Vert-I-Pak®

Single Package Vertical Air Conditioning System

A-Series

24,000 BTU/h

Installation&OperationManual

920-159-01(10-03)

 

 

920-159-01(10-03)

 

 

TableofContents

InstallationRecommendations.........................................................................................................................................................

3

I.

GeneralSpecifications

 

 

ModelNumberIdentificationGuide...................................................................................................................................

4

 

VERT-I-PAKChassisSpecifications...................................................................................................................................

4

II.Installation

1.

UtilityClosetDimensions...................................................................................................................................................

5

2.

WallPlenum&ArchitecturalLouverInstallation ................................................................................................................

6

3.

ElectricalInformation .....................................................................................................................................................

7-9

4.

IndoorReturnAirGrilleInstallation..................................................................................................................................

10

5.

DuctworkPreparationandCFM.......................................................................................................................................

11

6.

ChassisInstallation..........................................................................................................................................................

11

7. ChassisFinalConnections(Electrical,Duct,Drain&WallThermostat)............................................................................

12

8.

FinalInstallationChecklist...............................................................................................................................................

12

III.ChassisOperation

9.

ThermostatControl..........................................................................................................................................................

12

10.

LowAmbientProtectionforCompressor&Fan................................................................................................................

12

11.

HeatingDefrost(HeatPumpModelsonly)........................................................................................................................

12

12.

FreshAirDoor...................................................................................................................................................................

13

13.

CondensateDisposalSystem ..........................................................................................................................................

13

IV.

Service,Maintenance&Warranty

 

14.

Servicing/ChassisQuickChangeouts.............................................................................................................................

13

15.

RoutineMaintenance.......................................................................................................................................................

13

16.

Warranty ..........................................................................................................................................................................

14

V.

Vert-I-PakAccessories ....................................................................................................................................................

15

Please read this manual thoroughly prior to equipment installation or operation. It is the installer’s responsibility to properly apply and install the equipment. Installation must be in conformance with theNFPA70-2002NationalElectricCodeorcurrenteditionandUniversalMechanicalCodecurrentedition and applicable local or national codes.

Proper installation is not difficult but it is essential.

2

920-159-01(10-03)

Vert-I-PakInstallationRecommendations

Forproperunitperformanceandmaximumoperatinglifepleaserefertotheminimuminstallationclearancesbelow.

Figure1

VERT-I-PAK® units must be installed on an outside wall. Confined spaces and/or covered areas should be avoided. Units should be installed no closer than 12" apart when two units are side by side. If three of more units are to operate next to one another allow a minimum of 60" between units or pairs of units. Also, a vertical clearance of 60" should be maintained between units. Units installed on the bottom floor should be mounted at least 6" off of the ground.

6"

 

 

B

 

 

60"

60"

A

 

 

SMALL RECESS OK

LARGER RECESS OK. IF A> 5xB

60"

60"

 

 

 

60"

 

60"

 

 

60"

60"

60"

 

 

60"

60"

 

6"

6"

12"

 

 

Figure2

Any time obstructions are present use the following guidelines for proper spacing from the VERT-I-PAKlouver:

For minor obstructions such as lamp poles or small shrubbery a clearance of 24" from the outdoor louver should be maintained.

For major obstructions such as a solid fence, wall or other heat rejecting device like a condensing unit, a minimum distance of 72" should be kept.

BUILDING

 

60"

24"

 

VPAK

12"

VPAK

VPAK

 

 

 

24"

 

POLE

 

SHRUB

 

 

 

OUTDOOR

 

 

72"

CONDENSING

 

 

 

UNIT

FENCE

 

 

MAJOR OBSTRUCTION

Theabovesuggestionsareforreferenceonlyanddonotrepresentallpossibleinstallations.Pleasecontactthefactory for information regarding affects of other installation arrangements.

By following these simple recommendations you can be confident that your Friedrich Vert-I-Pak® will provide years ofworry-freeoperation.

3

920-159-01(10-03)

SectionI. GeneralSpecifications

VERT-I-PAK® MODEL IDENTIFICATION GUIDE

MODEL NUMBER

V

E

A

24

K

50

RT

A

SERIES

 

 

 

 

 

 

 

ENGINEERING CODE

 

 

 

 

 

 

 

 

OPTIONS

V=Vertical Series

 

 

 

 

 

 

 

 

 

 

 

 

 

 

RT = Standard Remote Operation

E=Cooling with or without electric heat

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SP = Seacoast Protected

H=Heat Pump

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ELECTRIC HEATER SIZE

DESIGN SERIES

 

 

 

 

 

 

 

 

 

 

 

 

A-Series

A = 32" and 47" Cabinet

 

 

 

 

 

 

 

 

 

 

 

00

= No electric heat

 

 

 

 

 

 

NOMINAL CAPACITY

 

 

