Emerson MODBUS 485, BACNET IP, MODBUS IP User Manual

4 (1)
Emerson MODBUS 485, BACNET IP, MODBUS IP User Manual

Liebert® IntelliSlot® Modbus 485, Modbus IP and BACnet IP

Reference Guide

TABLE OF CONTENTS

1.0 LIEBERT EQUIPMENT COMPATIBILITY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1

1.1 What’s New in This Manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 1.2 Connectivity to Liebert IntelliSlot Using Modbus 485, Modbus IP or BACnet IP . . . . . . . . . 1

1.2.1 How to Use This Manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1

1.3 Compatibility with Liebert Equipment. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2

Table 1 Liebert Equipment and Compatible Liebert IntelliSlot® Cards . . . . . . . . . . . . . . . . . . . . . 2

2.0 MODBUS COMMUNICATIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5

2.1 Implementation Basics. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 2.2 Transmission Format . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5

Table 2 Modbus Remote Transmission Unit settings for Liebert IntelliSlot 485/IP interface

card . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5

2.3 Modbus Packet Format . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5

2.3.1 Device Address . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 2.3.2 Function Code . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6

Table 3 Supported Modbus function codes. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6

2.3.3 Data Fields . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 2.3.4 Error Check Field. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6

2.4 RTU Framing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6

Table 4 Query sample . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 Table 5 Response sample . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6

3.0 MODBUS 485 AND MODBUS IP PROTOCOLS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7

3.1 Thermal Management Products . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7

Table 6 Liebert Challenger 3000, Liebert Challenger ITR, Liebert CW, Liebert Deluxe System/3, Liebert DS, Liebert DSE, Liebert HPM, Liebert PeX- Status

and Coil. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 Table 7 Extra notes key to Table 6 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12

Table 8 Liebert Challenger 3000, Liebert Challenger ITR, Liebert CW, Liebert Deluxe System/3, Liebert DS, Liebert DSE, Liebert HPM, Liebert PeX- Input

and Holding . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13 Table 9 Extra notes key to Table 8 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25

Table 10 Liebert Challenger 3000, Liebert Challenger ITR, Liebert CW, Liebert Deluxe System/3, Liebert DS, Liebert DSE, Liebert HPM, Liebert PeX- Glossary . . . . . 26

Table 11 Liebert CRV- Status and Coil . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39 Table 12 Liebert CRV- Input and Holding . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41 Table 13 Liebert CRV- Glossary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45 Table 14 Liebert HPC(Chiller) - Status and Coil . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49 Table 15 Liebert HPC(Chiller) - Input and Holding . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51 Table 16 Extra notes key to Table 15 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55 Table 17 Liebert HPC(Chiller) - Glossary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55

i

Table 18 Liebert XDC- Status and Coil . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58 Table 19 Liebert XDC- Input and Holding . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59 Table 20 Liebert XDP- Status and Coil . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60 Table 21 Liebert XDP- Input and Holding . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62 Table 22 Liebert XDP- Glossary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72 Table 23 Liebert DSand Liebert PeX- Status and Coil. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75 Table 24 Liebert DSand Liebert PeX- Input and Holding . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 78 Table 25 Liebert XDF- Status and Coil . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 81 Table 26 Liebert XDF- Input and Holding . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 82

Table 27 Liebert Challenger 3000, Liebert Deluxe System/3, Liebert Himod, Liebert

ICS- Input and Holding - LAM. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 83

Table 28 Liebert DataMate, Liebert Mini-Mate Plus, Liebert Mini-Mate2 - Input and

Holding - L0B . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 85 Table 29 Liebert DataMate, Liebert Mini-Mate2 - Input and Holding - MM2 . . . . . . . . . . . . . . 86 Table 30 Liebert Mini-Mate2 8 Ton - Input and Holding - L8T . . . . . . . . . . . . . . . . . . . . . . . . . . . 88

Table 31 Liebert Atlas Air, Liebert Atlas PEC, Liebert LECS 15- Input and

Holding - C10 2-step . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 90

Table 32 Liebert Atlas Air, Liebert Atlas PEC, Liebert CEMS 100- Input and

Holding - C100 4-step . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 92

3.2 Power Distribution and Power Conditioning Products . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 94

Table 33 Liebert Datawave, Liebert FPC, Liebert PPC- Input and Holding - PMP, PM2 Options for Liebert FPC and Liebert PPC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 94

Table 34 Liebert Datawave, Liebert FPC, Liebert PPC- Input and Holding - PMP

Option for Liebert FPC and Liebert PPC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 96 Table 35 Liebert FDC, Liebert FPC, Liebert RDC, Liebert RX- Status and Coil . . . . . . . . . 97 Table 36 Liebert FDC, Liebert FPC, Liebert RDC, Liebert RX- Input and Holding. . . . . . 100 Table 37 Liebert FDC, Liebert FPC, Liebert RDC, Liebert RX- Glossary. . . . . . . . . . . . . . 109 Table 38 Liebert STS, Liebert STS/PDU- Input and Holding - STS. . . . . . . . . . . . . . . . . . . . . 112 Table 39 Liebert STS2, Liebert STS2/PDU- Input and Holding - STS2. . . . . . . . . . . . . . . . . . 114

3.3 UPS Systems. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 118

Table 40 Liebert APM™, Liebert NXC, Liebert NXR- Status and Coil . . . . . . . . . . . . . . . . . . . 118 Table 41 Liebert APM, Liebert NXC, Liebert NXR- Input and Holding. . . . . . . . . . . . . . . . . 120 Table 42 Liebert APM, Liebert NXC, Liebert NXR- Glossary . . . . . . . . . . . . . . . . . . . . . . . . 122 Table 43 Liebert APS- Status and Coil. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 124 Table 44 Liebert APS- Input and Holding . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 126 Table 45 Liebert APS- Glossary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 132 Table 46 Liebert GXT2and Liebert GXT3- Status and Coil . . . . . . . . . . . . . . . . . . . . . . . . . . . 136 Table 47 Liebert GXT2and Liebert GXT3- Input and Holding . . . . . . . . . . . . . . . . . . . . . . . . 137 Table 48 Liebert HiNet- Status and Coil . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 138 Table 49 Liebert HiNet - Input and Holding . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 138 Table 50 Liebert Nfinity® - Status and Coil. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 139

ii

Table 51 Liebert Nfinity® - Input and Holding . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 140 Table 52 Liebert NX- Status and Coil. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 141 Table 53 Liebert NX- Input and Holding . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 143 Table 54 Liebert NX 225-600kVA UPS - Input and Holding 3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . 145 Table 55 Liebert NXL- 60Hz, UL version (Model 40) - Status and Coil . . . . . . . . . . . . . . . . . . . 148 Table 56 Liebert NXL- 60Hz, UL version (Model 40) - Input and Holding . . . . . . . . . . . . . . . . 151 Table 57 Liebert NXL- 60Hz, UL version (Model 40) - Glossary. . . . . . . . . . . . . . . . . . . . . . . . . 163 Table 58 Liebert NXL- 50Hz, CE version (Models 48 and 49) - Status and Coil . . . . . . . . . . . . 168 Table 59 Liebert NXL™ - 50Hz, CE version (Models 48 and 49) - Input and Holding . . . . . . . . . 171 Table 60 Liebert NXL- 50Hz, CE version (Models 48 and 49) - Glossary . . . . . . . . . . . . . . . . . 182 Table 61 Liebert PowerSureInteractive (before July 2008) - Status and Coil . . . . . . . . . . . . . . 190 Table 62 Liebert PowerSureInteractive (before July 2008) - Input and Holding. . . . . . . . . . . . 191 Table 63 Liebert PowerSureInteractive 2 - Status and Coil . . . . . . . . . . . . . . . . . . . . . . . . . . . . 192 Table 64 Liebert PowerSureInteractive 2 - Input and Holding. . . . . . . . . . . . . . . . . . . . . . . . . . 193 Table 65 Liebert Series 300UPS - Status and Coil . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 194 Table 66 Liebert Series 300UPS - Input and Holding . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 195 Table 67 Liebert Series 600UPS - Status and Coil . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 197 Table 68 Liebert Series 600UPS - Input and Holding . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 198 Table 69 Liebert Series 610SCC UPS - Status and Coil . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 199 Table 70 Liebert Series 610 SCC UPS - Input and Holding . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 200 Table 71 Liebert HiPulse™, Liebert SICE 7200- Input and Holding - SMM/SSM. . . . . . . . . . . . 201 Table 72 Liebert SICE 7200- Input and Holding - SSC. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 203 Table 73 Liebert Npower- Input and Holding - IMP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 205

3.4 Battery Monitoring Products . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 207

Table 74 Alber® BDSU- Status and Coil. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 207 Table 75 Alber® BDSU- Input and Holding . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 209

4.0 BACNET COMMUNICATIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .214

4.1 BACnet Protocol Implementation Conformance Statement . . . . . . . . . . . . . . . . . . . . . . . . 214

4.1.1 Segmentation Capability . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 214 4.1.2 Supported Services. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 215 4.1.3 Standard Object Types Supported . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 216 4.1.4 Object Properties . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 217

4.2 Thermal Management Products . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 220

Table 76 Liebert Challenger 3000, Liebert Challenger ITR, Liebert CW, Liebert Deluxe System/3, Liebert DS, Liebert DSE, Liebert HPM, Liebert PeX- Binary

Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 220

Table 77 Extra Notes to Table 76 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

226

Table 78 Liebert Challenger 3000, Liebert Challenger ITR, Liebert CW, Liebert Deluxe

System/3, Liebert DS, Liebert DSE, Liebert HPM, Liebert PeX- Analog

Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 227

iii

Table 79 Extra Notes to Table 78 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 235

Table 80 Liebert Challenger 3000, Liebert Challenger ITR, Liebert CW, Liebert Deluxe System/3, Liebert DS, Liebert DSE, Liebert HPM, Liebert PeX- Multistate

Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 236 Table 81 Extra Notes to Table 80 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 243

