FMI (V)G42HR-50HR User Manual

42" and 50" Wood Burning
Masonry Fireplace
OWNER’S OPERATION AND
INSTALLATION MANUAL
(V)G42/50
Smooth Face with Insulation
(V)G42R/50R
Smooth Face with Insulation and Bottom Door Rail
(V)G42H/50H
Smooth Face with Insulation and Herringbone Refractory
(V)G42HR/50HR
Smooth Face with Insulation, Bottom Door Rail and Herringbone Refractory
PFS ®
C US
SAVE THIS BOOK
This book is valuable. In addition to instructing you on how to install and maintain your appliance, it also contains information that will enable you to obtain replacement parts or accessory items when needed. Keep it with your other important papers.
This fireplace is approved for use as a wood burning fireplace or for use with a vented gas log approved to ANS Z21.60 or Z21.84 standards or for use with a
FOR CANADA: The authority having jurisdiction (such as the municipal building department, fire department, etc.) should be contacted before installation to determine the need to obtain a permit.
INSTALLER: Leave this manual with the appliance. CONSUMER: Retain this manual for future reference.
For more information, visit www.fmiproducts.com

Table of Contents
Safety Information................................................ | 2 | Glass Door Installation....................................... | 12 |
Specifications....................................................... | 3 | Operation and Maintenance Guidelines............. | 13 |
Fireplace Installation............................................ | 5 | Technical Service............................................... | 14 |
Venting Installation............................................... | 7 | Replacement Parts............................................. | 15 |
Optional Gas Line Installation............................. | 11 | Accessories........................................................ | 16 |
Safety
WARNING: Improper installation, adjustment, alteration, service or maintenance can causeinjury,propertydamageor loss of life. Refer to this manual for assistance or additional information. Consult a qualified installer or local distributor.
IMPORTANT:Checklocalcodes before installing this fireplace.
Beforebeginningtheinstallationofthefireplace, read these instructions through completely.
•ThisFMIPRODUCTS,LLCfireplaceandits componentsaresafewheninstalledaccording to this installation manual. Unless you use FMI PRODUCTS, LLC components, which have been designed and tested for the fireplace system, you may cause a fire hazard.
•The FMI PRODUCTS, LLC warranty will be voided by and FMI PRODUCTS, LLC disclaimsanyresponsibilityforthefollowing actions.
a.Modification of the fireplace, components, doors, air inlet system and damper control.
b.Useofanycomponentpartnotmanufactured or approved by FMI PRODUCTS,
LLC in combination with a FMI PROD-
UCTS, LLC fireplace system.
Proper installation is the most important step in ensuring safe and continuous operation of the fireplace. Consult the local building codes as to the particular requirements concerned with the installation of all factory built fireplaces.
WARNING: Do not install a fireplaceinsertinthisfireboxunless the manufacturer's instructions with the insert specifically state this fireplace has been tested for use with the insert.
This fireplace is not intended to be used as a substitute for a furnacetoheatanentirehome.Use for supplemental heat only.
FOR YOUR SAFETY
•Do not store or use gasoline oranyotherflammablevapors orliquidsinthevicinityofthis or any other appliance.
•Due to high temperatures, the appliance should be located out of traffic and away from furniture and draperies.
•Do not place clothing or other flammablematerialsonornear the appliance.
•Never leave children unattended when a fire is burning in the fireplace.
WARNING: Use solid wood or processed solid fuel firelogs only. When processed wood fuel fire logs are used, do not poke or stir the logs while they are burning. Use only fire logs that have been evaluated for the application in fireplace and refer to fire log warnings and caution markings on packaging prior to use.
WARNING: Always leave glass doors fully opened or fully closed when operating fireplace.
2 | www.fmiproducts.com |

Specifications
42" Models
ROUND TOP TERMINATION SQUARE
TERMINATION
2" CHIMNEY AIRSPACE CLEARANCE TO COMBUSTIBLE MATERIAL
NO COMBUSTIBLE
MATERIAL ON FACE
11/2" AIR SPACE BACK AND SIDES
OUTSIDE AIR
GAS LINE
KNOCKOUTS
0" TO
BOTTOM
67"
58"
49"
42"8"
51"
1"
24.25"
41.25"
COMBUSTIBLE
WALL BOARD
MINIMUM 18" TO
PERPENDICULAR
SIDEWALL
HEARTH EXTENSION 66" X 20"
12" EACH SIDE
12"
30.5"
11"
21.25"
28.5"
30"
| 0.625" | 51" |
|
|
|
| |
|
|
| AIR KIT |
|
| LEFT SIDE | KNOCK OUT |
|
|
| GAS LINE |
|
|
| KNOCK OUTS |
|
|
| 3.5" |
23.5" | 10.5" |
| 9.5" |
|
|
| |
|
| 8.5" |
|
|
| 13" |
|
|
| 17" |
|
www.fmiproducts.com | 3 |