 

 

 

25

= 2.5 KW

 

 

 

 

 

34

= 3.4 KW

A-Series(Btu/h)

 

 

 

 

 

 

 

 

 

 

50

= 5.0 KW

09 = 9,000

 

 

 

 

 

 

 

 

 

 

75

= 7.5 KW

12 = 12,000

 

 

 

 

 

 

 

 

 

 

10

= 10 KW

18 = 18,000

 

 

 

 

 

 

 

 

 

 

 

 

 

 

24 = 24,000

 

 

 

 

 

 

 

 

 

VOLTAGE

 

 

 

 

 

 

 

 

 

K = 208/230V-1Ph-60Hz

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Vert-I-Pak® Chassis Specifications

MODEL:

V(E,H)A24

Voltage (V)

230/208

Refrigerant

R-22

Chassis Width

23.125

Chassis Depth

23.125

Chassis Height **

47.25

Supply Duct Collar ***

10"

Drain Connection

3/4" FPT

Min. Circuit Amps

See Nameplate

CFM Indoor

See chart, pg. 11

Max. Duct ESP

.4 in. water

NOTES:

**Height includes 2" duct collar & isolators under unit.

***Factory collar accepts 10" flex duct.

4

920-159-01(10-03)

II. Installation

1) UtilityClosetDimensions

Recommended utility closet dimensions and a typical indoor installation are illustrated in Figure 1. Three inches minimum clearance on three sides of the unit must be allowed for return airflow, installation access and service access. See Figures 1 & 2 for clearances and reference dimensions.

Figure3

Typical Utility Closet

Chassis Shown in Closet, on Optional Platform

Field-supplied

Rigid Ductwork

 

Filter (25" x 20")

 

58"

 

Exterior Wall

 

Flexible Ductwork

Power

VPAWP1-8/1-14Wall Plenum

 

Disconnect

Plenum

 

29"

VPRG4 Access Panel &

Return Air Filter Grille

Optional Platform

3" Clearance on all

 

 

three sides

 

VPDP1 drain pan

minimum for

 

Chassis is

beneath unit is

 

 

shipped with

required on all

 

vibration

VEA/VHA24 units.

 

isolators

Drain pan must be

 

installed

installed prior to

 

 

chassis installation

Figure4

Top View

 

 

Vert-I-PakChassis2-tondimensions:

control box

 

23" wide x 23" deep x 47 1/4" high.

 

VPAWP1-8/1-14Wall Plenumcut-out

 

electrical

dimensions 24 5/8" wide x 30 7/8" high.

 

entrance

 

 

VPRG4 Access Panel cutout dimensions:

 

 

27" wide by 55 3/4" high.

 

See Figure 8 (Page 10) for proper

 

 

chassis installation.

 

NOTE: Drain pan must be installed in closet prior to chassis

 

insertion into plenum. See Figure 7 (page 8) for drain pan

 

installation details.

5

920-159-01(10-03)

2)WallPlenumandArchitecturalLouverInstallation

A. Install the wall plenum (VPAWP1-8/1-14)components in accordance with the installation instructions provided with each accessory.

IMPORTANT REMINDER: FRIEDRICH WALL PLENUM IS NOT DESIGNED TO CARRY STRUCTURAL LOADS. PROPER WALL HEADER CONSTRUCTION IS REQUIRED. THE PLENUM REQUIRES PROPER FLASHING, SHIM AND CAULK FOR A WEATHER RESISTANT INSTALLATION.

B. Ensure that the divider is adjusted properly for the depth of the wall in accordance with the accessory installation manual

Figure5

WallPlenum&OutdoorLouverInstallation

Proper Header

Caulk all 8

 

flange corners

Proper Flashing

Proper Caulking

Inside Wall Plenum

(Part B)

Outside Wall

Proper Caulking

 

Architectural louver VPAL2 mounted

 

on the outside wall plenum (Part A)

Proper Flashing

 

Rough opening dimension 24 5/8" wide x 30 7/8" high.

Ensure that the bottom of the plenum is 1 1/2" from the floor of the closet. Note: 9,000 / 12,000 / 18,000 installation height may be different. Refer to specific installation manual for clarification.

For proper airflow, maintain a minimum distance of 12" between Vert-I-Pakunits. Consult the factory for any installation or application questions.

