Liebert® IntelliSlot® Modbus 485, Modbus IP and BACnet IP
Reference Guide
TABLE OF CONTENTS
1.0 LIEBERT EQUIPMENT COMPATIBILITY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1
1.1 What’s New in This Manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 1.2 Connectivity to Liebert IntelliSlot Using Modbus 485, Modbus IP or BACnet IP . . . . . . . . . 1
1.2.1 How to Use This Manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
1.3 Compatibility with Liebert Equipment. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Table 1 Liebert Equipment and Compatible Liebert IntelliSlot® Cards . . . . . . . . . . . . . . . . . . . . . 2
2.0 MODBUS COMMUNICATIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
2.1 Implementation Basics. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 2.2 Transmission Format . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Table 2 Modbus Remote Transmission Unit settings for Liebert IntelliSlot 485/IP interface
card . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
2.3 Modbus Packet Format . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
2.3.1 Device Address . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 2.3.2 Function Code . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Table 3 Supported Modbus function codes. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
2.3.3 Data Fields . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 2.3.4 Error Check Field. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
2.4 RTU Framing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Table 4 Query sample . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 Table 5 Response sample . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
3.0 MODBUS 485 AND MODBUS IP PROTOCOLS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7
3.1 Thermal Management Products . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Table 6 Liebert Challenger 3000™, Liebert Challenger ITR™, Liebert CW™, Liebert Deluxe System/3™, Liebert DS™, Liebert DSE™, Liebert HPM™, Liebert PeX™ - Status
and Coil. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 Table 7 Extra notes key to Table 6 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Table 8 Liebert Challenger 3000™, Liebert Challenger ITR™, Liebert CW™, Liebert Deluxe System/3™, Liebert DS™, Liebert DSE™, Liebert HPM™, Liebert PeX™ - Input
and Holding . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13 Table 9 Extra notes key to Table 8 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Table 10 Liebert Challenger 3000™, Liebert Challenger ITR™, Liebert CW™, Liebert Deluxe System/3™, Liebert DS™, Liebert DSE™, Liebert HPM™, Liebert PeX™ - Glossary . . . . . 26
Table 11 Liebert CRV™ - Status and Coil . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39 Table 12 Liebert CRV™ - Input and Holding . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41 Table 13 Liebert CRV™ - Glossary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45 Table 14 Liebert HPC™ (Chiller) - Status and Coil . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49 Table 15 Liebert HPC™ (Chiller) - Input and Holding . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51 Table 16 Extra notes key to Table 15 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55 Table 17 Liebert HPC™ (Chiller) - Glossary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
i
Table 18 Liebert XDC™ - Status and Coil . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58 Table 19 Liebert XDC™ - Input and Holding . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59 Table 20 Liebert XDP™ - Status and Coil . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60 Table 21 Liebert XDP™ - Input and Holding . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62 Table 22 Liebert XDP™ - Glossary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72 Table 23 Liebert DS™ and Liebert PeX™ - Status and Coil. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75 Table 24 Liebert DS™ and Liebert PeX™ - Input and Holding . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 78 Table 25 Liebert XDF™ - Status and Coil . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 81 Table 26 Liebert XDF™ - Input and Holding . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 82
Table 27 Liebert Challenger 3000™, Liebert Deluxe System/3™, Liebert Himod™, Liebert
ICS™ - Input and Holding - LAM. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 83
Table 28 Liebert DataMate™, Liebert Mini-Mate Plus™, Liebert Mini-Mate2™ - Input and
Holding - L0B . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 85 Table 29 Liebert DataMate™, Liebert Mini-Mate2™ - Input and Holding - MM2 . . . . . . . . . . . . . . 86 Table 30 Liebert Mini-Mate2™ 8 Ton - Input and Holding - L8T . . . . . . . . . . . . . . . . . . . . . . . . . . . 88
Table 31 Liebert Atlas Air™, Liebert Atlas PEC™, Liebert LECS 15™ - Input and
Holding - C10 2-step . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 90
Table 32 Liebert Atlas Air™, Liebert Atlas PEC™, Liebert CEMS 100™ - Input and
Holding - C100 4-step . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 92
3.2 Power Distribution and Power Conditioning Products . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 94
Table 33 Liebert Datawave™, Liebert FPC™, Liebert PPC™ - Input and Holding - PMP, PM2 Options for Liebert FPC and Liebert PPC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 94
Table 34 Liebert Datawave™, Liebert FPC™, Liebert PPC™ - Input and Holding - PMP
Option for Liebert FPC and Liebert PPC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 96 Table 35 Liebert FDC™, Liebert FPC™, Liebert RDC™, Liebert RX™ - Status and Coil . . . . . . . . . 97 Table 36 Liebert FDC™, Liebert FPC™, Liebert RDC™, Liebert RX™ - Input and Holding. . . . . . 100 Table 37 Liebert FDC™, Liebert FPC™, Liebert RDC™, Liebert RX™ - Glossary. . . . . . . . . . . . . . 109 Table 38 Liebert STS™, Liebert STS/PDU™ - Input and Holding - STS. . . . . . . . . . . . . . . . . . . . . 112 Table 39 Liebert STS2™, Liebert STS2/PDU™ - Input and Holding - STS2. . . . . . . . . . . . . . . . . . 114
3.3 UPS Systems. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 118
Table 40 Liebert APM™, Liebert NXC™, Liebert NXR™- Status and Coil . . . . . . . . . . . . . . . . . . . 118 Table 41 Liebert APM™, Liebert NXC™, Liebert NXR™- Input and Holding. . . . . . . . . . . . . . . . . 120 Table 42 Liebert APM™, Liebert NXC™, Liebert NXR™ - Glossary . . . . . . . . . . . . . . . . . . . . . . . . 122 Table 43 Liebert APS™ - Status and Coil. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 124 Table 44 Liebert APS™ - Input and Holding . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 126 Table 45 Liebert APS™ - Glossary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 132 Table 46 Liebert GXT2™ and Liebert GXT3™ - Status and Coil . . . . . . . . . . . . . . . . . . . . . . . . . . . 136 Table 47 Liebert GXT2™ and Liebert GXT3™ - Input and Holding . . . . . . . . . . . . . . . . . . . . . . . . 137 Table 48 Liebert HiNet™ - Status and Coil . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 138 Table 49 Liebert HiNet - Input and Holding . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 138 Table 50 Liebert Nfinity® - Status and Coil. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 139
ii
Table 51 Liebert Nfinity® - Input and Holding . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 140 Table 52 Liebert NX™ - Status and Coil. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 141 Table 53 Liebert NX™ - Input and Holding . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 143 Table 54 Liebert NX 225-600kVA UPS - Input and Holding 3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . 145 Table 55 Liebert NXL™ - 60Hz, UL version (Model 40) - Status and Coil . . . . . . . . . . . . . . . . . . . 148 Table 56 Liebert NXL™ - 60Hz, UL version (Model 40) - Input and Holding . . . . . . . . . . . . . . . . 151 Table 57 Liebert NXL™ - 60Hz, UL version (Model 40) - Glossary. . . . . . . . . . . . . . . . . . . . . . . . . 163 Table 58 Liebert NXL™ - 50Hz, CE version (Models 48 and 49) - Status and Coil . . . . . . . . . . . . 168 Table 59 Liebert NXL™ - 50Hz, CE version (Models 48 and 49) - Input and Holding . . . . . . . . . 171 Table 60 Liebert NXL™ - 50Hz, CE version (Models 48 and 49) - Glossary . . . . . . . . . . . . . . . . . 182 Table 61 Liebert PowerSure™ Interactive (before July 2008) - Status and Coil . . . . . . . . . . . . . . 190 Table 62 Liebert PowerSure™ Interactive (before July 2008) - Input and Holding. . . . . . . . . . . . 191 Table 63 Liebert PowerSure™ Interactive 2 - Status and Coil . . . . . . . . . . . . . . . . . . . . . . . . . . . . 192 Table 64 Liebert PowerSure™ Interactive 2 - Input and Holding. . . . . . . . . . . . . . . . . . . . . . . . . . 193 Table 65 Liebert Series 300™ UPS - Status and Coil . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 194 Table 66 Liebert Series 300™ UPS - Input and Holding . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 195 Table 67 Liebert Series 600™ UPS - Status and Coil . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 197 Table 68 Liebert Series 600™ UPS - Input and Holding . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 198 Table 69 Liebert Series 610™ SCC UPS - Status and Coil . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 199 Table 70 Liebert Series 610 SCC UPS - Input and Holding . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 200 Table 71 Liebert HiPulse™, Liebert SICE 7200™- Input and Holding - SMM/SSM. . . . . . . . . . . . 201 Table 72 Liebert SICE 7200™ - Input and Holding - SSC. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 203 Table 73 Liebert Npower™ - Input and Holding - IMP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 205
3.4 Battery Monitoring Products . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 207
Table 74 Alber® BDSU™ - Status and Coil. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 207 Table 75 Alber® BDSU™ - Input and Holding . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 209
4.0 BACNET COMMUNICATIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .214
4.1 BACnet Protocol Implementation Conformance Statement . . . . . . . . . . . . . . . . . . . . . . . . 214
4.1.1 Segmentation Capability . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 214 4.1.2 Supported Services. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 215 4.1.3 Standard Object Types Supported . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 216 4.1.4 Object Properties . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 217
4.2 Thermal Management Products . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 220
Table 76 Liebert Challenger 3000™, Liebert Challenger ITR™, Liebert CW™, Liebert Deluxe System/3™, Liebert DS™, Liebert DSE™, Liebert HPM™, Liebert PeX™ - Binary
Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 220
Table 77 Extra Notes to Table 76 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
226 |
Table 78 Liebert Challenger 3000™, Liebert Challenger ITR™, Liebert CW™, Liebert Deluxe
System/3™, Liebert DS™, Liebert DSE™, Liebert HPM™, Liebert PeX™ - Analog
Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 227
iii
Table 79 Extra Notes to Table 78 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 235
Table 80 Liebert Challenger 3000™, Liebert Challenger ITR™, Liebert CW™, Liebert Deluxe System/3™, Liebert DS™, Liebert DSE™, Liebert HPM™, Liebert PeX™ - Multistate
Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 236 Table 81 Extra Notes to Table 80 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 243
Table 82 Liebert Challenger 3000™, Liebert Challenger ITR™, Liebert CW™, Liebert Deluxe System/3™, Liebert DS™, Liebert DSE™, Liebert HPM™, Liebert
PeX™ - Glossary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 244 Table 83 Liebert CRV™ - Binary Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 256 Table 84 Liebert CRV™ - Analog Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 259 Table 85 Liebert CRV™ - Multistate Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 262 Table 86 Liebert CRV™ - Glossary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 265 Table 87 Liebert HPC™ - Binary Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 271 Table 88 Liebert HPC™ - Analog Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 273 Table 89 Liebert HPC™ - Multistate Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 275 Table 90 Extra Notes. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 276 Table 91 Liebert HPC™ - Glossary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 276 Table 92 Liebert XDP™, Liebert XDC™ - Binary Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 279 Table 93 Liebert XDP™, Liebert XDC™ - Analog Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 281 Table 94 Liebert XDP™, Liebert XDC™ - Multistate Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 283 Table 95 Liebert XDP™, Liebert XDC™ - Glossary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 290 Table 96 Liebert DataMate™, Liebert Mini-Mate2™ - MM2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 297 Table 97 Liebert Mini-Mate2™ 8 Ton - L8T . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 298
4.3 UPS Systems. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 299
Table 98 Liebert APM™, Liebert NXC™, Liebert NXR™ - Binary Data . . . . . . . . . . . . . . . . . . . . . 299 Table 99 Liebert APM™, Liebert NXC™, Liebert NXR™ - Analog Data . . . . . . . . . . . . . . . . . . . . . 301 Table 100 Liebert APM™, Liebert NXC™, Liebert NXR™ - Multistate Data . . . . . . . . . . . . . . . . . . 302 Table 101 Liebert APM™, Liebert NXC™, Liebert NXR™ - Glossary . . . . . . . . . . . . . . . . . . . . . . . . 303 Table 102 Liebert APS™ - Binary Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 306 Table 103 Liebert APS™ - Analog Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 308 Table 104 Liebert APS™ - Multistate Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 310 Table 105 Liebert APS™ - Glossary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 312 Table 106 Liebert NXL™- 60Hz, UL version (Model 40) - Binary Data . . . . . . . . . . . . . . . . . . . . . . 316 Table 107 Liebert NXL™ - 60Hz, UL version (Model 40) - Analog Data . . . . . . . . . . . . . . . . . . . . . 321 Table 108 Liebert NXL™ - 60Hz, UL version (Model 40) - Multistate Data. . . . . . . . . . . . . . . . . . . 327 Table 109 Liebert NXL™ - 60Hz, UL version (Model 40) - Glossary. . . . . . . . . . . . . . . . . . . . . . . . . 333 Table 110 Liebert NXL™ - 50 Hz, CE version (Models 48 and 49)—Binary Data. . . . . . . . . . . . . . 341 Table 111 Liebert NXL™ - 50 Hz, CE version (Models 48 and 49)—Analog Data. . . . . . . . . . . . . . 345 Table 112 Liebert NXL™ - 50 Hz, CE version (Models 48 and 49)—Multistate Data. . . . . . . . . . . 348 Table 113 Liebert NXL™ - 50 Hz, CE version (Models 48 and 49)—Glossary. . . . . . . . . . . . . . . . . 355
iv
Liebert Equipment Compatibility - What’s New in This Manual
1.0LIEBERT EQUIPMENT COMPATIBILITY
Emerson Network Power® has introduced a new Liebert IntelliSlot® card platform—the Liebert IntelliSlot Unity™ card. This platform combines the Modbus 485, Modbus IP and BACnet IP outputs of existing cards into a common, unified platform. Liebert IS-UNITY™ allows selecting one of the available third-party protocols and the Liebert IS-UNITY-DP™ allows selection of two of the available protocols.
The Liebert IS-UNITY and LiebertIS-UNITY-DP cards are interchangeable with the IS-485L, IS-485X, IS-IPBML, IS-IPBMX, IS-WEBL and IS-WEBX cards for the protocols offered. The information output by the Unity cards is the same as the output of the IS-485L, IS-485X, IS-IPBML and IS-IPBMX cards. The cards offer Modbus IP/485 and BACnet IP.
The Liebert NX™ 225-600kVA UPS is also supported with the Chloride ManageUPS Net Adapter +B communication card so the Modbus mapping supported with this configuration has been included.
This publication describes the Modbus and BACnet communications protocols available for communication with Emerson Network Power equipment. Included are the Liebert IntelliSlot Modbus 485, Modbus IP and the BACnet IP communications cards.
•The Modbus information includes implementation basics, supported types, frame format, function code support and similar subjects.
•The BACnet information includes the BACnet service listing, object types, device objects, analog objects, binary objects, multistate objects and BACnet engineering units.
Table 1 shows the type of Liebert IntelliSlot card required for selected Liebert products. Find the product first and the Reference Table, the three columns to the right of that are the cards supported for the product.
The information is organized by Product Name, Table Number, Controller Protocol and Card Part Number.
Modbus tables are first and BACnet tables second with products in the following sections:
•Thermal Management Products
•Power Distribution and Power Conditioning Products (Modbus Only)
•UPS Systems
•Battery Monitoring Products (Modbus Only)
Products currently shipping are shown first in each section, followed by older equipment.