Specifications
50" Models
ROUND TOP TERMINATION | SQUARE |
| TERMINATION |
2" CHIMNEY AIRSPACE CLEARANCE TO COMBUSTIBLE MATERIAL
NO COMBUSTIBLE
MATERIAL ON FACE
COMBUSTIBLE
WALL BOARD
11/2" AIR SPACE BACK AND SIDES
OUTSIDE AIR
| MINIMUM 18" TO |
| PERPENDICULAR |
| SIDEWALL |
GAS LINE |
|
KNOCKOUTS | HEARTH EXTENSION |
| |
0" TO | 74" X 20" |
12" EACH SIDE |
BOTTOM
| 12" |
|
|
|
| 38.5" |
|
67" |
|
| 11" |
|
|
| |
58" |
|
| 21.25" |
28.5" |
|
| |
49" |
|
| |
30" |
|
| |
| 0.625" | 59" |
|
| 50" |
| |
8" |
|
| |
59" |
|
| |
|
|
| |
| 1" |
|
|
|
|
| AIR KIT |
|
| LEFT SIDE | KNOCK OUT |
| 32.75" |
| |
|
| GAS LINE | |
|
|
| |
|
|
| KNOCK OUTS |
|
|
| 3.5" |
| 10.5" |
| 9.5" |
| 23.5" |
|
|
|
| 8.5" |
|
|
| 13" |
|
| 50" | 17" |
|
|
|
|
4 | www.fmiproducts.com |

Fireplace Installation
Selecting location
To determine the safest and most efficient location for the fireplace, you must take into consideration the following guidelines:
1.The location must allow for proper clearances (see Figures 1 and 2).
2.Consider a location where the fireplace will not be affected by drafts, air conditioning ducts, windows or doors.
3.A location that avoids the cutting of joists or roof rafters will make installation easier.
4.An outside air kit is available with this fireplace (see Optional Outside Air Kit, page 6).
Minimum clearance to combustibles
Back and sides of fireplace 1 1/2" min.*
Front of fireplace | 48" min. |
Floor** | 0" min. |
Perpendicular wall to opening 12" min. | |
Top spacers | 0" min. |
Mantel clearance | see Mantels, |
| page 5 |
Chimney outer pipe surface 2" min.
* Not required at nailing flanges ** See step 2 of Framing
WARNING: Do not pack requiredairspaceswithinsulation or other materials.
Minimum/Maximum Chimney Height
The minimum height of the chimney, measured from the base of the fireplace to the flue gas outlet of the termination, is 16 feet for straight flue or a flue with one elbow set. The maximum distance between elbows is 6 feet.
For systems with two elbow sets, the minimum height is 22 feet. The maximum height of any system is 50 feet.This measurement includes the fireplace, chimney sections and the height of the termination assembly at the level of the flue gas outlet (see Figure 15, page 9).
Framing
1.Frame opening for fireplace using the dimensions shown in Figures 1 and 2.
2.If fireplace is to be installed directly on carpeting, tile (other than ceramic) or any combustible material other than wood flooring, the fireplace must be installed
upon a metal or wood panel extending the full width and depth of the fireplace.
3.Set the fireplace directly in front of this opening and slide unit back until nailing flanges touch side framing.
4.Check the level of fireplace and shim with sheet metal if necessary.
5.Before securing fireplace to prepared framing, the ember protector (provided) must be placed between hearth extension (not supplied) and under bottom front edge of fireplace to protect against glowing embers falling through. If the fireplace is to be installed on a raised platform, a
mum of 1 1/2". The ember protector should be made of galvanized sheet metal (28 gauge minimum to prevent corrosion.
6.Using screws or nails, secure the fireplace to the framing through flanges located on the sides of the fireplace.
| 67.125" | |
| 58.125" | |
51.25" (42") | 30.125" | |
59" (50") | ||
|
Maintain 1 1/2"
Clearance at Sides
65" (42" Models) and Back of Fireplace
71" (50" Models)
1 1/2" Clearance
Not Required at
Nailing Flanges
92" (42" Models)
100" (50" Models)
Figure 2 - Corner Installation
www.fmiproducts.com | 5 |