Table 82 Liebert Challenger 3000, Liebert Challenger ITR, Liebert CW, Liebert Deluxe System/3, Liebert DS, Liebert DSE, Liebert HPM, Liebert

PeX- Glossary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 244 Table 83 Liebert CRV- Binary Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 256 Table 84 Liebert CRV- Analog Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 259 Table 85 Liebert CRV- Multistate Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 262 Table 86 Liebert CRV- Glossary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 265 Table 87 Liebert HPC- Binary Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 271 Table 88 Liebert HPC- Analog Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 273 Table 89 Liebert HPC- Multistate Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 275 Table 90 Extra Notes. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 276 Table 91 Liebert HPC- Glossary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 276 Table 92 Liebert XDP, Liebert XDC- Binary Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 279 Table 93 Liebert XDP, Liebert XDC- Analog Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 281 Table 94 Liebert XDP, Liebert XDC- Multistate Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 283 Table 95 Liebert XDP, Liebert XDC- Glossary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 290 Table 96 Liebert DataMate, Liebert Mini-Mate2 - MM2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 297 Table 97 Liebert Mini-Mate2 8 Ton - L8T . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 298

4.3 UPS Systems. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 299

Table 98 Liebert APM, Liebert NXC, Liebert NXR- Binary Data . . . . . . . . . . . . . . . . . . . . . 299 Table 99 Liebert APM, Liebert NXC, Liebert NXR- Analog Data . . . . . . . . . . . . . . . . . . . . . 301 Table 100 Liebert APM, Liebert NXC, Liebert NXR- Multistate Data . . . . . . . . . . . . . . . . . . 302 Table 101 Liebert APM, Liebert NXC, Liebert NXR- Glossary . . . . . . . . . . . . . . . . . . . . . . . . 303 Table 102 Liebert APS- Binary Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 306 Table 103 Liebert APS- Analog Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 308 Table 104 Liebert APS- Multistate Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 310 Table 105 Liebert APS- Glossary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 312 Table 106 Liebert NXL- 60Hz, UL version (Model 40) - Binary Data . . . . . . . . . . . . . . . . . . . . . . 316 Table 107 Liebert NXL- 60Hz, UL version (Model 40) - Analog Data . . . . . . . . . . . . . . . . . . . . . 321 Table 108 Liebert NXL- 60Hz, UL version (Model 40) - Multistate Data. . . . . . . . . . . . . . . . . . . 327 Table 109 Liebert NXL- 60Hz, UL version (Model 40) - Glossary. . . . . . . . . . . . . . . . . . . . . . . . . 333 Table 110 Liebert NXL- 50 Hz, CE version (Models 48 and 49)—Binary Data. . . . . . . . . . . . . . 341 Table 111 Liebert NXL- 50 Hz, CE version (Models 48 and 49)—Analog Data. . . . . . . . . . . . . . 345 Table 112 Liebert NXL- 50 Hz, CE version (Models 48 and 49)—Multistate Data. . . . . . . . . . . 348 Table 113 Liebert NXL- 50 Hz, CE version (Models 48 and 49)—Glossary. . . . . . . . . . . . . . . . . 355

iv

Liebert Equipment Compatibility - What’s New in This Manual

1.0LIEBERT EQUIPMENT COMPATIBILITY

1.1What’s New in This Manual

Emerson Network Power® has introduced a new Liebert IntelliSlot® card platform—the Liebert IntelliSlot Unitycard. This platform combines the Modbus 485, Modbus IP and BACnet IP outputs of existing cards into a common, unified platform. Liebert IS-UNITY allows selecting one of the available third-party protocols and the Liebert IS-UNITY-DP allows selection of two of the available protocols.

The Liebert IS-UNITY and LiebertIS-UNITY-DP cards are interchangeable with the IS-485L, IS-485X, IS-IPBML, IS-IPBMX, IS-WEBL and IS-WEBX cards for the protocols offered. The information output by the Unity cards is the same as the output of the IS-485L, IS-485X, IS-IPBML and IS-IPBMX cards. The cards offer Modbus IP/485 and BACnet IP.

The Liebert NX225-600kVA UPS is also supported with the Chloride ManageUPS Net Adapter +B communication card so the Modbus mapping supported with this configuration has been included.

1.2Connectivity to Liebert IntelliSlot Using Modbus 485, Modbus IP or BACnet IP

This publication describes the Modbus and BACnet communications protocols available for communication with Emerson Network Power equipment. Included are the Liebert IntelliSlot Modbus 485, Modbus IP and the BACnet IP communications cards.

The Modbus information includes implementation basics, supported types, frame format, function code support and similar subjects.

The BACnet information includes the BACnet service listing, object types, device objects, analog objects, binary objects, multistate objects and BACnet engineering units.

1.2.1How to Use This Manual

Table 1 shows the type of Liebert IntelliSlot card required for selected Liebert products. Find the product first and the Reference Table, the three columns to the right of that are the cards supported for the product.

The information is organized by Product Name, Table Number, Controller Protocol and Card Part Number.

Modbus tables are first and BACnet tables second with products in the following sections:

Thermal Management Products

Power Distribution and Power Conditioning Products (Modbus Only)

UPS Systems

Battery Monitoring Products (Modbus Only)

Products currently shipping are shown first in each section, followed by older equipment.

1

Liebert® IntelliSlot® Modbus/BACnet IP

Liebert Equipment Compatibility - Compatibility with Liebert Equipment

1.3Compatibility with Liebert Equipment

Table 1 Liebert Equipment and Compatible Liebert IntelliSlot® Cards

 

Refer

 

Compatible Card Part Number

 

 

 

 

 

 

 

 

to

Controller /

Liebert IntelliSlot

Liebert IntelliSlot

 

Modbus IP /

Product Supported

Tables:

Protocol

Modbus 485 Card

Web / Modbus 485 Card

 

BACnet IP

MODBUS 485 & MODBUS IP PROTOCOLS

 

 

 

 

 

Thermal Management Products

 

 

 

 

 

 

Liebert Challenger 3000

6-10

 

 

 

 

 

Liebert Challenger ITR

6-10

 

 

 

 

 

Liebert CRV

11-13

 

 

 

 

 

Liebert CW

6-10

 

 

 

 

 

Liebert Deluxe System/3

6-10

Liebert

IS-485L

 

 

IS-IPBML

Liebert DS

6-10

 

 

 

 

iCOM®

IS-UNITY

 

IS-UNITY

Liebert DSE

6-10

 

v4

IS-UNITY-DP

 

 

IS-UNITY-DP

Liebert HPC(Chiller)

14-17

 

 

 

 

 

Liebert HPM

6-10

 

 

 

 

 

Liebert PeX

6-10

 

 

 

 

 

Liebert XDC

18-19

 

 

 

 

 

Liebert XDP

20-22

 

 

 

 

 

Liebert DS

23-24

Liebert

 

 

 

 

Liebert PeX

23-24

iCOM

OC485-LBDS

 

 

 

v3

 

 

 

 

Liebert XDF

25-26

 

 

 

 

Liebert Challenger 3000

27

 

 

 

 

 

Liebert Deluxe System/3

27

LAM

OC485-ADPT

IS-WEBADPT

 

Liebert Himod

27

 

 

 

 

 

 

Liebert ICS

27

 

 

 

 

 

Liebert DataMate

28

 

 

 

 

 

Liebert Mini-Mate Plus

28

L0B

OC485-ADPT

IS-WEBADPT

 

Liebert Mini-Mate2

28

 

 

 

 

 

Liebert DataMate

29

 

 

 

 

IS-WEBADPT

 

 

MM2

OC485-ADPT

IS-WEBADPT

 

(BACnet IP

Liebert Mini-Mate2

29

 

 

 

 

 

Only)

 

30

 

 

 

 

IS-WEBADPT

Liebert Mini-Mate2 8 Ton

L8T

OC485-ADPT

IS-WEBADPT

 

(BACnet IP

 

 

 

 

 

 

Only)

Liebert Atlas Air

31

C10

 

 

 

 

Liebert Atlas PEC

31

OC485-ADPT

IS-WEBADPT

 

 

 

2-step

 

 

 

 

Liebert LECS 15

31

 

 

 

 

 

 

 

 

 

Liebert Atlas Air

32

C100

 

 

 

 

Liebert Atlas PEC

32

OC485-ADPT

IS-WEBADPT

 

4-step

 

Liebert CEMS 100

32

 

 

 

 

 

 

 

 

 

Liebert® IntelliSlot® Modbus/BACnet IP

2

Liebert Equipment Compatibility - Compatibility with Liebert Equipment

Table 1

Liebert Equipment and Compatible Liebert IntelliSlot® Cards (continued)

 

 

 

Refer

 

Compatible Card Part Number

 

 

 

 

 

 

 

 

to

Controller /

Liebert IntelliSlot

Liebert IntelliSlot

Modbus IP /

Product Supported

Tables:

Protocol

Modbus 485 Card

Web / Modbus 485 Card

BACnet IP

Power Distribution & Power Conditioning Products

 

 

 

Liebert Datawave

33

PMP, PM2 for

 

 

 

Liebert FPC

33

Liebert FPC &

OC485-ADPT

IS-WEBADPT

 

 

Liebert PPC

 

 

 

Liebert PPC

33

 

 

 

Liebert FPC, Liebert RDC,

35-37

v4

IS-485S

IS-IPBMS

Liebert FDC, Liebert RX

(Modbus IP only)

Liebert Datawave

34

PMP for

 

 

 

Liebert FPC

34

Liebert FPC &

OC485-ADPT

IS-WEBADPT

 

 

 

Liebert PPC

 

 

 

Liebert PPC

34

 

 

 

 

 

 

 

Liebert STS/ Liebert STS/

38

STS

OC485-ADPT

IS-WEBADPT

PDU

 

Liebert STS2/ Liebert STS2/

39

STS2

OC485-ADPT

IS-WEBADPT

PDU

 

MODBUS 485 & MODBUS IP PROTOCOLS (continued)

 

 

 

UPS Systems

 

 

 

 

 

