INSTALLATION INSTRUCTIONS

AND

OWNER'S MANUAL

Installer: Please leave these instructions with the consumer.

Consumer: Please retain these instructions for future use.

WARNING: If not installed, operated and maintained in accordance with the manufacturer's instructions, this product could expose you to substances in fuel or from fuel combustion which can cause death or serious illness.

FAN TYPE

VENTED

WALL FURNACE

MODEL

FAW-40-1SPP

FAW-40-1IP

EFFECTIVE DATE

SEPTEMBER 2003

WARNING: If the information in this manual is not followed exactly, a fire or explosion may result causing property damage, personal injury or loss of life.

Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance.

WHAT TO DO IF YOU SMELL GAS

Do not try to light any appliance.

Do not touch any electrical switch; do not use any phone in your building.

Immediately call your gas supplier from a neighbor's phone. Follow the gas supplier's instructions.

If you cannot reach your gas supplier, call the fire department.

Installation and service must be performed by a qualified installer, service agency or the gas supplier.

12427-2-0903

Page 1

Introduction

Always consult your local Building Department regarding regulations, codes or ordinances which apply to the installation of a vented wall furnace.

Instructions to Installer

1.Installer must leave instruction manual with owner after installation.

2.Installer must have owner fill out and mail warranty card supplied with furnace.

3.Installer should show owner how to start and operate furnace and thermostat.

Warning:

Any change to this furnace or its control can be dangerous. This is a heating appliance and any panel, door or guard removed for servicing an appliance must be replaced prior to operating the appliance.

General Information

This series is design certified in accordance with American National Standard / CSA Standard Z21.86 and CSA 2.32 by the Canadian Standards Association, as a Fan Type Vented Wall Furnace and must be installed according to these instructions.

Any alteration of the original design, installed other than as shown in these instructions or use with a type of gas not shown on the rating plate is the responsibility of the person and company making the change.

Important

All correspondence should refer to complete Model No., Serial No. and type of gas.

Notice: During initial firing of this unit, its paint will bake out and smoke will occur. To prevent triggering of smoke alarms, ventilate the room in which the unit is installed.

Installation on Rugs and Tile

If this appliance is installed directly on carpeting, tile or other combustible material other than wood flooring the appliance shall be installed on a metal or wood panel extending the full width and depth of the appliance.

The base referred to above does not mean the fire-proofbase as used on wood stoves. The protection is for rugs that are extremely thick and light colored tile.

Installation in Residential Garages

Gas utilization equipment in residential garages shall be installed so that all burners and burner ignition devices are located not less than 18" (457mm) above the floor.

Such equipment shall be located, or protected, so it is not subject to physical damage by a moving vehicle.

Specifications

Model

 

FAW-40SPP

FAW-40IP

 

 

 

 

Input BTU/HR (KW/H)

 

40,000 (11.7)

40,000 (11.7)

 

 

 

 

Height

 

72 1/2" (184.2cm)

72 1/2" (184.2cm)

Width

 

14 1/8" (35.9mm)

14 1/8" (35.9mm)

 

 

 

 

Depth

 

10 3/8" (26.4mm)

10 3/8" (26.4mm)

 

 

 

 

Gas Inlet Pipe

 

1/2" (1.27cm)

1/2" (1.27cm)

Vent Collar Type B Oval

 

4" (10.2cm)

4" (10.2cm)

CFM

 

275

275

 

 

 

 

Accessories

 

 

 

 

 

Register, side outlet, fixed register

SOR-1

Side outlet, 10" (254mm)

 

SOK-1

maximum extension, fixed register

 

 

 

 

 

Rear Outlet, 10" (254mm)

 

ROK-1

maximum extension, adjustable register

 

 

 

 

Vent enclosure, 24" (61cm)

FVE-24

[for rooms up to 96 1/2" (245cm) in height]

 

Vent enclosure, 34" (86cm)

FVE-34

[for rooms up to 106 1/2" (270.5cm) in height]

 

 

 

 

Vent enclosure, 46" (117cm)

FVE-46

[for rooms up to 118 1/2" (301cm) in height]

 

 

 

 

Oval-to-Roundflue adapter kit 4" (102mm)

DV-648

 

 

 

 

THIS IS A HEATING APPLIANCE

DO NOT OPERATE THIS APPLIANCE WITHOUT FRONT PANELS INSTALLED.

Due to high temperatures the appliance should be located out

 

the flow of combustion and ventilation air.

of traffic and away from furniture and draperies.

