangeouts.............................................................................................................................

13

15.

RoutineMaintenance.......................................................................................................................................................

13

16.

Warranty ..........................................................................................................................................................................

14

V.

Vert-I-PakAccessories ....................................................................................................................................................

15

Please read this manual thoroughly prior to equipment installation or operation. It is the installer’s responsibility to properly apply and install the equipment. Installation must be in conformance with theNFPA70-2002NationalElectricCodeorcurrenteditionandUniversalMechanicalCodecurrentedition and applicable local or national codes.

Proper installation is not difficult but it is essential.

2

920-159-01(10-03)

Vert-I-PakInstallationRecommendations

Forproperunitperformanceandmaximumoperatinglifepleaserefertotheminimuminstallationclearancesbelow.

Figure1

VERT-I-PAK® units must be installed on an outside wall. Confined spaces and/or covered areas should be avoided. Units should be installed no closer than 12" apart when two units are side by side. If three of more units are to operate next to one another allow a minimum of 60" between units or pairs of units. Also, a vertical clearance of 60" should be maintained between units. Units installed on the bottom floor should be mounted at least 6" off of the ground.

6"

 

 

B

 

 

60"

60"

A

 

 

SMALL RECESS OK

LARGER RECESS OK. IF A> 5xB

60"

60"

 

 

 

60"

 

60"

 

 

60"

60"

60"

 

 

60"

60"

 

6"

6"

12"

 

 

Figure2

Any time obstructions are present use the following guidelines for proper spacing from the VERT-I-PAKlouver:

For minor obstructions such as lamp poles or small shrubbery a clearance of 24" from the outdoor louver should be maintained.

For major obstructions such as a solid fence, wall or other heat rejecting device like a condensing unit, a minimum distance of 72" should be kept.

BUILDING

 

60"

24"

 

VPAK

12"

VPAK

VPAK

 

 

 

24"

 

POLE

 

SHRUB

 

 

 

OUTDOOR

 

 

72"

CONDENSING

 

 

 

UNIT

FENCE

 

 

MAJOR OBSTRUCTION

Theabovesuggestionsareforreferenceonlyanddonotrepresentallpossibleinstallations.Pleasecontactthefactory for information regarding affects of other installation arrangements.

By following these simple recommendations you can be confident that your Friedrich Vert-I-Pak® will provide years ofworry-freeoperation.

3

920-159-01(10-03)

SectionI. GeneralSpecifications

VERT-I-PAK® MODEL IDENTIFICATION GUIDE

MODEL NUMBER

V

E

A

24

K

50

RT

A

SERIES

 

 

 

 

 

 

 

ENGINEERING CODE

 

 

 

 

 

 

 

 

OPTIONS

V=Vertical Series

 

 

 

 

 

 

 

 

 

 

 

 

 

 

RT = Standard Remote Operation

E=Cooling with or without electric heat

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SP = Seacoast Protected

H=Heat Pump

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ELECTRIC HEATER SIZE

DESIGN SERIES

 

 

 

 

 

 

 

 

 

 

 

 

A-Series

A = 32" and 47" Cabinet

 

 

 

 

 

 

 

 

 

 

 

00

= No electric heat

 

 

 

 

 

 

NOMINAL CAPACITY

 

 

 

 

 

25

= 2.5 KW

 

 

 

 

 

34

= 3.4 KW

A-Series(Btu/h)

 

 

 

 

 

 

 

 

 

 

50

= 5.0 KW

09 = 9,000

 

 

 

 

 

 

 

 

 

 

75

= 7.5 KW

12 = 12,000

 

 

 

 

 

 

 

 

 

 

10

= 10 KW

18 = 18,000

 

 

 

 

 

 

 

 

 

 

 

 

 

 

24 = 24,000

 

 

 

 

 

 

 

 

 

VOLTAGE

 

 

 

 

 

 

 

 

 

K = 208/230V-1Ph-60Hz

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Vert-I-Pak® Chassis Specifications

MODEL:

V(E,H)A24

Voltage (V)