Liebert APM

40-42

 

IS-485L

 

IS-IPBML

IS-UNITY

IS-UNITY

 

 

 

 

IS-UNITY-DP

 

IS-UNITY-DP

Liebert APS

43-45

IS-UNITY

IS-UNITY

 

 

 

 

IS-UNITY-DP

 

IS-UNITY-DP

Liebert GXT2

46-47

OC-485

Liebert GXT3

46-47

OC-485

Liebert HiNet

48-49

OC-485

Liebert Nfinity

50-51

OC-485

Liebert NX

52-53

OC-485

Liebert NXC

40-42

 

IS-485L

 

IS-IPBML

IS-UNITY

IS-UNITY

 

 

 

 

IS-UNITY-DP

 

IS-UNITY-DP

Liebert NXR

40-42

 

IS-485L

 

IS-IPBML

IS-UNITY

IS-UNITY

 

 

 

 

IS-UNITY-DP

 

IS-UNITY-DP

Liebert NXL- 60 Hz, UL version

55-57

IS-485X

IS-IPBMX

(Model 40—SA, SR, SN, MM, CD)

IS-UNITY

IS-UNITY

 

 

IS-UNITY-DP

 

IS-UNITY-DP

 

 

 

 

 

Liebert NXL- 50 Hz, CE version

58-60

 

IS-UNITY

 

IS-UNITY

(Model 48 and 49—SA, SR, SN,

IS-UNITY-DP

IS-UNITY-DP

MM, CD)

 

 

 

 

 

 

 

 

 

 

Liebert PowerSure Interactive

61-62

OC-485

Liebert PowerSure Interactive 2

63-64

OC-485

Liebert Series 300UPS

65-66

OC485-ADPT

IS-WEBADPT

Liebert Series 600UPS

67-68

OC485-ADPT

IS-WEBADPT

Liebert Series 610SCC UPS

69-70

OC485-ADPT

IS-WEBADPT

Liebert HiPulse

71

SMM/SSM

OC485-ADPT

IS-WEBADPT

Liebert SICE 7200

71

 

 

 

 

Liebert SICE 7200

72

SSC

OC485-ADPT

IS-WEBADPT

Liebert Npower

73

IMP

OC485-ADPT

IS-WEBADPT

Battery Monitoring Products

 

 

 

 

 

Alber BDSU

74-75

IS-485X

IS-IPBMX

 

 

 

 

 

 

(Modbus IP only)

3

Liebert® IntelliSlot® Modbus/BACnet IP

Liebert Equipment Compatibility - Compatibility with Liebert Equipment

Table 1

Liebert Equipment and Compatible Liebert IntelliSlot® Cards (continued)

 

 

 

Refer

 

Compatible Card Part Number

 

 

 

 

 

 

 

 

to

Controller /

Liebert IntelliSlot

Liebert IntelliSlot

Modbus IP /

 

Product Supported

Tables:

Protocol

Modbus 485 Card

Web / Modbus 485 Card

BACnet IP

BACNET IP PROTOCOL

 

 

 

 

 

 

 

 

 

 

 

Thermal Management Products

 

 

 

 

 

Liebert Challenger 3000

76-82

 

 

 

 

Liebert Challenger ITR

76-82

 

 

 

 

Liebert CRV

83-86

 

 

 

 

Liebert CW

76-82

 

 

 

 

Liebert Deluxe System/3

76-82

Liebert

 

 

IS-IPBML

Liebert DS

76-82

 

 

 

 

 

iCOM

IS-UNITY

Liebert DSE

76-82

v4

 

 

IS-UNITY-DP

Liebert HPC

87-91

 

 

 

 

Liebert HPM

76-82

 

 

 

 

Liebert PeX

76-82

 

 

 

 

Liebert XDC

92-95

 

 

 

 

Liebert XDP

92-95

 

 

 

 

Liebert DataMate

96

MM2

IS-WEBADPT

Liebert Mini-Mate2

96

 

 

 

(BACnet IP only)

Liebert Mini-Mate2 8 Ton

97

L8T

 

Power Protection Products

 

 

 

 

 

Liebert APM

98-101

IS-UNITY

IS-UNITY

IS-UNITY-DP

IS-UNITY-DP

 

 

 

 

 

Liebert APS

102-

IS-UNITY

IS-UNITY

105

IS-UNITY-DP

IS-UNITY-DP

 

 

 

 

Liebert NXC

98-101

IS-UNITY

IS-UNITY

 

 

 

 

IS-UNITY-DP

 

IS-UNITY-DP

Liebert NXR

98-101

IS-UNITY

IS-UNITY

 

 

 

 

IS-UNITY-DP

 

IS-UNITY-DP

Liebert NXL60Hz, UL version

106-

IS-UNITY

IS-UNITY

(Model 40)

109

IS-UNITY-DP

IS-UNITY-DP

 

 

Liebert NXL- 50Hz, CE version

110-

IS-UNITY-DP

IS-UNITY

(Models 48 and 49)

113

IS-UNITY

IS-UNITY-DP

 

 

Liebert® IntelliSlot® Modbus/BACnet IP

4

Modbus Communications - Implementation Basics

2.0MODBUS COMMUNICATIONS

2.1Implementation Basics

Modbus protocol provides control and data acquisition, through query and response, between master and slave devices. This protocol comprises the rules for communication, controlling the message format between devices, how master and slave devices initiate communications, as well as unit identification, message-handling and error-checking.

The Liebert IntelliSlot® 485/IP card acts as a slave device on a network. This network can be a multidrop configuration over EIA-485, where multiple slaves reside on a common wire or loop.

2.2Transmission Format

The Liebert IntelliSlot 485/IP interface card supports Modbus Remote Terminal Unit (RTU) transmission modes. See Table 2 below.

Table 2 Modbus Remote Transmission Unit settings for Liebert IntelliSlot 485/IP interface card

Physical

Transmission

Baud

Data

Parity

Stop

Start

Port

Mode

Rate

Bits

Bits

Bits

Bits

 

 

 

 

 

 

 

EIA-485/422

RTU

9600, 19200

8

None

1

1

2 wire

or 38400

 

 

 

 

 

2.3Modbus Packet Format

Each Modbus packet consists of these fields:

Device Address

Function Code

Data Field(s)

Error Check Field

2.3.1Device Address

The address field immediately follows the beginning of the frame and consists of 8-bits (RTU). This bit indicates the user-assigned address of the slave device that is to receive the message from the attached master device.

Each slave must be assigned a unique address. Only the addressed slave will respond to a query that contains its address.

5

Liebert® IntelliSlot® Modbus/BACnet IP

Modbus Communications - RTU Framing

2.3.2Function Code

The function code field tells the addressed slaves what function to perform. Function codes are designed to invoke a specific action by the slave device. The function code ranges from 1 to 127.

Liebert IntelliSlot® Modbus server supports the following Modbus function codes.

Table 3 Supported Modbus function codes

Code

Function

Description

 

 

 

 

 

Read from 1 to 2000 contiguous status of coils managed by the server. Coils in the

01

Read Coils

response message are packed as one per bit of a byte, 1=On and 0=Off. If the requested

 

 

quantity of coils is not a multiple of 8, zeros are padded in the final byte.

 

 

Read from 1 to 2000 contiguous input status managed by the server. Discrete inputs in

02

Read Discrete Inputs

the response message are packed as one per bit of a byte, 1=On and 0=Off. If the

 

 

requested number of inputs is not a multiple of 8, zeros are padded in the final byte.

03

Read Holding Registers

Read the contents of contiguous block of 1 to 127 holding registers. Data are packed as

two bytes per register; the first byte contains the high order bits.

 

 

04

Read Input Registers

Read the contents of contiguous block of 1 to 127 Input registers. Data are packed as

two bytes per register; the first byte contains the high order bits.

 

 

05

Write Single Coil

Write a single output to either On (1) or Off (0) mapped in coil section.

 

 

 

06

Write Single Register

Write a value into a single holding register;

 

 

 

15

Write Multiple Coils

Force each coil in a sequence of coils to either On or Off.

 

 

 

16

Write Multiple Registers

Write values into a block of contiguous registers (1 to 120)

 

 

 

2.3.3Data Fields

The data field length varies, depending on whether the message is a request or a response to a packet. This field typically contains information required by the slave device to perform the command specified or to the response to a data request from the master device.

2.3.4Error Check Field

The Error Check Field consists of a 16-bit (2 byte) Cyclical Redundancy Check (CRC16). It allows the receiving device to detect a packet that has been corrupted by transmission errors.

2.4RTU Framing

The example below shows a typical query and response from a Liebert IntelliSlot interface card. The master device initiates a query asking Slave Device, with address 2, for holding registers starting at holding register 40051 (offset 50) and including next two registers (three total).

Table 4

Query sample

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Slave

Function

 

Starting Register

Number of Registers

CRC16

 

 

 

 

 

 

 

Address

Code

 

Hi Byte

Lo Byte

Hi Byte

Lo Byte

Hi Byte

Lo Byte

 

 

 

 

 

 

 

 

 

02

03

 

00

32

00

03

E5

FA

 

 

 

 

 

 

 

 

 

Table 5

Response sample

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Count:

 

 

Register

 

 

CRC16

 

 

 

 

 

 

 

 

 

 

 

 

40051 Data

40052 Data

40053 Data

 

 

Slave

Function

Bytes of

 

 

 

 

 

 

 

 

 

 

Address

Code

Data

Hi

Lo

Hi

Lo

Hi

Lo

Hi Byte

Lo Byte

 

 

 

 

 

 

 

 

 

 

 

02

03

6

1

58

00

FA

00

54

1B

0D

 

 

 

 

 

 

 

 

 

 

 

Slave Device, with address 2, responds to Function Code 3 with 6 bytes of hexadecimal data and ends with CRC16 checksum.