• DO keep the appliance area clear and free from combustible

 

• Children and adults should be alerted to the hazards of high

 

material, gasoline and other flammable vapors and liquids.

surface temperatures and should stay away to avoid burns or

• DO examine venting system periodically and replace dam-

clothing ignition.

 

aged parts.

 

 

• Young children should be carefully supervised when they are

• DO make a periodic visual check of pilot and burners. Clean

in the same room as the appliance.

 

and replace damaged parts.

 

 

• Clothing or other flammable material should not be placed on

CAUTION: Pilot hole cover must be kept tightly closed

or near the appliance.

 

during operation.

 

 

• Any safety screen or guard removed for servicing an appliance

• DO NOT use this heater if any part has been under water.

must be replaced prior to operating the appliance.

 

Immediately call a qualified service technician to inspect the

 

 

• Keep burner and control compartment clean.

 

heater and to replace any part of the control system and any

• Installation and repair should be done by a QUALIFIED

 

gas control which has been under water.

 

 

 

SERVICE PERSON. The appliance should be inspected

This furnace must not be connected to a chimney flue serving

before use and at least annually by a qualified service person.

 

a separate solid-fuelburning appliance.

More frequent cleaning may be required due to excessive lint

 

 

 

IMPORTANT: This furnace has a washable permanent

 

from carpeting, bedding materials, etc. It is imperative that

 

 

type filter in the door which should be cleaned at least once

 

control compartments, burners and circulating air passage-

 

 

 

per year before the heating season. For dirty or high use

 

ways of the appliance be kept clean.

 

 

 

areas more frequent cleaning is required.

 

• DO NOT put anything around the furnace that will obstruct

 

 

 

 

 

 

 

 

 

Page 2

12427-2-0903

SAFETY INFORMATION FOR USERS OF LP-GAS

Propane (LP-Gas)is a flammable gas which can cause fires and explosions. In its natural state, propane is odorless and colorless. You may not know all the following safety precautions which can protect both you and your family from an accident. Read them carefully now, then review them point

by point with the members of your household. Someday when there may not be a minute to lose, everyone's safety will depend on knowing exactly what to do. If, after reading the following information, you feel you still need more information, please contact your gas supplier.

LP-GASWARNING ODOR

If a gas leak happens, you should be able to smell the gas because of the odorant put in the LP-Gas.That's your signal to go into immediate action!

Do not operate electric switches, light matches, use your phone. Do not do anything that could ignite the gas.

Get everyone out of the building, vehicle, trailer, or area. Do that IMMEDIATELY.

Close all gas tank or cylinder supply valves.

LP-Gasis heavier than air and may settle in low areas such as basements. When you have reason to suspect a gas leak, keep out of basements and other low areas. Stay out until

firefighters declare them to be safe.

Use your neighbor's phone and call a trained LP-Gasservice person and the fire department. Even though you may not continue to smell gas, do not turn on the gas again. Do notre-enterthe building, vehicle, trailer, or area.

Finally, let the service man and firefighters check for escaped gas. Have them air out the area before you return. Properly trainedLP-Gasservice people should repair the leak, then check and relight the gas appliance for you.

NO ODOR DETECTED - ODOR FADE

Some people cannot smell well. Some people cannot smell the odor of the chemical stench put into the gas. You must find out if you can smell the odorant in propane. Smoking can decrease your ability to smell. Being around an odor for a time can affect your sensitivity or ability to detect that odor. Sometimes other odors in the area mask the gas odor. People may not smell the gas odor or their minds are on something else. Thinking about smelling a gas odor can make it easier to smell.

The odorant in LP-gasis colorless, and it can fade under some circumstances.For example, if there is an underground leak, the movement of the gas through soil can filter the odorant. Odorants in LP-Gas also are subject to oxidation. This fading

can occur if there is rust inside the storage tank or in iron gas pipes.

The odorant in escaped gas can adsorb or absorb onto or into walls, masonry and other materials and fabrics in a room. That will take some of the odorant out of the gas, reducing its odor intensity.

LP-Gasmay stratify in a closed area, and the odor intensity could vary at different levels. Since it is heavier than air, there may be more odor at lower levels. Always be sensitive to the slightest gas odor. If you detect any odor, treat it as a serious leak. Immediately go into action as instructed earlier.

SOME POINTS TO REMEMBER

Learn to recognize the odor of LP-gas.Your local LP-Gas Dealer can give you a "Scratch and Sniff" pamphlet. Use it to find out what the propane odor smells like. If you suspect that your LP-Gas has a weak or abnormal odor, call your LPGas Dealer.