230/208

Refrigerant

R-22

Chassis Width

23.125

Chassis Depth

23.125

Chassis Height **

47.25

Supply Duct Collar ***

10"

Drain Connection

3/4" FPT

Min. Circuit Amps

See Nameplate

CFM Indoor

See chart, pg. 11

Max. Duct ESP

.4 in. water

NOTES:

**Height includes 2" duct collar & isolators under unit.

***Factory collar accepts 10" flex duct.

4

920-159-01(10-03)

II. Installation

1) UtilityClosetDimensions

Recommended utility closet dimensions and a typical indoor installation are illustrated in Figure 1. Three inches minimum clearance on three sides of the unit must be allowed for return airflow, installation access and service access. See Figures 1 & 2 for clearances and reference dimensions.

Figure3

Typical Utility Closet

Chassis Shown in Closet, on Optional Platform

Field-supplied

Rigid Ductwork

 

Filter (25" x 20")

 

58"

 

Exterior Wall

 

Flexible Ductwork

Power

VPAWP1-8/1-14Wall Plenum

 

Disconnect

Plenum

 

29"

VPRG4 Access Panel &

Return Air Filter Grille

Optional Platform

3" Clearance on all

 

 

three sides

 

VPDP1 drain pan

minimum for

 

Chassis is

beneath unit is

 

 

shipped with

required on all

 

vibration

VEA/VHA24 units.

 

isolators

Drain pan must be

 

installed

installed prior to

 

 

chassis installation

Figure4

Top View

 

 

Vert-I-PakChassis2-tondimensions:

control box

 

23" wide x 23" deep x 47 1/4" high.

 

VPAWP1-8/1-14Wall Plenumcut-out

 

electrical

dimensions 24 5/8" wide x 30 7/8" high.

 

entrance

 

 

VPRG4 Access Panel cutout dimensions:

 

 

27" wide by 55 3/4" high.

 

See Figure 8 (Page 10) for proper

 

 

chassis installation.

 

NOTE: Drain pan must be installed in closet prior to chassis

 

insertion into plenum. See Figure 7 (page 8) for drain pan

 

installation details.

5

920-159-01(10-03)

2)WallPlenumandArchitecturalLouverInstallation

A. Install the wall plenum (VPAWP1-8/1-14)components in accordance with the installation instructions provided with each accessory.

IMPORTANT REMINDER: FRIEDRICH WALL PLENUM IS NOT DESIGNED TO CARRY STRUCTURAL LOADS. PROPER WALL HEADER CONSTRUCTION IS REQUIRED. THE PLENUM REQUIRES PROPER FLASHING, SHIM AND CAULK FOR A WEATHER RESISTANT INSTALLATION.

B. Ensure that the divider is adjusted properly for the depth of the wall in accordance with the accessory installation manual

Figure5

WallPlenum&OutdoorLouverInstallation

Proper Header

Caulk all 8

 

flange corners

Proper Flashing

Proper Caulking

Inside Wall Plenum

(Part B)

Outside Wall

Proper Caulking

 

Architectural louver VPAL2 mounted

 

on the outside wall plenum (Part A)

Proper Flashing

 

Rough opening dimension 24 5/8" wide x 30 7/8" high.

Ensure that the bottom of the plenum is 1 1/2" from the floor of the closet. Note: 9,000 / 12,000 / 18,000 installation height may be different. Refer to specific installation manual for clarification.

For proper airflow, maintain a minimum distance of 12" between Vert-I-Pakunits. Consult the factory for any installation or application questions.