Register values: 40051 = 158

(hex) = 344

(decimal)

40052 =

FA

(hex) =

250

(decimal)

40053 =

54

(hex) =

84

(decimal)

Liebert® IntelliSlot® Modbus/BACnet IP

6

Modbus 485 and Modbus IP Protocols - Thermal Management Products

3.0MODBUS 485 AND MODBUS IP PROTOCOLS

3.1Thermal Management Products

Table 6 Liebert Challenger 3000, Liebert Challenger ITR, Liebert CW, Liebert Deluxe System/3, Liebert DS, Liebert DSE, Liebert HPM, Liebert PeX- Status and Coil

Controller

Liebert iCOM® v4

 

 

 

 

 

 

 

 

Units with Liebert iCOM Firmware

 

 

 

 

 

PA1.04.033.STD or later:

 

Units with

 

Liebert Challenger 3000

 

 

Liebert Challenger ITR

Liebert Products

Liebert iCOM®:

 

Liebert CW

 

 

Liebert HPM

 

Liebert Deluxe System/3

 

 

 

 

 

Liebert DS

 

 

 

 

 

 

Liebert DSE

 

 

 

 

 

 

Liebert PeX

 

Available Points

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Number

 

 

Data Label

Status

Coil

 

of Bits

Notes / Units

Extra Notes

Ext Reheat Lockout

10009

-

 

1

Active on Alarm

1, 2, 3, 4, 5, 6

 

 

 

 

 

 

 

Ext Humidifier Lockout

10010

-

 

1

Active on Alarm

1, 2, 3, 4, 5, 6

 

 

 

 

 

 

 

Minimum Chilled Water Temp Set Point Enable

10013

13

 

1

0 = disabled

1, 2, 3, 4, 5, 6

 

1 = enabled

 

 

 

 

 

 

Return Air Sensor Event Control

10019

19

 

1

0 = disabled

1, 2, 3, 4, 5, 6

 

1 = enabled

 

 

 

 

 

 

Ext Air Sensor A Event Control

10020

20

 

1

0 = disabled

1, 2, 3, 4, 5, 6

 

1 = enabled

 

 

 

 

 

 

Ext Compressor Lockout

10021

-

 

1

Active on Alarm

1, 2, 3, 4, 5, 6

 

 

 

 

 

 

 

System On/Off Control

-

25

 

1

0 = off

1, 2, 3, 4, 5, 6

 

1 = on

 

 

 

 

 

 

Fan State

10025

 

1

0 = off

1, 2, 3, 4, 5, 6

 

1 = on

 

 

 

 

 

 

Cooling State

10026

 

1

0 = off

1, 2, 3, 4, 5, 6

 

1 = on

 

 

 

 

 

 

Free Cooling State

10027

 

1

0 = off

1, 2, 3, 4, 5, 6

 

1 = on

 

 

 

 

 

 

Hot Water / Hot Gas State

10028

 

1

0 = off

1, 2, 3, 4, 5, 6

 

1 = on

 

 

 

 

 

 

Electric Reheat State

10029

 

1

0 = off

1, 2, 3, 4, 5, 6

 

1 = on

 

 

 

 

 

 

Humidifier State

10030

 

1

0 = off

1, 2, 3, 4, 5, 6

 

1 = on

 

 

 

 

 

 

Dehumidifier State

10031

 

1

0 = off

1, 2, 3, 4, 5, 6

 

1 = on

 

 

 

 

 

 

Main Fan Overload

10034

 

1

Active on Alarm

1, 2, 3, 4, 5, 6

 

 

 

 

 

 

 

Loss of Air Flow

10035

 

1

Active on Alarm

1, 2, 3, 4, 5, 6

 

 

 

 

 

 

 

Ext Loss of Flow

10036

 

1

Active on Alarm

1, 2, 3, 4, 5, 6

 

 

 

 

 

 

 

Compressor High Head Pressure

10037

 

1

Active on Alarm

1, 2, 3, 4, 5, 6

 

 

 

 

 

 

 

Compressor Low Suction Pressure

10038

 

1

Active on Alarm

1, 2, 3, 4, 5, 6

 

 

 

 

 

 

 

Compressor Thermal Overload

10039

 

1

Active on Alarm

1, 2, 3, 4, 5, 6

 

 

 

 

 

 

 

Compressor Pump Down Issue

10040

 

1

Active on Alarm

1, 2, 3, 4, 5, 6

 

 

 

 

 

 

 

Compressor High Head Pressure 2

10041

 

1

Active on Alarm

1, 2, 3, 4, 5, 6

 

 

 

 

 

 

 

Compressor Low Suction Pressure 2

10042

 

1

Active on Alarm

1, 2, 3, 4, 5, 6

 

 

 

 

 

 

 

Compressor Thermal Overload 2

10043

 

1

Active on Alarm

1, 2, 3, 4, 5, 6

 

 

 

 

 

 

 

7

Liebert® IntelliSlot® Modbus/BACnet IP

Modbus 485 and Modbus IP Protocols - Thermal Management Products

Table 6 Liebert Challenger 3000, Liebert Challenger ITR, Liebert CW, Liebert Deluxe System/3, Liebert DS, Liebert DSE, Liebert HPM, Liebert PeX- Status and Coil (continued)

Controller

Liebert iCOM® v4

 

 

 

 

 

 

 

 

Units with Liebert iCOM Firmware

 

 

 

 

 

PA1.04.033.STD or later:

 

Units with

 

Liebert Challenger 3000

 

 

Liebert Challenger ITR

Liebert Products

Liebert iCOM®:

 

Liebert CW

 

 

Liebert HPM

 

Liebert Deluxe System/3

 

 

 

 

 

Liebert DS

 

 

 

 

 

 

Liebert DSE

 

 

 

 

 

 

Liebert PeX

 

Available Points

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Number

 

 

Data Label

Status

Coil

 

of Bits

Notes / Units

Extra Notes

Compressor Pump Down Issue 2

10044

 

1

Active on Alarm

1, 2, 3, 4, 5, 6

 

 

 

 

 

 

 

Dig Scroll Comp Over Temp 1

10045

 

1

Active on Alarm

1, 2, 3, 4, 5, 6

 

 

 

 

 

 

 

Dig Scroll Comp Over Temp 2

10046

 

1

Active on Alarm

1, 2, 3, 4, 5, 6

 

 

 

 

 

 

 

Smoke Detected

10047

 

1

Active on Alarm

1, 2, 3, 4, 5, 6

 

 

 

 

 

 

 

Water Under Floor

10048

 

1

Active on Alarm

1, 2, 3, 4, 5, 6

 

 

 

 

 

 

 

Humidifier Issue

10049

 

1

Active on Alarm

1, 2, 3, 4, 5, 6

 

 

 

 

 

 

 

Ext Standby Glycol Pump On

10050

 

1

Active on Alarm

1, 2, 3, 4, 5, 6

 

 

 

 

 

 

 

Ext Standby Unit On

10051

 

1

Active on Alarm

1, 2, 3, 4, 5, 6

 

 

 

 

 

 

 

Ext Condenser Pump High Water

10052

 

1

Active on Alarm

1, 2, 3, 4, 5, 6

 

 

 

 

 

 

 

Return Air Sensor Issue

10053

 

1

Active on Alarm

1, 2, 3, 4, 5, 6

 

 

 

 

 

 

 

Ext Loss of Air Blower

10055

 

1

Active on Alarm

1, 2, 3, 4, 5, 6

 

 

 

 

 

 

 

Humidifier Low Water

10058

 

1

Active on Alarm

1, 2, 3, 4, 5, 6

 

 

 

 

 

 

 

Humidifier Over Current

10059

 

1

Active on Alarm

1, 2, 3, 4, 5, 6

 

 

 

 

 

 

 

Ext Over Temperature

10060

 

1

Active on Alarm

1, 2, 3, 4, 5, 6

 

 

 

 

 

 

 

Shutdown - Loss Of Power

10061

 

1

Active on Alarm

1, 2, 3, 4, 5, 6

 

 

 

 

 

 

 

Supply Chilled Water Over Temp

10065

 

1

Active on Alarm

1, 2, 3, 4, 5, 6

 

 

 

 

 

 

 

Return Air Over Temperature

10067

 

1

Active on Alarm

1, 2, 3, 4, 5, 6

 

 

 

 

 

 

 

Return Air Under Temperature

10068

 

1

Active on Alarm

1, 2, 3, 4, 5, 6

 

 

 

 

 

 

 

High Return Humidity

10069

 

1

Active on Alarm

1, 2, 3, 4, 5, 6

 

 

 

 

 

 

 

Low Return Humidity

10070

 

1

Active on Alarm

1, 2, 3, 4, 5, 6

 

 

 

 

 

 

 

Ext Air Sensor A Over Temperature

10071

 

1

Active on Alarm

1, 2, 3, 4, 5, 6

 

 

 

 

 

 

 

Ext Air Sensor A Under Temperature

10072

 

1

Active on Alarm

1, 2, 3, 4, 5, 6

 

 

 

 

 

 

 

Ext Air Sensor A High Humidity

10073

 

1

Active on Alarm

1, 2, 3, 4, 5, 6

 

 

 

 

 

 

 

Ext Air Sensor A Low Humidity

10074

 

1

Active on Alarm

1, 2, 3, 4, 5, 6

 

 

 

 

 

 

 

Supply Chilled Water Loss of Flow

10075

 

1

Active on Alarm

1, 2, 3, 4, 5, 6

 

 

 

 

 

 

 

Clogged Air Filter

10076

 

1

Active on Alarm

1, 2, 3, 4, 5, 6

 

 

 

 

 

 

 

Supply Air Sensor Issue

10077

 

1

Active on Alarm

1, 2, 3, 4, 5, 6

 

 

 

 

 

 

 

Free Cooling Temp Sensor Issue

10078

 

1

Active on Alarm

1, 2, 3, 4, 5, 6

 

 

 

 

 

 

 

Ext Air Sensor A Issue

10079

 

1

Active on Alarm

1, 2, 3, 4, 5, 6

 

 

 

 

 

 

 

Fan Hours Exceeded

10080

 

1

Active on Alarm

1, 2, 3, 4, 5, 6

 