1 |
Liebert® IntelliSlot® Modbus/BACnet IP |
Liebert Equipment Compatibility - Compatibility with Liebert Equipment
|
Refer |
|
Compatible Card Part Number |
|
||
|
|
|
|
|
|
|
|
to |
Controller / |
Liebert IntelliSlot |
Liebert IntelliSlot |
|
Modbus IP / |
Product Supported |
Tables: |
Protocol |
Modbus 485 Card |
Web / Modbus 485 Card |
|
BACnet IP |
MODBUS 485 & MODBUS IP PROTOCOLS |
|
|
|
|
|
|
• Thermal Management Products |
|
|
|
|
|
|
Liebert Challenger 3000™ |
6-10 |
|
|
|
|
|
Liebert Challenger ITR™ |
6-10 |
|
|
|
|
|
Liebert CRV™ |
11-13 |
|
|
|
|
|
Liebert CW™ |
6-10 |
|
|
|
|
|
Liebert Deluxe System/3™ |
6-10 |
Liebert |
IS-485L |
|
|
IS-IPBML |
Liebert DS™ |
6-10 |
|
|
|||
|
|
iCOM® |
IS-UNITY |
— |
|
IS-UNITY |
Liebert DSE™ |
6-10 |
|
||||
v4 |
IS-UNITY-DP |
|
|
IS-UNITY-DP |
||
Liebert HPC™ (Chiller) |
14-17 |
|
|
|
|
|
Liebert HPM™ |
6-10 |
|
|
|
|
|
Liebert PeX™ |
6-10 |
|
|
|
|
|
Liebert XDC™ |
18-19 |
|
|
|
|
|
Liebert XDP™ |
20-22 |
|
|
|
|
|
Liebert DS |
23-24 |
Liebert |
|
|
|
|
Liebert PeX |
23-24 |
iCOM |
OC485-LBDS |
— |
|
— |
|
|
v3 |
|
|
|
|
Liebert XDF™ |
25-26 |
|
|
|
|
|
Liebert Challenger 3000 |
27 |
|
|
|
|
|
Liebert Deluxe System/3 |
27 |
LAM |
OC485-ADPT |
IS-WEBADPT |
|
— |
Liebert Himod™ |
27 |
|
||||
|
|
|
|
|
||
Liebert ICS™ |
27 |
|
|
|
|
|
Liebert DataMate™ |
28 |
|
|
|
|
|
Liebert Mini-Mate Plus™ |
28 |
L0B |
OC485-ADPT |
IS-WEBADPT |
|
— |
Liebert Mini-Mate2™ |
28 |
|
|
|
|
|
Liebert DataMate™ |
29 |
|
|
|
|
IS-WEBADPT |
|
|
MM2 |
OC485-ADPT |
IS-WEBADPT |
|
(BACnet IP |
Liebert Mini-Mate2 |
29 |
|
||||
|
|
|
|
Only) |
||
|
30 |
|
|
|
|
IS-WEBADPT |
Liebert Mini-Mate2 8 Ton |
L8T |
OC485-ADPT |
IS-WEBADPT |
|
(BACnet IP |
|
|
|
|
|
|
|
Only) |
Liebert Atlas Air™ |
31 |
C10 |
|
|
|
|
Liebert Atlas PEC™ |
31 |
OC485-ADPT |
IS-WEBADPT |
|
— |
|
|
|
2-step |
|
|
|
|
Liebert LECS 15™ |
31 |
|
|
|
|
|
|
|
|
|
|
||
Liebert Atlas Air |
32 |
C100 |
|
|
|
|
Liebert Atlas PEC |
32 |
OC485-ADPT |
IS-WEBADPT |
|
— |
|
4-step |
|
|||||
Liebert CEMS 100™ |
32 |
|
|
|
|
|
|
|
|
|
|
Liebert® IntelliSlot® Modbus/BACnet IP |
2 |
Liebert Equipment Compatibility - Compatibility with Liebert Equipment
Table 1 |
Liebert Equipment and Compatible Liebert IntelliSlot® Cards (continued) |
|
|||||
|
|
Refer |
|
Compatible Card Part Number |
|||
|
|
|
|
|
|
||
|
|
to |
Controller / |
Liebert IntelliSlot |
Liebert IntelliSlot |
Modbus IP / |
|
Product Supported |
Tables: |
Protocol |
Modbus 485 Card |
Web / Modbus 485 Card |
BACnet IP |
||
• Power Distribution & Power Conditioning Products |
|
|
|
||||
Liebert Datawave™ |
33 |
PMP, PM2 for |
|
|
|
||
Liebert FPC™ |
33 |
Liebert FPC & |
OC485-ADPT |
IS-WEBADPT |
— |
||
|
|
Liebert PPC |
|
|
|
||
Liebert PPC™ |
33 |
|
|
|
|||
Liebert FPC, Liebert RDC™, |
35-37 |
v4 |
IS-485S |
— |
IS-IPBMS |
||
Liebert FDC, Liebert RX™ |
(Modbus IP only) |
||||||
Liebert Datawave |
34 |
PMP for |
|
|
|
||
Liebert FPC |
34 |
Liebert FPC & |
OC485-ADPT |
IS-WEBADPT |
— |
||
|
|
|
Liebert PPC |
|
|
|
|
Liebert PPC |
34 |
|
|
|
|||
|
|
|
|
||||
Liebert STS™ / Liebert STS/ |
38 |
STS |
OC485-ADPT |
IS-WEBADPT |
— |
||
PDU™ |
|
||||||
Liebert STS2™ / Liebert STS2/ |
39 |
STS2 |
OC485-ADPT |
IS-WEBADPT |
— |
||
PDU™ |
|
||||||
MODBUS 485 & MODBUS IP PROTOCOLS (continued) |
|
|
|
||||
• UPS Systems |
|
|
|
|
|
||
Liebert APM™ |
40-42 |
|
IS-485L |
|
IS-IPBML |
||
— |
IS-UNITY |
— |
IS-UNITY |
||||
|
|
|
|
IS-UNITY-DP |
|
IS-UNITY-DP |
|
Liebert APS™ |
43-45 |
— |
IS-UNITY |
— |
IS-UNITY |
||
|
|
|
|
IS-UNITY-DP |
|
IS-UNITY-DP |
|
Liebert GXT2™ |
46-47 |
— |
OC-485 |
— |
— |
||
Liebert GXT3™ |
46-47 |
— |
OC-485 |
— |
— |
||
Liebert HiNet™ |
48-49 |
— |
OC-485 |
— |
— |
||
Liebert Nfinity™ |
50-51 |
— |
OC-485 |
— |
— |
||
Liebert NX™ |
52-53 |
— |
OC-485 |
— |
— |
||
Liebert NXC™ |
40-42 |
|
IS-485L |
|
IS-IPBML |
||
— |
IS-UNITY |
— |
IS-UNITY |
||||
|
|
|
|
IS-UNITY-DP |
|
IS-UNITY-DP |
|
Liebert NXR™ |
40-42 |
|
IS-485L |
|
IS-IPBML |
||
— |
IS-UNITY |
— |
IS-UNITY |
||||
|
|
|
|
IS-UNITY-DP |
|
IS-UNITY-DP |
|
Liebert NXL™- 60 Hz, UL version |
55-57 |
— |
IS-485X |
— |
IS-IPBMX |
||
(Model 40—SA, SR, SN, MM, CD) |
IS-UNITY |
IS-UNITY |
|||||
|
|
IS-UNITY-DP |
|
IS-UNITY-DP |
|||
|
|
|
|
|
|||
Liebert NXL™- 50 Hz, CE version |
58-60 |
|
IS-UNITY |
|
IS-UNITY |
||
(Model 48 and 49—SA, SR, SN, |
— |
— |
|||||
IS-UNITY-DP |
IS-UNITY-DP |
||||||
MM, CD) |
|
|
|
|
|||
|
|
|
|
|
|
||
Liebert PowerSure Interactive™ |
61-62 |
— |
OC-485 |
— |
— |
||
Liebert PowerSure Interactive 2™ |
63-64 |
— |
OC-485 |
— |
— |
||
Liebert Series 300™ UPS |
65-66 |
— |
OC485-ADPT |
IS-WEBADPT |
— |
||
Liebert Series 600™ UPS |
67-68 |
— |
OC485-ADPT |
IS-WEBADPT |
— |
||
Liebert Series 610™ SCC UPS |
69-70 |
— |
OC485-ADPT |
IS-WEBADPT |
— |
||
Liebert HiPulse™ |
71 |
SMM/SSM |
OC485-ADPT |
IS-WEBADPT |
— |
||
Liebert SICE 7200™ |
71 |
||||||
|
|
|
|
||||
Liebert SICE 7200™ |
72 |
SSC |
OC485-ADPT |
IS-WEBADPT |
— |
||
Liebert Npower™ |
73 |
IMP |
OC485-ADPT |
IS-WEBADPT |
— |
||
• Battery Monitoring Products |
|
|
|
|
|
||
Alber BDSU™ |
74-75 |
— |
IS-485X |
— |
IS-IPBMX |
||
|
|
|
|
|
|
(Modbus IP only) |
3 |
Liebert® IntelliSlot® Modbus/BACnet IP |
Liebert Equipment Compatibility - Compatibility with Liebert Equipment
Table 1 |
Liebert Equipment and Compatible Liebert IntelliSlot® Cards (continued) |
|
|||||
|
|
Refer |
|
Compatible Card Part Number |
|||
|
|
|
|
|
|
||
|
|
to |
Controller / |
Liebert IntelliSlot |
Liebert IntelliSlot |
Modbus IP / |
|
|
Product Supported |
Tables: |
Protocol |
Modbus 485 Card |
Web / Modbus 485 Card |
BACnet IP |
|
BACNET IP PROTOCOL |
|
|
|
|
|
||
|
|
|
|
|
|
||
• Thermal Management Products |
|
|
|
|
|
||
Liebert Challenger 3000™ |
76-82 |
|
|
|
|
||
Liebert Challenger ITR™ |
76-82 |
|
|
|
|
||
Liebert CRV™ |
83-86 |
|
|
|
|
||
Liebert CW™ |
76-82 |
|
|
|
|
||
Liebert Deluxe System/3 |
76-82 |
Liebert |
|
|
IS-IPBML |
||
Liebert DS™ |
76-82 |
|
|
||||
|
|
|
iCOM |
— |
— |
IS-UNITY |
|
Liebert DSE™ |
76-82 |
||||||
v4 |
|
|
IS-UNITY-DP |
||||
Liebert HPC™ |
87-91 |
|
|
|
|
||
Liebert HPM™ |
76-82 |
|
|
|
|
||
Liebert PeX™ |
76-82 |
|
|
|
|
||
Liebert XDC™ |
92-95 |
|
|
|
|
||
Liebert XDP™ |
92-95 |
|
|
|
|
||
Liebert DataMate™ |
96 |
MM2 |
— |
— |
IS-WEBADPT |
||
Liebert Mini-Mate2 |
96 |
||||||
|
|
|
(BACnet IP only) |
||||
Liebert Mini-Mate2™ 8 Ton |
97 |
L8T |
— |
— |
|
||
• Power Protection Products |
|
|
|
|
|
||
Liebert APM |
98-101 |
— |
IS-UNITY |
— |
IS-UNITY |
||
IS-UNITY-DP |
IS-UNITY-DP |
||||||
|
|
|
|
|
|||
Liebert APS |
102- |
— |
IS-UNITY |
— |
IS-UNITY |
||
105 |
IS-UNITY-DP |
IS-UNITY-DP |
|||||
|
|
|
|
||||
Liebert NXC™ |
98-101 |
— |
IS-UNITY |
— |
IS-UNITY |
||
|
|
|
|
IS-UNITY-DP |
|
IS-UNITY-DP |
|
Liebert NXR™ |
98-101 |
— |
IS-UNITY |
— |
IS-UNITY |
||
|
|
|
|
IS-UNITY-DP |
|
IS-UNITY-DP |
|
Liebert NXL60Hz, UL version |
106- |
— |
IS-UNITY |
— |
IS-UNITY |
||
(Model 40) |
109 |
IS-UNITY-DP |
IS-UNITY-DP |
||||
|
|
||||||
Liebert NXL™ - 50Hz, CE version |
110- |
— |
IS-UNITY-DP |
— |
IS-UNITY |
||
(Models 48 and 49) |
113 |
IS-UNITY |
IS-UNITY-DP |
||||
|
|
Liebert® IntelliSlot® Modbus/BACnet IP |
4 |
Modbus Communications - Implementation Basics
2.0MODBUS COMMUNICATIONS
Modbus protocol provides control and data acquisition, through query and response, between master and slave devices. This protocol comprises the rules for communication, controlling the message format between devices, how master and slave devices initiate communications, as well as unit identification, message-handling and error-checking.
The Liebert IntelliSlot® 485/IP card acts as a slave device on a network. This network can be a multidrop configuration over EIA-485, where multiple slaves reside on a common wire or loop.
The Liebert IntelliSlot 485/IP interface card supports Modbus Remote Terminal Unit (RTU) transmission modes. See Table 2 below.
Physical |
Transmission |
Baud |
Data |
Parity |
Stop |
Start |
|
Port |
Mode |
Rate |
Bits |
Bits |
Bits |
Bits |
|
|
|
|
|
|
|
|
|
EIA-485/422 |
RTU |
9600, 19200 |
8 |
None |
1 |
1 |
|
2 wire |
or 38400 |
||||||
|
|
|
|
|
Each Modbus packet consists of these fields:
•Function Code
•Data Field(s)
•Error Check Field
2.3.1Device Address
The address field immediately follows the beginning of the frame and consists of 8-bits (RTU). This bit indicates the user-assigned address of the slave device that is to receive the message from the attached master device.
Each slave must be assigned a unique address. Only the addressed slave will respond to a query that contains its address.
5 |
Liebert® IntelliSlot® Modbus/BACnet IP |
Modbus Communications - RTU Framing
The function code field tells the addressed slaves what function to perform. Function codes are designed to invoke a specific action by the slave device. The function code ranges from 1 to 127.
Liebert IntelliSlot® Modbus server supports the following Modbus function codes.
Code |
Function |
Description |
|
|
|
|
|
|
|
Read from 1 to 2000 contiguous status of coils managed by the server. Coils in the |
|
01 |
Read Coils |
response message are packed as one per bit of a byte, 1=On and 0=Off. If the requested |
|
|
|
quantity of coils is not a multiple of 8, zeros are padded in the final byte. |
|
|
|
Read from 1 to 2000 contiguous input status managed by the server. Discrete inputs in |
|
02 |
Read Discrete Inputs |
the response message are packed as one per bit of a byte, 1=On and 0=Off. If the |
|
|
|
requested number of inputs is not a multiple of 8, zeros are padded in the final byte. |
|
03 |
Read Holding Registers |
Read the contents of contiguous block of 1 to 127 holding registers. Data are packed as |
|
two bytes per register; the first byte contains the high order bits. |
|||
|
|
||
04 |
Read Input Registers |
Read the contents of contiguous block of 1 to 127 Input registers. Data are packed as |
|
two bytes per register; the first byte contains the high order bits. |
|||
|
|
||
05 |
Write Single Coil |
Write a single output to either On (1) or Off (0) mapped in coil section. |
|
|
|
|
|
06 |
Write Single Register |
Write a value into a single holding register; |
|
|
|
|
|
15 |
Write Multiple Coils |
Force each coil in a sequence of coils to either On or Off. |
|
|
|
|
|
16 |
Write Multiple Registers |
Write values into a block of contiguous registers (1 to 120) |
|
|
|
|
The data field length varies, depending on whether the message is a request or a response to a packet. This field typically contains information required by the slave device to perform the command specified or to the response to a data request from the master device.
The Error Check Field consists of a 16-bit (2 byte) Cyclical Redundancy Check (CRC16). It allows the receiving device to detect a packet that has been corrupted by transmission errors.
The example below shows a typical query and response from a Liebert IntelliSlot interface card. The master device initiates a query asking Slave Device, with address 2, for holding registers starting at holding register 40051 (offset 50) and including next two registers (three total).
Table 4 |
Query sample |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Slave |
Function |
|
Starting Register |
Number of Registers |
CRC16 |
|||
|
|
|
|
|
|
|
||
Address |
Code |
|
Hi Byte |
Lo Byte |
Hi Byte |
Lo Byte |
Hi Byte |
Lo Byte |
|
|
|
|
|
|
|
|
|
02 |
03 |
|
00 |
32 |
00 |
03 |
E5 |
FA |
|
|
|
|
|
|
|
|
|
Table 5 |
Response sample |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Count: |
|
|
Register |
|
|
CRC16 |
||
|
|
|
|
|
|
|
|
|
|
|
|
|
40051 Data |
40052 Data |
40053 Data |
|
|
||||
Slave |
Function |
Bytes of |
|
|
||||||
|
|
|
|
|
|
|
|
|||
Address |
Code |
Data |
Hi |
Lo |
Hi |
Lo |
Hi |
Lo |
Hi Byte |
Lo Byte |
|
|
|
|
|
|
|
|
|
|
|
02 |
03 |
6 |
1 |
58 |
00 |
FA |
00 |
54 |
1B |
0D |
|
|
|
|
|
|
|
|
|
|
|
Slave Device, with address 2, responds to Function Code 3 with 6 bytes of hexadecimal data and ends with CRC16 checksum.