6

920-159-01(10-03)

3)ElectricalInformation

Electrical Data

 

 

 

 

 

MODEL

 

Voltage ( V)

VHA/VEA24K25 VHA/VEA24K34 VHA/VEA24K50VHA/VEA24K75VHA/VEA24K10VHA/VEA24K00

230/208

230/208

230/208

230/208

230/208

230/208

LRA - Comp. (A)

68

68

68

68

68

68

Cooling Current (A)

13.7/12.4

13.7/12.4 13.7/12.4 13.7/12.4 13.7/12.4 13.7/12.4

MIN. Ckt. Amps (A)

17.2/15.9

22.1/20.3 30.7/28.1 44.3/40.3 57.9/52.7 15.6/15.6

Max Branch Circuit Fust (Amps)

25/25

25/25

35/30

45/45

60/60

20/20

Power Connection

 

 

HARD WIRED

 

 

Recommended Branch

14/14

12/12

8/10

6/6

4/6

14/14

Circuit Wire Sizes*

AWG - American Wire Gauge

 

 

 

 

 

 

* Single circuit from main box. Based on copper wire, single insulated conductor at 60°C.

NOTE: Use copper conductors ONLY. Wire sizes are per NEC. Check local codes for overseas applications.

Sample Nameplate (see your chassis nameplate)

7

920-159-01(10-03)

IMPORTANT: ALL 208/230V CHASSIS MUST BE HARD WIRED WITH PROPERLY SIZED BREAKER. SEE NAMEPLATE FOR SPECIFIC CHASSIS ELECTRICAL REQUIREMENTS. SEE PAGE 9 - FIGURE 8 FOR UNIT WIRING AND WALL THERMOSTAT WIRING. SEE PAGE 7 FOR WIRE SIZE. USE HACR TYPE BREAKERS TO AVOID NUISANCE TRIPS. ALL FIELD WIRING MUST BE DONE IN ACCORDANCE WITH NEC AND LOCAL CODES.

3) Electrical Information (continued)

Figure6

ElectricalRequirements

Note:AllfieldwiringmustcomplywithNECandlocalcodes.It is the responsibility of the installer to insure that the electrical codes are met.

 

Wire Size

Use ONLY wiring size recommended for single

 

outlet branch circuit.

 

 

 

 

 

 

 

Use ONLY type and size fuse or HACR circuit

 

Fuse/Circuit

breakerindicatedonunit'sratingplate(Seesample

 

Breaker

on page 6). Proper current protection to the unit is

 

 

the responsibility of the owner.

 

 

 

 

 

Unit MUST be grounded from branch circuit to

 

Grounding

unit, or through separate ground wire provided on

 

permanentlyconnectedunits. Besurethatbranch

 

 

 

 

circuit or general purpose outlet is grounded.

 

 

 

 

 

Use recommended wire size given in tables and

 

Wire Sizing

installasinglebranchcircuit. Allwiringmustcomply

 

with local and national codes. NOTE: Use copper

 

 

 

 

conductors only.

 

 

 

CAUTION

Electric shock hazard.

Turn OFF electric power before service or installation.

AllelectricalconnectionsandwiringMUST be installed by a qualified electrician and conformtotheNationalElectricalCodeand all local codes which have jurisdiction.

Failure to do so can result in property damage, personal injury and/or death.

Figure7

DrainConnection andLocation

CAUTION

THE ACCESSORY DRAIN PAN (VPDP1) MUST BE INSTALLED BEFORE INSTALLING THE UNIT.

1.The accessory drain pan has two (2) provisions (left & right) for connecting an external condensate drain.

2.A field supplied condensate drain system must be connected to one of the two 3/4" FPT connections.

3.The remaining connection must be plugged using the 3/4" pipe plug (provided) and field suppled teflon tape or pipe joint compound.

4.Failure to follow these procedures may result in serious property damage.

8

920-159-01(10-03)

3)ElectricalData(continued)

Figure8

Electrical&ThermostatWiringDiagrams

RT2

THERMOSTAT (FRONT)

THERMOSTAT CONNECTIONS (EAR)

UP

G

R

R

WB

YC

FOR 208 VOLT MODELS ONLY MOVE THE WHITE WIRE AS

SHOWN BELOW

BLACK

WHITE

COM. 208V 240V

TRANSFORMER

24V

BLACK

RED

BROWN

TERM BOARD

RED

YELLOW

WHITE

C W Y R G B

BROWN

RED

COIL, SOLENOID

QUICK DISCONNECT

RED

L1

L2

 

 

RED

 

 

BLACK

BLACK

RED

 

 

WHITE

 

 

WHITE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

BLACK

 

 

 

BLACK

 

 

WHITE

 

 

 

 

BLUE

 

 

 

 

 

 

 

 

 

 

"F"

RED

 

 

 

 

 

 

 

 

PRESSURE

COMP WIRE HARNESS

RED

BLUE

BLACK

WHITE

 

 

COMPR RELAY

 

SWITCH

COMPRESSOR"F"

 

 

 

 

 

CS

 

 

 

 

 

 

 

 

 

"F"R

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2

4

 

 

 

 

 

 

c

 

COM.