If you are not qualified, do not light pilot lights, perform service, or make adjustments to appliances on the LP-Gassystem. If you are qualified, consciously think about the odor ofLP-Gasprior to and while lighting pilot lights or performing service or making adjustments.

Sometimes a basement or a closed-uphouse has a musty smell that can cover up theLP-Gasodor. Do not try to light pilot lights, perform service, or make adjustments in an area where the conditions are such that you may not detect the odor if there has been a leak ofLP-Gas.

Odor fade, due to oxidation by rust or adsorption on walls of new cylinders and tanks, is possible. Therefore, people should be particularly alert and careful when new tanks or cylinders are placed in service. Odor fade can occur in new tanks, or reinstalled old tanks, if they are filled and allowed

to set too long before refilling. Cylinders and tanks which have been out of service for a time may develop internal rust which will cause odor fade. If such conditions are suspected to exist, a periodic sniff test of the gas is advisable. If you have any question about the gas odor, call your LP-gas dealer. A periodic sniff test of the LP-gas is a good safety measure under any condition.

If, at any time, you do not smell the LP-Gasodorant and you think you should, assume you have a leak. Then take the same immediate action recommended above for the occasion when you do detect the odorizedLP-Gas.

If you experience a complete "gas out," (the container is under no vapor pressure), turn the tank valve off immediately. If the container valve is left on, the container may draw in some air through openings such as pilot light orifices. If this occurs, some new internal rusting could occur. If the valve is left open, then treat the container as a new tank. Always be sure your container is under vapor pressure by turning it off at the container before it goes completely empty or having it refilled before it is completely empty.

12427-2-0903

Page 3

Ventilation and Combustion Air

WARNING: Danger of property damage, bodily injury or death, this furnace and any other fuel burning appliance must be provided with enough fresh air for proper combustion and ventilation of flue gases. Most homes will require that outside air be supplied. Do not draw air from a corrosive environment such as a workshop or laundry room.

The requirements for providing air for combustion and ventilation are listed in the National Fuel Gas Codes NFPA 54/ANSI Z223.1 (in Canada - CAN/CGA B149).

Note: Air requirements for operation of exhaust fans, kitchen ventilation systems, clothes dryers, fireplace and any other fuel burning or ventilating equipment used in the space must be considered in determining combustion air requirements.

Ventilation Air Openings and Ducts

In determining the free area needed consideration must be given to the blocking effect of louvers, grills or screens protecting openings.

If a screen is used to cover openings it must not be smaller than 1/4" mesh.

Use the free area of a louver or grill to determine the size opening required to provide the free area specified. If the free area is not known assume a 20% free area for wood and a 60% free area for a metal louver or grill.

Ducts must have the same cross sectional area as the free area of the openings to which they connect.

The minimum dimension of air ducts must not be less than 3 inches.

Installation in an Unconfined Space

An unconfined space is an area including all rooms not separated by doors with a volume greater than 50 cubic feet per 1,000 Btuh of the combined total input rates of all appliances which draw combustion air from that space. For example, a space including a water heater rated at 40,000 Btuh input and a furnace rated at 40,000 Btuh requires a volume of 4,000 cubic feet (50 x (40 + 40) = 4,000) to be considered as unconfined. If the space has an 8 ft. ceiling, the floor area of the space must be 500 sq. ft. In general, particularly in older homes, a furnace installed in an unconfined space will not require outside air for combustion. However in a "tight" newly constructed home, outside air may be necessary to insure adequate combustion.

Installation in a Confined Space

A confined space is an area with volume less than 50 cubic feet per 1,000 Btuh of the combined input rates of all appliances drawing combustion air from that space. Small areas such as equipment rooms are confined spaces. Furnaces installed in a confined space which supply heated air to areas outside the space must draw return air from outside the space through tightly sealed return air ducts. A confined space must have 2 openings into the space for combustion air. One opening must be within 12 inches of the ceiling and the other must be within 12 inches of the floor. The required sizing of these openings is determined by whether inside or outside air is used to support combustion, the method by which the air is brought to the space (vertical or horizontal duct) and by the total input rate of all appliances in the space. See Figure 1.

All Air From Inside — Confined Space

If combustion air is taken from the heated space the 2 openings must each have a free area of at least one square inch per 1,000 Btuh of total input of all appliances in the confined space but not less than 100 square inches (645cm2) of free area.

For example: for a 40,000 Btuh furnace only in the confined space each opening must be 100 square inches (645cm2) each of free area.

WARNING: Combustion air must not be drawn from a heated space which includes exhaust fans, fireplaces or other devices that may produce a negative pressure in the space.