Register values: 40051 = 158 |
(hex) = 344 |
(decimal) |
||
40052 = |
FA |
(hex) = |
250 |
(decimal) |
40053 = |
54 |
(hex) = |
84 |
(decimal) |
Liebert® IntelliSlot® Modbus/BACnet IP |
6 |
Modbus 485 and Modbus IP Protocols - Thermal Management Products
3.0MODBUS 485 AND MODBUS IP PROTOCOLS
Controller |
Liebert iCOM® v4 |
|
|
|
||
|
|
|
|
|
Units with Liebert iCOM Firmware |
|
|
|
|
|
|
PA1.04.033.STD or later: |
|
|
Units with |
|
Liebert Challenger 3000 |
|||
|
|
Liebert Challenger ITR |
||||
Liebert Products |
Liebert iCOM®: |
|
Liebert CW |
|
||
|
Liebert HPM |
|
Liebert Deluxe System/3 |
|||
|
|
|
|
|
Liebert DS |
|
|
|
|
|
|
Liebert DSE |
|
|
|
|
|
|
Liebert PeX |
|
Available Points |
|
|
|
|||
|
|
|
|
|
|
|
|
|
|
|
Number |
|
|
Data Label |
Status |
Coil |
|
of Bits |
Notes / Units |
Extra Notes |
Ext Reheat Lockout |
10009 |
- |
|
1 |
Active on Alarm |
1, 2, 3, 4, 5, 6 |
|
|
|
|
|
|
|
Ext Humidifier Lockout |
10010 |
- |
|
1 |
Active on Alarm |
1, 2, 3, 4, 5, 6 |
|
|
|
|
|
|
|
Minimum Chilled Water Temp Set Point Enable |
10013 |
13 |
|
1 |
0 = disabled |
1, 2, 3, 4, 5, 6 |
|
1 = enabled |
|||||
|
|
|
|
|
|
|
Return Air Sensor Event Control |
10019 |
19 |
|
1 |
0 = disabled |
1, 2, 3, 4, 5, 6 |
|
1 = enabled |
|||||
|
|
|
|
|
|
|
Ext Air Sensor A Event Control |
10020 |
20 |
|
1 |
0 = disabled |
1, 2, 3, 4, 5, 6 |
|
1 = enabled |
|||||
|
|
|
|
|
|
|
Ext Compressor Lockout |
10021 |
- |
|
1 |
Active on Alarm |
1, 2, 3, 4, 5, 6 |
|
|
|
|
|
|
|
System On/Off Control |
- |
25 |
|
1 |
0 = off |
1, 2, 3, 4, 5, 6 |
|
1 = on |
|||||
|
|
|
|
|
|
|
Fan State |
10025 |
— |
|
1 |
0 = off |
1, 2, 3, 4, 5, 6 |
|
1 = on |
|||||
|
|
|
|
|
|
|
Cooling State |
10026 |
— |
|
1 |
0 = off |
1, 2, 3, 4, 5, 6 |
|
1 = on |
|||||
|
|
|
|
|
|
|
Free Cooling State |
10027 |
— |
|
1 |
0 = off |
1, 2, 3, 4, 5, 6 |
|
1 = on |
|||||
|
|
|
|
|
|
|
Hot Water / Hot Gas State |
10028 |
— |
|
1 |
0 = off |
1, 2, 3, 4, 5, 6 |
|
1 = on |
|||||
|
|
|
|
|
|
|
Electric Reheat State |
10029 |
— |
|
1 |
0 = off |
1, 2, 3, 4, 5, 6 |
|
1 = on |
|||||
|
|
|
|
|
|
|
Humidifier State |
10030 |
— |
|
1 |
0 = off |
1, 2, 3, 4, 5, 6 |
|
1 = on |
|||||
|
|
|
|
|
|
|
Dehumidifier State |
10031 |
— |
|
1 |
0 = off |
1, 2, 3, 4, 5, 6 |
|
1 = on |
|||||
|
|
|
|
|
|
|
Main Fan Overload |
10034 |
— |
|
1 |
Active on Alarm |
1, 2, 3, 4, 5, 6 |
|
|
|
|
|
|
|
Loss of Air Flow |
10035 |
— |
|
1 |
Active on Alarm |
1, 2, 3, 4, 5, 6 |
|
|
|
|
|
|
|
Ext Loss of Flow |
10036 |
— |
|
1 |
Active on Alarm |
1, 2, 3, 4, 5, 6 |
|
|
|
|
|
|
|
Compressor High Head Pressure |
10037 |
— |
|
1 |
Active on Alarm |
1, 2, 3, 4, 5, 6 |
|
|
|
|
|
|
|
Compressor Low Suction Pressure |
10038 |
— |
|
1 |
Active on Alarm |
1, 2, 3, 4, 5, 6 |
|
|
|
|
|
|
|
Compressor Thermal Overload |
10039 |
— |
|
1 |
Active on Alarm |
1, 2, 3, 4, 5, 6 |
|
|
|
|
|
|
|
Compressor Pump Down Issue |
10040 |
— |
|
1 |
Active on Alarm |
1, 2, 3, 4, 5, 6 |
|
|
|
|
|
|
|
Compressor High Head Pressure 2 |
10041 |
— |
|
1 |
Active on Alarm |
1, 2, 3, 4, 5, 6 |
|
|
|
|
|
|
|
Compressor Low Suction Pressure 2 |
10042 |
— |
|
1 |
Active on Alarm |
1, 2, 3, 4, 5, 6 |
|
|
|
|
|
|
|
Compressor Thermal Overload 2 |
10043 |
— |
|
1 |
Active on Alarm |
1, 2, 3, 4, 5, 6 |
|
|
|
|
|
|
|
7 |
Liebert® IntelliSlot® Modbus/BACnet IP |
Modbus 485 and Modbus IP Protocols - Thermal Management Products
Table 6 Liebert Challenger 3000™, Liebert Challenger ITR™, Liebert CW™, Liebert Deluxe System/3™, Liebert DS™, Liebert DSE™, Liebert HPM™, Liebert PeX™ - Status and Coil (continued)
Controller |
Liebert iCOM® v4 |
|
|
|
||
|
|
|
|
|
Units with Liebert iCOM Firmware |
|
|
|
|
|
|
PA1.04.033.STD or later: |
|
|
Units with |
|
Liebert Challenger 3000 |
|||
|
|
Liebert Challenger ITR |
||||
Liebert Products |
Liebert iCOM®: |
|
Liebert CW |
|
||
|
Liebert HPM |
|
Liebert Deluxe System/3 |
|||
|
|
|
|
|
Liebert DS |
|
|
|
|
|
|
Liebert DSE |
|
|
|
|
|
|
Liebert PeX |
|
Available Points |
|
|
|
|||
|
|
|
|
|
|
|
|
|
|
|
Number |
|
|
Data Label |
Status |
Coil |
|
of Bits |
Notes / Units |
Extra Notes |
Compressor Pump Down Issue 2 |
10044 |
— |
|
1 |
Active on Alarm |
1, 2, 3, 4, 5, 6 |
|
|
|
|
|
|
|
Dig Scroll Comp Over Temp 1 |
10045 |
— |
|
1 |
Active on Alarm |
1, 2, 3, 4, 5, 6 |
|
|
|
|
|
|
|
Dig Scroll Comp Over Temp 2 |
10046 |
— |
|
1 |
Active on Alarm |
1, 2, 3, 4, 5, 6 |
|
|
|
|
|
|
|
Smoke Detected |
10047 |
— |
|
1 |
Active on Alarm |
1, 2, 3, 4, 5, 6 |
|
|
|
|
|
|
|
Water Under Floor |
10048 |
— |
|
1 |
Active on Alarm |
1, 2, 3, 4, 5, 6 |
|
|
|
|
|
|
|
Humidifier Issue |
10049 |
— |
|
1 |
Active on Alarm |
1, 2, 3, 4, 5, 6 |
|
|
|
|
|
|
|
Ext Standby Glycol Pump On |
10050 |
— |
|
1 |
Active on Alarm |
1, 2, 3, 4, 5, 6 |
|
|
|
|
|
|
|
Ext Standby Unit On |
10051 |
— |
|
1 |
Active on Alarm |
1, 2, 3, 4, 5, 6 |
|
|
|
|
|
|
|
Ext Condenser Pump High Water |
10052 |
— |
|
1 |
Active on Alarm |
1, 2, 3, 4, 5, 6 |
|
|
|
|
|
|
|
Return Air Sensor Issue |
10053 |
— |
|
1 |
Active on Alarm |
1, 2, 3, 4, 5, 6 |
|
|
|
|
|
|
|
Ext Loss of Air Blower |
10055 |
— |
|
1 |
Active on Alarm |
1, 2, 3, 4, 5, 6 |
|
|
|
|
|
|
|
Humidifier Low Water |
10058 |
— |
|
1 |
Active on Alarm |
1, 2, 3, 4, 5, 6 |
|
|
|
|
|
|
|
Humidifier Over Current |
10059 |
— |
|
1 |
Active on Alarm |
1, 2, 3, 4, 5, 6 |
|
|
|
|
|
|
|
Ext Over Temperature |
10060 |
— |
|
1 |
Active on Alarm |
1, 2, 3, 4, 5, 6 |
|
|
|
|
|
|
|
Shutdown - Loss Of Power |
10061 |
— |
|
1 |
Active on Alarm |
1, 2, 3, 4, 5, 6 |
|
|
|
|
|
|
|
Supply Chilled Water Over Temp |
10065 |
— |
|
1 |
Active on Alarm |
1, 2, 3, 4, 5, 6 |
|
|
|
|
|
|
|
Return Air Over Temperature |
10067 |
— |
|
1 |
Active on Alarm |
1, 2, 3, 4, 5, 6 |
|
|
|
|
|
|
|
Return Air Under Temperature |
10068 |
— |
|
1 |
Active on Alarm |
1, 2, 3, 4, 5, 6 |
|
|
|
|
|
|
|
High Return Humidity |
10069 |
— |
|
1 |
Active on Alarm |
1, 2, 3, 4, 5, 6 |
|
|
|
|
|
|
|
Low Return Humidity |
10070 |
— |
|
1 |
Active on Alarm |
1, 2, 3, 4, 5, 6 |
|
|
|
|
|
|
|
Ext Air Sensor A Over Temperature |
10071 |
— |
|
1 |
Active on Alarm |
1, 2, 3, 4, 5, 6 |
|
|
|
|
|
|
|
Ext Air Sensor A Under Temperature |
10072 |
— |
|
1 |
Active on Alarm |
1, 2, 3, 4, 5, 6 |
|
|
|
|
|
|
|
Ext Air Sensor A High Humidity |
10073 |
— |
|
1 |
Active on Alarm |
1, 2, 3, 4, 5, 6 |
|
|
|
|
|
|
|
Ext Air Sensor A Low Humidity |
10074 |
— |
|
1 |
Active on Alarm |
1, 2, 3, 4, 5, 6 |
|
|
|
|
|
|
|
Supply Chilled Water Loss of Flow |
10075 |
— |
|
1 |
Active on Alarm |
1, 2, 3, 4, 5, 6 |
|
|
|
|
|
|
|
Clogged Air Filter |
10076 |
— |
|
1 |
Active on Alarm |
1, 2, 3, 4, 5, 6 |
|
|
|
|
|
|
|
Supply Air Sensor Issue |
10077 |
— |
|
1 |
Active on Alarm |
1, 2, 3, 4, 5, 6 |
|
|
|
|
|
|
|
Free Cooling Temp Sensor Issue |
10078 |
— |
|
1 |
Active on Alarm |
1, 2, 3, 4, 5, 6 |
|
|
|
|
|
|
|
Ext Air Sensor A Issue |
10079 |
— |
|
1 |
Active on Alarm |
1, 2, 3, 4, 5, 6 |
|
|
|
|
|
|
|
Fan Hours Exceeded |
10080 |
— |
|
1 |
Active on Alarm |
1, 2, 3, 4, 5, 6 |
|
|
|
|
|
|
|
Compressor Hours Exceeded 1 |
10081 |
— |
|
1 |
Active on Alarm |
1, 2, 3, 4, 5, 6 |
|
|
|
|
|
|
|
Compressor Hours Exceeded 2 |
10082 |
— |
|
1 |
Active on Alarm |
1, 2, 3, 4, 5, 6 |
|
|
|
|
|
|
|
Free Cooling Valve Hours Exceeded |
10083 |
— |
|
1 |
Active on Alarm |
1, 2, 3, 4, 5, 6 |
|
|
|
|
|
|
|
Electric Reheater Hours Exceeded 1 |
10084 |
— |
|
1 |
Active on Alarm |
1, 2, 3, 4, 5, 6 |
|
|
|
|
|
|
|
Liebert® IntelliSlot® Modbus/BACnet IP |
8 |
Modbus 485 and Modbus IP Protocols - Thermal Management Products
Table 6 Liebert Challenger 3000™, Liebert Challenger ITR™, Liebert CW™, Liebert Deluxe System/3™, Liebert DS™, Liebert DSE™, Liebert HPM™, Liebert PeX™ - Status and Coil (continued)
Controller |
Liebert iCOM® v4 |
|
|
|
||
|
|
|
|
|
Units with Liebert iCOM Firmware |
|
|
|
|
|
|
PA1.04.033.STD or later: |
|
|
Units with |
|
Liebert Challenger 3000 |
|||
|
|
Liebert Challenger ITR |
||||
Liebert Products |
Liebert iCOM®: |
|
Liebert CW |
|
||
|
Liebert HPM |
|
Liebert Deluxe System/3 |
|||
|
|
|
|
|
Liebert DS |
|
|
|
|
|
|
Liebert DSE |
|
|
|
|
|
|
Liebert PeX |
|
Available Points |
|
|
|
|||
|
|
|
|
|
|
|
|
|
|
|
Number |
|
|
Data Label |
Status |
Coil |
|
of Bits |
Notes / Units |
Extra Notes |
Electric Reheater Hours Exceeded 2 |
10085 |
— |
|
1 |
Active on Alarm |
1, 2, 3, 4, 5, 6 |
|
|
|
|
|
|
|
Electric Reheater Hours Exceeded 3 |
10086 |
— |
|
1 |
Active on Alarm |
1, 2, 3, 4, 5, 6 |
|
|
|
|
|
|
|
Hot Water / Hot Gas Valve Hours Exceeded |
10087 |
— |
|
1 |
Active on Alarm |
1, 2, 3, 4, 5, 6 |
|
|
|
|
|
|
|
Humidifier Hours Exceeded |
10088 |
— |
|
1 |
Active on Alarm |
1, 2, 3, 4, 5, 6 |
|
|
|
|
|
|
|
Dehumidifier Hours Exceeded |
10089 |
— |
|
1 |
Active on Alarm |
1, 2, 3, 4, 5, 6 |
|
|
|
|
|
|
|
Unit Communication Lost |
10091 |
— |
|
1 |
Active on Alarm |
1, 2, 3, 4, 5, 6 |
|
|
|
|
|
|
|
Master Unit Communication Lost |
10092 |
— |
|
1 |
Active on Alarm |
1, 2, 3, 4, 5, 6 |
|
|
|
|
|
|
|
Unit Code Missing |
10094 |
— |
|
1 |
Active on Alarm |
1, 2, 3, 4, 5, 6 |
|
|
|
|
|
|
|
Service Required |
10098 |
— |
|
1 |
Active on Alarm |
1, 2, 3, 4, 5, 6 |
|
|
|
|
|
|
|
Humidifier Control Board Not Detected |
10099 |
— |
|
1 |
Active on Alarm |
1, 2, 3, 4, 5, 6 |
|
|
|
|
|
|
|
Customer Input 1 |
10104 |
— |
|
1 |
Active on Alarm |
1, 2, 3, 4, 5, 6 |
|
|
|
|
|
|
|
Customer Input 2 |
10105 |
— |
|
1 |
Active on Alarm |
1, 2, 3, 4, 5, 6 |
|
|
|
|
|
|
|
Customer Input 3 |
10106 |
— |
|
1 |
Active on Alarm |
1, 2, 3, 4, 5, 6 |
|
|
|
|
|
|
|
Customer Input 4 |
10107 |
— |
|
1 |
Active on Alarm |
1, 2, 3, 4, 5, 6 |
|
|
|
|
|
|
|
Dig Scroll Comp Discharge Temp Sensor Issue 1 |
10108 |
— |
|
1 |
Active on Alarm |
1, 2, 3, 4, 5, 6 |
|
|
|
|
|
|
|
Dig Scroll Comp Discharge Temp Sensor Issue 2 |
10109 |
— |
|
1 |
Active on Alarm |
1, 2, 3, 4, 5, 6 |
|
|
|
|
|
|
|
Supply Air Over Temperature |
10209 |
— |
|
1 |
Active on Alarm |
1, 2, 3, 4, 5, 6 |
|
|
|
|
|
|
|
Supply Air Under Temperature |
10210 |
— |
|
1 |
Active on Alarm |
1, 2, 3, 4, 5, 6 |
|
|
|
|
|
|
|
Ambient Air Sensor Issue |
10211 |
— |
|
1 |
Active on Alarm |
2, 3, 4, 5, 6 |
|
|
|
|
|
|
|
Compressor Short Cycle 1 |
10212 |
— |
|
1 |
Active on Alarm |
1, 2, 3, 4, 5, 6 |
|
|
|
|
|
|
|
Compressor Short Cycle 2 |
10213 |
— |
|
1 |
Active on Alarm |
1, 2, 3, 4, 5, 6 |
|
|
|
|
|
|
|
Ext Free Cooling Lockout |
10214 |
— |
|
1 |
Active on Alarm |
1, 2, 3, 4, 5, 6 |
|
|
|
|
|
|
|
Reheater Over Temperature |
10215 |
— |
|
1 |
Active on Alarm |
1, 2, 3, 4, 5, 6 |
|
|
|
|
|
|
|
Humidifier Cylinder Worn |
10216 |
— |
|
1 |
Active on Alarm |
1, 2, 3, 4, 5, 6 |
|
|
|
|
|
|
|
Humidifier Under Current |
10217 |
— |
|
1 |
Active on Alarm |
1, 2, 3, 4, 5, 6 |
|
|
|
|
|
|
|
Fan Issue |
10218 |
— |
|
1 |
Active on Alarm |
1, 2, 3, 4, 5, 6 |
|
|
|
|
|
|
|
Condenser TVSS Issue |
10219 |
— |
|
1 |
Active on Alarm |
1, 2, 3, 4, 5, 6 |
|
|
|
|
|
|
|
Condenser VFD Issue |
10220 |
— |
|
1 |
Active on Alarm |
1, 2, 3, 4, 5, 6 |
|
|
|
|
|
|
|
Condenser Issue 1 |
10221 |
— |
|
1 |
Active on Alarm |
1, 2, 3, 4, 5, 6 |
|
|
|
|
|
|
|
Condenser Issue 2 |
10222 |
— |
|
1 |
Active on Alarm |
1, 2, 3, 4, 5, 6 |
|
|
|
|
|
|
|
BMS Communications Timeout |
10223 |
— |
|
1 |
Active on Alarm |
1, 2, 3, 4, 5, 6 |
|
|
|
|
|
|
|
Digital Output Board Not Detected 1 |
10224 |