208V240V

1

3

LOW AMBIENT

YELLOW

YELLOW

 

 

HERM

 

TRANSFORMER

 

 

CONTROL

 

 

 

 

FAN

 

 

24V

BLACK

 

RED

RED

 

 

 

 

 

 

 

 

CAPACITOR

 

 

 

 

 

 

 

 

 

 

 

 

 

 

WIRE NUT (RED)

 

 

 

 

 

 

 

 

 

 

 

 

 

GREEN

 

 

 

 

 

 

 

 

 

 

 

 

 

 

BLACK

 

 

 

 

 

 

 

 

SEE NOTE #6

 

 

 

 

 

 

 

BLACK

 

 

 

 

 

 

 

 

 

 

 

BLUE

 

 

 

 

 

 

 

 

 

 

 

GREEN

 

 

 

 

 

 

 

 

 

 

 

RED

 

 

 

 

 

 

 

 

 

 

 

YELLOW

 

 

 

 

 

 

 

 

 

 

 

WHITE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

WHITE

 

 

 

 

 

 

 

 

 

 

 

 

CAPACITOR

 

 

 

 

 

GREEN

 

 

WHITE

 

 

 

 

 

 

 

 

CONDENSER

 

 

 

 

FAN

 

 

 

 

 

TO MOTOR

 

 

 

 

 

 

 

 

 

MOTOR

 

BROWN

 

 

 

 

 

 

 

MOUNT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

HEATER

 

 

 

 

 

 

HEATER

2.5 KW & 3.4 KW

 

 

 

 

 

 

7.5 KW & 10 KW

5 KW

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

RED

 

RED

 

 

 

RED

 

RED

 

 

WHITE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FAN

 

 

REV VALVE

 

 

HEAT

 

 

HEAT

 

 

HEAT

HEAT

 

RELAY

 

 

RELAY

 

 

RELAY

 

 

RELAY

 

 

RELAY

RELAY

 

 

 

 

 

 

(2.5KW/3.4KW

 

 

(2.5KW/3.4KW

 

 

(7.5KW/10KW)

(7.5KW/10KW)

 

 

 

 

 

 

 

 

 

 

 

2

4

2

4

 

2

4

5 KW)

2

4

5 KW)

2

4

2

4

1

3

1

3

 

1

3

 

1

3

 

1

3

1

3

 

 

 

 

 

 

 

BLACK

 

 

BLACK

 

 

BLACK

 

 

BLACK

 

 

 

 

 

BLACK

 

 

BLACK

 

 

BLACK

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

RED

 

 

 

 

 

 

 

 

 

 

 

 

 

C H

 

 

T-STAT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

DEFROST

 

 

 

 

 

 

 

 

BLACK

 

 

 

 

 

INSULATOR

 

 

 

 

 

 

 

 

 

 

 

L

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2-REQ'D

 

 

 

 

 

 

 

 

 

 

 

 

 

 

GREEN

 

 

 

 

 

 

 

 

 

 

 

 

 

 

TO MOTOR

 

 

 

 

 

 

 

c

 

 

 

 

 

MOUNT

 

 

 

 

 

 

 

 

 

BLUE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

WIRE NUT (RED)

 

 

 

 

 

 

 

 

WHITE

 

 

 

 

 

 

 

 

 

 

 

BLOWER

 

 

 

 

 

 

 

 

 

 

BROWN

 

 

MOTOR

 

SEE NOTE #4

 

 

 

 

 

 

 

M

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

BLACK

 

 

 

 

 

 

 

 

ER

 

 

 

 

 

 

 

 

 

 

 

 

 

H

 

 

 

 

 

 

 

 

 

 

 

 

 

NOTE: THE DIAGRAM ABOVE ILLUSTRATES THE TYPICAL THERMOSTAT WIRING AND 208 VOLT TRANSFORMER WIRING. SEE THE UNIT CONTROL PANEL FOR THE ACTUAL UNIT WIRING DIAGRAM AND SCHEMATIC.