Page 4

furnace

opening

confined

 

space

 

Figure 1

Outdoor Air

Outlet and inlet air can be brought into the confined space via openings into a ventilated attic and ventilated crawl space.

attic ventilation louvers

outlet air

furnace

inlet air

crawl space ventilation louvers

Figure 2

Confined Space

Outdoor Air Using Vertical or Horizontal Ducts

If combustion air is taken from outdoors through vertical ducts, the openings and ducts must have a minimum free area of one square inch (6.5cm2) per 4,000 Btuh of total appliance input. In installations drawing combustion air from a ventilated attic both air ducts must extend above the attic insulation.

outlet air

furnace

vertical

inlet air ends one foot above floor

furnace

outlet air duct

 

inlet air duct

horizontal

Figure 3

If combustion air is taken from outdoors through horizontal ducts the openings and ducts must have a minimum free area of one square inch (6.5cm2) per 2,000 Btuh of total appliance input.

12427-2-0903

Qualified Installing Agency

Installation and replacement of gas piping, gas utilization equipment or accessories and repair and servicing of equipment shall be performed only by a qualified agency. The term "qualified agency" means any individual, firm, corporation or company which either in person or through a representative is engaged in and is responsible for (a) the installation or replacement of gas piping or (b) the connection, installation, repair or servicing of equipment, who is experienced in such work, familiar with all precautions required and has complied with all the requirements of the authority having jurisdiction.

The installation must conform with local codes or, in the absence of local codes, with the National Fuel Gas Code, ANSI Z223.1/NFPA 54* Natural and Propane Installation Code, CSA B149.1.

*Available from the American National Standards Institute, Inc., 11 West 42nd St., New York, N.Y. 10036.

Clearances

1.In selecting a location for installation, it is necessary to provide adequate accessibility clearances for servicing and proper installation.

2.The FAW-40can be attached to the wall or recessed into the wall up to 9 1/2 inches (24.1cm) in depth.Note: Do not place combustible header or material on top of unit when installed in wall. Maintain 3/4" minimum spacing above heater.

3.The wall in which the furnace is recessed has (0) zero (0mm) clearance to the furnace sides.

4.When using side discharge registers, SOR-1orSOK-1,the furnace cannot be recessed into the wall.

5.Clearance to sidewall or combustible material is 4 inches (10.2cm).

6.Ceiling clearance is 4 inches (10.2cm).

7.Floor and rear wall clearance is (0) zero inches (0mm).

8.Clearance of 18 inches (46cm) is required to adjacent wall or combustible material when flush mounted SOR-1,side outlet register is used.

Before Installing Consider The Following Venting

1.A chimney for residential-typeorlow-heatgas utilization equipment shall extend at least 3 feet (914mm) above the highest point where it passes through a roof of a building and at least 2 feet (610mm) higher than any portion of building within a horizontal distance of 10 feet (3m).

2.This furnace must not be connected to a chimney flue serving a separate solid-fuelburning appliance.

3.Uninsulated Single-WallMetal Pipe shall not be used outdoors in cold climates for venting gas utilization equipment.

4.Attention! This Fan Type Vented Wall Furnace is equipped with a vent safety switch. In the event of spillage of flue products due to improper venting the vent safety switch will open, which results in the main burners to "shut off".

Model No. FAW-40may be vented as shown in Figure 4. The vent cap termination must be at least 12 feet (3.7m) above the floor and must exhaust to the outdoors.. Clearance to combustible construction is held by the fixed spacers at 1 inch (25mm) withB-1or(B-W)vent pipe. Installation must conform to local codes.

A.4" (102mm) Round (all parts purchase locally except Item 2)

1.Type B-1round pipe

2.Part No. DV-648,4" (102mm)oval-to-roundflue adapter kit (see accessories)

3.Single story type B-1gas vents require a baseplate and one pair of ceiling plate spacers.

4.Multi-storytypeB-1gas vents require a baseplate, one pair of ceiling plate spacers at the first floor ceiling and one pair of fire stop spacers at each successive ceiling level.

B.4" (102mm) Oval (all parts purchase locally)

1.Type B-1oval pipe orB-Wvent pipe

2.Single story type B-1or(B-W)gas vents require a baseplate and one pair of ceiling plate spacers.

3.Multi-storytypeB-1or(B-W)gas vents require a baseplate, one pair of ceiling plate spacers at the first floor ceiling and one pair of fire stop spacers at each successive ceiling level.

