Fedders CH18ABD1VF, CH30ACD1VF, CH24ACD1VF, CH42ACD1VF, CH60ACZ1VF User Manual

...
0 (0)
Fedders CH18ABD1VF, CH30ACD1VF, CH24ACD1VF, CH42ACD1VF, CH60ACZ1VF User Manual

Residential & Light Commercial HVAC

Rated in Accordance with ARI Standard 210/240. Certification Applies Only When Used with Proper Components as Listed with ARI. Additional rating information can be found at www.aridirectory.org

Split System Heat Pump

112 thru 5 Tons

208/230 Volt, 1-Phase, 60 Hz

Performance:

Efficiency rating of 13 SEER

Cooling capacities from 112 to 5 tons

Refrigerant Circuit:

Factory installed biflow liquid line filter drier

Long life copper tubes, aluminum fins

State-of-the-art compressors

Large, wrap-around coil surface

Quality Built:

Galvanized steel exterior cabinet with 1,000-hour salt spray, powder-coated finish

Powder-coated fan guard

Full louvered panel to protect coil

Formed base with 212" ground clearance

Limited 5-year warranty on parts

Low pressure port

Integrated solid state control with adjustable time-temp demand defrost

Easy To Install:

Factory-charged

Only three screws to access electrical controls

Easy access to service valves

 

Model

Size

Refrigerant

Nominal

Min. Circuit

2Max. Fuse

Operating Dimensions

Min. Mounting

Ship / Operating

 

 

Number

(tons)

BTUH

Ampacity

or Breaker

H x W x D (inches)

Pad Size (inches)

Weight (lbs)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CH18ABD1VF

1 12

R-22

18,000

13.5

20

32 12 X 21 12 X 21 12

24 x 24

132 / 127

 

 

 

 

 

 

 

 

 

 

 

 

 

CH24ACD1VF

2

R-22

24,000

16.0

25

32 12 X 29 12 X 29 12

32 x 32

195 / 186

 

 

CH30ACD1VF

2 12

R-22

30,000

18.8

30

32 12

X 29 12

X 29 12

32 x 32

195 / 186

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CH36ACD1VF

3

R-22

36,000

20.5

35

32 12

X 29 12

X 29 12

32 x 32

197 / 188

 

 

CH42ACD1VF

3 12

R-22

42,000

24.8

40

32 12

X 29 12

X 29 12

32 x 32

208 / 201

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CH48ACD1VF

4

R-22

48,000

27.3

45

32 12

X 29 12

X 29 12

32 x 32

212 / 203

 

 

CH60ACZ1VF

5

R-410A

60,000

38.4

60

39 X 29 12 X 29 12

32 x 32

258 / 249

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Product Specifications

PHYSICAL DATA

 

MODEL SIZE

18

24

30

36

42

48

60

 

 

 

 

 

 

 

 

 

 

 

 

PERFORMANCE DATA

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NOMINAL CAPACITY (BTUH)

18,000

24,000

30,000

36,000

42,000

48,000

60,000

 

 

 

 

 

 

 

 

 

 

 

 

FAN DATA

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FAN MOTOR TYPE

PSC

PSC

PSC

PSC

PSC

PSC

PSC

 

 

 

 

 

 

 

 

 

 

 

 

HP

1/5

1/3

1/3

1/3

1/3

1/3

1/3

 

 

 

 

 

 

 

 

 

 

 

 

DIAMETER

18"

22"

22"

22"

22"

22"

24"

 

 

 

 

 

 

 

 

 

 

 

 

BLADE

3

3

3

3

3

3

3

 

 

 

 

 

 

 

 

 

 

 

 

RPM

1,050

1,050

1,050

1,050

1,050

1,050

950

 

 

 

 

 

 

 

 

 

 

 

 

CFM

1,800

3,400

3,400

3,400

3,400

3,400

4,000

 

 

 

 

 

 

 

 

 

 

 

 

OUTDOOR COIL

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

TYPE

 

Enhanced Aluminum Plate Fin / Rifled Copper Tube

 

 

 

 

 

 

 

 

 

 

 

 

 

COIL FACE AREA (ft2)

12.2

18.2

18.2

18.2

18.2

18.2

22.2

 

 

 

 

 

 

 

 

 

 

 

 

O.D.

3/8"

7mm

7mm

7mm

7mm

7mm

7mm

 

 

 

 

 

 

 

 

 

 

 

 

FPI / ROWS

18 -1

18-2

18-2

18-2

18-3

18-3

18-3

 

 

 

 

 

 

 

 

 

 

 

 

ELECTRICAL DATA (208/230 – 1-60, VOLTAGE RANGE 197V - 253V)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MINIMUM CIRCUIT AMPACITY - MCA (amps) 2

13.5

16.0

18.8

20.5

24.8

27.3

38.5

 

 

 

 

 

 

 

 

 

 

 

 

MAXIMUM OVERCURRENT PROTECTIVE DEVICE-MOCP(amps)3

20

25

30

35

40

45

50

 

 

COMPRESSOR RLA (Rated Load Amps)

10.0

11.4

13.6

15

18.4

20.9

29.4

 

 

 

 

 

 

 

 

 

 

 

 

COMPRESSOR LRA (Locked Rotor Amps)

41

56

67

73

95

109

134

 

 

 

 

 

 

 

 

 

 

 

 

FAN MOTOR FLA (Full Load Amps)

1.4

1.8

1.8

1.8

1.8

1.8

1.9

 

 

 

 

 

 

 

 

 

 

 

 

REFRIGERANT CONNECTIONS

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

LIQUID LINE CONNECTION SIZE (In. OD)

3/8

3/8

3/8

3/8

3/8

3/8

3/8

 

 

 

 

 

 

 

 

 

 

 

 

SUCTION LINE CONNECTION SIZE (In. OD)

3/4

3/4

7/8

7/8

7/8

7/8

7/8

 

 

 

 

 

 

 

 

 

 

 

 

RECOMMENDED LINE SET LIQUID TUBE DIAMETER (In. OD)

3/8

3/8

3/8

3/8

3/8

3/8

3/8

 

 

 

 

 

 

 

 

 

 

 

 

RECOMMENDED LINE SET SUCTION DIAMETER (In. OD)

3/4

3/4

7/8

7/8

7/8

1 1/8

1 1/8

 

 

 

 

 

 

 

 

 

 

 

 

FACTORY CHARGE - OZ.

103

164

154

164

207

233

233*

 

 

 

 

 

 

 

 

 

 

 

NOTE: Control circuit is 24V on all units and requires external power source. Copper wire must be used from service disconnect to unit. ALL motors/compressors contain internal overload protection.

1.Wire size should be determined in accordance with National Electrical Codes. Extensive wire runs will require larger wire sizes.

2.Time delay fuses may be used in place of HACR circuit breaker.

* Unit uses R-410A refrigerant.

2

Specifications subject to change without notice.

Loading...