6

920-159-01(10-03)

3)ElectricalInformation

Electrical Data

 

 

 

 

 

MODEL

 

Voltage ( V)

VHA/VEA24K25 VHA/VEA24K34 VHA/VEA24K50VHA/VEA24K75VHA/VEA24K10VHA/VEA24K00

230/208

230/208

230/208

230/208

230/208

230/208

LRA - Comp. (A)

68

68

68

68

68

68

Cooling Current (A)

13.7/12.4

13.7/12.4 13.7/12.4 13.7/12.4 13.7/12.4 13.7/12.4

MIN. Ckt. Amps (A)

17.2/15.9

22.1/20.3 30.7/28.1 44.3/40.3 57.9/52.7 15.6/15.6

Max Branch Circuit Fust (Amps)

25/25

25/25

35/30

45/45

60/60

20/20

Power Connection

 

 

HARD WIRED

 

 

Recommended Branch

14/14

12/12

8/10

6/6

4/6

14/14

Circuit Wire Sizes*

AWG - American Wire Gauge

 

 

 

 

 

 

* Single circuit from main box. Based on copper wire, single insulated conductor at 60°C.

NOTE: Use copper conductors ONLY. Wire sizes are per NEC. Check local codes for overseas applications.

Sample Nameplate (see your chassis nameplate)

SAMPLE

7

920-159-01(10-03)

IMPORTANT: ALL 208/230V CHASSIS MUST BE HARD WIRED WITH PROPERLY SIZED BREAKER. SEE NAMEPLATE FOR SPECIFIC CHASSIS ELECTRICAL REQUIREMENTS. SEE PAGE 9 - FIGURE 8 FOR UNIT WIRING AND WALL THERMOSTAT WIRING. SEE PAGE 7 FOR WIRE SIZE. USE HACR TYPE BREAKERS TO AVOID NUISANCE TRIPS. ALL FIELD WIRING MUST BE DONE IN ACCORDANCE WITH NEC AND LOCAL CODES.

3) Electrical Information (continued)

Figure6

ElectricalRequirements

Note:AllfieldwiringmustcomplywithNECandlocalcodes.It is the responsibility of the installer to insure that the electrical codes are met.

 

Wire Size

Use ONLY wiring size recommended for single

 

outlet branch circuit.

 

 

 

 

 

 

 

Use ONLY type and size fuse or HACR circuit

 

Fuse/Circuit

breakerindicatedonunit'sratingplate(Seesample

 

Breaker

on page 6). Proper current protection to the unit is

 

 

the responsibility of the owner.

 

 

 

 

 

Unit MUST be grounded from branch circuit to

 

Grounding

unit, or through separate ground wire provided on

 

permanentlyconnectedunits. Besurethatbranch

 

 

 

 

circuit or general purpose outlet is grounded.

 

 

 

 

 

Use recommended wire size given in tables and

 

Wire Sizing

installasinglebranchcircuit. Allwiringmustcomply

 

with local and national codes. NOTE: Use copper

 

 

 

 

conductors only.

 

 

 

CAUTION

Electric shock hazard.

Turn OFF electric power before service or installation.

AllelectricalconnectionsandwiringMUST be installed by a qualified electrician and conformtotheNationalElectricalCodeand all local codes which have jurisdiction.

Failure to do so can result in property damage, personal injury and/or death.

Figure7

DrainConnection andLocation

CAUTION

THE ACCESSORY DRAIN PAN (VPDP1) MUST BE INSTALLED BEFORE INSTALLING THE UNIT.

1.The accessory drain pan has two (2) provisions (left & right) for connecting an external condensate drain.

2.A field supplied condensate drain system must be connected to one of the two 3/4" FPT connections.

3.The remaining connection must be plugged using the 3/4" pipe plug (provided) and field suppled teflon tape or pipe joint compound.

4.Failure to follow these procedures may result in serious property damage.

8

920-159-01(10-03)

3)ElectricalData(continued)

Figure8

Electrical&ThermostatWiringDiagrams

RT2

THERMOSTAT (FRONT)

THERMOSTAT CONNECTIONS (EAR)

UP

G

R

R

WB

YC

FOR 208 VOLT MODELS ONLY MOVE THE WHITE WIRE AS

SHOWN BELOW

BLACK

WHITE

COM. 208V 240V

TRANSFORMER

24V

BLACK

RED

BROWN

TERM BOARD

RED

YELLOW

WHITE

C W Y R G B

BROWN

RED

COIL, SOLENOID

QUICK DISCONNECT

RED

L1

L2

 

 

RED

 

 

BLACK

BLACK

RED

 

 

WHITE

 

 

WHITE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

BLACK

 

 

 

BLACK

 

 

WHITE

 

 

 

 

BLUE

 

 

 

 

 

 

 

 

 

 

"F"

RED

 

 

 

 

 

 

 

 

PRESSURE

COMP WIRE HARNESS

RED

BLUE

BLACK

WHITE

 

 

COMPR RELAY

 

SWITCH

COMPRESSOR"F"

 

 

 

 

 

CS

 

 

 

 

 

 

 

 

 

"F"R

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2

4

 

 

 

 

 

 

c

 

COM.

