FMI CGDV32NR User Manual
Size:
2.07 Mb
Download

Location of Termination Cap

D

E V

B L

 

 

 

 

 

 

H

 

C

 

 

 

 

 

 

Fixed

V

 

B

V

I

 

Closed

Openable

Fixed

 

 

 

Openable

 

 

Closed

 

 

F

 

 

 

B

 

V

 

 

 

 

 

B

V J

X

G

 

 

 

 

B

 

A

 

M

 

 

 

N N

 

G

 

V

 

G

V K X

V

 

 

 

 

 

 

 

 

 

 

 

A

 

 

V TERMINATION CAP

X AIR SUPPLY INLET

 

G

GAS METER

 

 

RESTRICTED AREA

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(TERMINATION PROHIBITED)

A

=

clearance above grade, veranda, porch, deck, or

I

=

clearance to service regulator vent outlet [*72" (182.9 cm)

 

 

balcony [*12" (30.5 cm) minimum]

 

 

 

minimum]

 

 

 

B

=

clearance to window or door that may be opened

J

=

clearance to non-mechanicalair supply inlet to building

 

 

[6" (15 cm) min. for 10,000 Btu or less; 9" (23 cm) in US

 

 

or the combustion air inlet to any other fireplace

 

 

if between 10,000 and 50,000, 12" (30 cm) in Canada

 

 

[6" (15 cm) min. for 10,000 Btu or less; 9" (23 cm) in US

 

 

if between 10,000 and 100,000; 12" (30 cm) in US if

 

 

if between 10,000 and 50,000, 12" (30 cm) in Canada

 

 

greater than 50,000, 36" (91 cm) in Canada if greater

 

 

if between 10,000 and 100,000; 12" (30 cm) in US if

 

 

than 100,000]

 

 

 

greater than 50,000, 36" (91 cm) in Canada if greater

C

=

clearance to permanently closed window

 

 

 

than 100,000]

 

 

 

 

 

[minimum 12" (30.5 cm) recommended to prevent

K

=

clearance to a mechanical air supply inlet [*In Canada,

 

 

condensation on window]

 

 

 

6 ft. (1.83m) minimum; In US 3 ft. (91 cm) above if within

D

=

vertical clearance to ventilated soffit located above the

 

 

10 ft. (3 m) horizontally]

 

 

 

 

 

terminal within a horizontal distance of 24" (61 cm) from L

=

† clearance above paved side-walkor a paved driveway

 

 

the center-lineof the terminal [18" (45.7 cm) minimum]

 

 

located on public property [*84" (213.3 cm) minimum]

E

=

clearance to unventilated soffit [12" (30.5 cm) minimum] M =

clearance under veranda, porch, deck

F

=

clearance to outside corner (see below)

 

 

 

[*12" (30.5 cm) minimum ‡]

G

=

clearance to inside corner (see below)

 

N =

clearance above a roof shall extend a minimum of

H

=

*not to be installed above a meter/regulator assembly

 

 

24" (61 cm) above the highest point when it passes

 

 

within 36" (91.4 cm) horizontally from the center line

 

 

through the roof surface and any other obstruction within

 

 

of the regulator

 

 

 

a horizontal distance of 18" (45.7 cm)

vent shall not terminate directly above a side-walkor paved driveway which is located between two single family dwellings and serves both dwellings*

only permitted if veranda, porch, deck or balconey is fully open on a minimum of 2 sides beneath the floor* * as specified in CAN/CSA B149 (.1 or .2) Installation Codes (1991) for Canada and U.S.A.

Note: Local codes or regulations may require different clearances

Termination Clearances for Buildings with Combustible and Noncombustible Exteriors

Inside Corner

Outside Corner

Recessed Location

 

 

 

D

 

 

 

C

C

A

A = 6" (15.2 cm)

 

E

 

 

V

V

V

 

 

 

B = 6" (15.2 cm)

B

Balcony with No Side Wall

Balcony with Perpendicular Side Wall

G

V

G = 12" (30.5 cm) minimum clearance

H

V

J

Combustible &

Noncombustible H = 24" (61 cm) J = 20" (50.8 cm)

C = Maximum depth of 48" (121.9 cm) for recessed location

D = Minimum width for back wall of recessed location - Combustible - 38" (965 mm) Noncombustible - 24" (61 cm)

E = Clearance from corner in recessed locationCombustible - 6" (15.2 cm) Noncombustible - 2" (5.1 cm)

Figure 7 - Minimum Clearances for Termination Cap

116646-01J

www.fmiproducts.com

7

Venting Installation

NOTICE: Read these instructionscompletelybeforeattempting installation.