— |
|
1 |
Active on Alarm |
1, 2, 3, 4, 5, 6 |
|
|
|
|
|
|
|
Digital Output Board Not Detected 2 |
10225 |
— |
|
1 |
Active on Alarm |
1, 2, 3, 4, 5, 6 |
|
|
|
|
|
|
|
Digital Output Board Not Detected 3 |
10226 |
— |
|
1 |
Active on Alarm |
1, 2, 3, 4, 5, 6 |
|
|
|
|
|
|
|
9 |
Liebert® IntelliSlot® Modbus/BACnet IP |
Modbus 485 and Modbus IP Protocols - Thermal Management Products
Table 6 Liebert Challenger 3000™, Liebert Challenger ITR™, Liebert CW™, Liebert Deluxe System/3™, Liebert DS™, Liebert DSE™, Liebert HPM™, Liebert PeX™ - Status and Coil (continued)
Controller |
Liebert iCOM® v4 |
|
|
|
||
|
|
|
|
|
Units with Liebert iCOM Firmware |
|
|
|
|
|
|
PA1.04.033.STD or later: |
|
|
Units with |
|
Liebert Challenger 3000 |
|||
|
|
Liebert Challenger ITR |
||||
Liebert Products |
Liebert iCOM®: |
|
Liebert CW |
|
||
|
Liebert HPM |
|
Liebert Deluxe System/3 |
|||
|
|
|
|
|
Liebert DS |
|
|
|
|
|
|
Liebert DSE |
|
|
|
|
|
|
Liebert PeX |
|
Available Points |
|
|
|
|||
|
|
|
|
|
|
|
|
|
|
|
Number |
|
|
Data Label |
Status |
Coil |
|
of Bits |
Notes / Units |
Extra Notes |
RAM Battery Issue |
10227 |
— |
|
1 |
Active on Alarm |
1, 2, 3, 4, 5, 6 |
|
|
|
|
|
|
|
Water Leakage Detector Sensor Issue |
10228 |
— |
|
1 |
Active on Alarm |
1, 2, 3, 4, 5, 6 |
|
|
|
|
|
|
|
External Fire Detected |
10229 |
— |
|
1 |
Active on Alarm |
1, 2, 3, 4, 5, 6 |
|
|
|
|
|
|
|
Chilled Water Control Valve Failure 1 |
10230 |
— |
|
1 |
Active on Alarm |
1, 2, 3, 4, 5, 6 |
|
|
|
|
|
|
|
Chilled Water Control Valve Failure 2 |
10231 |
— |
|
1 |
Active on Alarm |
1, 2, 3, 4, 5, 6 |
|
|
|
|
|
|
|
Unit Off |
10232 |
— |
|
1 |
Active on Alarm |
1, 2, 3, 4, 5, 6 |
|
|
|
|
|
|
|
Unit On |
10233 |
— |
|
1 |
Active on Alarm |
1, 2, 3, 4, 5, 6 |
|
|
|
|
|
|
|
Unit Partial Shutdown |
10234 |
— |
|
1 |
Active on Alarm |
1, 2, 3, 4, 5, 6 |
|
|
|
|
|
|
|
Unit Shutdown |
10235 |
— |
|
1 |
Active on Alarm |
1, 2, 3, 4, 5, 6 |
|
|
|
|
|
|
|
High Power Shutdown |
10236 |
— |
|
1 |
Active on Alarm |
1, 2, 3, 4, 5, 6 |
|
|
|
|
|
|
|
Unit Standby |
10237 |
— |
|
1 |
Active on Alarm |
1, 2, 3, 4, 5, 6 |
|
|
|
|
|
|
|
Maintenance Due |
10238 |
— |
|
1 |
Active on Alarm |
1, 2, 3, 4, 5, 6 |
|
|
|
|
|
|
|
Maintenance Completed |
10239 |
— |
|
1 |
Active on Alarm |
1, 2, 3, 4, 5, 6 |
|
|
|
|
|
|
|
Compressor Low Pressure Transducer Issue 1 |
10240 |
— |
|
1 |
Active on Alarm |
1, 2, 3, 4, 5, 6 |
|
|
|
|
|
|
|
Compressor Low Pressure Transducer Issue 2 |
10241 |
— |
|
1 |
Active on Alarm |
1, 2, 3, 4, 5, 6 |
|
|
|
|
|
|
|
Compressor High Pressure Transducer Issue 1 |
10242 |
— |
|
1 |
Active on Alarm |
1, 2, 3, 4, 5, 6 |
|
|
|
|
|
|
|
Compressor High Pressure Transducer Issue 2 |
10243 |
— |
|
1 |
Active on Alarm |
1, 2, 3, 4, 5, 6 |
|
|
|
|
|
|
|
Compressor Capacity Reduced |
10244 |
— |
|
1 |
Active on Alarm |
1, 2, 3, 4, 5, 6 |
|
|
|
|
|
|
|
Dew Point Over Temperature |
10345 |
— |
|
1 |
Active on Alarm |
2, 3, 4, 5, 6 |
|
|
|
|
|
|
|
Dew Point Under Temperature |
10346 |
— |
|
1 |
Active on Alarm |
2, 3, 4, 5, 6 |
|
|
|
|
|
|
|
Ext Dew Point Over Temperature |
10347 |
— |
|
1 |
Active on Alarm |
2, 3, 4, 5, 6 |
|
|
|
|
|
|
|
Ext Dew Point Under Temperature |
10348 |
— |
|
1 |
Active on Alarm |
2, 3, 4, 5, 6 |
|
|
|
|
|
|
|
Compressor Superheat Over Threshold 1 |
10349 |
— |
|
1 |
Active on Alarm |
2, 3, 4, 5, 6 |
|
|
|
|
|
|
|
Compressor Superheat Over Threshold 2 |
10350 |
— |
|
1 |
Active on Alarm |
2, 3, 4, 5, 6 |
|
|
|
|
|
|
|
Unspecified General Event |
10351 |
— |
|
1 |
Active on Alarm |
2, 3, 4, 5, 6 |
|
|
|
|
|
|
|
Remote Sensor Average Over Temperature |
10352 |
— |
|
1 |
Active on Alarm |
2, 3, 4, 5, 6 |
|
|
|
|
|
|
|
Remote Sensor Average Under Temperature |
10353 |
— |
|
1 |
Active on Alarm |
2, 3, 4, 5, 6 |
|
|
|
|
|
|
|
Remote Sensor System Average Over Temperature |
10354 |
— |
|
1 |
Active on Alarm |
2, 3, 4, 5, 6 |
|
|
|
|
|
|
|
Remote Sensor System Average Under Temperature |
10355 |
— |
|
1 |
Active on Alarm |
2, 3, 4, 5, 6 |
|
|
|
|
|
|
|
Remote Sensor Over Temperature 1 |
10356 |
— |
|
1 |
Active on Alarm |
2, 3, 4, 5, 6 |
|
|
|
|
|
|
|
Remote Sensor Over Temperature 2 |
10357 |
— |
|
1 |
Active on Alarm |
2, 3, 4, 5, 6 |
|
|
|
|
|
|
|
Remote Sensor Over Temperature 3 |
10358 |
— |
|
1 |
Active on Alarm |
2, 3, 4, 5, 6 |
|
|
|
|
|
|
|
Remote Sensor Over Temperature 4 |
10359 |
— |
|
1 |
Active on Alarm |
2, 3, 4, 5, 6 |
|
|
|
|
|
|
|
Remote Sensor Over Temperature 5 |
10360 |
— |
|
1 |
Active on Alarm |
2, 3, 4, 5, 6 |
|
|
|
|
|
|
|
Liebert® IntelliSlot® Modbus/BACnet IP |
10 |
Modbus 485 and Modbus IP Protocols - Thermal Management Products
Table 6 Liebert Challenger 3000™, Liebert Challenger ITR™, Liebert CW™, Liebert Deluxe System/3™, Liebert DS™, Liebert DSE™, Liebert HPM™, Liebert PeX™ - Status and Coil (continued)
Controller |
Liebert iCOM® v4 |
|
|
|
||
|
|
|
|
|
Units with Liebert iCOM Firmware |
|
|
|
|
|
|
PA1.04.033.STD or later: |
|
|
Units with |
|
Liebert Challenger 3000 |
|||
|
|
Liebert Challenger ITR |
||||
Liebert Products |
Liebert iCOM®: |
|
Liebert CW |
|
||
|
Liebert HPM |
|
Liebert Deluxe System/3 |
|||
|
|
|
|
|
Liebert DS |
|
|
|
|
|
|
Liebert DSE |
|
|
|
|
|
|
Liebert PeX |
|
Available Points |
|
|
|
|||
|
|
|
|
|
|
|
|
|
|
|
Number |
|
|
Data Label |
Status |
Coil |
|
of Bits |
Notes / Units |
Extra Notes |
Remote Sensor Over Temperature 6 |
10361 |
— |
|
1 |
Active on Alarm |
2, 3, 4, 5, 6 |
|
|
|
|
|
|
|
Remote Sensor Over Temperature 7 |
10362 |
— |
|
1 |
Active on Alarm |
2, 3, 4, 5, 6 |
|
|
|
|
|
|
|
Remote Sensor Over Temperature 8 |
10363 |
— |
|
1 |
Active on Alarm |
2, 3, 4, 5, 6 |
|
|
|
|
|
|
|
Remote Sensor Over Temperature 9 |
10364 |
— |
|
1 |
Active on Alarm |
2, 3, 4, 5, 6 |
|
|
|
|
|
|
|
Remote Sensor Over Temperature 10 |
10365 |
— |
|
1 |
Active on Alarm |
2, 3, 4, 5, 6 |
|
|
|
|
|
|
|
Remote Sensor Under Temperature 1 |
10366 |
— |
|
1 |
Active on Alarm |
2, 3, 4, 5, 6 |
|
|
|
|
|
|
|
Remote Sensor Under Temperature 2 |
10367 |
— |
|
1 |
Active on Alarm |
2, 3, 4, 5, 6 |
|
|
|
|
|
|
|
Remote Sensor Under Temperature 3 |
10368 |
— |
|
1 |
Active on Alarm |
2, 3, 4, 5, 6 |
|
|
|
|
|
|
|
Remote Sensor Under Temperature 4 |
10369 |
— |
|
1 |
Active on Alarm |
2, 3, 4, 5, 6 |
|
|
|
|
|
|
|
Remote Sensor Under Temperature 5 |
10370 |
— |
|
1 |
Active on Alarm |
2, 3, 4, 5, 6 |
|
|
|
|
|
|
|
Remote Sensor Under Temperature 6 |
10371 |
— |
|
1 |
Active on Alarm |
2, 3, 4, 5, 6 |
|
|
|
|
|
|
|
Remote Sensor Under Temperature 7 |
10372 |
— |
|
1 |
Active on Alarm |
2, 3, 4, 5, 6 |
|
|
|
|
|
|
|
Remote Sensor Under Temperature 8 |
10373 |
— |
|
1 |
Active on Alarm |
2, 3, 4, 5, 6 |
|
|
|
|
|
|
|
Remote Sensor Under Temperature 9 |
10374 |
— |
|
1 |
Active on Alarm |
2, 3, 4, 5, 6 |
|
|
|
|
|
|
|
Remote Sensor Under Temperature 10 |
10375 |
— |
|
1 |
Active on Alarm |
2, 3, 4, 5, 6 |
|
|
|
|
|
|
|
Remote Sensor Issue 1 |
10376 |
— |
|
1 |
Active on Alarm |
1, 2, 3, 4, 5, 6 |
|
|
|
|
|
|
|
Remote Sensor Issue 2 |
10377 |
— |
|
1 |
Active on Alarm |
2, 3, 4, 5, 6 |
|
|
|
|
|
|
|
Remote Sensor Issue 3 |
10378 |
— |
|
1 |
Active on Alarm |
2, 3, 4, 5, 6 |
|
|
|
|
|
|
|
Remote Sensor Issue 4 |
10379 |
— |
|
1 |
Active on Alarm |
2, 3, 4, 5, 6 |
|
|
|
|
|
|
|
Remote Sensor Issue 5 |
10380 |
— |
|
1 |
Active on Alarm |
2, 3, 4, 5, 6 |
|
|
|
|
|
|
|
Remote Sensor Issue 6 |
10381 |
— |
|
1 |
Active on Alarm |
2, 3, 4, 5, 6 |
|
|
|
|
|
|
|
Remote Sensor Issue 7 |
10382 |
— |
|
1 |
Active on Alarm |
2, 3, 4, 5, 6 |
|
|
|
|
|
|
|
Remote Sensor Issue 8 |
10383 |
— |
|
1 |
Active on Alarm |
2, 3, 4, 5, 6 |
|
|
|
|
|
|
|
Remote Sensor Issue 9 |
10384 |
— |
|
1 |
Active on Alarm |
2, 3, 4, 5, 6 |
|
|
|
|
|
|
|
Remote Sensor Issue 10 |
10385 |
— |
|
1 |
Active on Alarm |
2, 3, 4, 5, 6 |
|
|
|
|
|
|
|
Air Economizer Emergency Override |
10386 |
— |
|
1 |
Active on Alarm |
2, 3, 4, 5, 6 |
|
|
|
|
|
|
|
Air Economizer Reduced Airflow |
10387 |
— |
|
1 |
Active on Alarm |
2, 3, 4, 5, 6 |
|
|
|
|
|
|
|
Temperature Control Sensor Issue |
10388 |
— |
|
1 |
Active on Alarm |
2, 3, 4, 5, 6 |
|
|
|
|
|
|
|
EEV Unspecified General Event |
10488 |
— |
|
1 |
Active on Alarm |
4, 5 |
|
|
|
|
|
|
|
Static Pressure Sensor Issue |
10489 |
— |
|
1 |
Active on Alarm |
3, 5, 6 |
|
|
|
|
|
|
|
High Static Pressure |
10490 |
— |
|
1 |
Active on Alarm |
3, 5, 6 |
|
|
|
|
|
|
|
Low Static Pressure |
10491 |
— |
|
1 |
Active on Alarm |
3, 5, 6 |
|
|
|
|
|
|
|
Pump Unspecified General Event |
10492 |
— |
|
1 |
Active on Alarm |
4, 5 |
|
|
|
|
|
|
|
Condenser Unit Unspecified General Event |
10493 |
— |
|
1 |
Active on Alarm |
3, 4, 5, 6 |
|
|
|
|
|
|
|
11 |
Liebert® IntelliSlot® Modbus/BACnet IP |
Modbus 485 and Modbus IP Protocols - Thermal Management Products
Table 6 Liebert Challenger 3000™, Liebert Challenger ITR™, Liebert CW™, Liebert Deluxe System/3™, Liebert DS™, Liebert DSE™, Liebert HPM™, Liebert PeX™ - Status and Coil (continued)
Controller |
Liebert iCOM® v4 |
|
|
|
|
||
|
|
|
|
|
Units with Liebert iCOM Firmware |
||
|
|
|
|
|
PA1.04.033.STD or later: |
||
|
Units with |
|
Liebert Challenger 3000 |
||||
|
|
Liebert Challenger ITR |
|
||||
Liebert Products |
Liebert iCOM®: |
|
Liebert CW |
|
|||
|
Liebert HPM |
|
Liebert Deluxe System/3 |
||||
|
|
|
|
|
Liebert DS |
|
|
|
|
|
|
|
Liebert DSE |
|
|
|
|
|
|
|
Liebert PeX |
|
|
Available Points |
|
|
|
|
|||
|
|
|
|
|
|
|
|
|
|
|
|
Number |
|
|
|
Data Label |
Status |
Coil |
|
of Bits |
Notes / Units |
|
Extra Notes |
Condenser Circuit Unspecified General Event |
10494 |
— |
|
1 |
Active on Alarm |
|
3, 4, 5, 6 |
|
|
|
|
|
|
|
|
Input Undervoltage 1 |
10500 |
— |
|
1 |
Active on Alarm |
|
6 |
|
|
|
|
|
|
|
|
Input Undervoltage 2 |
10501 |
— |
|
1 |
Active on Alarm |
|
6 |
|
|
|
|
|
|
|
|
Input Undervoltage 3 |
10502 |
— |
|
1 |
Active on Alarm |
|
6 |
|
|
|
|
|
|
|
|
Input Undervoltage 4 |
10503 |
— |
|
1 |
Active on Alarm |
|
6 |
|
|
|
|
|
|
|
|
Input Undervoltage 5 |
10504 |
— |
|
1 |
Active on Alarm |
|
6 |
|
|
|
|
|
|
|
|
Input Undervoltage 6 |
10505 |
— |
|
1 |
Active on Alarm |
|
6 |
|
|
|
|
|
|
|
|
Return Humidity Sensor Issue |
10600 |
— |
|
1 |
Active on Alarm |
|
5, 6 |
|
|
|
|
|
|
|
|
Compressor Low Differential Pressure Lockout 1 |
10601 |
— |
|
1 |
Active on Alarm |
|
5 |
|
|
|
|
|
|
|
|
Compressor Low Differential Pressure Lockout 2 |
10602 |
— |
|
1 |
Active on Alarm |
|
5 |
|
|
|
|
|
|
|
|
Airflow Sensor Issue |
10603 |
— |
|
1 |
Active on Alarm |
|
5, 6 |
|
|
|
|
|
|
|
|
Ext Air Damper Position Issue |
10604 |
— |
|
1 |
Active on Alarm |
|
5, 6 |
|
|
|
|
|
|
|
|
Ext Power Source A Failure |
10605 |
— |
|
1 |
Active on Alarm |
|
5, 6 |
|
|
|
|
|
|
|
|
Ext Power Source B Failure |
10606 |
— |
|
1 |
Active on Alarm |
|
5, 6 |
|
|
|
|
|
|
|
|
Static Pressure Sensor Out of Range |
10607 |
— |
|
1 |
Active on Alarm |
|
5, 6 |
|
|
|
|
|
|
|
|
Fluid Temperature Sensor Issue 1 |
10608 |
— |
|
1 |
Active on Alarm |
|
6 |
|
|
|
|
|
|
|
|
Fluid Temperature Sensor Issue 2 |
10609 |
— |
|
1 |
Active on Alarm |
|
6 |
|
|
|
|
|
|
|
|
Fluid Flow Sensor Issue 1 |
10610 |
— |
|
1 |
Active on Alarm |
|
6 |
|
|
|
|
|
|
|
|
Fluid Flow Sensor Issue 2 |
10611 |
— |
|
1 |
Active on Alarm |
|
6 |
|
|
|
|
|
|
|
|
Mixed Mode Lockout |
10620 |
— |
|
1 |
Active on Alarm |
|
5 |
|
|