Fireplace Installation
Hearth Extension
A hearth extension projecting a minimum of
20" in front of and a minimum of 12" beyond each side of the fireplace opening is required to protect combustible floor construction in front of the fireplace. Fabricate a hearth extension using a material which meets the following specifications: a layer of noncombustible, inorganic material having a thermal conductivity of K=0.84 BTU IN/FT, HR. F (or less) at 1" thick. For example, if the material selected has a K factor of 0.25, such as glass fiber, the following formula would apply:
0.25 x 1.0" = 0.30" thickness required
0.84
Thermal conductivity "K" of materials can be obtained from the manufacturer or supplier of the noncombustible material. If the hearth extension is to be covered, use noncombustible material such as tile, slate, brick, concrete, metal, glass, marble, stone, etc. Provide a means to prevent the hearth extension from shifting and seal gap between the fireplace frame and hearth extension with a noncombustible material (see Figure 3).
WARNING:Hearthextension
is to be installed only as shown
in Figure 3.
Fireplace Front | Seal Gap |
| |
Ember Protector |
|
Fireplace Front |
|
Raised Hearth |
|
Ember Protector | Hearth |
| Extension |
Fireplace Front | Seal Gap |
Elevated |
|
Ember Protector
Figure 3 - Hearth Extension
Mantels
A mantel may be installed if desired (see Figure 4). Woodwork such as wood trims, mantels or any other combustible material projecting from the front face must not be placed within 12" of the fireplace opening. Combustible materials above 12" and projecting more than 1 1/2" from the fireplace must not be placed less than 15" from the top opening of the fireplace (NFPA STD 211,
Sec.
Mantels or any other combustible material also may come up to the side edge of the black metal face of the fireplace just as long as the projection from the front face fall within the limit shown in Figure 4.
|
| Combustible |
| 12 1/4" Ref. | Material |
|
| Safe |
|
| Zone for |
6" |
| Projection of |
Ref. | 33° | Combustible |
| Materials | |
|
| |
| 3" Nom. |
|
15" Min. 11/2" Max.
12" Min.
Upper
Section of
Fireplace
Fireplace Opening
Top View of Fireplace
| FIREBOX | |
7.75" |
| |
SAFE ZONE | 3" Max. | |
4.5" | ||
33° | ||
| ||
Min. to | Combustible | |
Perpendicular | ||
Material Must | ||
Side Wall | ||
Not Overlap | ||
12" | ||
Front Face | ||
|
Figure 4 - Mantel Clearances to
Combustible Material
6 | www.fmiproducts.com |

Venting Installation
Optional Outside air Kit (Model ak4/ak4f)
The installation of an outside air kit should be performed during the rough framing of the fireplace due to the nature of it's location. Outside combustion air is accessed through a vented crawl space (AK4F) or through a sidewall (AK4).
CAUTION: Combustion air inlet ducts shall not terminate in attic space.
Secure to Collars with Metal Tape, Screws or Straps (Min. 1/4" x 20" size)
Air Inlet
Location
Must Allow For Bushes or Snow
| Air Inlet | |
| Eyebrow | |
Vented Crawl Space | Vent Hood | |
Required for | ||
(Check Local Codes | ||
Wall Installation | ||
Before Installing in a | ||
| ||
Vented Crawl Space) |
| |
Figure 5 - Outside Air Kit |
Chimney Pipe
The FMI PRODUCTS, LLC chimney system consists of 12", 18", 24", 36" and 48" snaplock,
WARNING: The opening in the collar around the chimney at the top of the fireplace must not be obstructed. Never use blown insulation to fill the chimney enclosure.
LINEAL GAIN
PART NO. | DESCRIPTION | GAIN | |
Georgian | Fireplace | 66 1/2" | |
Pipe Section | 10 5/8" | ||
|
| ||
Pipe Section | 16 5/8" | ||
|
| ||
Pipe Section | 23 5/8" | ||
|
| ||
Pipe Section | 34 5/8" | ||
|
| ||
Pipe Section | 46 5/8" | ||
|
| ||
Round Termination | 7 3/4"* | ||
|
| ||
Square | 7" to 15"* | ||
with Slip Section |
* The lineal gain for the terminations is measured to the flue gas outlet height.
15" Galvanized Outer Pipe
12 3/8" | Hemmed |
Stainless | End |
| |
Inner Pipe |
|
Figure 6 - Lineal Gain
Assembly and installation of double wall chimney system
Each double wall chimney section consists of a galvanizedouterpipe,astainlesssteelinnerflue pipe and a wire spacer. Pipe sections must be assembledindependentlyaschimneyisinstalled.
When connecting chimney directly to fireplace, the inner flue pipe section must be installed first with lanced side up. The outer pipe section can then be installed over the flue pipe section with hemmed end up. Press down on each pipe sectionuntillancessecurelyengagehemonfireplace starter. The wire will assure the proper spacing between inner and outer pipe sections.
Continue to assemble chimney sections as outlinedabove,makingsurethatbothinnerand outer pipe sections are locked together. When installing double wall
www.fmiproducts.com | 7 |