These models are tested and approved for use with FMI PRODUCTS, LLC (direct-vent)pipe components and terminations.

The venting system must terminate on the outside of the structure and can not be attached to a chimney or flue system serving a separate solid fuel or gas burning appliance. A direct-ventappliance must have its own venting system. DO NOT common vent this appliance.

These models are approved to be vented either horizontally through an outside wall or vertically through a roof or chase enclosure using the following guidelines:

When venting system terminates horizontally on an outside wall, you may install a standoff if the termination cap is to be installed directly on a combustible finish such as vinyl, wood, stucco, etc.

Never run the vent downward as this may cause excessive temperatures which could cause a fire.

Vent pipe air space clearances to combustibles are 1" on all sides except on the horizontal sections, which requires 2" clearance from the top of the pipe. Where the termination cap penetrates a combustible wall, 1" air space clearance is required.

Snorkel terminations are required when minimum clearance to grade cannot be met (see Figure 16 on page 12).

Have fireplace and selected vent components on hand to help determine the exact measurements when elbowing or offsetting. Always use wall firestops when penetrating walls and firestops when penetrating ceilings or attic spaces.

If using a venting configuration of only horizontal venting with no vertical run, a 1/4" rise for every 12" of run toward the termination is required.

For installation of fireplace at elevations of 4000 feet or greater, pay special attention to venting requirement recommendations.

WARNING: Read all instructionscompletelyandthoroughly before attempting installation.

Failure to do so could result in seriousinjury,propertydamage or loss of life.

NOTICE:Failuretofollowtheseinstructions will void the warranty.

NOTICE: Do not seal vent cap to pipe. Cap must be removable for service.

Installation Precautions

Wear gloves and safety glasses for protection

Use extreme caution when using ladders or when on roof tops

Be aware of electrical wiring locations in walls and ceilings

The following actions will void the warranty on your venting system:

Installation of any damaged venting component

Unauthorizedmodificationoftheventingsystem (Do not cut or alter vent components)

Installation of any component part not manufactured or approved by FMI PRODUCTS, LLC

Installation other than as instructed by these instructions

WARNING: This gas fireplace andventassemblymustbevented directlytotheoutside.Theventing system must NEVER be attached to a chimney serving a separate solidfuelburningappliance.Each direct-ventgasappliancemustuseaseparateventsystem.Donotuse common vent systems.

WARNING:Ventpipeairspace clearances to combustibles are

1" on all sides except on the horizontal sections, which require 2" clearances from the top of the pipe. Where the termination cap penetrates a combustible wall, 1" air space clearance is required.

8

www.fmiproducts.com

116646-01J

Venting Installation

Continued

INSTALLATION PLANNING

There are two basic types of direct-ventinstallation:

Horizontal Termination

Vertical Termination

Horizontal Termination Installation

IMPORTANT: Horizontal square terminations require only inner portion of wall firestop. Horizontal installations using round termination require exterior portion of wall firestop available only in vent kit HTK (see Figure 14, page 11).

1.Set fireplace in its desired location and determinetherouteyourhorizontalventing will take. Do not secure fireplace until all venting has been installed. Some installations require sliding fireplace in and out of position to make final venting connections. Figures14through18onpages11through 13showdifferentconfigurationsforventing withhorizontalterminationthatwillhelpyou decide which application best suits your installation. Check to see if wall studs or roof rafters are in the path of your desired venting route. If they are, you may want to adjust the location of the fireplace.

5.Carefully determine location where vent pipe assembly will penetrate the outside wall.The center of hole should line up with center line of horizontal vent pipe. Mark wall for a 11 1/2" x 111/2" square hole. Cut and frame the square hole in exterior wall where vent will be terminated. If wall being penetrated is constructed of noncombustible material, such as masonry block or concrete, a 81/2" hole with zero clearance is acceptable (see Figure 9).

WARNING: Do not recess vent termination into any wall. This will cause a fire hazard.

Female Locking Lugs

Male

Slots

2.Direct vent pipe sections and components are designed with special twist-lockconnections.