C.4" (102mm) Oval In-The-Wall(all parts purchase locally)

1.Type B-1oval pipe orB-Wvent pipe

2.Type B-1oval elbows orB-Woval elbows

3.Single story type B-1or(B-W)gas vents require a baseplate and one pair of ceiling plate spacers.

4.Multi-storytypeB-1or(B-W)gas vents require a baseplate, one pair of ceiling plate spacers at the first floor ceiling and one pair of fire stop spacers at each successive ceiling level.

Stud space around gas vents must be free of obstructions and building paper.

4" ROUND

VENT ENCLOSURE

ADAPTER

WALL

BASEPLATE

A.

SIDE

FRONT

4"B-1OVAL

BRACKET

BASEPLATE

B.

 

4" B-1OVAL

4" 45 DEG.

 

OVAL ELBOWS

SPACER

 

C.

BASEPLATE

 

 

4" B-1OVAL

 

SPACER

C.

BASEPLATE

Figure 4

12427-2-0903

Page 5

 

F

12"

 

Page 6

12427-2-0903

8.Align clearance holes on 6" x 10" (152mm x 254mm) duct with screw holes on inner casing back and mark duct to be 2 1/4" (57mm) shorter than 8" x 12" (203mm x 305mm) boot. Remove duct and cut to proper length.

9.Attach 6" x 10" (152mm x 254mm) duct to inner casing back with (4) #8 x 3/8" (9mm)screws removed in Step 3, 2 on top and 2 on bottom.

10.Insert rear register into 8" x 12" (203mm x 305mm) boot. Attach rear register to wall with (2) #10 x 1"(25mm) screws provided.

11.Installation of ROK-1is completed.

Locating Furnace On Wall

The furnace is to be located on a wall. The furnace is 14 1/8" (35.9cm) in width and can be recessed into the wall with typical stud spacing.

A template is provided in furnace carton for locating gas line connection. Also, refer to Figure 7 for positioning the furnace on wall and for locating gas line connection.

Locating Gas Supply

The gas line can enter the furnace either through the floor or wall. The gas line opening should be made at this time. Location of the opening will be determined by the position of floor joists and the valve and union used for servicing. See Figure 7.

72 3/4"

14 3/8"

CUT OUT OPENING FOR RECESSED MOUNTING

GAS LINE

ELECTRICAL WIRING HOLE

HOLE 1 1/4"

 

2 1/8"

RECESSED MOUNTING

LOCATION

4" 4" 8"

GAS LINE/ELECTRICAL OPENINGS FOR

RECESSED AND SURFACE MOUNT

Figure 7

Locating Electric Supply

A 7/8" (22mm) diameter knockout is provided at the bottom of the left and right side panels. A three-prong(grounding) plug assembly is located within the control compartment (bottom) of the furnace. Please remove 7/8" (22mm) knockout from appropriate side panel when routing plug assembly to an electrical outlet.

Installation of Three-prong(Grounding) Plug Assembly

1.Disconnect nylon cap on 3' (914mm) plug assembly from nylon plug on wiring harness. Remove 3' (914mm) plug assembly from control compartment (bottom) of the furnace.

2.Remove 7/8" (22mm) knockout from appropriate side panel.

3.Insert nylon cap on 3' (914mm) plug assembly into the 7/8" (22mm) hole in the side panel.

4.Connect nylon cap on 3' (914mm) plug assembly to nylon plug on the wiring harness.

5.Place 7/8" (22mm) strain relief bushing around the cord of the 3' (914mm) plug assembly. Insert 7/8" (22mm) strain relief bushing into the 7/8" (22mm) hole in the side panel.

12427-2-0903

Attention! The 7/8" (22mm) strain relief bushing is located within the same yellow envelope as the Installation Instructions and Owner's Manual.

Attaching Furnace to Wall

When attaching furnace to the wall remove that portion of baseboard and molding on the wall which is behind the furnace. Attach furnace to wall, at the outer casing top, with (2) toggle bolts provided and to floor, at the outer casing bottom, with (2) #10 x 1 1/2" (38mm) screws provided.

Gas Supply

Check all local codes for requirements, especially for the size and type of gas supply line required. On Natural gas lines less than 75' (22.9m) long, use 1/2" (13mm) pipe; on longer runs, use 3/4" (19mm) iron pipe or equal. On LP gas lines please consult LP gas supplier.

Installing a New Main Gas Cock

Each appliance should have its own manual gas cock.

A manual main gas cock should be located in the vicinity of the unit. Where none exists, or where its size or location is not adequate, contact your local authorized installer for installation or relocation.