Venting Installation
Continued
Using ELBOW offsets
1.To achieve desired offset, you may install combinations of 12", 18", 24", 36" and 48" length of double wall pipe (see offset chart and Figure 7).
OFFSET | RISE |
| CHIMNEY LENGTH |
| ||||
A | B | 12" | 18" | 24" | 36" | 48" | ||
4 3/8" | 16 3/8" |
|
| ELBOW | SET | ONLY |
|
|
9 3/4" | 25 1/2" | 1 |
|
|
|
|
|
|
12 3/4" 303/4" |
| 1 |
|
|
|
| ||
15" | 34 3/4" |
|
|
| 1 |
|
|
|
18" | 40" | 1 | 1 |
|
|
|
| |
21 1/4" 461/4" |
|
|
| 1 |
|
| ||
23 3/4" 491/4" |
| 1 | 1 |
|
|
| ||
27 3/4" 563/4" |
|
|
|
|
|
| 1 | |
30" | 60 3/4" |
| 1 | 1 |
|
| ||
33" | 66" | 1 |
|
|
|
|
| 1 |
36" | 71" |
| 1 |
|
|
| 1 | |
38 1/4" | 75" |
|
|
| 2 |
|
| |
41 1/4" 801/4" | 1 | 1 | 1 |
|
| |||
45" | 86 3/4" |
|
|
| 2 |
|
| |
46 3/4" 891/2" | 1 | 1 |
|
|
| 1 | ||
51" | 97" |
|
|
| 1 |
| 1 | |
53 1/4" | 101" |
| 1 | 2 |
|
| ||
56 1/4" | 106 1/4" |
|
|
|
|
|
| 2 |
59 1/4" | 111 1/2" |
| 1 | 1 |
| 1 | ||
61 3/4" | 115 1/2" | 1 |
|
|
|
|
| 2 |
64 3/4" | 120 3/4" |
| 1 |
|
|
| 2 | |
68 1/4" | 127" |
|
|
| 2 |
| 1 | |
70" | 130" | 1 | 1 |
|
|
| 2 | |
74 1/4" | 137 1/2" | 1 |
|
| 2 |
| 1 | |
76 3/4" | 141 1/2" |
| 1 | 2 |
| 1 | ||
79 3/4" | 146 3/4" |
|
|
| 4 |
|
|
OFFSET CHART
2. Chimney weight above offset rests on return elbow. Straps must be securely nailed to rafters or joists (see Figure 8, details a and b).
3. Maximumlengthofpipebetweensupports (return elbow or
4. All pipe connections between the offset and return must be secured with two screws on the outer pipe only (see Figure
9, page 9). Do not penetrate the inner stainless.
2" Min.
Straps
Detail BStraps | See Detail B | |
Angle Firestop | ||
|
Straps
Straps
Detail A
Return Elbow
Figure 8 - Ceiling Support Pipe
| Return |
| Return |
|
| |
| Elbow |
| Elbow | Return |
| |
Offset |
|
|
|
|
| |
| Offset |
|
| Elbow |
| |
Elbow | 6' Max. | Elbow | 6' Max. | Ceiling |
|
|
|
|
| ||||
|
|
|
| |||
Return |
|
|
| Support Pipe |
| |
| Return |
| 6' Max. | |||
Elbow |
|
| ||||
| Elbow |
|
|
|
| |
|
|
|
|
|
| |
| 6' Max. | Offset | Offset |
|
|
|
|
|
|
|
| ||
Offset |
| Elbow | 6' Max. Elbow |
| 6' Max. |
|
Elbow |
|
|
|
|
|
|
| A |
| B |
| C |
|
Figure 7 - Typical Offset Terminations
8 | www.fmiproducts.com |