Twist-LockProcedure:Female ends of pipes have locking lugs (indentations). These lugs will slide straight into matching slots on male ends of adjacent pipes. Push pipe sections together and twist one section clockwise approximately onequarter turn until sections are fully locked (see Figure 8). Note: Horizontal runs of vent must be supported every three feet. Use wall straps for this purpose.

3.Use a 45° elbow to connect venting system to fireplace flue collar. The elbow is designed to be twist-lockedonto flue collar as described in step 2.IMPORTANT: Do not attempt to alter configuration of elbow by cutting, twisting, bending, etc.

4.Assemble desired combination of pipe and elbows to fireplace flue collar. If there are long portions of venting run, preassembled pipe sections may be installed as subassemblies for convenience.

Figure 8 - Vent Pipe Connections

Vent Opening

 

Combustible Wall

11 1/2" Inside Framing

11 1/2"

 

11 1/2"

 

(Framing

Vent Opening

Detail)

 

Noncombustible Wall

 

8 1/2"

 

 

Center

 

of Hole

Figure 9 - Vent Opening Requirements

116646-01J

www.fmiproducts.com

9

Venting Installation

Continued

6.Noncombustible Exterior Wall: Position horizontal vent cap in center of the 8 1/2" round hole and attach to exterior wall with fourscrews(seeFigure10). Note: The four wood screws provided should be replaced with appropriate fasteners for stucco, brick, concrete or other types of sidings. Before attaching vent cap to exterior wall, run a bead of non-hardening mastic (pliable sealant) around outside edges to make a seal between it and outside wall.

Combustible Exterior Wall: For vinyl siding, stucco or wood exteriors, a siding standoff may be installed between vent cap and exterior wall. Siding standoff prevents excessive heat from damaging siding materials. Siding material must be cut to accommodate standoff. Bolt vent cap to standoff. Apply non-hardening mastic around outside edge of standoff. Position standoff/cap assembly in center of the 11 1/2" square hole and attach to exterior wall with wood screws provided (see Figure 11). Siding standoff must sit flush against exterior fascia material.

7.Connecting Vent Cap with Horizontal Vent Pipe: Slide wall firestop over vent pipe before connecting horizontal run to vent cap (see Figure 12).

Carefully move fireplace, with vent assembly attached, toward wall and insert vent pipe into horizontal termination. The pipe overlap should be a minimum of 1 1/4" (see Figure 13, page 11).

Apply Mastic to

All Four Sides

Vent

Cap

Wood

Screw

Figure 10 - Installing Horizontal Vent Cap

(Noncombustible Exterior)

Slide wall firestop against interior wall surface and attach with screws provided (see Figure 12). See Figure 13, page 11, for horizontal termination details.

Place fireplace into position and shim with noncombustible material if needed. Nail or screw side flanges to framing to secure unit in place. IMPORTANT: Make sure fireplace is level before securing. If fireplace is not level it will not work properly.

Cut Siding Away to

Fit Standoff

Standoff

Wood Screw

Vent Cap

Screws

Apply Mastic to All Four Sides

Figure 11 - Installing Siding Standoff

(Combustible Exterior)

Interior Wall

Surface

Wall

Firestop

Vent Cap

 

 

(Horizontal

Screw

Horizontal

Termination)

 

 

Vent Pipe

 

 

Figure 12 - Connecting Vent Cap with Horizontal Vent Pipe

10

www.fmiproducts.com

116646-01J

 

Venting Installation

 

 

Continued

 

 

 

Siding

GROUND FLOOR INSTALLATION

 

Recommended Applications:

 

 

Standoff

 

 

• Installation using cabinet surrounds

 

 

Minimum Pipe

Screws

• Through the wall using round or square

Overlap 1 1/4"

termination (up to 12") adjustable pipe)

Wall

 

• NOT FOR CORNER INSTALLATION

 

45° Elbow

 

Firestop

 

 

 

 

Horizontal High

 

 

 

Wind Square

 

 

 

 

Termination

 

 

Direct Vent

 

 

Adjustable

 

 

 

Pipe 12"

 

Pipe

 

 

 

High Wind

Wall

Max.

 

Maintain 1"

 

Termination

Firestop

 

Minimum Air Space

 

 

 

Apply Mastic

 

 

 

Around Outer Pipe

 

 

 

to Outside

 

 

 

When Penetrating

 

Square Termination

Edge of

 

a Wall

 

Standoff

 

Vertical (V)

Horizontal (H)

 

 

11 1/2" x 111/2"

 

 

29 3/4"

17" max.

