Emerson VSG, VSSG User Manual

0 (0)

VSG/VSSG compressor unit

Installation, operation & maintenance manual

VSG/VSSG Standard Vilter Warranty Statement

Seller warrants all new single screw gas compression units and bareshaft single screw compressors manufactured by it and supplied to Buyer to be free from defects in materials and workmanship for a period of (a) eighteen (18) months from the date of shipment or (b) twelve (12) months from the date of installation at the end user’s location, whichever occurs first.

If within such period any such product shall be proved to Seller’s satisfaction to be defective, such product shall be repaired or replaced at Seller’s option. Such repair or replacement shall be Seller’s sole obligation and Buyer’s exclusive remedy hereunder and shall be conditioned upon (a) Seller’s receiving written notice of any alleged defect within ten (10) days after its discovery, (b) payment in full of all amounts owed by Buyer to Seller and (c) at Seller’s option, Buyer shall have delivered such products to Seller, all expenses prepaid to its factory. Expenses incurred by Buyer in repairing or replacing any defective product (including, without limitation, labor, lost refrigerant or gas and freight costs) will not be allowed except by written permission of Seller. Further, Seller shall not be liable for any other direct, indirect, consequential, incidental, or special damages arising out of a breach of warranty.

This warranty is only applicable to products properly maintained and used according to Seller’s instructions. This warranty does not apply (i) to ordinary wear and tear, damage caused by corrosion, misuse, overloading, neglect, improper use or operation (including, without limitation, operation beyond rated capacity), substitution of parts not approved by Seller, accident or alteration, as determined by Seller or (ii) if the product is operated on a gas with an H2S level above 100 PPM. In addition, Seller does not warrant that any equipment and features meet the requirements of any local, state or federal laws or regulations. Products supplied by Seller hereunder which are manufactured by someone else are not warranted by Seller in any way, but Seller agrees to assign to Buyer any warranty rights in such products that Seller may have from the original manufacturer. Labor and expenses for repair are not covered by warranty.

THE WARRANTY CONTAINED HEREIN IS EXCLUSIVE AND IN LIEU OF ALL OTHER REPRESENTATIONS AND WARRANTIES, EXPRESS OR IMPLIED, AND SELLER EXPRESSLY DISCLAIMS AND EXCLUDES ANY IMPLIED WARRANTY OF MERCHANTABILITY OR IMPLIED WARRANTY OF FITNESS FOR A PARTICULAR PURPOSE.

Any description of the products, whether in writing or made orally by Seller or Seller’s agents, specifications, samples, models, bulletins, drawings, diagrams, engineering sheets or similar materials used in connection with Buyer’s order are for the sole purpose of identifying the products and shall not be construed as an express warranty. Any suggestions by Seller or Seller’s agents regarding use, application or suitability of the products shall not be construed as an express warranty unless confirmed to be such in writing by Seller.

VSG/VSSG • Installation, Operation and Maintenance Manual •Vilter/Emerson • 35391SSG

i

Important Message

READ CAREFULLY BEFORE INSTALLING AND STARTING YOUR COMPRESSOR.

The following instructions have been prepared to assist in installation, operation and removal of Vilter Single Screw Compressors. Following these instructions will result in a long life of the compressor with satisfactory operation.

The entire manual should be reviewed before attempting to install, operate, service or repair the compressor.

A compressor is a positive displacement machine. It is designed to compress gas. The compressor must not be subjected to liquid carry over. Care must be exercised in properly designing and maintaining the system to prevent conditions that could lead to liquid carry over. Vilter Manufacturing is not responsible for the system or the controls needed to prevent liquid carry over and as such Vilter Manufacturing cannot warrant equipment damaged by improperly protected or operating systems.

Vilter screw compressor components are thoroughly inspected at the factory. However, damage can occur in shipment. For this reason, the equipment should be thoroughly inspected upon arrival. Any damage noted should be reported immediately to the Transportation Company. This way, an authorized agent can examine the unit, determine the extent of damage and take necessary steps to rectify the claim with no serious or costly delays. At the same time, the local Vilter representative or the home office should be notified of any claim made.

All inquires should include the Vilter sales order number, compressor serial and model number. These can be found on the compressor name plate on the compressor.

All requests for information, services or parts should be directed to:

Vilter Manufacturing LLC

Customer Service Department

P.O. Box 8904

5555 South Packard Ave

Cudahy, WI 53110-8904 USA Telephone: 1-414-744-0111 Fax:1-414-744-3483

e-mail: info.vilter@emerson.com

Equipment Identification Numbers:

Vilter Order Number: _______________________Compressor Serial Number: _________________

Vilter Order Number: _______________________Compressor Serial Number: _________________

Vilter Order Number: _______________________Compressor Serial Number: _________________

Vilter Order Number: _______________________Compressor Serial Number: _________________

ii

VSG/VSSG • Installation, Operation and Maintenance Manual •Vilter/Emerson • 35391SSG

Table of Contents

Section Title

Section Number

VSG/VSSG Standard Vilter Warranty Statement .....................................................................................

i

Important Message................................................................................................................................

ii

Section 1 • General Information

 

How To Use This Manual.........................................................................................................................

1-1

Gas Compressor Unit Model Designations..............................................................................................

1-2

System Unit Identification .....................................................................................................................

1-3

Compressor Unit Component Identification...........................................................................................

1-4

Piping & Identification Component Tags.................................................................................................

1-7

Symbols and Identification.....................................................................................................................

1-8

Section 2 • Theory of Operation

 

Gas Flow ................................................................................................................................................

2-1

Oil Life and Oil Flow................................................................................................................................

2-1

Oil Pressure Regulating ..........................................................................................................................

2-2

Control System ......................................................................................................................................

2-2

RTDs and Pressure Transducers ..............................................................................................................

2-2

Section 3 • Installation

 

Delivery Inspection ................................................................................................................................

3-1

Rigging and Lifting.................................................................................................................................

3-1

Short Term Storage Recommendations..................................................................................................

3-2

Long Term Storage Recommendations...................................................................................................

3-2

Compressor Motor.....................................................................................................................

3-2

Air Cooled Oil Coolers ................................................................................................................

3-3

Compressor Unit Inspections Prior to Stoarge or Installation..................................................................

3-3

Recommended Onsite Tools ..................................................................................................................

3-3

Long Term Storage Log ..........................................................................................................................

3-4

Foundation ............................................................................................................................................

3-5

Piping ..................................................................................................................................................

3-10

Header Piping and Drains...........................................................................................................

3-10

Remote Air Cooled Oil Cooler Piping ..........................................................................................

3-10

General Installation Guideline for Multiple Air Coolers Installed in a Common Area ................................

3-12

Free Flow ...................................................................................................................................

3-12

One Fan Diameter......................................................................................................................

3-12

Intake Velocity...........................................................................................................................

3-12

Hot Air Recirculation..................................................................................................................

3-14

Pressure Testing.....................................................................................................................................

3-16

Initial Oil Charging .................................................................................................................................

3-16

Using Non-Vilter Oils..................................................................................................................

3-16

Unit Oil Charging and Priming....................................................................................................

3-16

Priming Oil Cooler (Shell and Tube)and Piping............................................................................

3-16

Priming Compressor and Oil Filters ............................................................................................

3-18

Priming Remote Oil Cooler and Piping (Initial Oil Charging)........................................................

3-20

Priming Compressor and Oil Filters ............................................................................................

3-21

Pre Start-Up ...........................................................................................................................................

3-22

Start-Up.................................................................................................................................................

3-24

VSG/VSSG • Installation, Operation and Maintenance Manual •Vilter/Emerson • 35391SSG

TOC - 1

Table of Contents

 

 

 

 

 

Section Title

Section Number

Section 4 • Operation

 

Oil Inspection ........................................................................................................................................