Compounds used on threaded joints of gas piping shall be resistant to the action of liquefied petroleum gases. The gas lines must be checked for leaks by the installer. This should be done with a soap solution watching for bubbles on all exposed connections, and if unexposed, a pressure test should be made.

Never use an exposed flame to check for leaks. Appliance must be disconnected from piping at inlet of control valve and pipe capped or plugged for pressure test. Never pressure test with appliance connected; control valve will sustain damage!

A gas valve and ground joint union should be installed in the gas line upstream of the gas control to aid in servicing. It is required by the National Fuel Gas Code that a drip line be installed near the gas inlet. This should consist of a vertical length of pipe tee connected into the gas line that is capped on the bottom in which condensation and foreign particles may collect.

Figure 8

Method of Installing a Tee Fitting Sediment Trap

The use of the following gas connectors is recommended:

ANS Z21.24 Appliance Connectors of Corrugated Metal Tubing and Fittings

ANS Z21.45 Assembled Flexible Appliance Connectors of Other Than All-MetalConstruction

The above connectors may be used if acceptable by the authority having jurisdiction.

Pressure Testing of the Gas Supply System

1.To check the inlet pressure to the gas valve, a 1/8" (3mm) N.P.T. plugged tapping, accessible for test gauge connection, must be placed immediately upstream of the gas supply connection to the appliance.

2.The appliance and its individual shutoff valve must be disconnected from the gas supply piping system during any pressure testing of that system at test pressures in excess of 1/2 psig (3.5 kPa).

3.The appliance must be isolated from the gas supply piping system by closing its individual manual shutoff valve during any pressure testing of the gas supply piping system at test pressures equal to or less than 1/2 psig (3.5 kPa).

Page 7

Attention! If one of the above procedures results in pressures in excess of 1/2 psig (14" w.c.) (3.5 kPa) on the appliance gas valve, it will result in a hazardous condition.

Checking Manifold Pressure

Both Propane and Natural gas valves have a built-inpressure regulator in the gas valve. Natural gas models will have a manifold pressure of approximately 4.0" w.c. (.996kPa) at the valve outlet with the inlet pressure to the valve from a minimum of 5.0" w.c. (1.24kPa) for the purpose of input adjustment to a maximum of 10.5" w.c. (2.615kPa). Propane gas models will have a manifold pressure approximately 10.0" w.c. (2.49kPa) at the valve outlet with the inlet pressure to the valve from a minimum of 11.0" w.c. (2.739kPa) for the purpose of input adjustment to a maximum of 13.0" w.c. (3.237kPa).

A 1/8" (3mm) N.P.T. plugged tapping, accessible for test gauge connection, is located on the outlet side of the gas control.

The built-inregulator comes on at approximately 1/4th pressure and full on in 10 seconds.

Figure 9

High Altitudes

For altitudes/elevations above 2,000 feet (610m), input ratings should be reduced at the rate of 4 percent for each 1,000 feet (305m) above sea level. For Canadian high altitude applications, this appliance is suitable for installation at elevations between 0 feet (0m) and 4,500 feet (1,372m) without change.

Piezo Pilot Ignitor Instructions

Depressing the red button completely causes a spark to occur at the pilot. This is a substitute for a match which requires opening the pilot hole cover.

To light the pilot, it is important that the electrode be 1/8" (3mm) from the thermocouple. The spark must occur at the point the burner flame hits the thermocouple. The end of the electrode will be red hot with the pilot on.

On a new installation with air in the gas line, it is suggested that a match be used. The match will light the pilot faster than the piezo under this condition.

Proper Pilot Flame

The correct pilot flame (Figure 10) will be blue, extending past the thermocouple. The flame will surround the thermocouple just below the tip.

Natural gas pilots require adjusting when the inlet gas pressure is above 5" w.c. (1.245kPa). Remove the pilot cover screw on the control valve (Figure 9), and turn the adjustment screw clockwise to reduce flame. Replace pilot cover screw to eliminate gas leakage.

LP gas (propane) will not require adjustment.

After use, cleaning may be required for the proper flame.

Proper Main Burner Flame

The correct flame will be a short, blue inner flame with a much larger, light blue, outer flame. The burner does not have a primary air adjustment. The flame will be correct if the factory-setpressure and orifice opening are used. After the furnace has been operating, the burner ports may be blocked by foreign matter carried in by combustion air. Therefore, cleaning of the burner may be needed for proper flame.