|
|
|
|
|
|
Number Description
1This point is supported on:
iCOM controller version 1.04.042.STD This point is supported on:
2iCOM controller version 2.00.11R for US
iCOM controller version 2.00.12R (for Japan and China – language corrections only)
3This point is supported on: iCOM controller version 2.01.23R
4This point is supported on: iCOM controller version 2.02.16R
5This point is supported on:
iCOM controller version 2.03.27.07R
6This point is supported on:
iCOM controller version 2.01.32.02R
Liebert® IntelliSlot® Modbus/BACnet IP |
12 |
Modbus 485 and Modbus IP Protocols - Thermal Management Products
Controller |
Liebert iCOM v4 |
|
|
|
|
||
|
|
|
|
|
|
|
|
|
Input |
Holding |
# of |
|
|
Extra |
|
Data Label |
Register |
Register |
Reg. |
Scale |
Notes / Units |
Notes |
|
|
|
|
|
|
0 = Disabled |
|
|
Free Cooling Internal Control Mode |
30017 |
40017 |
1 |
— |
1 = Contact |
1 |
|
|
|
|
|
|
2 = Value |
|
|
|
|
|
|
|
0 = Relative |
|
|
Humidity Proportional Control Type |
30018 |
40018 |
1 |
— |
1 = Compensated |
1 |
|
|
|
|
|
|
2 = Predictive |
|
|
Fan Speed Maximum Set Point |
30019 |
40019 |
1 |
— |
% |
1, 2, 3, 4, 5, 6 |
|
|
|
|
|
|
|
|
|
Supply Air Temperature Set Point |
30020 |
40020 |
1 |
— |
deg C |
1 |
|
|
|
|
|
|
|
|
|
Supply Air Temperature Set Point |
30733 |
40733 |
1 |
— |
deg F |
1 |
|
|
|
|
|
|
|
|
|
Free Cooling Internal Temperature Delta |
30021 |
40021 |
1 |
10 |
deg C |
1, 2, 3, 4, 5, 6 |
|
|
|
|
|
|
|
|
|
Free Cooling Internal Temperature Delta |
30734 |
40734 |
1 |
10 |
deg F |
1, 2, 3, 4, 5, 6 |
|
|
|
|
|
|
|
|
|
Minimum Chilled Water Temp Set Point |
30022 |
40022 |
1 |
10 |
deg C |
1, 2, 3, 4, 5, 6 |
|
|
|
|
|
|
|
|
|
Minimum Chilled Water Temp Set Point |
30735 |
40735 |
1 |
10 |
deg F |
1, 2, 3, 4, 5, 6 |
|
|
|
|
|
|
|
|
|
Air Temperature Set Point |
30023 |
40023 |
1 |
10 |
deg C |
1, 2, 3, 4, 5, 6 |
|
|
|
|
|
|
|
|
|
Air Temperature Set Point |
30736 |
40736 |
1 |
10 |
deg F |
1, 2, 3, 4, 5, 6 |
|
|
|
|
|
|
|
|
|
Air Temperature Proportional Band |
30024 |
40024 |
1 |
10 |
deg C |
1, 2, 3, 4, 5, 6 |
|
|
|
|
|
|
|
|
|
Air Temperature Proportional Band |
30737 |
40737 |
1 |
10 |
deg F |
1, 2, 3, 4, 5, 6 |
|
|
|
|
|
|
|
|
|
Air Temperature Dead Band |
30025 |
40025 |
1 |
10 |
deg C |
1, 2, 3, 4, 5, 6 |
|
|
|
|
|
|
|
|
|
Air Temperature Dead Band |
30738 |
40738 |
1 |
10 |
deg F |
1, 2, 3, 4, 5, 6 |
|
|
|
|
|
|
|
|
|
Air Temperature Control Integration Time |
30026 |
40026 |
1 |
10 |
min |
1, 2, 3, 4, 5, 6 |
|
|
|
|
|
|
|
|
|
Humidity Set Point |
30027 |
40027 |
1 |
— |
% RH |
1, 2, 3, 4, 5, 6 |
|
|
|
|
|
|
|
|
|
Humidity Proportional Band |
30028 |
40028 |
1 |
— |
% RH |
1, 2, 3, 4, 5, 6 |
|
|
|
|
|
|
|
|
|
Humidity Proportional Control Integration |
30029 |
40029 |
1 |
10 |
min |
1, 2, 3, 4, 5, 6 |
|
Time |
|||||||
|
|
|
|
|
|
||
Humidity Dead Band |
30030 |
40030 |
1 |
10 |
% RH |
1, 2, 3, 4, 5, 6 |
|
|
|
|
|
|
|
|
|
Auto Restart Delay |
30031 |
40031 |
1 |
— |
sec |
1, 2, 3, 4, 5, 6 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
0 = Proportional |
|
|
Air Temperature Control Type |
30033 |
40033 |
1 |
— |
1 = Prop+Integral |
1, 2, 3, 4, 5, 6 |
|
|
|
|
|
|
3 = Intelligent |
|
|
BMS Timeout Period |
30045 |
40045 |
1 |
— |
min |
1, 2, 3, 4, 5, 6 |
|
|
|
|
|
|
|
|
|
Return Air Over Temp Threshold |
30050 |
40050 |
1 |
10 |
deg C |
1, 2, 3, 4, 5, 6 |
|
|
|
|
|
|
|
|
|
Return Air Over Temp Threshold |
30739 |
40739 |
1 |
10 |
deg F |
1, 2, 3, 4, 5, 6 |
|
|
|
|
|
|
|
|
|
Return Air Under Temp Threshold |
30051 |
40051 |
1 |
10 |
deg C |
1, 2, 3, 4, 5, 6 |
|
|
|
|
|
|
|
|
|
Return Air Under Temp Threshold |
30740 |
40740 |
1 |
10 |
deg F |
1, 2, 3, 4, 5, 6 |
|
|
|
|
|
|
|
|
|
Ext Air Sensor A Over Temp Threshold |
30052 |
40052 |
1 |
10 |
deg C |
1, 2, 3, 4, 5, 6 |
|
|
|
|
|
|
|
|
|
Ext Air Sensor A Over Temp Threshold |
30741 |
40741 |
1 |
10 |
deg F |
1, 2, 3, 4, 5, 6 |
|
|
|
|
|
|
|
|
|
Ext Air Sensor A Under Temp Threshold |
30053 |
40053 |
1 |
10 |
deg C |
1, 2, 3, 4, 5, 6 |
|
|
|
|
|
|
|
|
|
Ext Air Sensor A Under Temp Threshold |
30742 |
40742 |
1 |
10 |
deg F |
1, 2, 3, 4, 5, 6 |
|
|
|
|
|
|
|
|
|
High Return Humidity Threshold |
30054 |
40054 |
1 |
10 |
% RH |
1, 2, 3, 4, 5, 6 |
|
|
|
|
|
|
|
|
|
Low Return Humidity Threshold |
30055 |
40055 |
1 |
10 |
% RH |
1, 2, 3, 4, 5, 6 |
|
|
|
|
|
|
|
|
|
Ext Air Sensor A High Humidity Threshold |
30056 |
40056 |
1 |
10 |
% RH |
1, 2, 3, 4, 5, 6 |
|
|
|
|
|
|
|
|
|
Ext Air Sensor A Low Humidity Threshold |
30057 |
40057 |
1 |
10 |
% RH |
1, 2, 3, 4, 5, 6 |
|
|
|
|
|
|
|
|
|
Fan Hours Threshold |
30070 |
40070 |
1 |
— |
hr |
1, 2, 3, 4, 5, 6 |
|
|
|
|
|
|
|
|
13 |
Liebert® IntelliSlot® Modbus/BACnet IP |
Modbus 485 and Modbus IP Protocols - Thermal Management Products
Table 8 Liebert Challenger 3000™, Liebert Challenger ITR™, Liebert CW™, Liebert Deluxe System/3™, Liebert DS™, Liebert DSE™, Liebert HPM™, Liebert PeX™ - Input and Holding (continued)
Controller |
Liebert iCOM v4 |
|
|
|
|
|
|
|
|
|
|
|
|
|
Input |
Holding |
# of |
|
|
Extra |
Data Label |
Register |
Register |
Reg. |
Scale |
Notes / Units |
Notes |
Compressor Hours Threshold 1 |
30071 |
40071 |
1 |
— |
hr |
1, 2, 3, 4, 5, 6 |
|
|
|
|
|
|
|
Compressor Hours Threshold 2 |
30072 |
40072 |
1 |
— |
hr |
1, 2, 3, 4, 5, 6 |
|
|
|
|
|
|
|
Humidifier Hours Threshold |
30073 |
40073 |
1 |
— |
hr |
1, 2, 3, 4, 5, 6 |
|
|
|
|
|
|
|
Dehumidifier Hours Threshold |
30074 |
40074 |
1 |
— |
hr |
1, 2, 3, 4, 5, 6 |
|
|
|
|
|
|
|
Free Cooling Valve Hours Threshold |
30075 |
40075 |
1 |
— |
hr |
1, 2, 3, 4, 5, 6 |
|
|
|
|
|
|
|
Electric Reheater Hours Threshold 1 |
30076 |
40076 |
1 |
— |
hr |
1, 2, 3, 4, 5, 6 |
|
|
|
|
|
|
|
Electric Reheater Hours Threshold 2 |
30077 |
40077 |
1 |
— |
hr |
1, 2, 3, 4, 5, 6 |
|
|
|
|
|
|
|
Electric Reheater Hours Threshold 3 |
30078 |
40078 |
1 |
— |
hr |
1, 2, 3, 4, 5, 6 |
|
|
|
|
|
|
|
Hot Water / Hot Gas Valve Hours Threshold |
30079 |
40079 |
1 |
— |
hr |
1, 2, 3, 4, 5, 6 |
|
|
|
|
|
|
|
|
|
|
|
|
0 = off |
|
System Operating State |
30100 |
— |
1 |
— |
1 = on |
1, 2, 3, 4, 5, 6 |
|
|
|
|
|
2 = standby |
|
|
|
|
|
|
1 = Normal Operation |
|
|
|
|
|
|
2 = StartUp |
|
System Status |
30102 |
— |
1 |
— |
8 = Normal with Warning |
1, 2, 3, 4, 5, 6 |
|
|
|
|
|
16 = Normal with Alarm |
|
|
|
|
|
|
32 = Abnormal Operation |
|
Fan Speed |
30103 |
— |
1 |
— |
% |
1, 2, 3, 4, 5, 6 |
|
|
|
|
|
|
|
Compressor Utilization |
30104 |
— |
1 |
— |
% |
1 |
|
|
|
|
|
|
|
Free Cooling Valve Open Position |
30105 |
— |
1 |
— |
% |
1, 2, 3, 4, 5, 6 |
|
|
|
|
|
|
|
Reheat Utilization |
30106 |
— |
1 |
— |
% |
1, 2, 3, 4, 5, 6 |
|
|
|
|
|
|
|
Humidifier Utilization |
30107 |
— |
1 |
— |
% |
1, 2, 3, 4, 5, 6 |
|
|
|
|
|
|
|
Dehumidifier Utilization |
30108 |
— |
1 |
— |
% |
1, 2, 3, 4, 5, 6 |
|
|
|
|
|
|
|
|
|
|
|
|
0 = off |
|
Free Cooling Status |
30109 |
— |
1 |
— |
2 = on |
1, 2, 3, 4, 5, 6 |
|
|
|
|
|
3 = No Support |
|
Return Air Temperature |
30110 |
— |
1 |
10 |
deg C |
1, 2, 3, 4, 5, 6 |
|
|
|
|
|
|
|
Return Air Temperature |
30743 |
— |
1 |
10 |
deg F |
1, 2, 3, 4, 5, 6 |
|
|
|
|
|
|
|
Supply Air Temperature |
30112 |
— |
1 |
10 |
deg C |
1, 2, 3, 4, 5, 6 |
|
|
|
|
|
|
|
Supply Air Temperature |
30744 |
— |
1 |
10 |
deg F |
1, 2, 3, 4, 5, 6 |
|
|
|
|
|
|
|
Supply Air Temperature Set Point |
30113 |
— |
1 |
— |
deg C |
1 |
|
|
|
|
|
|
|
Supply Air Temperature Set Point |
30745 |
— |
1 |
— |
deg F |
1 |
|
|
|
|
|
|
|
Free Cooling Fluid Temperature |
30115 |
— |
1 |
10 |
deg C |
1, 2, 3, 4, 5, 6 |
|
|
|
|
|
|
|
Free Cooling Fluid Temperature |
30746 |
— |
1 |
10 |
deg F |
1, 2, 3, 4, 5, 6 |
|
|
|
|
|
|
|
Ext Air Sensor A Temperature |
30116 |
— |
1 |
10 |
deg C |
1, 2, 3, 4, 5, 6 |
|
|
|
|
|
|
|
Ext Air Sensor A Temperature |
30747 |
— |
1 |
10 |
deg F |
1, 2, 3, 4, 5, 6 |
|
|
|
|
|
|
|
Ext Air Sensor B Temperature |
30117 |
— |
1 |
10 |
deg C |
1, 2, 3, 4, 5, 6 |
|
|
|
|
|
|
|
Ext Air Sensor B Temperature |
30748 |
— |
1 |
10 |
deg F |
1, 2, 3, 4, 5, 6 |
|
|
|
|
|
|
|
Ext Air Sensor C Temperature |
30118 |
— |
1 |
10 |
deg C |
1, 2, 3, 4, 5, 6 |
|
|
|
|
|
|
|
Ext Air Sensor C Temperature |
30749 |
— |
1 |
10 |
deg F |
1, 2, 3, 4, 5, 6 |
|
|
|
|
|
|
|
Dig Scroll Comp Discharge Temp 1 |
30119 |
— |
1 |
— |
deg C |
1, 2, 3, 4, 5, 6 |
|
|
|
|
|
|
|
Dig Scroll Comp Discharge Temp 1 |
30750 |
— |
1 |
— |
deg F |
1, 2, 3, 4, 5, 6 |
|
|
|
|
|
|
|
Dig Scroll Comp Discharge Temp 2 |
30120 |
— |
1 |
— |
deg C |
1, 2, 3, 4, 5, 6 |
|
|
|
|
|
|
|
Liebert® IntelliSlot® Modbus/BACnet IP |
14 |
Modbus 485 and Modbus IP Protocols - Thermal Management Products
Table 8 Liebert Challenger 3000™, Liebert Challenger ITR™, Liebert CW™, Liebert Deluxe System/3™, Liebert DS™, Liebert DSE™, Liebert HPM™, Liebert PeX™ - Input and Holding (continued)
Controller |
Liebert iCOM v4 |
|
|
|
|
||
|
|
|
|
|
|
|
|
|
Input |
Holding |
# of |
|
|
Extra |
|
Data Label |
Register |
Register |
Reg. |
Scale |
Notes / Units |
Notes |
|
Dig Scroll Comp Discharge Temp 2 |
30751 |
— |
1 |
— |
deg F |
1, 2, 3, 4, 5, 6 |
|
|
|
|
|
|
|
|
|
Return Humidity |
30130 |
— |
1 |
10 |
% RH |
1, 2, 3, 4, 5, 6 |
|
|
|
|
|
|
|
|
|
Ext Air Sensor A Humidity |
30132 |
— |
1 |
10 |
% RH |
1, 2, 3, 4, 5, 6 |
|
|
|
|
|
|
|
|
|
Ext Air Sensor B Humidity |
30133 |
— |
1 |
10 |
% RH |
1, 2, 3, 4, 5, 6 |
|
|
|
|
|
|
|
|
|
Ext Air Sensor C Humidity |
30134 |
— |
1 |
10 |
% RH |
1, 2, 3, 4, 5, 6 |
|
|
|
|
|
|
|
|
|
Fan Hours |
30141 |
40141 |
1 |
— |
hr |
1, 2, 3, 4, 5, 6 |
|
|
|
|
|
|
|
|
|
Compressor Hours 1 |
30142 |
40142 |
1 |
— |
hr |
1, 2, 3, 4, 5, 6 |
|
|
|
|
|
|
|
|
|
Compressor Hours 2 |
30143 |
40143 |
1 |
— |
hr |
1, 2, 3, 4, 5, 6 |
|
|
|
|
|
|
|
|
|
Humidifier Hours |
30144 |
40144 |
1 |
— |
hr |
1, 2, 3, 4, 5, 6 |
|
|
|
|
|
|
|
|
|
Dehumidifier Hours |
30145 |
40145 |
1 |
— |
hr |
1, 2, 3, 4, 5, 6 |
|
|
|
|
|
|
|
|
|
Free Cooling Valve Hours |
30146 |
40146 |
1 |
— |
hr |
1, 2, 3, 4, 5, 6 |
|
|
|
|
|
|
|
|
|
Electric Reheater Hours 1 |
30147 |
40147 |
1 |
— |
hr |
1, 2, 3, 4, 5, 6 |
|
|
|
|
|
|
|
|
|
Electric Reheater Hours 2 |
30148 |
40148 |
1 |
— |
hr |
1, 2, 3, 4, 5, 6 |
|
|
|
|
|
|
|
|
|
Electric Reheater Hours 3 |
30149 |
40149 |
1 |
— |
hr |
1, 2, 3, 4, 5, 6 |
|
|
|
|
|
|
|
|
|
Hot Water / Hot Gas Valve Hours |
30150 |
40150 |
1 |
— |
hr |
1, 2, 3, 4, 5, 6 |
|
|
|
|
|
|
|
|
|
Today's High Air Temperature |
30151 |
— |
1 |
10 |
deg C |
1, 2, 3, 4, 5, 6 |
|
|
|
|
|
|
|
|
|
Today's High Air Temperature |
30752 |
— |
1 |
10 |
deg F |
1, 2, 3, 4, 5, 6 |
|
|
|
|
|
|
|
|
|
Today's Low Air Temperature |
30153 |
— |
1 |
10 |
deg C |
1, 2, 3, 4, 5, 6 |
|
|
|
|
|
|
|
|
|
Today's Low Air Temperature |
30753 |
— |
1 |
10 |
deg F |
1, 2, 3, 4, 5, 6 |
|
|
|
|
|
|
|
|
|
Today's High Humidity |
30155 |
— |
1 |
10 |
% RH |
1, 2, 3, 4, 5, 6 |
|
|
|
|
|
|
|
|
|
Today's Low Humidity |
30157 |
— |
1 |
10 |
% RH |
1, 2, 3, 4, 5, 6 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
1 = UPS |
|
|
Server Class |
30257 |
— |
1 |
— |
2 = AIR |
1, 2, 3, 4, 5, 6 |
|
3 = PMP |
|||||||
|
|
|
|
|
|
||
|
|
|
|
|
4 = PDU |
|
|
|
|
|
|
|
|
|
|
Today's High Air Temperature Time |
30258 |
— |
2 |
- |
Seconds since Midnight |
1, 2, 3, 4, 5, 6 |
|
|
|
|
|
|
|
|
|
Today's Low Air Temperature Time |
30260 |
— |
2 |
- |
Seconds since Midnight |