4-1

Dual Oil Filters........................................................................................................................................

4-1

Control System Calibration ....................................................................................................................

4-2

Starting, Stopping and Restarting the Compressor ................................................................................

4-2

Calibrate Slide Valve Actualors ...............................................................................................................

4-2

Oil Temperature Control Valve (Oil Mixing Valve) Operation...................................................................

4-7

Manual Override ........................................................................................................................

4-8

Purging with Dry Nitrogen .....................................................................................................................

4-9

Purging with Dry Gas .............................................................................................................................

4-11

Coalescing Oil Return Line Setup............................................................................................................

4-14

Section 5 • Maintenance/Service

 

Maintenance and Service Schedule ........................................................................................................

5-1

Maintaining Proper Operation................................................................................................................

5-2

Compressor Unit Isolation for Maintenance/Service ...............................................................................

5-3

Compressor Unit Leak Check..................................................................................................................

5-3

Oil System Components.........................................................................................................................

5-4

Oil Sampling...............................................................................................................................

5-4

Oil Charging ...............................................................................................................................

5-5

Oil Draining................................................................................................................................

5-6

Oil Filter Replacement ................................................................................................................

5-6

Coalescing Oil Filter Replacment.................................................................................................

5-8

Oil Pump Strainer .......................................................................................................................

5-9

Drive Coupling (Form-Flex BPU) Installation...........................................................................................

5-10

Drive Center Member (Form-Flex BPU) Installation and Alignment .........................................................

5-11

Drive Coupling (Form-Flex BPU) Removal...............................................................................................

5-13

Drive Coupling (Type C Sure-Flex) Replacement .....................................................................................

5-13

Compressor Replacement ......................................................................................................................

5-14

Compressor Bearing Float Inspections ...................................................................................................

5-16

Gate Rotor Float and Gate Rotor Bearing Float Inspection.......................................................................

5-17

Gate Rotor and Support Clearance .........................................................................................................

5-19

Gate Rotor Assembly Replacement (All VSG & VSSG Compressors Except VSG 301-701 Compressors)....5-21

Gate Rotor Assembly Replacement (VSG 301-701 Compressors ONLY)...................................................

5-24

Gate Rotor Disassembly .........................................................................................................................

5-26

Gate Rotor Blade Removal/Installation .......................................................................................

5-26

Gate Rotor Thrust Bearing Removal/Installation .........................................................................

5-27

Gate Rotor Roller Bearing Removal/Installation...........................................................................

5-27

Slide Valve Actuator Assembly Replacement ..........................................................................................

5-28

Command Shaft Assembly Replacement................................................................................................

5-29

Command Shaft Seal Replacement.........................................................................................................

5-29

Section 6 • Troubleshooting

 

Table 6-1. Slide Valve Actuator Troubleshooting Guide...........................................................................

6-1

Table 6-2. Slide Valve Actuator LED Blink Codes......................................................................................

6-3

Table 6-3. Troubleshooting Guide - General Problems & Solutions ..........................................................

6-5

TOC - 2

VSG/VSSG • Installation, Operation and Maintenance Manual •Vilter/Emerson • 35391SSG

List of Tables and Figures

Section Title

 

Section Number

 

Section 7 • Warranty and Parts

 

Warranty Claim Processing ....................................................................................................................

7-1

On Site Service Support .........................................................................................................................

7-1

Remanufactured Bare Shaft Compressors Process..................................................................................

7-2

Explanation of Rebuild Levels .....................................................................................................

7-2

Bare Shaft Compressor Description............................................................................................

7-2

 

Appendices

 

Appendix A

Torque Specifications......................................................................................................

A

Appendix B

Motor (Compressor) General Storage Instructions ..........................................................

B

Appendix C

Oil Analysis Report..........................................................................................................

C

Appendix D

Recommended Header Piping ........................................................................................

D

Appendix E

Recommended Remote Air Cooled Oil Cooler Piping.......................................................

E

Table/Figure

Section Number

Tables

 

Table 3-1. Long Term Storage Compressor Hardware .............................................................................

3-2

Table 3-2. Maximum Allowable Flange Loads .........................................................................................

3-11

Table 4-1. Command Shaft Rotation Specifi cations................................................................................

4-6

Table 5-1. Maintenance/Service Schedule ..............................................................................................

5-1

Table 5-2. Oil Filter Elements and Compressor Models............................................................................

5-6

Table 5-3. Shaft and Hub Distances ........................................................................................................

5-10

Table 5-4. Hub Clamp Bolt and Set Screw Torque Specifi cations.............................................................

5-12

Table 5-5. Disc Pack Installation Torque Specifi cations...........................................................................

5-12

Table 5-6. Clamping Bolts and Set Screw Torque Specifi cations..............................................................

5-14

Table 5-7. Maximum Bearing Float (Compressor Shaft) ..........................................................................

5-17

Table 5-8. Gate Rotor Float.....................................................................................................................

5-18

Table 5-9. Gate Rotor Tool Sets...............................................................................................................

5-21

Table 6-1. Slide Valve Actuator Troubleshooting Guide (1 of 2) ...............................................................

6-1

Table 6-2. Slide Valve Actuator LED Blink Codes* (1 of 2)........................................................................

6-3

Table 6-3. Troubleshooting Guide - General Problems & Solutions (1 of 3) ..............................................

6-5

Figures

 

Figure 1-1. Gas Compressor Unit Model Designation .............................................................................

1-2

Figure 1-2. Gas Compressor Unit Components .......................................................................................

1-4

Figure 2-1. Gas Compressor Unit P&ID ...................................................................................................

2-1

Figure 3-1. Rigging and Lifting Points.....................................................................................................

3-1

Figure 3-2. Concrete Pad with Compressor Unit Dimensions - Side View ................................................

3-5

Figure 3-3. Concrete Pad with Compressor Unit Dimensions - Front View...............................................

3-6

Figure 3-4. Interior Foundation Isolation ................................................................................................

3-6

Figure 3-5. Foundation with Housekeeping Pads Dimensions - Top View ................................................

3-7

Figure 3-6. Housekeeping Pad Dimension Detail - Top View ...................................................................

3-9

Figure 3-7. Level Compressor Unit Using Top Surface of Spherical Washers ............................................

3-9

Figure 3-8. Concrete Pad Housekeeping Detail.......................................................................................

3-10

Figure 3-9. Maximum Allowable Flange Loads........................................................................................

3-11

Figure 3-10. Installation of Coolers - One Fan Diameter Next to Building ................................................

3-12

Figure 3-11. Leg Height..........................................................................................................................

3-13

VSG/VSSG • Installation, Operation and Maintenance Manual •Vilter/Emerson • 35391SSG

TOC - 3

List of Tables and Figures

Table/Figure

Section Number

Figure 3-12. Installation of Coolers - Next to Buildling ............................................................................

 

3-13

Figure 3-13. Discharge Elevation of Coolers............................................................................................

 

3-15

Figure 3-14. Cooler Placement and Spacing............................................................................................

 

3-15

Figure 3-15. Oil Operating Levels ...........................................................................................................

 

3-17

Figure 3-16. Suction Oil Charging Valve, Oil Cooler Drain and Oil Filter Shut-Off Valves...........................

 

3-17

Figure 3-17. Priming Oil Cooler (Shell & Tube) and Piping.......................................................................

 

3-18

Figure 3-18. Priming Compressor (with Shell & Tube Oil Cooler) and Piping............................................

 

3-19

Figure 3-19. Priming Remote Oil Cooler and Piping ................................................................................

 

3-20

Figure 3-20. Priming Compressor and Oil Filters.....................................................................................