 

 

 

 

 

 

Compressor Hours Exceeded 1

10081

 

1

Active on Alarm

1, 2, 3, 4, 5, 6

 

 

 

 

 

 

 

Compressor Hours Exceeded 2

10082

 

1

Active on Alarm

1, 2, 3, 4, 5, 6

 

 

 

 

 

 

 

Free Cooling Valve Hours Exceeded

10083

 

1

Active on Alarm

1, 2, 3, 4, 5, 6

 

 

 

 

 

 

 

Electric Reheater Hours Exceeded 1

10084

 

1

Active on Alarm

1, 2, 3, 4, 5, 6

 

 

 

 

 

 

 

Liebert® IntelliSlot® Modbus/BACnet IP

8

Modbus 485 and Modbus IP Protocols - Thermal Management Products

Table 6 Liebert Challenger 3000, Liebert Challenger ITR, Liebert CW, Liebert Deluxe System/3, Liebert DS, Liebert DSE, Liebert HPM, Liebert PeX- Status and Coil (continued)

Controller

Liebert iCOM® v4

 

 

 

 

 

 

 

 

Units with Liebert iCOM Firmware

 

 

 

 

 

PA1.04.033.STD or later:

 

Units with

 

Liebert Challenger 3000

 

 

Liebert Challenger ITR

Liebert Products

Liebert iCOM®:

 

Liebert CW

 

 

Liebert HPM

 

Liebert Deluxe System/3

 

 

 

 

 

Liebert DS

 

 

 

 

 

 

Liebert DSE

 

 

 

 

 

 

Liebert PeX

 

Available Points

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Number

 

 

Data Label

Status

Coil

 

of Bits

Notes / Units

Extra Notes

Electric Reheater Hours Exceeded 2

10085

 

1

Active on Alarm

1, 2, 3, 4, 5, 6

 

 

 

 

 

 

 

Electric Reheater Hours Exceeded 3

10086

 

1

Active on Alarm

1, 2, 3, 4, 5, 6

 

 

 

 

 

 

 

Hot Water / Hot Gas Valve Hours Exceeded

10087

 

1

Active on Alarm

1, 2, 3, 4, 5, 6

 

 

 

 

 

 

 

Humidifier Hours Exceeded

10088

 

1

Active on Alarm

1, 2, 3, 4, 5, 6

 

 

 

 

 

 

 

Dehumidifier Hours Exceeded

10089

 

1

Active on Alarm

1, 2, 3, 4, 5, 6

 

 

 

 

 

 

 

Unit Communication Lost

10091

 

1

Active on Alarm

1, 2, 3, 4, 5, 6

 

 

 

 

 

 

 

Master Unit Communication Lost

10092

 

1

Active on Alarm

1, 2, 3, 4, 5, 6

 

 

 

 

 

 

 

Unit Code Missing

10094

 

1

Active on Alarm

1, 2, 3, 4, 5, 6

 

 

 

 

 

 

 

Service Required

10098

 

1

Active on Alarm

1, 2, 3, 4, 5, 6

 

 

 

 

 

 

 

Humidifier Control Board Not Detected

10099

 

1

Active on Alarm

1, 2, 3, 4, 5, 6

 

 

 

 

 

 

 

Customer Input 1

10104

 

1

Active on Alarm

1, 2, 3, 4, 5, 6

 

 

 

 

 

 

 

Customer Input 2

10105

 

1

Active on Alarm

1, 2, 3, 4, 5, 6

 

 

 

 

 

 

 

Customer Input 3

10106

 

1

Active on Alarm

1, 2, 3, 4, 5, 6

 

 

 

 

 

 

 

Customer Input 4

10107

 

1

Active on Alarm

1, 2, 3, 4, 5, 6

 

 

 

 

 

 

 

Dig Scroll Comp Discharge Temp Sensor Issue 1

10108

 

1

Active on Alarm

1, 2, 3, 4, 5, 6

 

 

 

 

 

 

 

Dig Scroll Comp Discharge Temp Sensor Issue 2

10109

 

1

Active on Alarm

1, 2, 3, 4, 5, 6

 

 

 

 

 

 

 

Supply Air Over Temperature

10209

 

1

Active on Alarm

1, 2, 3, 4, 5, 6

 

 

 

 

 

 

 

Supply Air Under Temperature

10210

 

1

Active on Alarm

1, 2, 3, 4, 5, 6

 

 

 

 

 

 

 

Ambient Air Sensor Issue

10211

 

1

Active on Alarm

2, 3, 4, 5, 6

 

 

 

 

 

 

 

Compressor Short Cycle 1

10212

 

1

Active on Alarm

1, 2, 3, 4, 5, 6

 

 

 

 

 

 

 

Compressor Short Cycle 2

10213

 

1

Active on Alarm

1, 2, 3, 4, 5, 6

 

 

 

 

 

 

 

Ext Free Cooling Lockout

10214

 

1

Active on Alarm

1, 2, 3, 4, 5, 6

 

 

 

 

 

 

 

Reheater Over Temperature

10215

 

1

Active on Alarm

1, 2, 3, 4, 5, 6

 

 

 

 

 

 

 

Humidifier Cylinder Worn

10216

 

1

Active on Alarm

1, 2, 3, 4, 5, 6

 

 

 

 

 

 

 

Humidifier Under Current

10217

 

1

Active on Alarm

1, 2, 3, 4, 5, 6

 

 

 

 

 

 

 

Fan Issue

10218

 

1

Active on Alarm

1, 2, 3, 4, 5, 6

 

 

 

 

 

 

 

Condenser TVSS Issue

10219

 

1

Active on Alarm

1, 2, 3, 4, 5, 6

 

 

 

 

 

 

 

Condenser VFD Issue

10220

 

1

Active on Alarm

1, 2, 3, 4, 5, 6

 

 

 

 

 

 

 

Condenser Issue 1

10221

 

1

Active on Alarm

1, 2, 3, 4, 5, 6

 

 

 

 

 

 

 

Condenser Issue 2

10222

 

1

Active on Alarm

1, 2, 3, 4, 5, 6

 

 

 

 

 

 

 

BMS Communications Timeout

10223

 

1

Active on Alarm

1, 2, 3, 4, 5, 6

 

 

 

 

 

 

 

Digital Output Board Not Detected 1

10224

 

1

Active on Alarm

1, 2, 3, 4, 5, 6

 

 

 

 

 

 

 

Digital Output Board Not Detected 2

10225

 

1

Active on Alarm

1, 2, 3, 4, 5, 6

 

 

 

 

 

 

 

Digital Output Board Not Detected 3

10226

 

1

Active on Alarm

1, 2, 3, 4, 5, 6

 

 

 

 

 

 

 

9

Liebert® IntelliSlot® Modbus/BACnet IP

Modbus 485 and Modbus IP Protocols - Thermal Management Products

Table 6 Liebert Challenger 3000, Liebert Challenger ITR, Liebert CW, Liebert Deluxe System/3, Liebert DS, Liebert DSE, Liebert HPM, Liebert PeX- Status and Coil (continued)

Controller

Liebert iCOM® v4

 

 

 

 

 

 

 

 

Units with Liebert iCOM Firmware

 

 

 

 

 

PA1.04.033.STD or later:

 

Units with

 

Liebert Challenger 3000

 

 

Liebert Challenger ITR

Liebert Products

Liebert iCOM®:

 

Liebert CW

 

 

Liebert HPM

 

Liebert Deluxe System/3

 

 

 

 

 

Liebert DS

 

 

 

 

 

 

Liebert DSE

 

 

 

 

 

 

Liebert PeX

 

Available Points

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Number

 

 

Data Label

Status

Coil

 

of Bits

Notes / Units

Extra Notes

RAM Battery Issue

10227

 

1

Active on Alarm

1, 2, 3, 4, 5, 6

 

 

 

 

 

 

 

Water Leakage Detector Sensor Issue

10228

 

1

Active on Alarm

1, 2, 3, 4, 5, 6

 

 

 

 

 

 

 

External Fire Detected

10229

 

1

Active on Alarm

1, 2, 3, 4, 5, 6

 

 

 

 

 

 

 

Chilled Water Control Valve Failure 1

10230

 

1

Active on Alarm

1, 2, 3, 4, 5, 6

 

 

 

 

 

 

 

Chilled Water Control Valve Failure 2

10231

 

1

Active on Alarm

1, 2, 3, 4, 5, 6

 

 

 

 

 

 

 

Unit Off

10232

 

1

Active on Alarm

1, 2, 3, 4, 5, 6

 

 

 

 

 

 

 

Unit On

10233

 

1

Active on Alarm

1, 2, 3, 4, 5, 6

 

 

 

 

 

 

 

Unit Partial Shutdown

10234

 

1

Active on Alarm

1, 2, 3, 4, 5, 6

 

 

 

 

 

 

 

Unit Shutdown

10235

 

1

Active on Alarm

1, 2, 3, 4, 5, 6

 

 

 

 

 

 

 

High Power Shutdown

10236

 

1

Active on Alarm

1, 2, 3, 4, 5, 6

 

 

 

 

 

 

 

Unit Standby

10237

 

1

Active on Alarm

1, 2, 3, 4, 5, 6

 

 

 

 

 

 

 

Maintenance Due

10238

 

1

Active on Alarm

1, 2, 3, 4, 5, 6

 

 

 

 

 

 

 

Maintenance Completed

10239

 

1

Active on Alarm

1, 2, 3, 4, 5, 6

 

 

 

 

 

 

 

Compressor Low Pressure Transducer Issue 1

10240

 

1

Active on Alarm

1, 2, 3, 4, 5, 6

 

 

 

 

 

 

 

Compressor Low Pressure Transducer Issue 2

10241

 

1

Active on Alarm

1, 2, 3, 4, 5, 6

 

 

 

 

 

 

 

Compressor High Pressure Transducer Issue 1

10242

 

1

Active on Alarm

1, 2, 3, 4, 5, 6

 

 

 

 

 

 

 

Compressor High Pressure Transducer Issue 2

10243

 