9

920-159-01(10-03)

4) IndoorReturnAirGrilleInstallation

There are three Indoor Return Air Grille options as shown in Figure 9. Choose the option that best suits your needs. Use the installation instructions provided with accessories for installation details.

Figure9

ReturnAirGrilleOptions

Option1

VPRG4

ReturnAirGrillewithAccessPanel

A field-supplied(25" x 20") filter is mounted inside the hinged access door.

Option2

VPRG2

ReturnAirGrille

Unit requires a field-suppliedaccess door or panel and a 16" x 20" filter.

All Vert-I-Pakchassis are shipped with a 20" x 14" filter installed. If an accessory filter holder is to be used, you MUST remove the factory shipped filter from the chassis. Do NOT use two filters

Notes:

A.These are the Friedrich recommended return air grille / filter / access panel arrangements. Consult the factory on other arrangements. Improper return air arrangements will cause performance problems.

B.Return air arrangements are shown from the front, but can also be installed from the right or left side of the unit.

10

920-159-01(10-03)

5)IndoorAirflowData

The Vert-I-PakA series units must be installed with a free return air configuration. Thetablebelowliststheindoorairflowatcorresponding staticpressures. Allunitsareshippedfromthefactoryandarerated at low speed.

To change to high speed replace the low speed lead (blue) with the high speed lead (black) on the blower relay.

 

VEA/VHA24K

 

 

Low

High

 

.1” ESP

750

815

 

.2” ESP

725

780

All values listed are inches

.3” ESP

700

745

W.C. with a wet indoor coil

 

 

 

with filter installed.

.4” ESP

675

700

 

6)ChassisInstallation

NOTE: Priortoinstallingthechassis,ensurethatthedrainpanand line are free from debris.

A.Ensure that the wall plenum is installed in accordance with the VPAWP1-8/1-14Installation Manual.

B.Ensure that the VPDP1 drain pan is installed correctly (see page 8). Using the 3/4" plugs supplied with the pan, plug the unused condensate drain hole. Connect a drain to the condensate exit location. Be sure to use teflon tape or approved pipe sealant on all drain connections and plugs (see page 8).

C.Place the chassis into the closet with the outdoor side facing the wall plenum opening.

D.Slide the chassis into the wall plenum until the plenum divider seal is established and the factory-installedchassis to plenum gasket has sealed to the top flange of the plenum. (See Figure 10)

Figure10

Slide-inView/ChassisInstallation

TheVert-I-Pakchassismustbeinsertedintothe wall plenum so that the plenum divider gasket makes contact with the condenser baffle in the unit. The chassis will fit approximately 23/8" into the wall plenum.

NOTE: Prior to installing the chassis,

 

ensure that the drain pan and line are free

23/8

from debris.

Chassis to plenum gasket

11

920-159-01(10-03)

7) ChassisFinalConnections

With the chassis in place, you are now ready to begin chassis connections:

A.Move the thermostat switches to "OFF" and "AUTO." This will keep the thermostat from cycling the chassis until final connections are complete.

B.Connecttheductworkontothe10"collar. Plasticwireties(field supplied)aresuggestedtosecuretheductworkinplace. Use 2 wire ties, one for each inner and outer flex duct sleeve.

D.For208Voltpoweronly: youmustmovethetransformerwire as shown in Figure 8, Page 9.

E.Review the Final Installation Checklist on Page 12 before replacing the power quick disconnect, reconnecting power tothechassis,pluggingintheremotethermostatharness,or operating the chassis.