 

3-21

Figure 4-1. Oil Operatiing Levels.............................................................................................................

 

4-1

Figure 4-2. Actuator Assembly ...............................................................................................................

 

4-3

Figure 4-3. Menu Screen and Slide Calibraiton Button (Compact Logix PLC) ...........................................

 

4-4

Figure 4-4. Slide Valve Calibraiton Screen (Compact Logix PLC)..............................................................

 

4-5

Figure 4-5. Photo-chopper .....................................................................................................................

 

4-5

Figure 4-6. Oil Temperature Control Valve (Oil Mixing Valve)..................................................................

 

4-8

Figure 4-7. PLC Main Screen ...................................................................................................................

 

4-9

Figure 4-8. Suction Bypass Valve and Equalizing Solenoid.......................................................................

 

4-10

Figure 4-9. Suction Oil Charging Valve and Discharge Bleed Valve ..........................................................

 

4-10

Figure 4-10. Customer Purge Line ..........................................................................................................

 

4-11

Figure 4-11. PLC Main Screen .................................................................................................................

 

4-12

Figure 4-12. Suction Bypass Valve and Equalizing Solenoid.....................................................................

 

4-13

Figure 4-13. Suction Oil Charging Valve .................................................................................................

 

4-13

Figure 4-14. Coalescing Oil Return Line ..................................................................................................

 

4-14

Figure 5-1. Suction Bypass Valve (Manual) Location (1 of 2)....................................................................

 

5-2

Figure 5-1. Suction Bypass Valve (Equalizing Solenoid) Location (2 of 2).................................................

 

5-3

Figure 5-2. Oil Analysis Kit......................................................................................................................

 

5-4

Figure 5-3. Suction Oil Charging, Oil Cooler Drain Valve and Oil Filter Shut-Off Valves ............................

 

5-5

Figure 5-4. Oil Filter Assemblies (Single and Dual) ..................................................................................

 

5-6

Figure 5-5. Oil Filter Drain, Vent and Shut-Off Valves ..............................................................................

 

5-7

Figure 5-6. Oil Separator Manhole Cover and Coalescing Filter Assembly................................................

 

5-8

Figure 5-7. Oil Pump Strainer and Drain Valve ........................................................................................

 

5-9

Figure 5-8. Hub Distance (Axial Spacing) ................................................................................................

 

5-11

Figure 5-9. Angular Alignment and Parallel Offset ..................................................................................

 

5-12

FIgure 5-10. Compressor Replacement and Hardware Assembly (Models 2401-3001 Shown) ................

5-15

FIgure 5-11. Bearing Axial Float Inspection (Compressor).......................................................................

 

5-16

FIgure 5-12. Bearing Radial Float Inspection (Compressor).....................................................................

 

5-17

FIgure 5-13. Gate Rotor Float .................................................................................................................

 

5-17

FIgure 5-14. Gate Rotor Bearing Float.....................................................................................................

 

5-18

FIgure 5-15. Gate Rotor and Support Clearance - Minimum Clearances ..................................................

 

5-19

FIgure 5-16. Gate Rotor and Support Clearance - Measuring...................................................................

 

5-20

FIgure 5-17. Gate Rotor Assembly Removal and Tools ............................................................................

 

5-22

FIgure 5-18. Gate Rotor Assembly Removal............................................................................................

 

5-22

FIgure 5-19. Gate Rotor Assembly and Tools...........................................................................................

 

5-23

FIgure 5-20. Gate Rotor and Shelf Clearance...........................................................................................

 

5-23

FIgure 5-21. Gate Rotor Assembly Breakdown........................................................................................

 

5-24

FIgure 5-22. Gate Rotor Thrust Bearing ..................................................................................................

 

5-25

FIgure 5-23. Gate Rotor and Shelf Clearance...........................................................................................

 

5-25

FIgure 5-24. Gate Rotor Blade Assembly.................................................................................................

 

5-26

FIgure 5-25. Gate Rotor Blade Installation ..............................................................................................

 

5-26

FIgure 5-26. Gate Rotor Thrust Bearing ..................................................................................................

 

5-27

FIgure 5-27. Thrust Bearing Installation..................................................................................................

 

5-27

FIgure 5-28. Roller Bearing Assembly .....................................................................................................

 

5-28

FIgure 5-29. Command Shaft Seal ..........................................................................................................

 

5-29

FIgure 5-30. Command Shaft Seal Installation........................................................................................

 

5-30

TOC - 4

VSG/VSSG • Installation, Operation and Maintenance Manual •Vilter/Emerson • 35391SSG

Section 1 • General Information

How To Use This Manual

This manual contains instructions for gas compressor units. It has been divided into eight sections:

Section 1: General Information

Section 2: Theory of Operation

Section 3: Installation

Section 4: Operation

Section 5: Maintenance & Service

Section 6: Troubleshooting

Section 7: Warranty and Parts

Appendices

It is highly recommended that the manual be reviewed prior to servicing system parts.

Figures and tables are included to illustrate key concepts.

Safety precautions are shown throughout the manual. They are defined as the following:

NOTICE - Notice statements are shown when there are important information that shall be followed. Not following such notices may result in void of warranty, serious fines, serious injury and/or death.

WARNING - Warning statements are shown when there are hazardous situations, if not avoided, will result in serious injury and/or death.

CAUTION - Caution statements are shown when there are potentially hazardous situations, if not avoided, will result in damage to equipment.

NOTE - Notes are shown when there are addtional information pertaining to the instructions explained.

Additional installation, operation and maintenance instructions can be found in the associated software manual and bareshaft compressor manual.

VSG/VSSG • Installation, Operation and Maintenance Manual •Vilter/Emerson • 35391SSG

1 – 1

Section 1 • General Information

Gas Compressor Unit Model Designations

The compressor unit model designation can be found on the nameplate. For nameplate location, see Component Identification on section page 1-4.

VSG-601-VVR-L-HP-VFD-36H-NEC-ST-WTR

1

2

3

 

 

5

6

7

8

9

10

4

Figure 1-1. Gas Compressor Unit Model Designation

1. Compressor Model

VSG = Vilter Single Screw Compressor

VSSG = Vilter Single Screw Compressor

(Compressor models 291, 341, 451 & 601 - these are 240mm diameter rotors with counter clockwise rotation)

VRSG = Vilter Twin Screw

2. Size

CFM - Nominal CFM displacement of the compressor at 3600 rpm

3. Slide Arrangement

VVR = Variable Volume Ratio; Parallex™

4.Gas Compressed

L = Landfill Gas

D = Digester Service Site Application N = Natural Gas (Primarily Methane) G = Other Gas Type

5.Application

HP = High Stage with Oil Pump

HN = High Stage no Oil Pump

6. Driver

VFD = Variable Frequency Drive

EMD = Electric Motor Drive

ENG = Engine Drive

7. Separator Type

 

16 = 16 inch diameter

36 = 36 inch diameter

20 = 20 inch diameter

42 = 42 inch diameter

24 = 24 inch diameter

48 = 48 inch diameter

30 = 30 inch diameter

54 = 54 inch diameter

H = Horizontal

V = Vertical

SH = Special Horizontal

SV = Special Vertical

8. Economizer

NEC = No Economizer, Economizer Ports Plugged HEC = Holes drilled in Economizer Plug for Oil

or Unloading

9.Oil Cooler

PLT = Plate

ST = Shell and Tube REM = Remote

10.Oil Cooling Medium

REF = Refrigerant WTR = Water

GL = Glycol

AIR = Air

1 – 2

VSG/VSSG • Installation, Operation and Maintenance Manual •Vilter/Emerson • 35391SSG

Section 1 • General Information

System Unit Identification

To keep definitions of units simple and consistent, Vilter has defined the following three:

Bare Shaft Compressor

Compressor Unit

Package Unit

Bare Shaft Compressor

A bare shaft compressor is just the compressor with no coupling and motor nor foundation.