1, 2, 3, 4, 5, 6 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
0 = Disabled |
|
|
Supply Air Temperature Sensor Control |
30262 |
40262 |
1 |
— |
1 = Limit |
1 |
|
2 = Control |
|||||||
|
|
|
|
|
|
||
|
|
|
|
|
3 = Temp Only |
|
|
|
|
|
|
|
|
|
|
Return Air Temperature Set Point |
30263 |
40263 |
1 |
— |
deg C |
1 |
|
|
|
|
|
|
|
|
|
Return Air Temperature Set Point |
30754 |
40754 |
1 |
— |
deg F |
1 |
|
|
|
|
|
|
|
|
|
Return Humidity Set Point |
30264 |
40264 |
1 |
— |
% RH |
1 |
|
|
|
|
|
|
|
|
|
Today's High Humidity Time |
30265 |
— |
2 |
— |
Seconds since Midnight |
1, 2, 3, 4, 5, 6 |
|
|
|
|
|
|
|
|
|
Today's Low Humidity Time |
30267 |
— |
2 |
— |
Seconds since Midnight |
1, 2, 3, 4, 5, 6 |
|
|
|
|
|
|
|
|
|
Fixed Compressor State 1 |
30269 |
— |
1 |
— |
0 = off |
1, 2, 3, 4, 5, 6 |
|
1 = on |
|||||||
|
|
|
|
|
|
||
Fixed Compressor State 2 |
30270 |
— |
1 |
— |
0 = off |
1, 2, 3, 4, 5, 6 |
|
1 = on |
|||||||
|
|
|
|
|
|
||
Compressor Capacity Control State 1 |
30271 |
— |
1 |
— |
0 = off |
1, 2, 3, 4, 5, 6 |
|
1 = on |
|||||||
|
|
|
|
|
|
||
Compressor Capacity Control State 2 |
30272 |
— |
1 |
— |
0 = off |
1, 2, 3, 4, 5, 6 |
|
1 = on |
|||||||
|
|
|
|
|
|
15 |
Liebert® IntelliSlot® Modbus/BACnet IP |
Modbus 485 and Modbus IP Protocols - Thermal Management Products
Table 8 Liebert Challenger 3000™, Liebert Challenger ITR™, Liebert CW™, Liebert Deluxe System/3™, Liebert DS™, Liebert DSE™, Liebert HPM™, Liebert PeX™ - Input and Holding (continued)
Controller |
Liebert iCOM v4 |
|
|
|
|
||
|
|
|
|
|
|
|
|
|
Input |
Holding |
# of |
|
|
Extra |
|
Data Label |
Register |
Register |
Reg. |
Scale |
Notes / Units |
Notes |
|
Infrared Humidifier Flush Rate |
30273 |
40273 |
1 |
— |
% |
1, 2, 3, 4, 5, 6 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
0 = Auto |
|
|
Fan Control Mode |
30274 |
40274 |
1 |
— |
1 = Manual |
1 |
|
2 = Economy |
|||||||
|
|
|
|
|
|
||
|
|
|
|
|
4 = Delta |
|
|
|
|
|
|
|
|
|
|
Analog Input Reading 1 |
30275 |
— |
1 |
100 |
— |
1, 2, 3, 4, 5, 6 |
|
|
|
|
|
|
|
|
|
Analog Input Reading 2 |
30276 |
— |
1 |
100 |
— |
1, 2, 3, 4, 5, 6 |
|
|
|
|
|
|
|
|
|
Analog Input Reading 3 |
30277 |
— |
1 |
100 |
— |
1, 2, 3, 4, 5, 6 |
|
|
|
|
|
|
|
|
|
Analog Input Reading 4 |
30278 |
— |
1 |
100 |
— |
1, 2, 3, 4, 5, 6 |
|
|
|
|
|
|
|
|
|
System Control Mode |
30280 |
— |
1 |
— |
0 = Internal (Auto) |
1, 2, 3, 4, 5, 6 |
|
1 = External (Manual) |
|||||||
|
|
|
|
|
|
||
|
|
|
|
|
0 = Reason Unknown |
|
|
|
|
|
|
|
1 = Network Display |
|
|
|
|
|
|
|
2 = Alarm |
|
|
System Operating State Reason |
30281 |
— |
1 |
— |
3 = Schedule |
1, 2, 3, 4, 5, 6 |
|
|
|
|
|
|
4 = Remote System |
|
|
|
|
|
|
|
5 = External Input |
|
|
|
|
|
|
|
6 = Local Display |
|
|
Maintenance Ramp |
30282 |
— |
1 |
— |
% |
1, 2, 3, 4, 5, 6 |
|
|
|
|
|
|
|
|
|
Calculated Next Maintenance Month |
30283 |
— |
1 |
— |
|
1, 2, 3, 4, 5, 6 |
|
|
|
|
|
|
|
|
|
Calculated Next Maintenance Year |
30284 |
— |
1 |
— |
|
1, 2, 3, 4, 5, 6 |
|
|
|
|
|
|
|
|
|
Hot Water / Hot Gas Valve Open Position |
30285 |
— |
1 |
— |
% |
1, 2, 3, 4, 5, 6 |
|
|
|
|
|
|
|
|
|
Maintenance Tracking State |
30286 |
— |
1 |
— |
0 = off |
1, 2, 3, 4, 5, 6 |
|
1 = on |
|||||||
|
|
|
|
|
|
||
Customer Input 1 - Event Control |
30287 |
40287 |
1 |
— |
0 = disabled |
1, 2, 3, 4, 5, 6 |
|
1 = enabled |
|||||||
|
|
|
|
|
|
||
|
|
|
|
|
0 = Message |
|
|
Customer Input 1 - Event Type |
30288 |
40288 |
1 |
— |
1 = Warning |
1, 2, 3, 4, 5, 6 |
|
|
|
|
|
|
2 = Alarm |
|
|
Customer Input 2 - Event Control |
30289 |
40289 |
1 |
— |
0 = disabled |
1, 2, 3, 4, 5, 6 |
|
1 = enabled |
|||||||
|
|
|
|
|
|
||
|
|
|
|
|
0 = Message |
|
|
Customer Input 2 - Event Type |
30290 |
40290 |
1 |
— |
1 = Warning |
1, 2, 3, 4, 5, 6 |
|
|
|
|
|
|
2 = Alarm |
|
|
Customer Input 3 - Event Control |
30291 |
40291 |
1 |
— |
0 = disabled |
1, 2, 3, 4, 5, 6 |
|
1 = enabled |
|||||||
|
|
|
|
|
|
||
|
|
|
|
|
0 = Message |
|
|
Customer Input 3 - Event Type |
30292 |
40292 |
1 |
— |
1 = Warning |
1, 2, 3, 4, 5, 6 |
|
|
|
|
|
|
2 = Alarm |
|
|
Customer Input 4 - Event Control |
30293 |
40293 |
1 |
— |
0 = disabled |
1, 2, 3, 4, 5, 6 |
|
1 = enabled |
|||||||
|
|
|
|
|
|
||
|
|
|
|
|
0 = Message |
|
|
Customer Input 4 - Event Type |
30294 |
40294 |
1 |
— |
1 = Warning |
1, 2, 3, 4, 5, 6 |
|
|
|
|
|
|
2 = Alarm |
|
|
Ext Free Cooling Lockout - Event Control |
30295 |
40295 |
1 |
— |
0 = disabled |
1, 2, 3, 4, 5, 6 |
|
1 = enabled |
|||||||
|
|
|
|
|
|
||
|
|
|
|
|
0 = Message |
|
|
Ext Free Cooling Lockout - Event Type |
30296 |
40296 |
1 |
— |
1 = Warning |
1, 2, 3, 4, 5, 6 |
|
|
|
|
|
|
2 = Alarm |
|
Liebert® IntelliSlot® Modbus/BACnet IP |
16 |
Modbus 485 and Modbus IP Protocols - Thermal Management Products
Table 8 Liebert Challenger 3000™, Liebert Challenger ITR™, Liebert CW™, Liebert Deluxe System/3™, Liebert DS™, Liebert DSE™, Liebert HPM™, Liebert PeX™ - Input and Holding (continued)
Controller |
Liebert iCOM v4 |
|
|
|
|
||
|
|
|
|
|
|
|
|
|
Input |
Holding |
# of |
|
|
Extra |
|
Data Label |
Register |
Register |
Reg. |
Scale |
Notes / Units |
Notes |
|
Ext Condenser Pump High Water - Event |
30297 |
40297 |
1 |
— |
0 = disabled |
1, 2, 3, 4, 5, 6 |
|
Control |
1 = enabled |
||||||
|
|
|
|
|
|||
Ext Condenser Pump High Water - Event |
|
|
|
|
0 = Message |
|
|
30298 |
40298 |
1 |
— |
1 = Warning |
1, 2, 3, 4, 5, 6 |
||
Type |
|||||||
|
|
|
|
2 = Alarm |
|
||
|
|
|
|
|
|
||
|
|
|
|
|
|
|
|
Ext Standby Glycol Pump On - Event |
30299 |
40299 |
1 |
— |
0 = disabled |
1, 2, 3, 4, 5, 6 |
|
Control |
1 = enabled |
||||||
|
|
|
|
|
|||
|
|
|
|
|
0 = Message |
|
|
Ext Standby Glycol Pump On - Event Type |
30300 |
40300 |
1 |
— |
1 = Warning |
1, 2, 3, 4, 5, 6 |
|
|
|
|
|
|
2 = Alarm |
|
|
Ext Standby Unit On - Event Control |
30301 |
40301 |
1 |
— |
0 = disabled |
1, 2, 3, 4, 5, 6 |
|
1 = enabled |
|||||||
|
|
|
|
|
|
||
|
|
|
|
|
0 = Message |
|
|
Ext Standby Unit On - Event Type |
30302 |
40302 |
1 |
— |
1 = Warning |
1, 2, 3, 4, 5, 6 |
|
|
|
|
|
|
2 = Alarm |
|
|
Ext Humidifier Lockout - Event Control |
30303 |
40303 |
1 |
— |
0 = disabled |
1, 2, 3, 4, 5, 6 |
|
1 = enabled |
|||||||
|
|
|
|
|
|
||
|
|
|
|
|
0 = Message |
|
|
Ext Humidifier Lockout - Event Type |
30304 |
40304 |
1 |
— |
1 = Warning |
1, 2, 3, 4, 5, 6 |
|
|
|
|
|
|
2 = Alarm |
|
|
Ext Loss of Flow - Event Control |
30305 |
40305 |
1 |
— |
0 = disabled |
1, 2, 3, 4, 5, 6 |
|
1 = enabled |
|||||||
|
|
|
|
|
|
||
|
|
|
|
|
0 = Message |
|
|
Ext Loss of Flow - Event Type |
30306 |
40306 |
1 |
— |
1 = Warning |
1, 2, 3, 4, 5, 6 |
|
|
|
|
|
|
2 = Alarm |
|
|
Ext Over Temperature - Event Control |
30307 |
40307 |
1 |
— |
0 = disabled |
1, 2, 3, 4, 5, 6 |
|
1 = enabled |
|||||||
|
|
|
|
|
|
||
|
|
|
|
|
0 = Message |
|
|
Ext Over Temperature - Event Type |
30308 |
40308 |
1 |
— |
1 = Warning |
1, 2, 3, 4, 5, 6 |
|
|
|
|
|
|
2 = Alarm |
|
|
Ext Reheat Lockout - Event Control |
30309 |
40309 |
1 |
— |
0 = disabled |
1, 2, 3, 4, 5, 6 |
|
1 = enabled |
|||||||
|
|
|
|
|
|
||
|
|
|
|
|
0 = Message |
|
|
Ext Reheat Lockout - Event Type |
30310 |
40310 |
1 |
— |
1 = Warning |
1, 2, 3, 4, 5, 6 |
|
|
|
|
|
|
2 = Alarm |
|
|
High Power Shutdown - Event Control |
30311 |
40311 |
1 |
— |
0 = disabled |
1, 2, 3, 4, 5, 6 |
|
1 = enabled |
|||||||
|
|
|
|
|
|
||
|
|
|
|
|
0 = Message |
|
|
High Power Shutdown - Event Type |
30312 |
40312 |
1 |
— |
1 = Warning |
1, 2, 3, 4, 5, 6 |
|
|
|
|
|
|
2 = Alarm |
|
|
Humidifier Issue - Event Control |
30313 |
40313 |
1 |
— |
0 = disabled |
1, 2, 3, 4, 5, 6 |
|
1 = enabled |
|||||||
|
|
|
|
|
|
||
|
|
|
|
|
0 = Message |
|
|
Humidifier Issue - Event Type |
30314 |
40314 |
1 |
— |
1 = Warning |
1, 2, 3, 4, 5, 6 |
|
|
|
|
|
|
2 = Alarm |
|
|
Master Unit Communication Lost - Event |
30315 |
40315 |
1 |
— |
0 = disabled |
1, 2, 3, 4, 5, 6 |
|
Control |
1 = enabled |
||||||
|
|
|
|
|
|||
Master Unit Communication Lost - Event |
|
|
|
|
0 = Message |
|
|
30316 |
40316 |
1 |
— |
1 = Warning |
1, 2, 3, 4, 5, 6 |
||
Type |
|||||||
|
|
|
|
2 = Alarm |
|
||
|
|
|
|
|
|
||
|
|
|
|
|
|
|
17 |
Liebert® IntelliSlot® Modbus/BACnet IP |
Modbus 485 and Modbus IP Protocols - Thermal Management Products
Table 8 Liebert Challenger 3000™, Liebert Challenger ITR™, Liebert CW™, Liebert Deluxe System/3™, Liebert DS™, Liebert DSE™, Liebert HPM™, Liebert PeX™ - Input and Holding (continued)
Controller |
Liebert iCOM v4 |
|
|
|
|
||
|
|
|
|
|
|
|
|
|
Input |
Holding |
# of |
|
|
Extra |
|
Data Label |
Register |
Register |
Reg. |
Scale |
Notes / Units |
Notes |
|
Service Required - Event Control |
30317 |
40317 |
1 |
— |
0 = disabled |
1, 2, 3, 4, 5, 6 |
|
1 = enabled |
|||||||
|
|
|
|
|
|
||
|
|
|
|
|
0 = Message |
|
|
Service Required - Event Type |
30318 |
40318 |
1 |
— |
1 = Warning |
1, 2, 3, 4, 5, 6 |
|
|
|
|
|
|
2 = Alarm |
|
|
Shutdown - Loss Of Power - Event Control |
30319 |
40319 |
1 |
— |
0 = disabled |
1, 2, 3, 4, 5, 6 |
|
1 = enabled |
|||||||
|
|
|
|
|
|
||
|
|
|
|
|
0 = Message |
|
|
Shutdown - Loss Of Power - Event Type |
30320 |
40320 |
1 |
— |
1 = Warning |
1, 2, 3, 4, 5, 6 |
|
|
|
|
|
|
2 = Alarm |
|
|
Smoke Detected - Event Control |
30321 |
40321 |
1 |
— |
0 = disabled |
1, 2, 3, 4, 5, 6 |
|
1 = enabled |
|||||||
|
|
|
|
|
|
||
|
|
|
|
|
0 = Message |
|
|
Smoke Detected - Event Type |
30322 |
40322 |
1 |
— |
1 = Warning |
1, 2, 3, 4, 5, 6 |
|
|
|
|
|
|
2 = Alarm |
|
|
Water Under Floor - Event Control |
30323 |
40323 |
1 |
— |
0 = disabled |
1, 2, 3, 4, 5, 6 |
|
1 = enabled |
|||||||
|
|
|
|
|
|
||
|
|
|
|
|
0 = Message |
|
|
Water Under Floor - Event Type |
30324 |
40324 |
1 |
— |
1 = Warning |
1, 2, 3, 4, 5, 6 |
|
|
|
|
|
|
2 = Alarm |
|
|
Ext Compressor Lockout - Event Control |
30325 |
40325 |
1 |
— |
0 = disabled |
1, 2, 3, 4, 5, 6 |
|
1 = enabled |
|||||||
|
|
|
|
|
|
||
|
|
|
|
|
0 = Message |
|
|
Ext Compressor Lockout - Event Type |
30326 |
40326 |
1 |
— |
1 = Warning |
1, 2, 3, 4, 5, 6 |
|
|
|
|
|
|
2 = Alarm |
|
|
Clogged Air Filter - Event Control |
30327 |
40327 |
1 |
— |
0 = disabled |
1, 2, 3, 4, 5, 6 |
|
1 = enabled |
|||||||
|
|
|
|
|
|
||
|
|
|
|
|
0 = Message |
|
|
Clogged Air Filter - Event Type |
30328 |
40328 |
1 |
— |
1 = Warning |
1, 2, 3, 4, 5, 6 |
|
|
|
|
|
|
2 = Alarm |
|
|
Ext Loss of Air Blower - Event Control |
30329 |
40329 |
1 |
— |
0 = disabled |
1, 2, 3, 4, 5, 6 |
|
1 = enabled |
|||||||
|
|
|
|
|
|
||
|
|
|
|
|
0 = Message |
|
|
Ext Loss of Air Blower - Event Type |
30330 |
40330 |
1 |
— |
1 = Warning |
1, 2, 3, 4, 5, 6 |
|
|
|
|
|
|
2 = Alarm |
|
|
Compressor High Head Pressure - Event |
30331 |
40331 |
1 |
— |
0 = disabled |
1, 2, 3, 4, 5, 6 |
|
Control 1 |
1 = enabled |
||||||
|
|
|
|
|
|||
Compressor High Head Pressure - Event |
30332 |
40332 |
1 |
— |
0 = disabled |
1, 2, 3, 4, 5, 6 |
|
Control 2 |
1 = enabled |
||||||
|
|
|
|
|
|||
Compressor High Head Pressure - Event |
|
|
|
|
0 = Message |
|
|
30333 |
40333 |
1 |
— |
1 = Warning |
1, 2, 3, 4, 5, 6 |
||
Type 1 |
|||||||
|
|
|
|
2 = Alarm |
|
||
|
|
|
|
|
|
||
|
|
|
|
|
|
|
|
Compressor High Head Pressure - Event |
|
|
|
|
0 = Message |
|
|
30334 |
40334 |
1 |
— |
1 = Warning |
1, 2, 3, 4, 5, 6 |
||
Type 2 |
|||||||
|
|
|
|
2 = Alarm |
|
||
|
|
|
|
|
|
||
|
|
|
|
|
|
|
|
Compressor Low Suction Pressure - Event |