1

Active on Alarm

1, 2, 3, 4, 5, 6

 

 

 

 

 

 

 

Compressor Capacity Reduced

10244

 

1

Active on Alarm

1, 2, 3, 4, 5, 6

 

 

 

 

 

 

 

Dew Point Over Temperature

10345

 

1

Active on Alarm

2, 3, 4, 5, 6

 

 

 

 

 

 

 

Dew Point Under Temperature

10346

 

1

Active on Alarm

2, 3, 4, 5, 6

 

 

 

 

 

 

 

Ext Dew Point Over Temperature

10347

 

1

Active on Alarm

2, 3, 4, 5, 6

 

 

 

 

 

 

 

Ext Dew Point Under Temperature

10348

 

1

Active on Alarm

2, 3, 4, 5, 6

 

 

 

 

 

 

 

Compressor Superheat Over Threshold 1

10349

 

1

Active on Alarm

2, 3, 4, 5, 6

 

 

 

 

 

 

 

Compressor Superheat Over Threshold 2

10350

 

1

Active on Alarm

2, 3, 4, 5, 6

 

 

 

 

 

 

 

Unspecified General Event

10351

 

1

Active on Alarm

2, 3, 4, 5, 6

 

 

 

 

 

 

 

Remote Sensor Average Over Temperature

10352

 

1

Active on Alarm

2, 3, 4, 5, 6

 

 

 

 

 

 

 

Remote Sensor Average Under Temperature

10353

 

1

Active on Alarm

2, 3, 4, 5, 6

 

 

 

 

 

 

 

Remote Sensor System Average Over Temperature

10354

 

1

Active on Alarm

2, 3, 4, 5, 6

 

 

 

 

 

 

 

Remote Sensor System Average Under Temperature

10355

 

1

Active on Alarm

2, 3, 4, 5, 6

 

 

 

 

 

 

 

Remote Sensor Over Temperature 1

10356

 

1

Active on Alarm

2, 3, 4, 5, 6

 

 

 

 

 

 

 

Remote Sensor Over Temperature 2

10357

 

1

Active on Alarm

2, 3, 4, 5, 6

 

 

 

 

 

 

 

Remote Sensor Over Temperature 3

10358

 

1

Active on Alarm

2, 3, 4, 5, 6

 

 

 

 

 

 

 

Remote Sensor Over Temperature 4

10359

 

1

Active on Alarm

2, 3, 4, 5, 6

 

 

 

 

 

 

 

Remote Sensor Over Temperature 5

10360

 

1

Active on Alarm

2, 3, 4, 5, 6

 

 

 

 

 

 

 

Liebert® IntelliSlot® Modbus/BACnet IP

10

Modbus 485 and Modbus IP Protocols - Thermal Management Products

Table 6 Liebert Challenger 3000, Liebert Challenger ITR, Liebert CW, Liebert Deluxe System/3, Liebert DS, Liebert DSE, Liebert HPM, Liebert PeX- Status and Coil (continued)

Controller

Liebert iCOM® v4

 

 

 

 

 

 

 

 

Units with Liebert iCOM Firmware

 

 

 

 

 

PA1.04.033.STD or later:

 

Units with

 

Liebert Challenger 3000

 

 

Liebert Challenger ITR

Liebert Products

Liebert iCOM®:

 

Liebert CW

 

 

Liebert HPM

 

Liebert Deluxe System/3

 

 

 

 

 

Liebert DS

 

 

 

 

 

 

Liebert DSE

 

 

 

 

 

 

Liebert PeX

 

Available Points

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Number

 

 

Data Label

Status

Coil

 

of Bits

Notes / Units

Extra Notes

Remote Sensor Over Temperature 6

10361

 

1

Active on Alarm

2, 3, 4, 5, 6

 

 

 

 

 

 

 

Remote Sensor Over Temperature 7

10362

 

1

Active on Alarm

2, 3, 4, 5, 6

 

 

 

 

 

 

 

Remote Sensor Over Temperature 8

10363

 

1

Active on Alarm

2, 3, 4, 5, 6

 

 

 

 

 

 

 

Remote Sensor Over Temperature 9

10364

 

1

Active on Alarm

2, 3, 4, 5, 6

 

 

 

 

 

 

 

Remote Sensor Over Temperature 10

10365

 

1

Active on Alarm

2, 3, 4, 5, 6

 

 

 

 

 

 

 

Remote Sensor Under Temperature 1

10366

 

1

Active on Alarm

2, 3, 4, 5, 6

 

 

 

 

 

 

 

Remote Sensor Under Temperature 2

10367

 

1

Active on Alarm

2, 3, 4, 5, 6

 

 

 

 

 

 

 

Remote Sensor Under Temperature 3

10368

 

1

Active on Alarm

2, 3, 4, 5, 6

 

 

 

 

 

 

 

Remote Sensor Under Temperature 4

10369

 

1

Active on Alarm

2, 3, 4, 5, 6

 

 

 

 

 

 

 

Remote Sensor Under Temperature 5

10370

 

1

Active on Alarm

2, 3, 4, 5, 6

 

 

 

 

 

 

 

Remote Sensor Under Temperature 6

10371

 

1

Active on Alarm

2, 3, 4, 5, 6

 

 

 

 

 

 

 

Remote Sensor Under Temperature 7

10372

 

1

Active on Alarm

2, 3, 4, 5, 6

 

 

 

 

 

 

 

Remote Sensor Under Temperature 8

10373

 

1

Active on Alarm

2, 3, 4, 5, 6

 

 

 

 

 

 

 

Remote Sensor Under Temperature 9

10374

 

1

Active on Alarm

2, 3, 4, 5, 6

 

 

 

 

 

 

 

Remote Sensor Under Temperature 10

10375

 

1

Active on Alarm

2, 3, 4, 5, 6

 

 

 

 

 

 

 

Remote Sensor Issue 1

10376

 

1

Active on Alarm

1, 2, 3, 4, 5, 6

 

 

 

 

 

 

 

Remote Sensor Issue 2

10377

 

1

Active on Alarm

2, 3, 4, 5, 6

 

 

 

 

 

 

 

Remote Sensor Issue 3

10378

 

1

Active on Alarm

2, 3, 4, 5, 6

 

 

 

 

 

 

 

Remote Sensor Issue 4

10379

 

1

Active on Alarm

2, 3, 4, 5, 6

 

 

 

 

 

 

 

Remote Sensor Issue 5

10380

 

1

Active on Alarm

2, 3, 4, 5, 6

 

 

 

 

 

 

 

Remote Sensor Issue 6

10381

 

1

Active on Alarm

2, 3, 4, 5, 6

 

 

 

 

 

 

 

Remote Sensor Issue 7

10382

 

1

Active on Alarm

2, 3, 4, 5, 6

 

 

 

 

 

 

 

Remote Sensor Issue 8

10383

 

1

Active on Alarm

2, 3, 4, 5, 6

 

 

 

 

 

 

 

Remote Sensor Issue 9

10384

 

1

Active on Alarm

2, 3, 4, 5, 6

 

 

 

 

 

 

 

Remote Sensor Issue 10

10385

 

1

Active on Alarm

2, 3, 4, 5, 6

 

 

 

 

 

 

 

Air Economizer Emergency Override

10386

 

1

Active on Alarm

2, 3, 4, 5, 6

 

 

 

 

 

 

 

Air Economizer Reduced Airflow

10387

 

1

Active on Alarm

2, 3, 4, 5, 6

 

 

 

 

 

 

 

Temperature Control Sensor Issue

10388

 

1

Active on Alarm

2, 3, 4, 5, 6

 

 

 

 

 

 

 

EEV Unspecified General Event

10488

 

1

Active on Alarm

4, 5

 

 

 

 

 

 

 

Static Pressure Sensor Issue

10489

 

1

Active on Alarm

3, 5, 6

 

 

 

 

 

 

 

High Static Pressure

10490

 

1

Active on Alarm

3, 5, 6

 

 

 

 

 

 

 

Low Static Pressure

10491

 

1

Active on Alarm

3, 5, 6

 

 

 

 

 

 

 

Pump Unspecified General Event

10492

 

1

Active on Alarm

4, 5

 

 

 

 

 

 

 

Condenser Unit Unspecified General Event

10493

 

1

Active on Alarm

3, 4, 5, 6

 

 

 

 

 

 

 

11

Liebert® IntelliSlot® Modbus/BACnet IP

Modbus 485 and Modbus IP Protocols - Thermal Management Products

Table 6 Liebert Challenger 3000, Liebert Challenger ITR, Liebert CW, Liebert Deluxe System/3, Liebert DS, Liebert DSE, Liebert HPM, Liebert PeX- Status and Coil (continued)

Controller

Liebert iCOM® v4

 

 

 

 

 

 

 

 

 

Units with Liebert iCOM Firmware

 

 

 

 

 

PA1.04.033.STD or later:

 

Units with

 

Liebert Challenger 3000

 

 

Liebert Challenger ITR

 

Liebert Products

Liebert iCOM®:

 

Liebert CW

 

 

Liebert HPM

 

Liebert Deluxe System/3

 

 

 

 

 

Liebert DS

 

 

 

 

 

 

Liebert DSE

 

 

 

 

 

 

Liebert PeX

 

Available Points

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Number

 

 

 

Data Label

Status

Coil

 

of Bits

Notes / Units

 

Extra Notes

Condenser Circuit Unspecified General Event

10494

 

1

Active on Alarm

 

3, 4, 5, 6

 

 

 

 

 

 

 

 

Input Undervoltage 1

10500

 

1

Active on Alarm

 

6

 

 

 

 

 

 

 

 

Input Undervoltage 2

10501

 

1

Active on Alarm

 

6

 

 

 

 

 

 

 

 

Input Undervoltage 3

10502

 

1

Active on Alarm

 

6

 

 

 

 

 

 

 

 

Input Undervoltage 4

10503

 

1

Active on Alarm

 

6

 

 

 

 

 

 

 

 

Input Undervoltage 5

10504

 