Compressor Unit

A compressor unit consists of the bare shaft compressor with the coupling, motor, oil separator, frame, micro-control- ler system and oil system. A compressor unit typically a single screw compressor unit, is not mounted on a structural steel base.

Package Unit

A package unit is a complete system mounted on a structural steel base with interconnecting piping.

VSG/VSSG • Installation, Operation and Maintenance Manual •Vilter/Emerson • 35391SSG

1 – 3

Section 1 • General Information

Compressor Unit Component Identification

Each gas compressor unit may differ, but below are typical components that can be found on each unit.

1

- Motor

9 - Block & Bleed Assembly

17

- Discharge Connection

2

- Coupling

10

- Oil Pump

18

- Oil Separator Inspection Port

3

- Suction Strainer

11

- Oil Heater

19

- Thermal/Acoustic Oil Separator

4

- Suction Check Valve

12

- Oil Separator

 

Blanket

 

 

5a - Suction Stop Valve

13

- Oil Temperature Control Valve

 

(Optional Per Application)

 

 

5b - Suction Stop Butterfly Valve

 

(Oil Mixing Valve)

20

- Nameplate

 

 

 

 

 

(Typically Shipped Loose)

14

- Oil Pump Strainer

21

- Heat Trace Insulation

 

 

 

 

 

6

- Compressor

15

- Oil Sight Glass

 

(Optional Per Application)

 

 

 

 

7

- Discharge Pipe

16

- Oil Filter

22

- Frame

 

 

 

 

8

- PLC Panel

 

(Optional Dual Oil Filters Shown)

23

- Oil Cooler (Shell and Tube Heat

 

 

 

Exchanger)

 

 

 

 

 

5b

1

2

3

4

5a

6 7

17

8

16

9

11

15

14

13

12

11

10

Figure 1-2. Gas Compressor Unit Components (1 of 3)

1 – 4

VSG/VSSG • Installation, Operation and Maintenance Manual •Vilter/Emerson • 35391SSG

Section 1 • General Information

4 3

20

18 19

17

22

21

14

20

23

Figure 1-2. Gas Compressor Unit Components (2 of 3)

VSG/VSSG • Installation, Operation and Maintenance Manual •Vilter/Emerson • 35391SSG

1 – 5

Section 1 • General Information

Component Identification (Continued)

24

- RTD (Oil Filter Outlet)

28

- RTD (Suction)

 

 

31

- Block & Bleed Assembly

25

- Pressure Transducer (Oil Injection

29

- Capacity Slide Valve Actuator

32

- Remote Oil Cooler (Finned Fan

 

Temperature)

30

- Pressure Transducers

 

 

Heat Exchanger)

26

- Volume Slide Valve Actuator

 

33

- RTD (Oil Separator)

 

(Discharge, Oil Filter Inlet and

27

- RTD (Discharge)

 

Outlet)

 

 

 

 

 

 

 

 

 

 

 

 

 

25

26

27

 

28

 

24

 

 

 

 

 

29

 

 

 

 

 

 

 

30

 

 

 

 

 

 

 

31

33

32

OUTLET

INLET

Figure 1-2. Gas Compressor Unit Components (3 of 3)

1 – 6

VSG/VSSG • Installation, Operation and Maintenance Manual •Vilter/Emerson • 35391SSG

Section 1 • General Information

Piping & Identification Component Tags

Use this list to identify components shown in the Piping & Identification Diagram.

A

Atmosphere

AN

Anode - Sacrificial

AV

Angle Valve

BFV

Butterfly Valve

BDV

Automatic Blowdown

 

Valve

BV

Ball Valve

C

Compressor

CPL

Coupling

CRR

Cooling Refrigerant Liquid

 

Return

CRS

Cooling Refrigerant Liquid

 

Supply

CS

Carbon Steel or Cold Side

CV

Check Valve

CWR

Cooling Water Return

CWS

Cooling Water Supply

DDrive Motor or Drain

EHeat Exchanger

EQ

Equalizing Line

F

Fan

FC

Fail Closed or Flow

 

Controller

FG

Flow Switch Indicator or

 

Glass

FI

Flow Indicator

FIT

Flow Indicating

 

Transmitter

FO

Fail Open

FSI

Flow Sight Indicator

FT

Flow Transmitter (Blind)

FV

Flow Control Valve

 

(Pneumatic Actuator)

GLV

Globe Valve

GTV

Gate Valve

HS

Hand Switch or Hot Side

HEV

Hand Expansion Valve

HV

Hand Valve

IA

Instrument Air

II

Current Indicator

IT

Current Transmitter

JB

Electrical Terminal Box or

 

Junction Box

LC

Level Control

LE

Level Probe

LI

Level Indicator or Gauge

LIT

Liquid Level Indicating

 

Transmitter

LO

Lube Oil or Lock Open

LP

Local Panel

LSH

Level Switch High

LSHH

Level Switch Shutdown

 

High High

LSL

Level Switch Low

LSLL

Level Switch Shutdown

 

Low Low

LV

Level Control Valve -

 

Pneumatic Actuator

MCC

Motor Control Center or

 

Motor Starter

MV

Motor Operated Valve

MGV

Manifold Gauge Valve

MI

Moisture Indicator

N

Nitrogen

NC

Normally Closed

NO

Normally Open

NV

Needle Valve

P

Pump or Process

PDI

Differential Pressure

 

Indicator - Gauge

PDIT

Differential Pressure

 

Indicating Transmitter

PDSH

Differential Pressure

 

Switch High

PDSHH Differential Pressure

 

Switch Shutdown High

 

High

PDSL

Differential Pressure

 

Switch Low

PDSLL

Differential Pressure

 

Switch Shutdown Low

 

Low

PDT

Differential Pressure

 

Transmitter - Blind

PDV

Differential Pressure

 

Control Valve - Pneumatic

 

Actuator

PI

Pressure Indicator or

 

Gauge

PIT

Pressure Indicating

 

Transmitter

PSH

Pressure Switch High

PSHH

Pressure Switch

 

Shutdown High High

PSL

Pressure Switch Low

PSLL

Pressure Switch

 

Shutdown Low Low

PSV

Pressure Safety Relief

 

Valve

PT

Pressure Transmitter

 

- Blind

PV

Pressure Control Valve

QE

Heater Element -

 

Immersion Heater

R

Refrigerant

RD

Rupture Disc

SDV

Automatic Shut-off Valve

SG

Sight Glass

SSStainless Steel or Heat Exchanger Shell Side

STR

Strainer

SV

Safety Relief or Slide Valve

SW

Selector Switch

TE

Temperature Element -

 

RTD or Thermocouple

VSG/VSSG • Installation, Operation and Maintenance Manual •Vilter/Emerson • 35391SSG

1 – 7

Section 1 • General Information

TI

Temperature Indicator or

TW

Thermowell

YZT

Axial proximitor

 

Thermometer

V

Vent

 

Transmitter - Axial

 

 

 

Displacement

TIT

Temperature Indicator

VG

Gauge Valve

 

 

 

 

Transmitter

YZU

Axial Proximitor

 

VTRI

Venturi

TRV

Transfer Valve - 3-way or

 

Monitoring System

 

 

 

VLV

Stop Valve

 

 

 

6-way Valve

ZE

Position Element

 

 

 

TS

Heat Exchanger Tube Side

XV

Solenoid Valve

 

- Positioner

 

 

 

 

TSH

Temperature Switch High

YE

Vibration Probe

ZI

Position Indicator

 

 

 

 

TSHH

Temperature Switch

YSH

Vibration Switch High

ZIT

Position Indicating

 

 

 

Transmitter

 

Shutdown High High

YSHH

Vibration Switch

 

 

ZT

Position Transmitter

TTSL

Temperature Switch Low

 

Shutdown High High

 

 

 

- Blind

TSLL

Temperature Switch

YT

Vibration Transmitter

 

 

 

 

 

 

 

 

Shutdown Low Low

YU

Vibration Monitoring

 

 

TT

Temperature Transmitter

 

System

 

 

 

 

 

 

 

- Blind

YZE

Axial Proximitor Probe -

 

 

TV

Temperature Control

 

Axial Displacement

 

 

 

 

 

 

 

Valve

 

 

 

 

Symbols and Identifications

Use this list to identify components shown in the Piping & Identification Diagram.