30335 |
40335 |
1 |
— |
0 = disabled |
1, 2, 3, 4, 5, 6 |
|
Control 1 |
1 = enabled |
||||||
|
|
|
|
|
|||
Compressor Low Suction Pressure - Event |
30336 |
40336 |
1 |
— |
0 = disabled |
1, 2, 3, 4, 5, 6 |
|
Control 2 |
1 = enabled |
||||||
|
|
|
|
|
Liebert® IntelliSlot® Modbus/BACnet IP |
18 |
Modbus 485 and Modbus IP Protocols - Thermal Management Products
Table 8 Liebert Challenger 3000™, Liebert Challenger ITR™, Liebert CW™, Liebert Deluxe System/3™, Liebert DS™, Liebert DSE™, Liebert HPM™, Liebert PeX™ - Input and Holding (continued)
Controller |
Liebert iCOM v4 |
|
|
|
|
||
|
|
|
|
|
|
|
|
|
Input |
Holding |
# of |
|
|
Extra |
|
Data Label |
Register |
Register |
Reg. |
Scale |
Notes / Units |
Notes |
|
Compressor Low Suction Pressure - Event |
|
|
|
|
0 = Message |
|
|
30337 |
40337 |
1 |
— |
1 = Warning |
1, 2, 3, 4, 5, 6 |
||
Type 1 |
|||||||
|
|
|
|
2 = Alarm |
|
||
|
|
|
|
|
|
||
|
|
|
|
|
|
|
|
Compressor Low Suction Pressure - Event |
|
|
|
|
0 = Message |
|
|
30338 |
40338 |
1 |
— |
1 = Warning |
1, 2, 3, 4, 5, 6 |
||
Type 2 |
|||||||
|
|
|
|
2 = Alarm |
|
||
|
|
|
|
|
|
||
|
|
|
|
|
|
|
|
Compressor Pump Down Issue - Event |
30339 |
40339 |
1 |
— |
0 = disabled |
1, 2, 3, 4, 5, 6 |
|
Control 1 |
1 = enabled |
||||||
|
|
|
|
|
|||
Compressor Pump Down Issue - Event |
30340 |
40340 |
1 |
— |
0 = disabled |
1, 2, 3, 4, 5, 6 |
|
Control 2 |
1 = enabled |
||||||
|
|
|
|
|
|||
Compressor Pump Down Issue - Event |
|
|
|
|
0 = Message |
|
|
30341 |
40341 |
1 |
— |
1 = Warning |
1, 2, 3, 4, 5, 6 |
||
Type 1 |
|||||||
|
|
|
|
2 = Alarm |
|
||
|
|
|
|
|
|
||
|
|
|
|
|
|
|
|
Compressor Pump Down Issue - Event |
|
|
|
|
0 = Message |
|
|
30342 |
40342 |
1 |
— |
1 = Warning |
1, 2, 3, 4, 5, 6 |
||
Type 2 |
|||||||
|
|
|
|
2 = Alarm |
|
||
|
|
|
|
|
|
||
|
|
|
|
|
|
|
|
Compressor Short Cycle - Event Control 1 |
30343 |
40343 |
1 |
— |
0 = disabled |
1, 2, 3, 4, 5, 6 |
|
1 = enabled |
|||||||
|
|
|
|
|
|
||
Compressor Short Cycle - Event Control 2 |
30344 |
40344 |
1 |
— |
0 = disabled |
1, 2, 3, 4, 5, 6 |
|
1 = enabled |
|||||||
|
|
|
|
|
|
||
|
|
|
|
|
0 = Message |
|
|
Compressor Short Cycle - Event Type 1 |
30345 |
40345 |
1 |
— |
1 = Warning |
1, 2, 3, 4, 5, 6 |
|
|
|
|
|
|
2 = Alarm |
|
|
|
|
|
|
|
0 = Message |
|
|
Compressor Short Cycle - Event Type 2 |
30346 |
40346 |
1 |
— |
1 = Warning |
1, 2, 3, 4, 5, 6 |
|
|
|
|
|
|
2 = Alarm |
|
|
Compressor Thermal Overload - Event |
30347 |
40347 |
1 |
— |
0 = disabled |
1, 2, 3, 4, 5, 6 |
|
Control 1 |
1 = enabled |
||||||
|
|
|
|
|
|||
Compressor Thermal Overload - Event |
30348 |
40348 |
1 |
— |
0 = disabled |
1, 2, 3, 4, 5, 6 |
|
Control 2 |
1 = enabled |
||||||
|
|
|
|
|
|||
Compressor Thermal Overload - Event |
|
|
|
|
0 = Message |
|
|
30349 |
40349 |
1 |
— |
1 = Warning |
1, 2, 3, 4, 5, 6 |
||
Type 1 |
|||||||
|
|
|
|
2 = Alarm |
|
||
|
|
|
|
|
|
||
|
|
|
|
|
|
|
|
Compressor Thermal Overload - Event |
|
|
|
|
0 = Message |
|
|
30350 |
40350 |
1 |
— |
1 = Warning |
1, 2, 3, 4, 5, 6 |
||
Type 2 |
|||||||
|
|
|
|
2 = Alarm |
|
||
|
|
|
|
|
|
||
|
|
|
|
|
|
|
|
Dig Scroll Comp Discharge Over Temp - |
30351 |
40351 |
1 |
— |
0 = disabled |
1, 2, 3, 4, 5, 6 |
|
Event Ctrl 1 |
1 = enabled |
||||||
|
|
|
|
|
|||
Dig Scroll Comp Discharge Over Temp - |
30352 |
40352 |
1 |
— |
0 = disabled |
1, 2, 3, 4, 5, 6 |
|
Event Ctrl 2 |
1 = enabled |
||||||
|
|
|
|
|
|||
Dig Scroll Comp Discharge Over Temp - |
|
|
|
|
0 = Message |
|
|
30353 |
40353 |
1 |
— |
1 = Warning |
1, 2, 3, 4, 5, 6 |
||
Event Type 1 |
|||||||
|
|
|
|
2 = Alarm |
|
||
|
|
|
|
|
|
||
|
|
|
|
|
|
|
|
Dig Scroll Comp Discharge Over Temp - |
|
|
|
|
0 = Message |
|
|
30354 |
40354 |
1 |
— |
1 = Warning |
1, 2, 3, 4, 5, 6 |
||
Event Type 2 |
|||||||
|
|
|
|
2 = Alarm |
|
||
|
|
|
|
|
|
||
|
|
|
|
|
|
|
|
Ext Air Sensor A High Humidity - Event |
30355 |
40355 |
1 |
— |
0 = disabled |
1, 2, 3, 4, 5, 6 |
|
Control |
1 = enabled |
||||||
|
|
|
|
|
|||
Ext Air Sensor A High Humidity - Event |
|
|
|
|
0 = Message |
|
|
30356 |
40356 |
1 |
— |
1 = Warning |
1, 2, 3, 4, 5, 6 |
||
Type |
|||||||
|
|
|
|
2 = Alarm |
|
||
|
|
|
|
|
|
||
|
|
|
|
|
|
|
19 |
Liebert® IntelliSlot® Modbus/BACnet IP |
Modbus 485 and Modbus IP Protocols - Thermal Management Products
Table 8 Liebert Challenger 3000™, Liebert Challenger ITR™, Liebert CW™, Liebert Deluxe System/3™, Liebert DS™, Liebert DSE™, Liebert HPM™, Liebert PeX™ - Input and Holding (continued)
Controller |
Liebert iCOM v4 |
|
|
|
|
||
|
|
|
|
|
|
|
|
|
Input |
Holding |
# of |
|
|
Extra |
|
Data Label |
Register |
Register |
Reg. |
Scale |
Notes / Units |
Notes |
|
Ext Air Sensor A Low Humidity - Event |
30357 |
40357 |
1 |
— |
0 = disabled |
1, 2, 3, 4, 5, 6 |
|
Control |
1 = enabled |
||||||
|
|
|
|
|
|||
|
|
|
|
|
0 = Message |
|
|
Ext Air Sensor A Low Humidity - Event Type |
30358 |
40358 |
1 |
— |
1 = Warning |
1, 2, 3, 4, 5, 6 |
|
|
|
|
|
|
2 = Alarm |
|
|
Ext Air Sensor A Over Temp - Event Control |
30359 |
40359 |
1 |
— |
0 = disabled |
1, 2, 3, 4, 5, 6 |
|
1 = enabled |
|||||||
|
|
|
|
|
|
||
|
|
|
|
|
0 = Message |
|
|
Ext Air Sensor A Over Temp - Event Type |
30360 |
40360 |
1 |
— |
1 = Warning |
1, 2, 3, 4, 5, 6 |
|
|
|
|
|
|
2 = Alarm |
|
|
Ext Air Sensor A Under Temp - Event |
30361 |
40361 |
1 |
— |
0 = disabled |
1, 2, 3, 4, 5, 6 |
|
Control |
1 = enabled |
||||||
|
|
|
|
|
|||
|
|
|
|
|
0 = Message |
|
|
Ext Air Sensor A Under Temp - Event Type |
30362 |
40362 |
1 |
— |
1 = Warning |
1, 2, 3, 4, 5, 6 |
|
|
|
|
|
|
2 = Alarm |
|
|
High Return Humidity - Event Control |
30363 |
40363 |
1 |
— |
0 = disabled |
1, 2, 3, 4, 5, 6 |
|
1 = enabled |
|||||||
|
|
|
|
|
|
||
|
|
|
|
|
0 = Message |
|
|
High Return Humidity - Event Type |
30364 |
40364 |
1 |
— |
1 = Warning |
1, 2, 3, 4, 5, 6 |
|
|
|
|
|
|
2 = Alarm |
|
|
Low Return Humidity - Event Control |
30365 |
40365 |
1 |
— |
0 = disabled |
1, 2, 3, 4, 5, 6 |
|
1 = enabled |
|||||||
|
|
|
|
|
|
||
|
|
|
|
|
0 = Message |
|
|
Low Return Humidity - Event Type |
30366 |
40366 |
1 |
— |
1 = Warning |
1, 2, 3, 4, 5, 6 |
|
|
|
|
|
|
2 = Alarm |
|
|
Return Air Over Temp - Event Control |
30367 |
40367 |
1 |
— |
0 = disabled |
1, 2, 3, 4, 5, 6 |
|
1 = enabled |
|||||||
|
|
|
|
|
|
||
|
|
|
|
|
0 = Message |
|
|
Return Air Over Temp - Event Type |
30368 |
40368 |
1 |
— |
1 = Warning |
1, 2, 3, 4, 5, 6 |
|
|
|
|
|
|
2 = Alarm |
|
|
Return Air Under Temp - Event Control |
30369 |
40369 |
1 |
— |
0 = disabled |
1, 2, 3, 4, 5, 6 |
|
1 = enabled |
|||||||
|
|
|
|
|
|
||
|
|
|
|
|
0 = Message |
|
|
Return Air Under Temp - Event Type |
30370 |
40370 |
1 |
— |
1 = Warning |
1, 2, 3, 4, 5, 6 |
|
|
|
|
|
|
2 = Alarm |
|
|
Fan Hours Exceeded - Event Control |
30371 |
40371 |
1 |
— |
0 = disabled |
1, 2, 3, 4, 5, 6 |
|
1 = enabled |
|||||||
|
|
|
|
|
|
||
|
|
|
|
|
0 = Message |
|
|
Fan Hours Exceeded - Event Type |
30372 |
40372 |
1 |
— |
1 = Warning |
1, 2, 3, 4, 5, 6 |
|
|
|
|
|
|
2 = Alarm |
|
|
Fan Issue - Event Control |
30373 |
40373 |
1 |
— |
0 = disabled |
1 |
|
1 = enabled |
|||||||
|
|
|
|
|
|
||
|
|
|
|
|
0 = Message |
|
|
Fan Issue - Event Type |
30374 |
40374 |
1 |
— |
1 = Warning |
1 |
|
|
|
|
|
|
2 = Alarm |
|
|
Main Fan Overload - Event Control |
30375 |
40375 |
1 |
— |
0 = disabled |
1, 2, 3, 4, 5, 6 |
|
1 = enabled |
|||||||
|
|
|
|
|
|
||
|
|
|
|
|
0 = Message |
|
|
Main Fan Overload - Event Type |
30376 |
40376 |
1 |
— |
1 = Warning |
1, 2, 3, 4, 5, 6 |
|
|
|
|
|
|
2 = Alarm |
|
Liebert® IntelliSlot® Modbus/BACnet IP |
20 |
Modbus 485 and Modbus IP Protocols - Thermal Management Products
Table 8 Liebert Challenger 3000™, Liebert Challenger ITR™, Liebert CW™, Liebert Deluxe System/3™, Liebert DS™, Liebert DSE™, Liebert HPM™, Liebert PeX™ - Input and Holding (continued)
Controller |
Liebert iCOM v4 |
|
|
|
|
||
|
|
|
|
|
|
|
|
|
Input |
Holding |
# of |
|
|
Extra |
|
Data Label |
Register |
Register |
Reg. |
Scale |
Notes / Units |
Notes |
|
Condenser Issue - Event Control 1 |
30377 |
40377 |
1 |
— |
0 = disabled |
1, 2, 3, 4, 5, 6 |
|
1 = enabled |
|||||||
|
|
|
|
|
|
||
Condenser Issue - Event Control 2 |
30378 |
40378 |
1 |
— |
0 = disabled |
1, 2, 3, 4, 5, 6 |
|
1 = enabled |
|||||||
|
|
|
|
|
|
||
|
|
|
|
|
0 = Message |
|
|
Condenser Issue - Event Type 1 |
30379 |
40379 |
1 |
— |
1 = Warning |
1, 2, 3, 4, 5, 6 |
|
|
|
|
|
|
2 = Alarm |
|
|
|
|
|
|
|
0 = Message |
|
|
Condenser Issue - Event Type 2 |
30380 |
40380 |
1 |
— |
1 = Warning |
1, 2, 3, 4, 5, 6 |
|
|
|
|
|
|
2 = Alarm |
|
|
System Event Acknowledge/Reset |
— |
40381 |
1 |
— |
2 = Reset |
1, 2, 3, 4, 5, 6 |
|
4 = Acknowledge |
|||||||
|
|
|
|
|
|
||
|
|
|
|
|
0 = Supply |
|
|
Air Temperature Control Sensor |
30481 |
40481 |
1 |
— |
1 = Remote |
2, 3, 4, 5, 6 |
|
|
|
|
|
|
2 = Return |
|
|
Supply Air Over Temp Threshold |
30482 |
40482 |
1 |
10 |
deg C |
2, 3, 4, 5, 6 |
|
|
|
|
|
|
|
|
|
Supply Air Over Temp Threshold |
30755 |
40755 |
1 |
10 |
deg F |
2, 3, 4, 5, 6 |
|
|
|
|
|
|
|
|
|
Supply Air Under Temp Threshold |
30483 |
40483 |
1 |
10 |
deg C |
2, 3, 4, 5, 6 |
|
|
|
|
|
|
|
|
|
Supply Air Under Temp Threshold |
30756 |
40756 |
1 |
10 |
deg F |
2, 3, 4, 5, 6 |
|
|
|
|
|
|
|
|
|
Outside Air Temperature |
30484 |
— |
1 |
10 |
deg C |
2, 3, 4, 5, 6 |
|
|
|
|
|
|
|
|
|
Outside Air Temperature |
30757 |
— |
1 |
10 |
deg F |
2, 3, 4, 5, 6 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
0 = Relative |
|
|
Humidity Proportional Control Type |
30485 |
40485 |
1 |
— |
1 = Compensated |
2, 3, 4, 5, 6 |
|
2 = Predictive |
|||||||
|
|
|
|
|
|
||
|
|
|
|
|
3 = Dew Point |
|
|
|
|
|
|
|
|
|
|
Ext Air Sensor A Dew Point Temp |
30486 |
- |
1 |
10 |
deg C |
2, 3, 4, 5, 6 |
|
|
|
|
|
|
|
|
|
Ext Air Sensor A Dew Point Temp |
30758 |
- |
1 |
10 |
deg F |
2, 3, 4, 5, 6 |
|
|
|
|
|
|
|
|
|
Ext Dew Point Over Temp Threshold |
30487 |
40487 |
1 |
10 |
deg C |
2, 3, 4, 5, 6 |
|
|
|
|
|
|
|
|
|
Ext Dew Point Over Temp Threshold |
30759 |
40759 |
1 |
10 |
deg F |
2, 3, 4, 5, 6 |
|
|
|
|
|
|
|
|
|
Ext Dew Point Under Temp Threshold |
30488 |
40488 |
1 |
10 |
deg C |
2, 3, 4, 5, 6 |
|
|
|
|
|
|
|
|
|
Ext Dew Point Under Temp Threshold |
30760 |
40760 |
1 |
10 |
deg F |
2, 3, 4, 5, 6 |
|
|
|
|
|
|
|
|
|
Compressor Lockout |
30489 |
40489 |
1 |
— |
0 = disabled |
2, 3, 4, 5, 6 |
|
1 = enabled |
|||||||
|
|
|
|
|
|
||
Main Chilled Water Valve |
30491 |
40491 |
1 |
— |
0 = Valve 1 |
2, 3, 4, 5, 6 |
|
1 = Valve 2 |
|||||||
|
|
|
|
|
|
||
Reheater Lockout |
30492 |
40492 |
1 |
— |
0 = disabled |
2, 3, 4, 5, 6 |
|
1 = enabled |
|||||||
|
|
|
|
|
|
||
Humidifier Lockout |
30493 |
40493 |
1 |
— |
0 = disabled |
2, 3, 4, 5, 6 |
|
1 = enabled |
|||||||
|
|
|
|
|
|
||
|
|
|
|
|
0 = Supply |
|
|
Fan Control Sensor |
30494 |
40494 |
1 |
— |
1 = Remote |
2, 3, 4, 5, 6 |
|
2 = Return |
|||||||
|
|
|
|
|
|
||
|
|
|
|
|
3 = Manual |
|
|
|
|
|
|
|
|
|
|
Fan Speed Minimum Set Point |
30495 |
40495 |
1 |
— |
% |
2, 3, 4, 5, 6 |
|
|
|
|
|
|
|
|
|
Fan Speed Temperature Set Point |
30497 |
40497 |
1 |
10 |
deg C |
2, 3, 4, 5, 6 |
|
|
|
|
|
|
|
|
|
Fan Speed Temperature Set Point |
30761 |
40761 |
1 |
10 |
deg F |
2, 3, 4, 5, 6 |
|
|
|
|
|
|
|
|
|
Standby Units |
30498 |
40498 |
1 |
— |
— |
2, 3, 4, 5, 6 |
|
|
|
|
|
|
|
|
21 |
Liebert® IntelliSlot® Modbus/BACnet IP |