1

Active on Alarm

 

6

 

 

 

 

 

 

 

 

Input Undervoltage 6

10505

 

1

Active on Alarm

 

6

 

 

 

 

 

 

 

 

Return Humidity Sensor Issue

10600

 

1

Active on Alarm

 

5, 6

 

 

 

 

 

 

 

 

Compressor Low Differential Pressure Lockout 1

10601

 

1

Active on Alarm

 

5

 

 

 

 

 

 

 

 

Compressor Low Differential Pressure Lockout 2

10602

 

1

Active on Alarm

 

5

 

 

 

 

 

 

 

 

Airflow Sensor Issue

10603

 

1

Active on Alarm

 

5, 6

 

 

 

 

 

 

 

 

Ext Air Damper Position Issue

10604

 

1

Active on Alarm

 

5, 6

 

 

 

 

 

 

 

 

Ext Power Source A Failure

10605

 

1

Active on Alarm

 

5, 6

 

 

 

 

 

 

 

 

Ext Power Source B Failure

10606

 

1

Active on Alarm

 

5, 6

 

 

 

 

 

 

 

 

Static Pressure Sensor Out of Range

10607

 

1

Active on Alarm

 

5, 6

 

 

 

 

 

 

 

 

Fluid Temperature Sensor Issue 1

10608

 

1

Active on Alarm

 

6

 

 

 

 

 

 

 

 

Fluid Temperature Sensor Issue 2

10609

 

1

Active on Alarm

 

6

 

 

 

 

 

 

 

 

Fluid Flow Sensor Issue 1

10610

 

1

Active on Alarm

 

6

 

 

 

 

 

 

 

 

Fluid Flow Sensor Issue 2

10611

 

1

Active on Alarm

 

6

 

 

 

 

 

 

 

 

Mixed Mode Lockout

10620

 

1

Active on Alarm

 

5

 

 

 

 

 

 

 

 

Table 7 Extra notes key to Table 6

Number Description

1This point is supported on:

iCOM controller version 1.04.042.STD This point is supported on:

2iCOM controller version 2.00.11R for US

iCOM controller version 2.00.12R (for Japan and China – language corrections only)

3This point is supported on: iCOM controller version 2.01.23R

4This point is supported on: iCOM controller version 2.02.16R

5This point is supported on:

iCOM controller version 2.03.27.07R

6This point is supported on:

iCOM controller version 2.01.32.02R

Liebert® IntelliSlot® Modbus/BACnet IP

12

Modbus 485 and Modbus IP Protocols - Thermal Management Products

Table 8 Liebert Challenger 3000, Liebert Challenger ITR, Liebert CW, Liebert Deluxe System/3, Liebert DS, Liebert DSE, Liebert HPM, Liebert PeX- Input and Holding

Controller

Liebert iCOM v4

 

 

 

 

 

 

 

 

 

 

 

 

Input

Holding

# of

 

 

Extra

Data Label

Register

Register

Reg.

Scale

Notes / Units

Notes

 

 

 

 

 

0 = Disabled

 

Free Cooling Internal Control Mode

30017

40017

1

1 = Contact

1

 

 

 

 

 

2 = Value

 

 

 

 

 

 

0 = Relative

 

Humidity Proportional Control Type

30018

40018

1

1 = Compensated

1

 

 

 

 

 

2 = Predictive

 

Fan Speed Maximum Set Point

30019

40019

1

%

1, 2, 3, 4, 5, 6

 

 

 

 

 

 

 

Supply Air Temperature Set Point

30020

40020

1

deg C

1

 

 

 

 

 

 

 

Supply Air Temperature Set Point

30733

40733

1

deg F

1

 

 

 

 

 

 

 

Free Cooling Internal Temperature Delta

30021

40021

1

10

deg C

1, 2, 3, 4, 5, 6

 

 

 

 

 

 

 

Free Cooling Internal Temperature Delta

30734

40734

1

10

deg F

1, 2, 3, 4, 5, 6

 

 

 

 

 

 

 

Minimum Chilled Water Temp Set Point

30022

40022

1

10

deg C

1, 2, 3, 4, 5, 6

 

 

 

 

 

 

 

Minimum Chilled Water Temp Set Point

30735

40735

1

10

deg F

1, 2, 3, 4, 5, 6

 

 

 

 

 

 

 

Air Temperature Set Point

30023

40023

1

10

deg C

1, 2, 3, 4, 5, 6

 

 

 

 

 

 

 

Air Temperature Set Point

30736

40736

1

10

deg F

1, 2, 3, 4, 5, 6

 

 

 

 

 

 

 

Air Temperature Proportional Band

30024

40024

1

10

deg C

1, 2, 3, 4, 5, 6

 

 

 

 

 

 

 

Air Temperature Proportional Band

30737

40737

1

10

deg F

1, 2, 3, 4, 5, 6

 

 

 

 

 

 

 

Air Temperature Dead Band

30025

40025

1

10

deg C

1, 2, 3, 4, 5, 6

 

 

 

 

 

 

 

Air Temperature Dead Band

30738

40738

1

10

deg F

1, 2, 3, 4, 5, 6

 

 

 

 

 

 

 

Air Temperature Control Integration Time

30026

40026

1

10

min

1, 2, 3, 4, 5, 6

 

 

 

 

 

 

 

Humidity Set Point

30027

40027

1

% RH

1, 2, 3, 4, 5, 6

 

 

 

 

 

 

 

Humidity Proportional Band

30028

40028

1

% RH

1, 2, 3, 4, 5, 6

 

 

 

 

 

 

 

Humidity Proportional Control Integration

30029

40029

1

10

min

1, 2, 3, 4, 5, 6

Time

 

 

 

 

 

 

Humidity Dead Band

30030

40030

1

10

% RH

1, 2, 3, 4, 5, 6

 

 

 

 

 

 

 

Auto Restart Delay

30031

40031

1

sec

1, 2, 3, 4, 5, 6

 

 

 

 

 

 

 

 

 

 

 

 

0 = Proportional

 

Air Temperature Control Type

30033

40033

1

1 = Prop+Integral

1, 2, 3, 4, 5, 6

 

 

 

 

 

3 = Intelligent

 

BMS Timeout Period

30045

40045

1

min

1, 2, 3, 4, 5, 6

 

 

 

 

 

 

 

Return Air Over Temp Threshold

30050

40050

1

10

deg C

1, 2, 3, 4, 5, 6

 

 

 

 

 

 

 

Return Air Over Temp Threshold

30739

40739

1

10

deg F

1, 2, 3, 4, 5, 6

 

 

 

 

 

 

 

Return Air Under Temp Threshold

30051

40051

1

10

deg C

1, 2, 3, 4, 5, 6

 

 

 

 

 

 

 

Return Air Under Temp Threshold

30740

40740

1

10

deg F

1, 2, 3, 4, 5, 6

 

 

 

 

 

 

 

Ext Air Sensor A Over Temp Threshold

30052

40052

1

10

deg C

1, 2, 3, 4, 5, 6

 

 

 

 

 

 

 

Ext Air Sensor A Over Temp Threshold

30741

40741

1

10

deg F

1, 2, 3, 4, 5, 6

 

 

 

 

 

 

 

Ext Air Sensor A Under Temp Threshold

30053

40053

1

10

deg C

1, 2, 3, 4, 5, 6

 

 

 

 

 

 

 

Ext Air Sensor A Under Temp Threshold

30742

40742

1

10

deg F

1, 2, 3, 4, 5, 6

 

 

 

 

 

 

 

High Return Humidity Threshold

30054

40054

1

10

% RH

1, 2, 3, 4, 5, 6

 

 

 

 

 

 

 

Low Return Humidity Threshold

30055

40055

1

10

% RH

1, 2, 3, 4, 5, 6

 

 

 

 

 

 

 

Ext Air Sensor A High Humidity Threshold

30056

40056

1

10

% RH

1, 2, 3, 4, 5, 6

 

 

 

 

 

 

 

Ext Air Sensor A Low Humidity Threshold

30057

40057

1

10

% RH

1, 2, 3, 4, 5, 6

 

 

 

 

 

 

 

Fan Hours Threshold

30070

40070

1

hr

1, 2, 3, 4, 5, 6

 

 

 

 

 

 

 

13

Liebert® IntelliSlot® Modbus/BACnet IP

Modbus 485 and Modbus IP Protocols - Thermal Management Products

Table 8 Liebert Challenger 3000, Liebert Challenger ITR, Liebert CW, Liebert Deluxe System/3, Liebert DS, Liebert DSE, Liebert HPM, Liebert PeX- Input and Holding (continued)

Controller

Liebert iCOM v4

 

 

 

 

 

 

 

 

 

 

 

 

Input

Holding

# of

 

 

Extra

Data Label

Register

Register

Reg.