3-Way Valve

 

Suction Strainer

Angle Valve

M

Motorized Valve

 

Globe Valve

 

T

3-Way Thermostatic Valve

 

Gate Valve

 

Hand Expansion Valve

Butterfly Valve

 

Restriction Orifice

Ball Valve

 

Rupture Disc

Schrader Valve

 

Inlet Pressure Regulating

Pressure Safety Relief

 

Valve

 

 

Valve

 

Outlet Pressure

Spring-Closing Drain

 

Regulating Valve

 

 

Valve

 

Differential Pressure

Block & Bleed Manifold

 

Regulating Valve

 

Pneumatic Actuator

S

 

 

Control Valve Fail Close

Solenoid Valve

 

 

 

S

 

 

3-Way Solenoid Valve

 

Pneumatic Actuator

 

 

Needle Valve

 

Control Valve Open

 

 

Check Valve

 

Diaphragm Actuator

Strainer

 

Diaphragm

 

 

Spring-Opposed

Diaphragm

Pressure-Balanced

Vilter Venturi Injector

Nozzle

Flange Set

Pipe Reducer

TW

Thermowell

Drive Coupling

CInsulation Not by Vilter

V

Insulation by Vilter

Vibration Absorber

QE Heater

Heat Trace

Low Side Float Valve

1 – 8

VSG/VSSG • Installation, Operation and Maintenance Manual •Vilter/Emerson • 35391SSG

Section 1 • General Information

High Side Float Valve

Steady-Mount

Bulb & Capillary

Thermostatic Expansion

Valve

GPilot Light (Color Inside)

MW Man-Way Cover

BYVILTER

BY OTHERS

 

 

Scope of Supply

SV

E1

Economizer Regulator

Compressor

Motor

Heat Exchanger

Fan

Vertical Tank/Drum Vessel

Horizontal Tank/Drum

Vessel

Positive Displacement

Pump

Centrifugal Pump

Rotary Pump

Filter

Plate & Frame Heat

Exchanger

Discrete Instrument, Field Mounted

Discrete Instrument, Remote, Mount, Normally Accessible to Operator

Discrete Instrument, Local Rack Mounted, Normally Accessible to Operator

Shared Display/Control, Field Mounted

Shared Display/Control, DCS or Remote Control Panel Normally Accessible to Operator

Shared Display/Control, Local Control Panel Normally Accessible to Operator

Programmable Logic Control, Field Mounted

Programmable Logic Control, DCS or Remote

Control Panel, Normally

Accessible to Operator

Programmable Logic

Control, Local Control

Panel, Normally

Accessible to Operator

Pneumatic Signal

X X X X X

Capillary Tube

 

Electrical Signal

Internal System Link (Software or Data Link)

Mechanical Link

L L L L L

Hydraulic Signal

EQUIPMENTTYPE

V100

SERIES NUMBER

Equipment Number

Identification

VSG/VSSG • Installation, Operation and Maintenance Manual •Vilter/Emerson • 35391SSG

1 – 9

1 – 10 / Blank

VSG/VSSG • Installation, Operation and Maintenance Manual •Vilter/Emerson • 35391SSG

Emerson VSG, VSSG User Manual

Section 2 • Theory of Operation

1

2

3

4

5

 

 

 

 

SUCTION GAS

 

 

 

 

 

6

 

 

 

TE

 

 

 

CHECK DISCHARGE

 

 

 

 

 

 

VALVE

STOP VALVE

 

1/4” OIL CHARGING

 

 

 

 

 

 

 

 

COMPRESSOR

 

 

TE

 

 

BLEED

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MOTOR

 

 

 

 

1/4”

 

 

 

 

 

 

 

 

 

 

 

 

14

13

 

 

 

 

BLEED

 

 

 

 

15

 

 

 

 

 

OIL SEPARATOR

 

 

 

 

 

 

 

 

 

 

TE

 

12

 

 

 

 

 

 

 

 

 

 

FILTER

 

 

 

 

11

 

 

 

 

STANDARD SINGLE

TE

 

 

BLEED

DRAIN

 

 

OIL FILTER

 

100#

 

 

DRAIN

 

 

MOTOR

7

 

 

 

 

 

 

 

 

 

BLEED

 

 

M

 

 

 

 

 

 

 

FG

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

 

 

 

 

 

 

 

PUMP

 

FILTER

DRAIN

 

 

 

 

 

 

 

 

 

 

 

8

 

 

 

FILTER

 

 

 

 

OPTIONAL DUAL OIL FILTERS

DRAIN

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

10

 

 

 

 

 

 

 

 

 

 

 

VENT

 

 

 

 

 

 

 

OIL COOLER

 

9

OIL

 

 

 

 

DRAIN

 

 

DRAIN

 

 

 

 

 

STANDARD WATER COOLED OIL COOLER

OPTIONAL REMOTE AIR COOLED OIL COOLER

Figure 2-1. Gas Compressor Unit P&ID

The gas and oil systems work in unison, but each one will be explained separately. Reference Figure 3 - Gas Compressor Unit P&ID for gas and oil flow descriptions.

Gas Flow

The gas compression process begins as processed gas enters the suction inlet (1). The processed gas flows through a stop valve (2), check valve (3) then through a suction line strainer (4) to the compressor (14). The processed gas is then pressurized through the compressor and discharged as high pressure gas vapor into the oil separator (13). In the oil separator, the oil is then separated from the discharged gas vapor by impingement separation. The high pressure gas flows out to

the aftercooler and scrubber for cooling while the oil is pumped or syphoned back to the compressor.

Moreover, check valves (3) and (6) are provided between the oil separator to prevent gas vapor or liquid from flowing back to the compressor during shutdown periods.

An equalizing line is also installed between the high pressure side (oil separator) and low pressure side (suc-

tion) to allow .

Oil Life and Oil Flow

The life of the oil is directly affected by the quality of the gas. Proper separation of any liquids must be accomplished to prevent droplets of liquid at the compressor

VSG/VSSG • Installation, Operation and Maintenance Manual •Vilter/Emerson • 35391SSG

2 – 1

Section 2 • Theory of Operation

suction. The discharge temperature of the compressor must be kept a minimum of 30°F (or 17°C) above the discharge gas dew point to prevent the condensing of liquids in the oil separator. The oil separator shell and legs must be insulated when the gas stream has a high probability of having condensables.

Oil in the gas compressor unit serves three primary purposes. They are compressor lubrication, sealing clearances between moving parts, and heat removal resulting from heat of compression and friction. Initially, oil flow is driven by a mechanical gear pump (7). Once the system reaches design conditions, the oil pump is shut off and oil flow is maintained by differential pressure in the gas system.

As the oil is separated from the gas in the oil separator, it is pumped or syphoned through an oil cooler (9), then filtered through a single (11) or dual oil filters (15) and back to the injection port of the compressor (14). The standard oil cooler is a shell and tube water cooled heat exchanger (9). The other option is to air cool oil remotely through a finned fan heat exchanger (8).