To clean burner port disconnect the gas supply to the valve, and remove the screws fastening the burner door. After removing the burner door

Page 8

from the burner box, remove each main burner. Pilot mounting bracket will need to be unscrewed and moved out of the way to remove all burners. Burners can be blown out using compressed air or by blowing through them. Be sure there is no lint or foreign debris blocking the burner ports. Reassemble using the same screws earlier removed and locate pilot in the same position as before and noted above.

THERMOCOUPLE

BURNER

SPARK

PILOT

ELECTRODE

STANDING PILOT

THERMOCOUPLE

PILOT SHIELD

SPARK

ELECTRODE

PILOT LOCATION END VIEW

STANDING PILOT SHOWN

3/8" TO 1/2" PILOT FLAME

GROUND

ELECTRODE

BURNER

PILOT

HOT SURFACE

FLAME

IGNITOR

ROD

IP-MODELPILOT

Figure 10

Figure 11

Cleaning Combustion (Exchanger) Assembly

A QUALIFIED SERVICE PERSON should remove the combustion (exchanger) assembly and flue baffles. Apply air pressure to the inside of the combustion (exchanger) assembly and flue baffles in order to clear all passageways.

12427-2-0903

Oiling the Motor

The fan motor should be cleaned and oiled once each heating season. Oil holes are located on the top at each end of the motor. Use a few drops of #10 motor oil. To clean the motor, blow air through its ventilation openings with a vacuum cleaner or low pressure air source.

Wiring

The appliance, when installed, must be electrically grounded in accordance with local codes or, in the absence of local codes, with the

National Electrical Code, ANSI/NFPA 70 or Canadian Electrical Code, CSA C22.1, if an external electrical source is utilized. This appliance is equipped with a three-prong [grounding] plug for your protection against shock hazard and should be plugged directly into a properly grounded three-prong receptacle. Do not cut or remove the grounding prong from this plug. For an ungrounded receptacle, an adapter, which has two prongs and a wire for grounding, can be purchased, plugged into the ungrounded receptacle and its wire connected to the receptacle mounting screw. With this wire completing the ground, the appliance cord plug can be plugged into the adapter and be electrically grounded. A 7/8" (22mm) hole is provided in the junction box for use with a conduit connector if local codes require this type of protection.

Thermostat Installation

The thermostat should be installed in the same room as the furnace 4' (1.2m) to 5' (1.5m) above the floor and away from another heat source (cooking stove, hot water heater, etc.) including walls and doorways with a heat source in an adjoining room. Do Not Install Thermostat on

Outside Wall.

Insulated Vent Enclosure

Vented wall furnaces installed in buildings with flat roofs can have poor venting. The cold vent pipe will have a delay in proper venting and cause the wall furnace to shut "OFF" by the vent safety switch. To prevent delayed venting as well as condensation of flue products an insulated vent enclosure is recommended.

Use type B vent pipe and maintain at least a one inch (25mm) clearance to combustibles.

Use metal thimble to protect vent pipe as it passes through combustibles.

Figure 12

Vent Safety Shutoff System

This appliance must be properly connected to a venting system. This appliance is equipped with a vent safety shutoff system.

Warning: Operation of this wall furnace when not connected to a properly installed and maintained venting system or tampering with the vent safety shutoff system can result in carbon monoxide (CO) poisoning and possible death.

This furnace is equipped with a manual reset vent safety switch. The manual reset vent safety switch will cause gas flow to the main burners to "shut off" due to improper venting or a blocked flue.

12427-2-0903

To reset the manual reset vent safety switch:

1.Remove front panel.

2.Depress manual reset button. The manual reset vent safety switch is located on the draft diverter.

3.Replace front panel.

If the manual reset vent safety switch continues to "shut off" the gas flow to the main burners a qualified service person must be contacted to inspect for improper venting, blockage in the vent pipe or the manual reset vent safety switch for being defective.

Figure 13

FLUE CONNECTOR

 

VENT LIMIT SWITCH

 

DRAFT DIVERTER

 

FAN

 

LIMITFANSWITCH

 

FANLIMITSWITCHSWITCH

PIEZO

BURNER BOX

IGNITOR

 

 

GAS VALVE

 

JUNCTION BOX-

 

TRANSFORMER

Figure 14

Page 9

SERVICE AND MAINTENANCE SUGGESTIONS

CALL SERVICEMAN

GENERAL: All furnaces have beenfire-testedto check for proper operation. This includes, main burner flame, pilot flame, fan operation, fan control, limit control and automatic valve operation. If the furnace fails to function on initial installation, it is advisable tore-checkthe following:

1.115 volts to the junction box.

2.Inlet gas pressure.

3.The 24 volt system.

4.Type of gas being used and that shown on the rating label.