Electricalshockandmovingpartshazardcancauseinjury or death. If you have not done so, pull out the disconnect headfoundonthefrontofchassisbeforecontinuinginstallation! Disconnect external power at the breaker.

8) FinalInstallationChecklist

oCorrect line voltage?

oChassis deck level?

oPlenum divider baffle installed?

oWall plenum caulked? Level? Flashing?

oHACR type breaker/fuse?

oSingle circuit only?

oDuctwork connected?

oChassis weather seal in place?

oWall thermostat wired correctly?

oChassis inserted into plenum?

RT2DigitalThermostat

III.ChassisOperation

9)RemoteThermostatControl

Thechassisrequiresasimplesinglestageheat-coolwallthermostat.Each chassis comes with a terminal strip located in the electrical controlbox.Allinternalchassiswiring(low&highvoltage)isfactory ready for 230 Volt operation. For 208 Volt operation a single wire MUSTBECHANGEDONTHETRANSFORMER. RefertoFigure 8 on page 9.

10)LowAmbientProtection

EachchassisisequippedwithLowAmbientProtectionintheformof asuctionlinethermostat.Thisthermostatwillprevent compressor operation at low suction line temperatures. Each chassis is also equipped with a factory installed bellows that will drain water from the base pan to prevent the fan slinger from freezing during winter weather.

11)HeatingDefrost (HeatPumpModelsOnly)

All Heat Pumps have a passive heating defrost system. Defrost occursasneededandautomaticallyswitchestoelectricheatduring defrost.Whentheoutdoorambienttemperaturedropsbelowa45°F factory setting, the chassis automatically switches to electric heat. As outdoor ambient temperatures rise above 45°F, the chassis returns to the heat pump mode. The changeover temperature is user adjustable from approximately 32°F - 55°F. The defrost thermostat may also be used to lock out the compressor in an emergency heat situation.

12

920-159-01(10-03)

12)FreshAirDoor

The Fresh Air Door is an "intake" system. The fresh air door is opened via a slide on the front of the chassis located just above the indoor coil. Move the slide left to open and right to close the fresh air door. The system is capable of up to 60 CFM of fresh air @ ~.3" H20 internal static pressure.

13)CondensateDisposalSystem

The VPDP1 drain pan features two 3⁄4 female PVC fittings to attach a drain connection to on the left or right side of the drain pan. Condensate piping can be routed to the left, right or beneath

the unit platform.

See page 8 or the drain pan installation manual for more information.

Part 1: The system’s first stage increases energy efficiency utilizing a factory installed fan that slings the cold condensate onto the hot outdoor coil.

Part 2: When high outdoor humidity prevents the slinger from disposing of all the condensate, the excess condensate overflows into the condensate drain pan and out of the 3⁄4" internal drain connections.

Part 3: If Parts 1 & 2 fail for any reason, excess condensate overflows from a spillway directly into the wall plenum to the outside of the building.IF

THIS OCCURS, THIS IS YOUR WARNING THAT THE CHASSIS OR DRAIN NEEDS SERVICING.

IV.Service&Warranty

14)Servicing/ChassisQuickChangeouts

The chassis is designed for quick disconnect and change out. For minor electrical service, the control box cover lifts straight up after the screws & disconnect head are removed. For major electrical, refrigeration and fan service the chassis may be removed from utility closet.

To Remove the Chassis from the Closet:

A.Switch the wall Thermostat off.

B.Pull the Power Disconnect located in the front of the chassis.

C.Disconnect the thermostat wiring harness.

D.Disconnect the electrical connection.

E.Disconnect the ductwork.

F.Slide the chassis out of the wall plenum.

G.Lift the chassis out of the utility closet.

Electricalshockandmovingpartshazardcancauseinjury or death. Pull out the disconnect head found on the front of the chassis before servicing.

15)RoutineMaintenance

PerformingRoutineMaintenance

With the proper maintenance and care, your system will operate economically and dependably. Maintenance can be accomplished easily by referring to the following directions. However, before performing any maintenance, consider these important safety precautions:

WARNING:ElectricalShockHazard.Beforeattemptinganyservice work or routine maintenance, turn off all electrical connections to the unit. Failure to do so may result in property damage, personal injury and/or death.