Furthermore, to collect oil from the coalescing side of the oil separator (12), a line is installed between the oil separator and the compressor. By opening the shut-off valve (6), this will allow oil dripping off the coalescing filters to be fed back to the compressor. In addition, the oil cooler (8 or 9) is piped in parallel to the oil temperature control valve (oil mixing vlave) (10), which acts as a bypass valve.

On units with a full-time oil pump, oil pressure is regulated by the oil pressure regulator (12). It controls upstream pressure to the compressor bearings and should be adjusted to hold the oil pressure at 20 psig above suction pressure. Excess oil not required for bearing lubrication is passed through the regulator and back into the oil separator (13).

This is a continuous cycle.

RTDs and Pressure Transducers

Resistance Thermometers (RTDs) and pressure transducers are instruments used to measure temperatures and pressures at specific locations on the gas compressor unit, see Figure 1-2. Gas Compressor Unit Components. RTDs are typically mounted on the suction pipe, discharge pipe, oil separator and oil filter outlet pipe. Pressure transducers are typically mounted on the block and bleed assembly and directly on the suction pipe. The pressure transducers measure suction pressure, inlet and outlet oil pressure, and oil separator pressure.

Control System

The gas compressor unit is controlled by a Programmable Logic Controller (PLC) panel. This PLC panel’s main function is to control the gas compression system from the data that it receives from the sensors around the unit. Refer to Compact Logix PLC manual (35391CL) for additional information.

2 – 2

VSG/VSSG • Installation, Operation and Maintenance Manual •Vilter/Emerson • 35391SSG

Section 3 • Installation

Delivery Inspection

All equipment supplied by Vilter are thoroughly inspected at the factory. However, damage can occur in shipment. For this reason, the units should be thoroughly inspected upon arrival, prior to off-loading. Any damage noted should be photographed and reported immediately to the transportation company. This way, an authorized agent can examine the unit, determine the extent of damage and take necessary steps to rectify the claim with no serious or costly delays. At the same time, the local Vilter representative or the home office should be notified of any claims made within ten (10) days after its discovery. Refer to long term storage for additional recommendations.

Rigging and Lifting of Compressor

Unit

WARNING

Whenriggingandliftingacompressorunit,useproper lifting device capable of lifting and maneuvering the weight and size of the compressor unit. Use only qualified personnel and additional personnel and lifting equipment (i.e. spreader bar) as required. Failure to comply may result in death, serious injury

and/or damage to equipment.

Only qualified personnel shall operate rigging and lifting equipment. Ensure that the lifting device is capable of lifting the weight of the compressor unit, refer to the supplied Vilter General Assembly (GA) drawing.

To lift the compressor unit, use lifting points on compressor unit frame to attach the lifting device, see Figure 3-1. There are a few points to consider prior to moving the unit:

Ensure that the weight is evenly distributed amongst the lifting device (i.e. lifting chains and spreader bar) prior to lifting.

Ensure that the lifting device is not obstructed by any parts of the compressor unit to prevent damage to components.

Use additional personnel as needed to spot and aid in maneuvering the compressor unit.

Ensure there is plenty of space to maneuver the compressor unit and a clear path to its location.

Lifting Point

Use lifting chains/straps and spreader bar. Evenly distribute weight. Keep lifting chains and spreader bar clear of components to prevent damage.

Figure 3-1. Rigging and Lifting Points

VSG/VSSG • Installation, Operation and Maintenance Manual •Vilter/Emerson • 35391SSG

3 – 1

Section 3 • Installation

Long Term Storage Recommendations

The procedure described is a general recommendation for long term storage (over one month of no operation) of Vilter compressor units. It is the responsibility of the installation firm and end user to address any unusual conditions. Use the supplied long term storage log sheet to help with record keeping, see section page 3-3.

Warranty of the system remains in effect as described at the beginning of this manual, section page i.

The following are recommendations regarding long term storage:

COMPRESSOR MOTOR

The following are general recommendations. Refer to specific motor manufacturer instructions for storage recommendations.

Remove the condensation drain plugs from those units equipped with them and insert silica-gel into the openings. Insert one-half pound bags of silicagel (or other desiccant material) into the air inlets and outlets of drip-proof type motors.

NOTE

Bags must remain visible and tagged, so they will be noticed and removed when the unit is prepared for service.

If the unit is designed for indoor duty, it must be stored in a heated building.

If the unit is designed for outdoor duty and is to be stored outdoors, a canvas tarp is recommended for protection until installation. Adequate drainage should be provided. Place wood blocks under the base skid so that water does not collect inside the base perimeter or low spots in the tarp.

All compressor stop valves are to be closed to isolate the compressor from the remainder of the system. All other valves, except those venting to atmosphere, are to be open. The unit is shipped with dry nitrogen holding charge of approximately 5 psi above atmospheric pressure. It is essential that the nitrogen holding charge be maintained.

The nitrogen or clean dry gas holding charge in the system and compressor are to be monitored on a regular basis for leakage. If not already installed, it is required that a gauge is to be added to help monitor the nitrogen holding charge pressure. If a drop in pressure occurs, the source of leakage must be found and corrected. The system must be evacuated and recharged with dry nitrogen to maintain the package integrity.

Cover all bare metal surfaces (coupling, flange faces, etc.) with rust inhibitor.

Desiccant is to be placed in the control panel. If the panel is equipped with a space heater, it is to be energized. Use an approved electrical spray-on corrosion inhibitor for panel components (relays, switches, etc.)

All pneumatic controllers and valves (Fisher, Taylor, etc.) are to be covered with plastic bags and sealed with desiccant bags inside.

Cover the motor completely to exclude dirt, dust, moisture, and other foreign materials.

If the motor can be moved, it is suggested that the entire motor be encased in a strong, transparent plastic bag. Before sealing this bag, a moisture indicator should be attached to the side of the motor and several bags of silica-gel desiccant be placed inside the bag around the motor. When the moisture indicator shows that the desiccant has lost its effectiveness, replace desiccants.

Whenever the motor cannot be sealed, space heaters must be installed to keep the motor at least 10°F above the ambient temperature.

Rotate motor and compressor shafts several revolutions (approximately 6) per month to eliminate flat spots on the bearing surfaces. For motors utilizing anti-friction bearings, the shaft should be rotated once every 30 days by hand at 30 RPM for 15 seconds in each direction. Bearings should also be re-lubricat- ed at 2-year intervals using the grease specified on the motor lubrication nameplate.

If the compressor unit is installed, wired and charged with oil, open all oil line valves and run the oil pump for 10 seconds prior to rotating the compressor shaft. Continue running the oil pump while the compressor shaft is being turned to help lubricate the surfaces of the shaft seal.

For additional storage information, refer to Appendices.

3 – 2

VSG/VSSG • Installation, Operation and Maintenance Manual •Vilter/Emerson • 35391SSG

Section 3 • Installation

AIR COOLED OIL COOLERS

The following are general recommendations. Refer to specific air cooled oil cooler manufacturer instructions for storage recommendations.

If the coolers are to be stored or not operated for an extended period of time, the fan motors may ingress moisture if they are not protected or operated regularly. In severe cases, the moisture will reduce the insulation level of the windings or cause rusting of the bearings necessitating removal for repairs at a motor repair facility. This is a common problem with large generating installations when the coolers are often ready but commissioning of the main turbine-gener- ator is delayed for several months.

The simplest remedy for installed coolers is to operate the fan motors for a few hours every week during the downtime period until regular operation resumes. The fan motors on stored coolers must be protected from the elements by covering them with waterproof tarps.