The Service Department at Empire Comfort Systems, Inc. may be contacted to assist in servicing furnace.

Standing Pilot Model

Servicing the Pilot and Main Burners, Pilot Orifice, Thermocouple, and Main Burner Orifices: Disconnect the gas supply at the inlet to the control valve. Then remove the burner door to gain access to the above listed components.

Spark Igniter Does Not Light Pilot: With air in the gas line, such as when the furnace is first installed or was off all summer, the pilot flame may be too lean to ignite on the first few trials. Turn the control valve knob to pilot position and depress the red reset button. Holding the button down continually to bleed the line;.

1.Use lighter rod to light pilot with a match.

2.Use the piezo ignitor at 30 second intervals until it lights.

If Electrode Does Not Produce Spark:

1.Check wire connections.

2.Check gap for pilot burner to the electrode tip. Should be between 1/8" (3mm) and 3/16" (5mm). Electrode wire and tip must be more than 1/4" (6mm) away from all other metal components.

If Pilot Does Not Light By Any Means:

1.Check valve knob for being in the "Pilot" position.

2.Check pilot adjustment for being full open (counterclockwise to open).

3.If gas is available in the supply tubing, the pilot orifice and/or pilot burner is probably restricted by a spider web. Clean pilot assembly and relight.

If Pilot Does Not Remain On After Releasing Knob:

1.Follow instructions and hold button down longer and harder.

2.Determine if pilot flame extends past thermocouple; if not, adjust input or clean pilot burner.

3.Replace thermocouple if millivolts read less than 15 millivolts.

Main Gas Valve Does Not Open When Thermostat Is Turned To On:

1.Check for 24 volts to valve by removing one wire and touching to the SAME TERMINAL it was on. Terminal should have a light spark.DO NOT SHORT ACROSS TERMINALS, AS IT WILL

BURN OUT THE WALL THERMOSTAT.

2.Thermostat wires at the wall may be shorted, so check for a faulty thermostat.

3.To check for line voltage to furnace, remove front panel and short across two-terminalfan control to allow fan to operate (Figure 14).

CAUTION: Label all wires prior to disconnection when servicing controls. Wiring errors can cause improper and dangerous operation. Verify proper operation after servicing.

IP-ModelPilot

This heater is using a Honeywell "Smart Valve" system for intermittent pilot ignition.

On a call for heat by the thermostat this control turns on a 24 volt mini hot surface ignitor which lights a pilot that in turn lights the main burner. The gas valve used in this system is a step opening which opens at a lower pressure for ignition and then steps to a full inlet pressure of 4" H2O pressure on Natural gas and 10" H20 pressure on LP gas.

Pilot Flame Adjustment

The pilot flame should envelop 3/8 to 1/2 inch (10 to 13mm) of the tip of the flame rod. See Figure 10.

To adjust:

1.Remove the pilot adjustment cover screw.

2.Turn the inner adjustment screw clockwise to decrease or counterclockwiseto increase pilot flame. Pilot adjustment is shipped at full flow rate. Turn the inner adjustment screw clockwiseif the inlet pressure is too high.

3.Replace the cover screw after the adjustment to prevent gas leakage.

PRESSURE REGULATOR

ADJUSTMENT-UNDERCAP

SCREW

 

 

 

 

OUTLET PRESSURE TAP

 

 

 

 

 

PILOT ADJUSTMENT-

INLET PRESSURE TAP

 

 

 

 

UNDER CAP SCREW

 

 

 

 

IGNITOR

GAS FLOW

 

 

 

 

 

 

 

OFF

 

 

 

CONTROL

PILOT OUTLET

ON

 

 

 

 

 

 

 

 

IGNITOR-PILOTASSY.

 

 

 

IGNITOR

 

WIRING

 

 

CONTROL

 

 

TO 24 V. THERMOSTAT

 

 

 

 

 

TO 24 V."HOT" ON TRANSFORMER

 

 

 

 

TO 24 V. COMMON ON TRANSFORMER

 

 

 

 

 

I P-MODELGAS VALVE AND WIRING

L2 NEUTRAL

L1 "HOT"

 

120 VAC

 

FAN

 

SWITCH

 

MOTOR

 

120VAC

 

40 VA TRANSFORMER

VALVE CONTROL

24 VAC

 

CONNECTOR

 

LIMIT

CONTROL

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

THERMOSTAT

VENT SAFETY

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

LIMIT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

HONEYWELL IP

SMART VALVE

LADDER WIRING DIAGRAM-IPVALVE

Figure 15

Page 10

12427-2-0903