Venting Installation
Continued
Screws
B
A
Figure 9 - Elbow Offset
Firestop Spacers
Firestop spacers are required at each point where the chimney penetrates a floor space. Their purpose is to establish and maintain the required clearance between the chimney and the combustible materials. When the pipe passes through a framed opening into a living space above, the firestop must be placed onto ceiling from below as shown in Figure 10.
They also provide complete separation from one floor space to another or attic space as required by most codes. When the double wall pipe passes through a framed opening into an attic space, the firestop must be placed into an attic floor as shown in Figure 11.
Existing Ceiling
Frame
Firestop
Spacer
Screws or Staples
(Min. of 8)
Figure 10 - Firestop Spacer with Living Space Above Ceiling
Screws or Staples Firestop (Min. of 8)
Spacer
Existing
Ceiling
Frame
Figure 11 - Firestop Spacer with Attic Space Above Ceiling
Penetrating roof
Tomaintaina1"clearancetopipeonaroofwith a pitch, a rectangular opening must be cut.
1.Determine the center point through which pipe will penetrate roof.
2.Determinethecenterpointoftheroof.Pitch is the distance the roof drops over a given span, usually 12".A6/12 pitch means that theroofdrops6"foreach12"onemeasure horizontally down from the roof rafters.
3.Use the roof opening chart (Figure 12) to determine the correct opening length and flashing required.
4.Remove shingles around the opening measured. Cut out this section.
5.Add next sections of pipe until the end penetrates roof line. Check to see that the proper clearances are maintained. Extend chimney by adding sections of double wall pipe until pipe is minimum of 30" above the highest point of the roof cutout. Termination and chimney must extend a minimum of 36" above the highest point where it passes through the roof.
19.5" Min. | 30" Min. |
| |
| 2" Min. |
| 2" Min. |
| 2" Min. |
| Opening "A" |
Pitch | Slope | Opening | Used Flashing |
|
| "A" Max. | Model No. |
Flat | 0° | 19.5" | |
26.6° | 22" | ||
6/1212/12 | 45.0° | 27" |
Figure 12 - Roof Opening Measurements
Flashing installation
Determine flashing to be used with the roof opening chart. Slide flashing over pipe until base is flat against roof. Replace as many shingles as needed to cover exposed area andflashingbase.Secureinpositionbynailing through shingles (see Figure 13, page 10). DO
NOT NAIL THROUGH FLASHING CONE.
www.fmiproducts.com | 9 |

Venting Installation
Continued
Storm | Overlap | |
Collar | ||
Shingles Top | ||
Flashing | ||
and Sides Only | ||
Cone | ||
|
Nail Only
Outer
Perimeter
of Flashing
Underlap Shingles
at Bottom
Figure 13 - Flashing Installation
Installing Flashing on a Metal Roof
When installing the flashing on a metal roof, it is required that putty tape be used between the flashing and the roof.The flashing must be secured to the roof using #8 x 3/4" screws and then sealed with roof coating to prevent leakage through the screw holes. A roof coating must also be applied around the perimeter of the flashing to provide a proper seal.
Storm Collar Installation
Place storm collar over pipe and slide down until it is snug against the open edge of the flashing (see Figure 14). Apply waterproof caulk around the perimeter of the collar to provide a proper seal.
Chimney | Waterproof |
Pipe | Caulk |
Storm | Flashing |
Collar |
CAUTION:Donotsealopeningsontherooftopflashing.Follow the installation instructions provided with the termination being used.
Stainless | ||
Level of | ||
Inner Flue | ||
Flue Gas | ||
Pipe | ||
Outlet | ||
| ||
Secure |
| |
Termination | Waterproof | |
to Outer | ||
Caulking | ||
Pipe with 3 | ||
Screws | Storm | |
| Collar | |
| Flashing |
Overlap | Underlap | |
Shingles (Top and Sides | ||
Shingles | ||
of Flashing Base) | ||
| ||
Figure 15 - Termination |
Chase installations
Instructions for chase installations are included with the chase style termination chosen. In a multiple chase installation, be sure to provide adequate distance between terminations to prevent smoke spillage from one termination to another. Terminations be separated a minimum of 24" center to center and stacked at a minimum vertical height difference of 18" (see Figure 16).
Note: If a decorative shroud is to be installed, contact the manufacturer for specifications.
Figure 14 - Storm Collar
Terminations/Spark Arrestor
The fireplace system must be terminated with the listed round top or chase terminations. In any case, refer to the installation instructions supplied with the termination.
18"
Min.
Typ.
24" Min.
24" Min.
Figure 16 - Multiple Chase Installation
10 | www.fmiproducts.com |