CAUTION: Although great care has been taken to minimize sharp edges in the construction of your unit, be extremely careful when handling parts or reaching into the unit.

ReplaceAirFilter

A dirty air filter reduces the efficiency of your Vert-I-Pakand allows lint and dirt to accumulate on theindoor-aircoil. Lint and dirt on theindoor-aircoil can damage your unit and void the warranty. The air filter should be replaced as it becomes dirty.

To replace the filter (chassis mounted return air filter):

1.Slide the filter clear of the filter rails.

2.Remove the filter.

3.Install new disposable filter.

CAUTION: Do not operate your system without a filter in place, nor block the front of the unit return air opening.

InspectandCleanIndoor-airCoil

Eventually, minor amounts of lint and dirt may pass through the filter and collect on the indoor-aircoil. These minor accumulations can be carefully vacuumed away with a brush attachment on

a vacuum cleaner. Care must be taken to avoid bending the aluminum fins on the coil. Bent fins should be straightened using a special fin tool available from most HVAC service technicians.

InspectOutdoor-airIntakeandExhaust

The unit’s outdoor-airintake andoutdoor-airexhaust paths must remain clear. Check the OA exhaust frequently. Keep it free of all debris, snow, or ice. The OA intake should also be kept free of obstructions. Blocking the OA exhaust or OA intake opening will reduce the efficiency of your unit, could damage it, and may void your warranty.

InspectandCleanCondensateDrain

The condensate drain must be routed to a suitable drainage area. Check the unit condensate drain periodically. Keep it free of anything that may block or impede the flow of condensate water. If there is any accumulation of foreign matter in the drain pipe, it should be removed and cleaned. The entire drain line must be protected from freezing.

16)Warranty

Allserviceworkmustbedonebyaqualifiedservicer. SeeWarranty on the next page, and consult your dealer or contractor for details

13

920-159-01(10-03)

FRIEDRICH AIR CONDITIONING CO.

Post Office Box 1540 · San Antonio, Texas 78295-1540

(210) 357-4400· FAX (210)357-4480

VERT- I-PAK® A SERIES SINGLE PACKAGE VERTICAL AIR CONDITIONERS

LIMITED WARRANTY

SAVE THIS CERTIFICATE. It gives you specific rights, you may also have other rights which may vary from state to state and province to province.

In the event that your unit needs servicing, contact your nearest authorized service center. If you do not know the nearest service center, ask the company that installed your unit or contact us - see address and telephone number below. To obtain service and/or warranty parts replacement, you must notify an authorized FRIEDRICHAir Conditioning Co. service center, distributor, dealer, or contractor of any defect within the applicable warranty period.

When requesting service: please have themodel andserial number from your unit readily available.

Unless specified otherwise herein, the following applies:

FRIEDRICH VERT-I-PAKA SERIES VERTICALAIR CONDITIONERS AND HEAT PUMPS

LIMITED WARRANTY - FIRST YEAR (Twelve (12) months from the date of installation). Any part found to be defective in the material or workmanship will be repaired or replaced free of charge by our authorized service center during the normal working hours; and

LIMITED WARRANTY - SECOND THROUGH FIFTH YEAR (Sixty (60) months from the date of installation). ON THE SEALED REFRIGERATION SYSTEM. Any part of the sealed refrigeration system that is defective in material or workmanship will be repaired or replaced free of charge (excluding freight charges) by our authorized service center during normal working hours. The sealed refrigeration system consists of the compressor, metering device, evaporator, condenser, reversing valve, check valve, and the interconnecting tubing.

These warranties apply only while the unit remains at the original site and only to units installed inside the continental United States,Alaska,Hawaii,PuertoRicoandCanada.Thewarrantyappliesonlyiftheunitisinstalledandoperatedinaccordancewith the printed instructions and in compliance with applicable local installation and building codes and good trade practices.