Framed Opening Exterior Wall

45° Elbow

 

 

 

 

Exterior

with Vinyl Siding

 

 

 

 

Figure 13 - Typical Horizontal

Wall

 

 

 

Portion of Wall

 

 

 

Firestop (Round

Termination Cap Mounting with

Firestop

 

 

Termination Only)

Additional Siding Standoff Installed

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Horizontal Termination Configurations

 

 

 

 

 

 

 

 

 

 

 

 

 

Figures14through18showdifferentconfigura-

 

 

 

 

 

 

 

 

 

 

 

 

 

tionsandalternativesforventingwithhorizontal

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

termination. Each figure includes a chart with

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

critical minimum and maximum dimensions

 

 

 

 

 

 

 

 

 

 

 

 

 

which MUST be met. IMPORTANT: If using a

 

 

 

 

Slide Ring

venting configuration of only horizontal venting

 

 

 

 

 

 

 

 

Over Elbow

with no vertical run, a 1/4" rise for every 12" of

 

 

 

 

 

 

 

 

to Complete

run toward termination is required.

 

 

 

 

 

 

 

 

Connection

 

 

 

 

 

 

NOTICE:Donotsealtermination

 

 

 

 

 

 

 

 

Horizontal Round

cap to vent pipe. Cap must be

 

 

 

 

 

 

 

 

Termination

removable for vent inspection

 

 

Round Termination

and maintenance.

 

 

 

(Kit HTK Shown)

 

 

Figure 14 - Horizontal Termination

 

 

WARNING: Never run vent

 

Configuration for Square or Round

 

 

 

Termination

downward as this may cause

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

excessive temperatures which

 

 

 

 

 

 

 

 

 

 

 

 

 

 

could cause a fire. Operation of

 

 

 

 

 

 

 

 

 

 

 

 

 

 

improperly installed and main-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

tained venting system could

 

 

 

 

 

 

 

 

 

 

 

 

 

 

resultinseriousinjury,property

 

 

 

 

 

 

 

 

 

 

 

 

 

 

damage or loss of life.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

116646-01J

www.fmiproducts.com

11

12" Min.
Snorkel
Termination

Venting Installation

Continued

CORNER INSTALLATION

Recommended Applications:

Corner ground floor installation

Ground floor installation where pipe vents horizontally through wall (over 12" horizontal pipe)

Basement installation where one foot clearance from ground to termination is possible

 

Not to Exceed

90° Elbow

Not to Exceed

Square

 

(H) Limits

 

 

(H) Limits

Square

As Required

Termination

 

90°

Termination

for (V), See

 

Elbow

 

 

 

Chart for

 

 

 

 

 

 

 

Pipe Section

 

 

 

 

Required

 

 

 

 

 

 

Wall

12" Min.

 

 

 

 

Firestop

 

Wall

45°

 

 

 

 

Firestop

 

 

 

 

Elbow

 

 

45°

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Elbow

 

 

 

 

Vertical (V)

Required

 

 

Vertical (V)

Vertical Pipe

Horizontal (H)

 

 

*43 3/4" min.

None

30" max.

 

 

53 3/4" min.

1 ft.

48" max.

 

 

65 3/4" min.

2 ft.

60" max.

 

 

77 3/4" min.

3 ft.

84" max.

 

 

89 3/4" min.

4 ft.

20' max.

 

* Ground Floor Corner Venting

Figure 15 - Horizontal Termination Configuration for Corner Installation Using One

90° Elbow

SNORKEL TERMINATION INSTALLATION

Recommended Applications:

Installations requiring a vertical rise on building exterior

Any installation using snorkel termination to achieve one foot above ground

Snorkel terminations are available for installations requiring a vertical rise on exterior of building. If installing snorkel termination below grade, you must provide proper drainage to prevent water from entering snorkel termination (see Figure 16). Do not back fill around snorkel termination.

Snorkel

Termination

12" Min.

Snorkel

 

 

Wall

Termination

 

Firestop

 

 

 

90° Elbow

 

12" Min.

 

 

 

Adequate

Drainage

Figure 16 - Snorkel Termination Configurations for Below Ground Installation

12

www.fmiproducts.com

116646-01J

Venting Installation

Continued

HORIZONTAL SYSTEM INSTALLATION USING TWO 90° ELBOWS

The following configurations show the minimum vertical rise requirements for a horizontal system using two 90° elbows.