Modbus 485 and Modbus IP Protocols - Thermal Management Products
Table 8 Liebert Challenger 3000™, Liebert Challenger ITR™, Liebert CW™, Liebert Deluxe System/3™, Liebert DS™, Liebert DSE™, Liebert HPM™, Liebert PeX™ - Input and Holding (continued)
Controller |
Liebert iCOM v4 |
|
|
|
|
||
|
|
|
|
|
|
|
|
|
Input |
Holding |
# of |
|
|
Extra |
|
Data Label |
Register |
Register |
Reg. |
Scale |
Notes / Units |
Notes |
|
Adjusted Humidity |
30499 |
— |
1 |
10 |
% RH |
2, 3, 4, 5, 6 |
|
|
|
|
|
|
|
|
|
Return Dew Point |
30500 |
— |
1 |
10 |
deg C |
2, 3, 4, 5, 6 |
|
|
|
|
|
|
|
|
|
Return Dew Point |
30762 |
— |
1 |
10 |
deg F |
2, 3, 4, 5, 6 |
|
|
|
|
|
|
|
|
|
Actual Air Temperature Set Point |
30501 |
— |
1 |
10 |
deg C |
2, 3, 4, 5, 6 |
|
|
|
|
|
|
|
|
|
Actual Air Temperature Set Point |
30763 |
— |
1 |
10 |
deg F |
2, 3, 4, 5, 6 |
|
|
|
|
|
|
|
|
|
Actual Humidity Set Point |
30502 |
— |
1 |
- |
% RH |
2, 3, 4, 5, 6 |
|
|
|
|
|
|
|
|
|
Dew Point Set Point |
30503 |
40503 |
1 |
10 |
deg C |
2, 3, 4, 5, 6 |
|
|
|
|
|
|
|
|
|
Dew Point Set Point |
30764 |
40764 |
1 |
10 |
deg F |
2, 3, 4, 5, 6 |
|
|
|
|
|
|
|
|
|
Supply Air Over/Under Temperature - Event |
30504 |
40504 |
1 |
— |
0 = disabled |
2, 3, 4, 5, 6 |
|
Control |
1 = enabled |
||||||
|
|
|
|
|
|||
Remote Sensor Over Temp Threshold |
30505 |
40505 |
1 |
10 |
deg C |
2, 3, 4, 5, 6 |
|
|
|
|
|
|
|
|
|
Remote Sensor Over Temp Threshold |
30765 |
40765 |
1 |
10 |
deg F |
2, 3, 4, 5, 6 |
|
|
|
|
|
|
|
|
|
Remote Sensor Under Temp Threshold |
30506 |
40506 |
1 |
10 |
deg C |
2, 3, 4, 5, 6 |
|
|
|
|
|
|
|
|
|
Remote Sensor Under Temp Threshold |
30766 |
40766 |
1 |
10 |
deg F |
2, 3, 4, 5, 6 |
|
|
|
|
|
|
|
|
|
Remote Sensor Average Temperature |
30507 |
— |
1 |
10 |
deg C |
2, 3, 4, 5, 6 |
|
|
|
|
|
|
|
|
|
Remote Sensor Average Temperature |
30767 |
— |
1 |
10 |
deg F |
2, 3, 4, 5, 6 |
|
|
|
|
|
|
|
|
|
Remote Sensor Maximum Temperature |
30508 |
— |
1 |
10 |
deg C |
2, 3, 4, 5, 6 |
|
|
|
|
|
|
|
|
|
Remote Sensor Maximum Temperature |
30768 |
— |
1 |
10 |
deg F |
2, 3, 4, 5, 6 |
|
|
|
|
|
|
|
|
|
Remote Sensor System Average |
30509 |
— |
1 |
10 |
deg C |
2, 3, 4, 5, 6 |
|
Temperature |
|||||||
|
|
|
|
|
|
||
Remote Sensor System Average |
30769 |
— |
1 |
10 |
deg F |
2, 3, 4, 5, 6 |
|
Temperature |
|||||||
|
|
|
|
|
|
||
Remote Sensor System Maximum |
30510 |
— |
1 |
10 |
deg C |
2, 3, 4, 5, 6 |
|
Temperature |
|||||||
|
|
|
|
|
|
||
Remote Sensor System Maximum |
30770 |
— |
1 |
10 |
deg F |
2, 3, 4, 5, 6 |
|
Temperature |
|||||||
|
|
|
|
|
|
||
Remote Sensor Temperature 1 |
30551 |
— |
1 |
10 |
deg C |
2, 3, 4, 5, 6 |
|
|
|
|
|
|
|
|
|
Remote Sensor Temperature 1 |
30771 |
— |
1 |
10 |
deg F |
2, 3, 4, 5, 6 |
|
|
|
|
|
|
|
|
|
Remote Sensor Temperature 2 |
30552 |
— |
1 |
10 |
deg C |
2, 3, 4, 5, 6 |
|
|
|
|
|
|
|
|
|
Remote Sensor Temperature 2 |
30772 |
— |
1 |
10 |
deg F |
2, 3, 4, 5, 6 |
|
|
|
|
|
|
|
|
|
Remote Sensor Temperature 3 |
30553 |
— |
1 |
10 |
deg C |
2, 3, 4, 5, 6 |
|
|
|
|
|
|
|
|
|
Remote Sensor Temperature 3 |
30773 |
— |
1 |
10 |
deg F |
2, 3, 4, 5, 6 |
|
|
|
|
|
|
|
|
|
Remote Sensor Temperature 4 |
30554 |
— |
1 |
10 |
deg C |
2, 3, 4, 5, 6 |
|
|
|
|
|
|
|
|
|
Remote Sensor Temperature 4 |
30774 |
— |
1 |
10 |
deg F |
2, 3, 4, 5, 6 |
|
|
|
|
|
|
|
|
|
Remote Sensor Temperature 5 |
30555 |
— |
1 |
10 |
deg C |
2, 3, 4, 5, 6 |
|
|
|
|
|
|
|
|
|
Remote Sensor Temperature 5 |
30775 |
— |
1 |
10 |
deg F |
2, 3, 4, 5, 6 |
|
|
|
|
|
|
|
|
|
Remote Sensor Temperature 6 |
30556 |
— |
1 |
10 |
deg C |
2, 3, 4, 5, 6 |
|
|
|
|
|
|
|
|
|
Remote Sensor Temperature 6 |
30776 |
— |
1 |
10 |
deg F |
2, 3, 4, 5, 6 |
|
|
|
|
|
|
|
|
|
Remote Sensor Temperature 7 |
30557 |
— |
1 |
10 |
deg C |
2, 3, 4, 5, 6 |
|
|
|
|
|
|
|
|
|
Remote Sensor Temperature 7 |
30777 |
— |
1 |
10 |
deg F |
2, 3, 4, 5, 6 |
|
|
|
|
|
|
|
|
|
Remote Sensor Temperature 8 |
30558 |
— |
1 |
10 |
deg C |
2, 3, 4, 5, 6 |
|
|
|
|
|
|
|
|
|
Remote Sensor Temperature 8 |
30778 |
— |
1 |
10 |
deg F |
2, 3, 4, 5, 6 |
|
|
|
|
|
|
|
|
Liebert® IntelliSlot® Modbus/BACnet IP |
22 |
Modbus 485 and Modbus IP Protocols - Thermal Management Products
Table 8 Liebert Challenger 3000™, Liebert Challenger ITR™, Liebert CW™, Liebert Deluxe System/3™, Liebert DS™, Liebert DSE™, Liebert HPM™, Liebert PeX™ - Input and Holding (continued)
Controller |
Liebert iCOM v4 |
|
|
|
|
||
|
|
|
|
|
|
|
|
|
Input |
Holding |
# of |
|
|
Extra |
|
Data Label |
Register |
Register |
Reg. |
Scale |
Notes / Units |
Notes |
|
Remote Sensor Temperature 9 |
30559 |
— |
1 |
10 |
deg C |
2, 3, 4, 5, 6 |
|
|
|
|
|
|
|
|
|
Remote Sensor Temperature 9 |
30779 |
— |
1 |
10 |
deg F |
2, 3, 4, 5, 6 |
|
|
|
|
|
|
|
|
|
Remote Sensor Temperature 10 |
30560 |
— |
1 |
10 |
deg C |
2, 3, 4, 5, 6 |
|
|
|
|
|
|
|
|
|
Remote Sensor Temperature 10 |
30780 |
— |
1 |
10 |
deg F |
2, 3, 4, 5, 6 |
|
|
|
|
|
|
|
|
|
Air Economizer Availability |
30561 |
— |
1 |
— |
0 = Not Available |
2, 3, 4, 5, 6 |
|
1 = Available |
|||||||
|
|
|
|
|
|
||
|
|
|
|
|
0 = disabled |
|
|
Air Economizer Control Source |
30562 |
40562 |
1 |
— |
1 = internal |
2, 3, 4, 5, 6 |
|
|
|
|
|
|
2 = external |
|
|
Chilled Water Valve Hours |
30563 |
40563 |
1 |
— |
hr |
2, 3, 4, 5, 6 |
|
|
|
|
|
|
|
|
|
Cooling Capacity |
30564 |
— |
1 |
— |
% |
2, 3, 4, 5, 6 |
|
|
|
|
|
|
|
|
|
Cooling Control Temperature |
30565 |
— |
1 |
10 |
deg C |
2, 3, 4, 5, 6 |
|
|
|
|
|
|
|
|
|
Cooling Control Temperature |
30781 |
— |
1 |
10 |
deg F |
2, 3, 4, 5, 6 |
|
|
|
|
|
|
|
|
|
Fan Speed Control Temperature |
30566 |
— |
1 |
10 |
deg C |
2, 3, 4, 5, 6 |
|
|
|
|
|
|
|
|
|
Fan Speed Control Temperature |
30782 |
— |
1 |
10 |
deg F |
2, 3, 4, 5, 6 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
0 = Disabled |
|
|
Free Cooling Internal Control Mode |
30567 |
40567 |
1 |
— |
1 = Contact |
2, 3, 4, 5, 6 |
|
2 = Temperature |
|||||||
|
|
|
|
|
|
||
|
|
|
|
|
3 = Set Point |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
0 = Supply |
|
|
Humidity Control Sensor |
30667 |
40667 |
1 |
— |
1 = Remote |
3, 4, 5, 6 |
|
|
|
|
|
|
2 = Return |
|
|
Digital Scroll Compressor Loading 1 |
30668 |
— |
1 |
— |
% |
3, 4, 5, 6 |
|
|
|
|
|
|
|
|
|
Digital Scroll Compressor Loading 2 |
30669 |
— |
1 |
— |
% |
3, 4, 5, 6 |
|
|
|
|
|
|
|
|
|
Static Pressure Set Point |
30672 |
40672 |
1 |
10 |
Pa |
3, 6 |
|
|
|
|
|
|
|
|
|
Unit Static Pressure |
30673 |
— |
1 |
10 |
Pa |
3, 6 |
|
|
|
|
|
|
|
|
|
System Static Pressure |
30674 |
— |
1 |
10 |
Pa |
3, 6 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
0 = Inactive |
|
|
Condenser Low Noise Mode State |
30675 |
— |
1 |
— |
1 = Active (Interval) |
3, 4, 5, 6 |
|
|
|
|
|
|
2 = Active (Full Day) |
|
|
Condenser Low Noise Mode Schedule |
30676 |
40676 |
1 |
— |
0 = disabled |
3, 4, 5, 6 |
|
Control |
1 = enabled |
||||||
|
|
|
|
|
|||
Condenser Low Noise Mode Max Fan |
30677 |
40677 |
1 |
— |
% |
3, 4, 5, 6 |
|
Speed |
|||||||
|
|
|
|
|
|
||
Condenser Normal Mode Max Fan Speed |
30678 |
40678 |
1 |
— |
% |
3, 4, 5, 6 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
1 = Monday |
|
|
|
|
|
|
|
2 = Tuesday |
|
|
|
|
|
|
|
4 = Wednesday |
3, 4, 5, 6 |
|
Condenser Low Noise Mode - Interval Days |
30679 |
40679 |
1 |
— |
8 = Thursday |
||
|
|
|
|
|
16 = Friday |
|
|
|
|
|
|
|
32 = Saturday |
|
|
|
|
|
|
|
64 = Sunday |
|
|
|
|
|
|
|
1 = Monday |
|
|
|
|
|
|
|
2 = Tuesday |
|
|
|
|
|
|
|
4 = Wednesday |
|
|
Condenser Low Noise Mode - Full Days |
30680 |
40680 |
1 |
— |
8 = Thursday |
3, 4, 5, 6 |
|
|
|
|
|
|
16 = Friday |
|
|
|
|
|
|
|
32 = Saturday |
|
|
|
|
|
|
|
64 = Sunday |
|
23 |
Liebert® IntelliSlot® Modbus/BACnet IP |
Modbus 485 and Modbus IP Protocols - Thermal Management Products
Table 8 Liebert Challenger 3000™, Liebert Challenger ITR™, Liebert CW™, Liebert Deluxe System/3™, Liebert DS™, Liebert DSE™, Liebert HPM™, Liebert PeX™ - Input and Holding (continued)
Controller |
Liebert iCOM v4 |
|
|
|
|
|
|
|
|
|
|
|
|
|
Input |
Holding |
# of |
|
|
Extra |
Data Label |
Register |
Register |
Reg. |
Scale |
Notes / Units |
Notes |
Condenser Low Noise Mode Start Time |
30681 |
40681 |
2 |
— |
Seconds since Midnight |
3, 4, 5, 6 |
|
|
|
|
|
|
|
Condenser Low Noise Mode Stop Time |
30683 |
40683 |
2 |
— |
Seconds since Midnight |
3, 4, 5, 6 |
|
|
|
|
|
|
|
Pump Hours 1 |
30685 |
40685 |
2 |
— |
hr |
5 |
|
|
|
|
|
|
|
Pump Hours 2 |
30687 |
40687 |
2 |
— |
hr |
5 |
|
|
|
|
|
|
|
System Input RMS A-N 1 |
30800 |
— |
1 |
10 |
VAC |
6 |
|
|
|
|
|
|
|
System Input RMS A-N 2 |
30801 |
— |
1 |
10 |
VAC |
6 |
|
|
|
|
|
|
|
System Input RMS A-N 3 |
30802 |
— |
1 |
10 |
VAC |
6 |
|
|
|
|
|
|
|
System Input RMS A-N 4 |
30803 |
— |
1 |
10 |
VAC |
6 |
|
|
|
|
|
|
|
System Input RMS A-N 5 |
30804 |
— |
1 |
10 |
VAC |
6 |
|
|
|
|
|
|
|
System Input RMS A-N 6 |
30805 |
— |
1 |
10 |
VAC |
6 |
|
|
|
|
|
|
|
System Input RMS B-N 1 |
30810 |
— |
1 |
10 |
VAC |
6 |
|
|
|
|
|
|
|
System Input RMS B-N 2 |
30811 |
— |
1 |
10 |
VAC |
6 |
|
|
|
|
|
|
|
System Input RMS B-N 3 |
30812 |
— |
1 |
10 |
VAC |
6 |
|
|
|
|
|
|
|
System Input RMS B-N 4 |
30813 |
— |
1 |
10 |
VAC |
6 |
|
|
|
|
|
|
|
System Input RMS B-N 5 |
30814 |
— |
1 |
10 |
VAC |
6 |
|
|
|
|
|
|
|
System Input RMS B-N 6 |
30815 |
— |
1 |
10 |
VAC |
6 |
|
|
|
|
|
|
|
System Input RMS C-N 1 |
30820 |
— |
1 |
10 |
VAC |
6 |
|
|
|
|
|
|
|
System Input RMS C-N 2 |
30821 |
— |
1 |
10 |
VAC |
6 |
|
|
|
|
|
|
|
System Input RMS C-N 3 |
30822 |
— |
1 |
10 |
VAC |
6 |
|
|
|
|
|
|
|
System Input RMS C-N 4 |
30823 |
— |
1 |
10 |
VAC |
6 |
|
|
|
|
|
|
|
System Input RMS C-N 5 |
30824 |
— |
1 |
10 |
VAC |
6 |
|
|
|
|
|
|
|
System Input RMS C-N 6 |
30825 |
— |
1 |
10 |
VAC |
6 |
|
|
|
|
|
|
|
System Input RMS Current Phase A 1 |
30830 |
— |
1 |
10 |
A AC |
6 |
|
|
|
|
|
|
|
System Input RMS Current Phase A 2 |
30831 |
— |
1 |
10 |
A AC |
6 |
|
|
|
|
|
|
|
System Input RMS Current Phase A 3 |
30832 |
— |
1 |
10 |
A AC |
6 |
|
|
|
|
|
|
|
System Input RMS Current Phase A 4 |
30833 |
— |
1 |
10 |
A AC |
6 |
|
|
|
|
|
|
|
System Input RMS Current Phase A 5 |
30834 |
— |
1 |
10 |
A AC |
6 |
|
|
|
|
|
|
|
System Input RMS Current Phase A 6 |
30835 |
— |
1 |
10 |
A AC |
6 |
|
|
|
|
|
|
|
System Input RMS Current Phase B 1 |
30840 |
— |
1 |
10 |
A AC |
6 |
|
|
|
|
|
|
|
System Input RMS Current Phase B 2 |
30841 |
— |
1 |
10 |
A AC |
6 |
|
|
|
|
|
|
|
System Input RMS Current Phase B 3 |
30842 |
— |
1 |
10 |
A AC |
6 |
|
|
|
|
|
|
|
System Input RMS Current Phase B 4 |
30843 |
— |
1 |
10 |
A AC |
6 |
|
|
|
|
|
|
|
System Input RMS Current Phase B 5 |
30844 |
— |
1 |
10 |
A AC |
6 |
|
|
|
|
|
|
|
System Input RMS Current Phase B 6 |
30845 |
— |
1 |
10 |
A AC |
6 |
|
|
|
|
|
|
|
System Input RMS Current Phase C 1 |
30850 |
— |
1 |
10 |
A AC |
6 |
|
|
|
|
|
|
|
System Input RMS Current Phase C 2 |
30851 |
— |
1 |
10 |
A AC |
6 |
|
|
|
|
|
|
|
System Input RMS Current Phase C 3 |
30852 |
— |
1 |
10 |
A AC |
6 |
|
|
|
|
|
|
|
System Input RMS Current Phase C 4 |
30853 |
— |
1 |
10 |
A AC |
6 |
|
|
|
|
|
|
|
System Input RMS Current Phase C 5 |
30854 |
— |
1 |
10 |
A AC |
6 |
|
|
|
|
|
|
|
System Input RMS Current Phase C 6 |
30855 |
— |
1 |
10 |
A AC |
6 |
|
|
|
|
|
|
|
Liebert® IntelliSlot® Modbus/BACnet IP |
24 |