For international warranty information, contact the Friedrich Air Conditioning Company - International Division.

Any defective part to be replaced must be made available to FRIEDRICH in exchange for the replacement part. Reasonable proof must be presented to establish the date of install, otherwise the beginning date of this certificate will be considered to be our shipment date plus sixty days. Replacement parts can be new or remanufactured. Replacement parts and labor are only warranted for any unused portion of the unit’s warranty.

We will not be responsible for and the user will pay for:

1.Service calls to:

A)Instruct on unit operation. B) Replace house fuses or correct house wiring. C) Clean or replace air filters. D) Remove the unit from its installed location when not accessible for service required. E) Correct improper installations.

2.Parts or labor provided by anyone other than an authorized service center.

3.Damage caused by:

A)Accident, abuse, negligence, misuse, riot, fire, flood, or acts of God. B) Operating the unit where there is a corrosive atmosphere containing chlorine, fluorine, or any damaging chemicals (other than in a normal residential environment). C) Unauthorized alteration or repair of the unit, which in turn affects its stability or performance. D) Failing to provide proper maintenance and service. E)

Using other than a “Seacoast Protected” unit in a coastal environment. F) Using an incorrect power source. G) Faulty installation or application of the unit.

We shall not be liable for any incidental, consequential, or special damages or expenses in connection with any use or failure of this unit. We have not made and do not make any representation or warranty of fitness for a particular use or purpose and there is no implied condition of fitness for a particular use or purpose. We make no expressed warranties except as stated in this certificate. No one is authorized to change this certificate or to create for us any other obligation or liability in connection with this unit. Any implied warranties shall last for one year after the original purchase date. Some states and provinces do not allow limitations on how long an implied warranty or condition lasts, so the above limitations or exclusions may not apply to you. The provisions of this warranty are in addition to and not a modification of or subtraction from the statutory warranties and other rights and remedies provided by law.

In case of any questions regarding the provisions of this warranty, the English version will govern.

Rev 9-03

14

920-159-01(10-03)

IV. Vert-I-PakAccessories

MODEL

DESCRIPTION

PHOTO

 

 

 

 

WALL PLENUM Two-partsleeve that telescopes in and

 

VPAWP1-8

out from 51/2" to 8" in depth. The wall plenum sits inside

 

the exterior wall penetration.

 

 

DIMENSIONS: 303/8" high x 241/8" wide.

 

 

CUTOUT DIMENSIONS: 307/8" high x 245/8" wide.

 

 

 

 

VPAWP1-14

Same as VPAWP1-8,but telescopes 8" to 14" as required.

 

 

 

 

VPAL2

ARCHITECTURAL LOUVER Extruded aluminum louver

 

that attaches to the outdoor section of the wall plenum.

 

 

DIMENSIONS: 311/16" high x 259/16" wide.

 

 

 

 

VPSC2

Same as VPAL2 but can be ordered in a special color to

 

match the exterior wall.

 

 

 

 

 

 

RT2

DIGITAL THERMOSTAT Digital electronic thermostat with

 

"one touch" adjustment. Mounts to wall for control of unit.

 

 

 

 

 

 

 

ACCESS PANEL / RETURN AIR GRILLE Serves as

 

 

an access panel to chassis and interior return air grille.

 

VPRG4

A Þeld-supplied(25" x 20") Þlter is mounted inside the

 

hinged access door.

 

 

 

 

DIMENSIONS: 58" high x 29" wide.

 

 

CUTOUT DIMENSIONS: 553/4" high x 27" wide.

 

 

 

 

 

RETURN AIR GRILLE Interior return air grille that

 

VPRG2

hinges to allow a Þeld supplied (16" x 20") Þlter to slip

 

inside. Must be used when an access door / panel

 

 

already exists in closet.

 

 

DIMENSIONS: 187/16" high x 223/8" wide.

 

 

 

 

VPDP1

DRAIN PAN for VEA/VHA24 models. Drain pan may be

 

installed prior to chassis for easy installation/removal.

 

 

 

 

 

 

15