Compressor Unit Inspections Prior to Storage or Installation

The compressor unit must be inspected prior to installation since components could have come loose and/or damaged during shipment or moving.

Check for loose bolts, particularly the compressor and motor mounting nuts.

Check for bent or damaged components. The compressor unit should have also been inspected prior to off-loading, see Delivery Inspection.

Check that the nitrogen pressure is still holding pressure. The pressure gauge is located at the discharge bleed valve on the block and bleed assembly. Any leaks must be fixed and the system purged and recharged with dry nitrogen.

Recommended Onsite Tools

The tools recommended to have on site are important for troubleshooting, inspections and compressor unit operation. Besides general mechanic tools, these tools are recommended:

Oil Pump (maximum of 2-3 GPM with motor approved for Division 1 or Division 2 and with ability to overcome suction pressure)

Infrared Heat Gun

Torque Wrenches (with ranges from 0 to 600 ft-lbs)

Sockets and wrenches up to 2-1/2” (63.5 mm)

Voltmeter

VSG/VSSG • Installation, Operation and Maintenance Manual •Vilter/Emerson • 35391SSG

3 – 3

Section 3 • Installation

LONG TERM STORAGE LOG

Date: _______________________________

Name: _______________________________ Intial:_______________

Company:

Vilter Order No. _____________________________________________

Compressor Serial Number: ________________________________________________________

Was Compressor Shaft Rotated?

_______YES

_______ NO

HOW OFTEN? __________

Was Air Cooled Oil Cooler Rotated?

_______YES

_______ NO

HOW OFTEN? __________

Was Compressor Motor Rotated?

_______YES

_______ NO

HOW OFTEN? __________

Was Compressor Motor Lubricated?

_______YES

_______ NO HOW OFTEN? __________

What was the Nitrogen pressure?

_______PSIG

 

 

Was it necessary to recharge with Nitrogen?

________YES _______NO

If unit needed recharging, was the leak found?

________YES _______NO

Please briefly explain nature of leak:

 

 

 

Is compressor stored in a building that is heated and insulated to prevent condensation of moisture and freezing of Equipment?

___________YES _________NO

Are all machined surfaces exposed to atmosphere coated with a light grease to prevent rusting (compressor shaft)?

 

__________YES _________NO

Compressor has been placed in operation as of:

DATE ______________

3 – 4

VSG/VSSG • Installation, Operation and Maintenance Manual •Vilter/Emerson • 35391SSG

Section 3 • Installation

Foundation

Foundation Materials

Materials needed to build the foundation are forms,

Vilter Single Screw compressor units are low vibra-

concrete, sand, rebar, wire, grout, anchor bolts, ex-

tion machines. Under most conditions, no elaborate

pansion board and shims. A set of concrete forms will

foundation is necessary. However a sound foundation

need to be acquired; generally, these can be rented or

maintains motor alignment and proper elevation, and

constructed from dimensional lumber. There should

is therefore required. Provided are recommendations

be enough 4,000 psi concrete with one inch aggregate

for the foundation and anchoring of the compressor

to build the foundation. Also, there should be enough

unit. The Vilter foundation supports the entire operating

sand to provide a base of compacted sand four inches

weight of the unit and is suitable for years of continuous

thick for the foundation to rest on, see Figure 1 - Con-

duty. Included are specifications for concrete, rebar, ag-

crete Pad with Compressor Unit Dimensions - Side

gregate, anchors and grout.

View. The rebar required is ASTM 615, grade 60, sizes

 

 

Considerations Prior to Starting

#4 and #6. Wires will also be needed to tie the rebar

together. The recommended grout is Masterflow 648CP

Consult professionals, such as building inspectors,

high performance non-shirk grout to provide at least

structural engineers, geotechnical engineers and/or

a 1” thick pad under each foot. The recommended an-

construction contractors prior to starting. Below are a

chors are 5/8” Diameter HILTI HAS SS threaded rod for

few points to consider:

outdoor installations or HAS-E rods for indoor installa-

 

 

tions. Anchor bolts shall have a five inch projection and

Site Characteristics:

12-3/8” embedment. The required adhesive is HIT-ICE/

Soil information

HIT/HY 150 anchoring system. There should be enough

Site drainage

one inch expansion boards to go around the perimeter

of the foundation. Finally there should be enough shim

Wind data

stock and extra anchor bolt nuts to level the compres-

Seismic zone

sor unit.

 

Ingress and egress

Building the Foundation

• Power and power lines

Use the Vilter General Arrangement (GA) and founda-

 

 

 

 

tion drawings to help secure a building permit and

Site Layout:

foundation construction. The Vilter GA drawing will

• Plant elevations, grading, drainage and erosion

have the necessary dimensions required to determine

• Accessibility to compressors for service

the overall foundation size and where to locate the

compressor unit on the foundation. It will also show the

• Location of surrounding buildings

dimensions required to form up the housekeeping piers

• Property lines and roadways

that the compressor unit rests on. The Vilter foundation

Power

drawing lists the necessary information to construct a

suitable foundation. It includes the rebar requirements

Fire safety

and locations. It also shows anchor bolt locations,

 

 

grouting and the concrete specifications. Using the

Safety:

Vilter GA drawing, Vilter foundation drawing and the

information from site characteristics, site layout and

 

NOTE

 

safety studies will provide enough data to allow build-

Always check with a safety engineer before proceeding.

ing the foundation to proceed.

 

 

• Arranging equipment with adequate access space for

The foundation is to be cast and permanently exposed

 

safe operation and maintenance

 

against the earth. Therefore, if constructing on an exist-

Wherever possible, arrange equipment to be served

ing floor, typically indoors, the floor will need to be bro-

 

by crane. If not feasible, consider other handling

 

ken up to get to the earth. If starting from undisturbed

 

methods

 

soil, it must be also be prepared accordingly. In either

 

 

• Make all valves and devices safely accessible

case, these are some check points to consider:

• Use special bright primary color schemes to differen-

• Check the depth of your frost line to ensure

 

tiate service lines

 

the foundation extends below it

• Lightening protection for outdoor installations

• Ensure the foundation rests entirely on natural rock

Relief valve venting

or entirely on solid earth, but never on a combination

VSG/VSSG • Installation, Operation and Maintenance Manual •Vilter/Emerson • 35391SSG

3 – 5

Section 3 • Installation

of both

Check the ability of the soil to carry the load

Check wet season and dry season soil characteristics for static loading limits and elasticity

Check local codes for Seismic Design requirements

For examples of foundation diagrams, see to Figure 3-2 and Figure 3-3.

trolled level and a surface texture etched in place. Leave the concrete to cure for at least 28 days.

Compressor Unit Installation

Once the foundation has cured, the compressor unit can be placed on the foundation, see Figure 3-5 and Figure 3-6. With the appropriate material handling equipment, lift the compressor unit by locations shown on the Vilter GA drawing and slowly place it on the

G.A.

G.A.

COMPRESSOR UNIT

CENTER LINE OF

GAS COMPRESSION

SYSTEM

 

CLR.

GRADE

2"(TYP.)

2"(TYP.)

 

 

EL. TOP OF

 

 

 

2"

 

 

4" COMPACTED

 

 

 

 

0"

6"

 

 

SAND

 

 

 

1'-

 

 

 

 

 

CLR.

 

# 6 @ 12"

 

 

 

EACH WAY

 

 

3"

 

 

 

 

TOP & BOTTOM

 

 

 

 

 

 

 

 

 

EXCAVATE TO FROST DEPTH AS REQ'D AND BACKFILL

 

 

 

 

WITH CLSM OR NON-FROST SUSCEPTIBLE FILL

Figure 3-2. Concrete Pad with Compressor Unit Dimensions - Side View

NOTE

In Figures 3-3 and 3-8, the recommended housekeeping height of 6” is to allow maintenance/ service of the oil strainer and oil pump.