Venting with Two 90° Elbows

 

 

Horizontal (H1) +

Vertical (V)

Horizontal (H1)

Horizontal (H2)

5' min.

2' max.

6' max.

6' min.

4' max.

12' max.

7' min.

6' max.

18' max.

8' min.

8' max.

20' max.

20' max.

8' max.

20' max.

45° Elbow

Figure 17 - Horizontal Termination Configuration for Venting Using Two 90° Elbows

Venting with Two 90° Elbows

 

 

Horizontal (H1) +

 

Vertical (V) Horizontal (H2)

 

5' min.

6' max.

 

6' min.

12' max.

 

7' min.

18' max.

45° Elbow

8' min.

20' max.

 

20' max.

20' max.

 

Figure 18 - Horizontal Termination Configuration for Venting Using Two 90° Elbows with Termination at 90° with Fireplace

116646-01J

www.fmiproducts.com

13

Venting Installation

Continued

installation for vertical termination

Note: Vertical restrictor must be installed in all vertical installations.

1.Determine route your vertical venting will take. If ceiling joists, roof rafters or other framing will obstruct venting system, consider an offset (see Figure 19) to avoid cutting load bearing members. Note: Pay special attention to these installation instructions for required clearances (air space) to combustibles when passing through ceilings, walls, roofs, enclosures, attic rafters, etc. Do not pack air spaces with insulation. Also note maximum vertical rise of venting system and any maximum horizontal offset limitations.

2.Set fireplace in desired location. Drop a plumb line down from ceiling to position of fireplace exit flue. Mark center point where vent will penetrate ceiling. Drill a small locating hole at this point.

Drop a plumb line from inside of roof to locating hole in ceiling. Mark center point where vent will penetrate roof. Drill a small locating hole at this point.

Roof

Flashing

Wall Strap

45° Elbow

Flat Ceiling Installation

1.Cuta111/2"squareholeinceilingusinglocatingholeasacenterpoint.Openingshouldbe framed to 111/2" x 111/2" inside dimensions, asshowninFigure9onpage9usingframing lumberthesamesizeasceilingjoists.Ifarea abovetheceilingisaninsulatedceilingoran attic,nailfirestopfromtopside.Thisprevents loose insulation from falling into required clearance space. If area above ceiling is a living space, install firestop below framed hole.Firestopshouldbeinstalledwithnoless than 3 nails per side (see Figure 20).

2.Assemble desired lengths of pipe and elbows necessary to reach from fireplace flue up through firestop. Be sure all pipe and elbow connections are fully twistlocked (see Figure 8, page 9).

3.Cut a hole in roof using locating hole as a center point. (Cover any exposed open vent pipes before cutting hole in roof.)The

111/2" x 111/2" hole must be measured on the horizontal; actual length may be larger depending on pitch of roof. There must be a 1" clearance from vent pipe to combustible materials. Frame opening as shown in Figure 9, page 9.

4.Connect a section of pipe and extend up through hole.

Note: If an offset is needed to avoid obstructions, you must support vent pipe every 3 feet. Use wall straps for this purpose (see Figure 19). Whenever possible, use 45° elbows instead of 90° elbows. The

45°elbowofferslessrestrictiontotheflow of flue gases and intake air.

5.Place flashing over pipe section(s) extending through roof. Secure base of flashing to roof and framing with roofing nails. Be sure roofing material overlaps top edge of flashing as shown in Figure

19.There must be a 1" clearance from vent pipe to combustible materials.

Ceiling

Firestop

Figure 19 - Offset with Wall Strap and 45° Elbows

If area above is an

If area above is a

attic or insulated

living space, install

area, install firestop

firestop below framed

above framed hole.

hole.

Figure 20 - Installing Firestop

14

www.fmiproducts.com

116646-01J

Venting Installation

Continued

6.Continue to add pipe sections until height of vent cap meets the minimum building code requirements described in Figure 7 on page 7. Note: You must increase vent height for steep roof pitches. Nearby trees, adjoining rooflines, steep pitched roofs and other similar factors may cause poor draft or down-drafting in high winds. Increasing vent height may solve this problem.

7.Twist-lockvent cap onto last section of vent pipe.