208V240V

1

3

LOW AMBIENT

YELLOW

YELLOW

 

 

HERM

 

TRANSFORMER

 

 

CONTROL

 

 

 

 

FAN

 

 

24V

BLACK

 

RED

RED

 

 

 

 

 

 

 

 

CAPACITOR

 

 

 

 

 

 

 

 

 

 

 

 

 

 

WIRE NUT (RED)

 

 

 

 

 

 

 

 

 

 

 

 

 

GREEN

 

 

 

 

 

 

 

 

 

 

 

 

 

 

BLACK

 

 

 

 

 

 

 

 

SEE NOTE #6

 

 

 

 

 

 

 

BLACK

 

 

 

 

 

 

 

 

 

 

 

BLUE

 

 

 

 

 

 

 

 

 

 

 

GREEN

 

 

 

 

 

 

 

 

 

 

 

RED

 

 

 

 

 

 

 

 

 

 

 

YELLOW

 

 

 

 

 

 

 

 

 

 

 

WHITE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

WHITE

 

 

 

 

 

 

 

 

 

 

 

 

CAPACITOR

 

 

 

 

 

GREEN

 

 

WHITE

 

 

 

 

 

 

 

 

CONDENSER

 

 

 

 

FAN

 

 

 

 

 

TO MOTOR

 

 

 

 

 

 

 

 

 

MOTOR

 

BROWN

 

 

 

 

 

 

 

MOUNT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

HEATER

 

 

 

 

 

 

HEATER

2.5 KW & 3.4 KW

 

 

 

 

 

 

7.5 KW & 10 KW

5 KW

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

RED

 

RED

 

 

 

RED

 

RED

 

 

WHITE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FAN

 

 

REV VALVE

 

 

HEAT

 

 

HEAT

 

 

HEAT

HEAT

 

RELAY

 

 

RELAY

 

 

RELAY

 

 

RELAY

 

 

RELAY

RELAY

 

 

 

 

 

 

(2.5KW/3.4KW

 

 

(2.5KW/3.4KW

 

 

(7.5KW/10KW)

(7.5KW/10KW)

 

 

 

 

 

 

 

 

 

 

 

2

4

2

4

 

2

4

5 KW)

2

4

5 KW)

2

4

2

4

1

3

1

3

 

1

3

 

1

3

 

1

3

1

3

 

 

 

 

 

 

 

BLACK

 

 

BLACK

 

 

BLACK

 

 

BLACK

 

 

 

 

 

BLACK

 

 

BLACK

 

 

BLACK

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

RED

 

 

 

 

 

 

 

 

 

 

 

 

 

C H

 

 

T-STAT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

DEFROST

 

 

 

 

 

 

 

 

BLACK

 

 

 

 

 

INSULATOR

 

 

 

 

 

 

 

 

 

 

 

L

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2-REQ'D

 

 

 

 

 

 

 

 

 

 

 

 

 

 

GREEN

 

 

 

 

 

 

 

 

 

 

 

 

 

 

TO MOTOR

 

 

 

 

 

 

 

c

 

 

 

 

 

MOUNT

 

 

 

 

 

 

 

 

 

BLUE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

WIRE NUT (RED)

 

 

 

 

 

 

 

 

WHITE

 

 

 

 

 

 

 

 

 

 

 

BLOWER

 

 

 

 

 

 

 

 

 

 

BROWN

 

 

MOTOR

 

SEE NOTE #4

 

 

 

 

 

 

 

M

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

BLACK

 

 

 

 

 

 

 

 

ER

 

 

 

 

 

 

 

 

 

 

 

 

 

H

 

 

 

 

 

 

 

 

 

 

 

 

 

NOTE: THE DIAGRAM ABOVE ILLUSTRATES THE TYPICAL THERMOSTAT WIRING AND 208 VOLT TRANSFORMER WIRING. SEE THE UNIT CONTROL PANEL FOR THE ACTUAL UNIT WIRING DIAGRAM AND SCHEMATIC.

9

920-159-01(10-03)

4) IndoorReturnAirGrilleInstallation

There are three Indoor Return Air Grille options as shown in Figure 9. Choose the option that best suits your needs. Use the installation instructions provided with accessories for installation details.

Figure9

ReturnAirGrilleOptions

Option1

VPRG4

ReturnAirGrillewithAccessPanel

A field-supplied(25" x 20") filter is mounted inside the hinged access door.

Option2

VPRG2

ReturnAirGrille

Unit requires a field-suppliedaccess door or panel and a 16" x 20" filter.

All Vert-I-Pakchassis are shipped with a 20" x 14" filter installed. If an accessory filter holder is to be used, you MUST remove the factory shipped filter from the chassis. Do NOT use two filters

Notes:

A.These are the Friedrich recommended return air grille / filter / access panel arrangements. Consult the factory on other arrangements. Improper return air arrangements will cause performance problems.

B.Return air arrangements are shown from the front, but can also be installed from the right or left side of the unit.

10