Once the site has been excavated and prepared, place four inches of sand down on the bed where the foundation will rest. The sand must be compacted before placing the forms and rebar. After the sand is compacted, use the Vilter GA drawing to construct the forms for the foundation. With forms in place, install expansion boards on the inside of the forms, for example, see Figure 3-4. Next, place your rebar in the forms as per the Vilter foundation drawing. When all rebars are in place the concrete can be poured. The concrete must then be

foundation housekeeping piers. As per the Vilter GA drawing, ensure the compressor unit is correctly placed on the foundation. Once placed, use the spherical washers directly under the compressor as the surface to level the compressor unit, see Figure 3-7. Place shims under the feet of the compressor unit, as needed, until it is leveled, see Figure 3-8. Select the correct drill bit and drill thru the anchor bolt hole in the mounting feet of the compressor unit to the depth called for on the Vilter foundation drawing. Finally using the HILTI instructions, put your anchor bolts in place and wait for them to cure. Then place the nuts on the anchor bolts to finger tight and prepare to grout.

3 – 6

VSG/VSSG • Installation, Operation and Maintenance Manual •Vilter/Emerson • 35391SSG

Section 3 • Installation

Leveling and Grouting

recommendations for setting, precautions, mixing, and

The unit should be level in all directions. Wet the

grout placement, finishing and curing. The grout must

be worked under all areas of the feet with no bubbles or

concrete pad according to the grout manufacturer’s

voids. If the grout is settled with a slight outside slope,

directions. Mix a sufficient amount of grout. The grout

oil and water can run off of the base. Once the grout has

must be an expanding grout rather than shrinking to

cured, torque the anchor bolts as per HILTI instructions.

provide a tighter bond. Follow the manufacturer’s

 

G.A.

G.A.

COMPRESSOR UNIT

CENTER LINE OF

GAS COMPRESSION

SYSTEM

EL. TOP OF

GRADE

6"

# 6 @ 12" EACH WAY TOP & BOTTOM

EXCAVATE TO FROST DEPTH AS REQ'D AND BACKFILL

WITH CLSM OR NON-FROST SUSCEPTIBLE FILL

Figure 3-3. Concrete Pad with Compressor Unit Dimensions - Front View

 

 

 

 

 

 

ISOLATION JOINT,

 

 

 

 

 

 

 

 

 

 

 

 

1" MINIMUM

COMPRESSOR UNIT

 

CHAMFER EDGE

 

 

 

THICKNESS

 

 

 

FOUNDATION

 

 

 

 

 

 

CONCRETE SLAB IN

6” BUILDING

Figure 3-4. Interior Foundation Isolation

VSG/VSSG • Installation, Operation and Maintenance Manual •Vilter/Emerson • 35391SSG

3 – 7

Section 3 • Installation

Additional Information

Codes and Standards

Vilter followed the following codes and standards when designing your foundation:

ACI

ASTM

ASCE 7

IBC 2006

General Design Requirements

The compressor foundation is designed to:

Maintain the compressor in alignment and at proper elevation.

Minimize vibration and prevents its transmission to other structures

Provide a permanently rigid support

Operation and Performance

• Provide sufficient depth to dampen vibrations.

The foundation was designed for:

 

Outside environment severe exposure

Ambient temperature -10 degrees F to 105 degrees F

Unit weight 20,000 lbs

RPM 3600

Soil bearing capacity 1,500 lbs/sq.ft.

Wind speed 120 MPH

Exposure factor D

Wind importance factor 1.15

Concrete poured on and permanently cast against the earth

OVER ALL G.A. LENGTH + 4'-0"

10'-0"

5'-0"

CENTER LINE GAS COMPRESSION SYSTEM

Figure 3-5. Foundation with Housekeeping Pads Dimensions - Top View

3 – 8

VSG/VSSG • Installation, Operation and Maintenance Manual •Vilter/Emerson • 35391SSG

Section 3 • Installation

 

 

 

1" (TYP.)

 

 

 

G.A.

G.A.

 

 

 

(2) - # 4

 

 

G.A.

CLOSED TIES

 

 

CENTER LINE

 

 

G.A.

 

 

 

+ 2"

G.A.

G.A.

 

G.A.

 

 

(5) - # 6 VERT.

 

 

 

 

 

 

WITH STD. 90° HOOK

 

 

 

AT BOTTOM EACH

 

 

 

FACE

 

 

 

5/8" DIA. HILTI HAS SS THREADED ROD

 

 

 

(HAS-E RODS ARE ACCEPTABLE FOR INTERIOR

 

 

 

INSTALLATIONS) INSTALLED USING

 

 

 

HIT-ICE/HIT-HY 150 ADHESIVE ANCHORING

 

 

 

SYSTEM.

 

 

 

(5" PROJECTION, 12 3/8" EMBEDMENT.)

 

 

 

HOLES TO BE INSTALLED WITH HAMMER DRILL.

 

 

 

DO NOT DIAMOND CORE. (TYP.)

Figure 3-6. Housekeeping Pad Dimension Detail - Top View

LEVEL

SPHERICAL

WASHERS

COMPRESSOR UNIT

HOUSEKEEPING PADS

Figure 3-7. Level Compressor Unit Using Top Surface of Spherical Washers

VSG/VSSG • Installation, Operation and Maintenance Manual •Vilter/Emerson • 35391SSG

3 – 9

Section 3 • Installation

 

 

70+6 .')

010Ä5*4+0-

*1.& &190 076

'21:; )4176

 

 

9#5*'4

 

.'8'.+0) 076

 

/+0

4'%1//'0&'&

 

(14

 

*175'-''2+0)

 

%10%4'6'

#0%*14 $1.6

 

$#5'

 

Figure 3-8. Concrete Pad Housekeeping Detail

Piping

The ideal load applied to flanges of the compressor unit is zero. However, it’s not practical to expect that no loads will be applied to unit connections. Thermal, dead, live, wind & seismic loads must be considered and even tolerated. Well supported external piping connected to the compressor will still result in some loads applying forces and moments in three axes to unit flanges.

The most important issue is the motor-compressor misalignment caused by external forces (F in lbf) and moments (M in ft-lbf) imposed by plant piping. In Figure 3-9 and Table 3-2, are the maximum allowable forces and moments that can be applied to compressor flanges when the compressor is mounted on an oil separator.

It must be noted that it is necessary to check for compressor shaft movement when the job is complete. In no case shall the attached piping be allowed to cause more than 0.002” movement at the compressor shaft. If more than 0.002” movement is detected the piping must be adjusted to reduce the compressor shaft movement to less than 0.002”. For example, the compressor shaft should not move more than 0.002” when piping is removed or connected to the compressor.

IMPORTANT – piping elements shall be supported per the requirements of ASME B31.5 / B31.3 as applicable. See guidelines below, particularly with concern to minimizing loads on check valves.

Header Piping and Drains

Header drains should also be installed to allow drainage of liquids from the discharge and suction headers. See Appendices for Recommended Header Piping.

CAUTION

Accumulated liquid in the suction header can damage the compressor if not drained. Always drain headers (suction and discharge headers) prior to start-ups. Failure to comply may result in damage to equipment.

Remote Air Cooled Oil Cooler Piping

If equipped with a remote air cooled oil cooler, it is important that the piping be installed correctly to and from the compressor unit and remote air cooled oil cooler. See Appendices for Recommended Air Cooled Oil Cooler Piping.

3 – 10

VSG/VSSG • Installation, Operation and Maintenance Manual •Vilter/Emerson • 35391SSG

Loading...
+ 76 hidden pages