Note: If vent pipe passes through any occupied areas above first floor, including storage spaces and closets, you must enclose pipe. You may frame and sheetrock enclosure with standard construction material. Make sure and meet minimum allowable clearances to combustibles. Do not fill any required air spaces with insulation.

Vertical Termination Configurations

Figures 21 through 24 show four different configurations for vertical termination.

Venting with Two 90° Elbows

 

Horizontal (H1) +

Vertical (V) Horizontal (H2)

5' min.

2' max.

6' min.

4' max.

7' min.

6' max.

8' min.

8' max.

20' max.

8' max.

45° Elbow

Note: Install restrictor into inner collar of fireplace as shown.

Figure 21 - Vertical Venting

Configuration Using Two 90° Elbows

with Two Horizontal Runs (Vertical

Round High Wind Termination Shown)

Venting with One 90° Elbow

Vertical (V) Horizontal (H)

5' min.

2' max.

6' min.

4' max.

7' min.

6' max.

8' min.

8' max.

20' max.

8' max.

45° Elbow

 

Note: Install restrictor into inner collar of fireplace as shown.

Figure 22 - Vertical Venting Configuration

Using One 90° Elbow (Vertical Round

High Wind Termination Shown)

Note: Install

restrictor into inner

collar of fireplaceas shown.

45° Elbow

Venting with Two 90° Elbows

Vertical (V1)

Horizontal (H)

5' min.

6' max.

6' min.

12' max.

7' min.

18' max.

8' min.

20' max.

Note: Vertical (V1) + Vertical (V2) = 40' max.

Figure 23 - Vertical Venting Configuration Using Two 90° Elbows (Vertical Round

High Wind Termination Shown)

116646-01J

www.fmiproducts.com

15

Venting Installation

Continued

starter elbow (see Figure 25) and a round

horizontal termination be used.

45° Starter

Elbow

12"

Extension

Vertical Venting

V = 40' max.

Note: Install restrictor into inner collar of fireplace as shown.

45° Elbow

Figure 24 - Vertical Venting Configuration

With No Horizontal Run (Vertical Round

High Wind Termination Shown)

High Altitude Installation

Your FMI PRODUCTS, LLC direct-ventfireplace has been tested and approved for elevations from0-2000feet (USA).

Fireplaces for High Altitude (models ending in -HA)are for installation above 4000 feet only.These fireplaces are equipped with parts specific for higher altitudes.

When installing a non-highaltitude fireplace at an elevation above 2000 feet (in the USA), you may need to decrease the input rating by changing the existing burner orifice to a smaller size. Reduce input 4% for each 1000 feet above sea level. Check with your local gas company for proper orifice size identification.

IMPORTANT: For horizontal installations above 2,000 feet, it is recommended that a 12" extension pipe be added before

Figure 25 - Recommended 12" Extension

for High Altitude Installation

Parts list for venting kits and components

FMIPRODUCTS,LLC(5"/8")Pipe&VentKits Number Description

P58-66" Section Double Wall Pipe, Galvanized

P58-1212" Section Double Wall Pipe, Galvanized

P58-2424" Section Double Wall Pipe, Galvanized

P58-3636" Section Double Wall Pipe, Galvanized

P58-4848" Section Double Wall Pipe, Galvanized

PA58-712Adjustable7"-12"Section Double

Wall Pipe, Galvanized E58-4545° Elbow, GalvanizedE58-9090° Elbow, Galvanized

VKG-58Ground Floor Vent Kit, Galvanized (Includes: 45° Elbow,7"-12"Adjustable Pipe, Wall Firestop, Horizontal Square Termination, 16 Screws)

VKB-58Basement Vent Kit, Galvanized (Includes: 45° Elbow,7"-12"Adjustable Pipe, Wall Firestop, Horizontal Square Termination, 4' Pipe, 90° Elbow, 20 Screws)

VKS-58Snorkel Vent Kit, Galvanized (Includes: 45° Elbow,7"-12"AdjustablePipe, Wall Firestop, 36" Snorkel Termination, 4' Pipe, 1' Pipe, 90° Elbow, 26 Screws)

VKR-58Roof Vent Kit, Galvanized (Includes: 45° Elbow,7"-12"Adjustable Pipe, Flue Restrictor, Vertical High Wind Termination, 2' Pipe, 4' Pipe, Wall Firestop, Storm Collar, Roof Flashing [0/12 - 6/12], 26 Screws)

16

www.fmiproducts.com

116646-01J