Scale

Notes / Units

Notes

Compressor Hours Threshold 1

30071

40071

1

hr

1, 2, 3, 4, 5, 6

 

 

 

 

 

 

 

Compressor Hours Threshold 2

30072

40072

1

hr

1, 2, 3, 4, 5, 6

 

 

 

 

 

 

 

Humidifier Hours Threshold

30073

40073

1

hr

1, 2, 3, 4, 5, 6

 

 

 

 

 

 

 

Dehumidifier Hours Threshold

30074

40074

1

hr

1, 2, 3, 4, 5, 6

 

 

 

 

 

 

 

Free Cooling Valve Hours Threshold

30075

40075

1

hr

1, 2, 3, 4, 5, 6

 

 

 

 

 

 

 

Electric Reheater Hours Threshold 1

30076

40076

1

hr

1, 2, 3, 4, 5, 6

 

 

 

 

 

 

 

Electric Reheater Hours Threshold 2

30077

40077

1

hr

1, 2, 3, 4, 5, 6

 

 

 

 

 

 

 

Electric Reheater Hours Threshold 3

30078

40078

1

hr

1, 2, 3, 4, 5, 6

 

 

 

 

 

 

 

Hot Water / Hot Gas Valve Hours Threshold

30079

40079

1

hr

1, 2, 3, 4, 5, 6

 

 

 

 

 

 

 

 

 

 

 

 

0 = off

 

System Operating State

30100

1

1 = on

1, 2, 3, 4, 5, 6

 

 

 

 

 

2 = standby

 

 

 

 

 

 

1 = Normal Operation

 

 

 

 

 

 

2 = StartUp

 

System Status

30102

1

8 = Normal with Warning

1, 2, 3, 4, 5, 6

 

 

 

 

 

16 = Normal with Alarm

 

 

 

 

 

 

32 = Abnormal Operation

 

Fan Speed

30103

1

%

1, 2, 3, 4, 5, 6

 

 

 

 

 

 

 

Compressor Utilization

30104

1

%

1

 

 

 

 

 

 

 

Free Cooling Valve Open Position

30105

1

%

1, 2, 3, 4, 5, 6

 

 

 

 

 

 

 

Reheat Utilization

30106

1

%

1, 2, 3, 4, 5, 6

 

 

 

 

 

 

 

Humidifier Utilization

30107

1

%

1, 2, 3, 4, 5, 6

 

 

 

 

 

 

 

Dehumidifier Utilization

30108

1

%

1, 2, 3, 4, 5, 6

 

 

 

 

 

 

 

 

 

 

 

 

0 = off

 

Free Cooling Status

30109

1

2 = on

1, 2, 3, 4, 5, 6

 

 

 

 

 

3 = No Support

 

Return Air Temperature

30110

1

10

deg C

1, 2, 3, 4, 5, 6

 

 

 

 

 

 

 

Return Air Temperature

30743

1

10

deg F

1, 2, 3, 4, 5, 6

 

 

 

 

 

 

 

Supply Air Temperature

30112

1

10

deg C

1, 2, 3, 4, 5, 6

 

 

 

 

 

 

 

Supply Air Temperature

30744

1

10

deg F

1, 2, 3, 4, 5, 6

 

 

 

 

 

 

 

Supply Air Temperature Set Point

30113

1

deg C

1

 

 

 

 

 

 

 

Supply Air Temperature Set Point

30745

1

deg F

1

 

 

 

 

 

 

 

Free Cooling Fluid Temperature

30115

1

10

deg C

1, 2, 3, 4, 5, 6

 

 

 

 

 

 

 

Free Cooling Fluid Temperature

30746

1

10

deg F

1, 2, 3, 4, 5, 6

 

 

 

 

 

 

 

Ext Air Sensor A Temperature

30116

1

10

deg C

1, 2, 3, 4, 5, 6

 

 

 

 

 

 

 

Ext Air Sensor A Temperature

30747

1

10

deg F

1, 2, 3, 4, 5, 6

 

 

 

 

 

 

 

Ext Air Sensor B Temperature

30117

1

10

deg C

1, 2, 3, 4, 5, 6

 

 

 

 

 

 

 

Ext Air Sensor B Temperature

30748

1

10

deg F

1, 2, 3, 4, 5, 6

 

 

 

 

 

 

 

Ext Air Sensor C Temperature

30118

1

10

deg C

1, 2, 3, 4, 5, 6

 

 

 

 

 

 

 

Ext Air Sensor C Temperature

30749

1

10

deg F

1, 2, 3, 4, 5, 6

 

 

 

 

 

 

 

Dig Scroll Comp Discharge Temp 1

30119

1

deg C

1, 2, 3, 4, 5, 6

 

 

 

 

 

 

 

Dig Scroll Comp Discharge Temp 1

30750

1

deg F

1, 2, 3, 4, 5, 6

 

 

 

 

 

 

 

Dig Scroll Comp Discharge Temp 2

30120

1

deg C

1, 2, 3, 4, 5, 6

 

 

 

 

 

 

 

Liebert® IntelliSlot® Modbus/BACnet IP

14

Modbus 485 and Modbus IP Protocols - Thermal Management Products

Table 8 Liebert Challenger 3000, Liebert Challenger ITR, Liebert CW, Liebert Deluxe System/3, Liebert DS, Liebert DSE, Liebert HPM, Liebert PeX- Input and Holding (continued)

Controller

Liebert iCOM v4

 

 

 

 

 

 

 

 

 

 

 

 

Input

Holding

# of

 

 

Extra

Data Label

Register

Register

Reg.

Scale

Notes / Units

Notes

Dig Scroll Comp Discharge Temp 2

30751

1

deg F

1, 2, 3, 4, 5, 6

 

 

 

 

 

 

 

Return Humidity

30130

1

10

% RH

1, 2, 3, 4, 5, 6

 

 

 

 

 

 

 

Ext Air Sensor A Humidity

30132

1

10

% RH

1, 2, 3, 4, 5, 6

 

 

 

 

 

 

 

Ext Air Sensor B Humidity

30133

1

10

% RH

1, 2, 3, 4, 5, 6

 

 

 

 

 

 

 

Ext Air Sensor C Humidity

30134

1

10

% RH

1, 2, 3, 4, 5, 6

 

 

 

 

 

 

 

Fan Hours

30141

40141

1

hr

1, 2, 3, 4, 5, 6

 

 

 

 

 

 

 

Compressor Hours 1

30142

40142

1

hr

1, 2, 3, 4, 5, 6

 

 

 

 

 

 

 

Compressor Hours 2

30143

40143

1

hr

1, 2, 3, 4, 5, 6

 

 

 

 

 

 

 

Humidifier Hours

30144

40144

1

hr

1, 2, 3, 4, 5, 6

 

 

 

 

 

 

 

Dehumidifier Hours

30145

40145

1

hr

1, 2, 3, 4, 5, 6

 

 

 

 

 

 

 

Free Cooling Valve Hours

30146

40146

1

hr

1, 2, 3, 4, 5, 6

 

 

 

 

 

 

 

Electric Reheater Hours 1

30147

40147

1

hr

1, 2, 3, 4, 5, 6

 

 

 

 

 

 

 

Electric Reheater Hours 2

30148

40148

1

hr

1, 2, 3, 4, 5, 6

 

 

 

 

 

 

 

Electric Reheater Hours 3

30149

40149

1

hr

1, 2, 3, 4, 5, 6

 

 

 

 

 

 

 

Hot Water / Hot Gas Valve Hours

30150

40150

1

hr

1, 2, 3, 4, 5, 6

 

 

 

 

 

 

 

Today's High Air Temperature

30151

1

10

deg C

1, 2, 3, 4, 5, 6

 

 

 

 

 

 

 

Today's High Air Temperature

30752

1

10

deg F

1, 2, 3, 4, 5, 6

 

 

 

 

 

 

 

Today's Low Air Temperature

30153

1

10

deg C

1, 2, 3, 4, 5, 6

 

 

 

 

 

 

 

Today's Low Air Temperature

30753

1

10

deg F

1, 2, 3, 4, 5, 6

 

 

 

 

 

 

 

Today's High Humidity

30155

1

10

% RH

1, 2, 3, 4, 5, 6

 

 

 

 

 

 

 

Today's Low Humidity

30157

1

10

% RH

1, 2, 3, 4, 5, 6

 

 

 

 

 

 

 

 

 

 

 

 

1 = UPS

 

Server Class

30257

1

2 = AIR

1, 2, 3, 4, 5, 6

3 = PMP

 

 

 

 

 

 

 

 

 

 

 

4 = PDU

 

 

 

 

 

 

 

 

Today's High Air Temperature Time

30258

2

-

Seconds since Midnight

1, 2, 3, 4, 5, 6

 

 

 

 

 

 

 

Today's Low Air Temperature Time

30260

2

-

Seconds since Midnight

1, 2, 3, 4, 5, 6

 

 

 

 

 

 

 

 

 

 

 

 

0 = Disabled

 

Supply Air Temperature Sensor Control

30262

40262

1

1 = Limit

1

2 = Control

 

 

 

 

 

 

 

 

 

 

 

3 = Temp Only

 

 

 

 

 

 

 

 

Return Air Temperature Set Point

30263

40263

1

deg C

1

 

 

 

 

 

 

 

Return Air Temperature Set Point

30754

40754

1

deg F

1

 

 

 

 

 

 

 

Return Humidity Set Point

30264

40264

1

% RH

1

 

 

 

 

 

 

 

Today's High Humidity Time

30265

2

Seconds since Midnight

1, 2, 3, 4, 5, 6

 

 

 

 

 

 

 

Today's Low Humidity Time

30267

2

Seconds since Midnight

1, 2, 3, 4, 5, 6

 

 

 

 

 

 

 

Fixed Compressor State 1

30269

1

0 = off

1, 2, 3, 4, 5, 6

1 = on

 

 

 

 

 

 

Fixed Compressor State 2

30270

1

0 = off

1, 2, 3, 4, 5, 6

1 = on

 

 

 

 

 

 

Compressor Capacity Control State 1

30271

1

0 = off

1, 2, 3, 4, 5, 6

1 = on

 

 

 

 

 

 

Compressor Capacity Control State 2

30272

1

0 = off

1, 2, 3, 4, 5, 6

1 = on

 

 

 

 

 

 

15

Liebert® IntelliSlot® Modbus/BACnet IP

Modbus 485 and Modbus IP Protocols - Thermal Management Products

Table 8 Liebert Challenger 3000, Liebert Challenger ITR, Liebert CW, Liebert Deluxe System/3, Liebert DS, Liebert DSE, Liebert HPM, Liebert PeX- Input and Holding (continued)

Controller

Liebert iCOM v4

 

 

 

 

 

 

 

 

 

 

 

 

Input

Holding

# of

 

 

Extra

Data Label

Register

Register

Reg.

Scale

Notes / Units

Notes

Infrared Humidifier Flush Rate

30273

40273

1

%

1, 2, 3, 4, 5, 6

 

 

 

 

 

 

 

 

 

 

 

 

0 = Auto

 

Fan Control Mode

30274

40274

1

1 = Manual

1

2 = Economy

 

 

 

 

 

 

 

 

 

 

 

4 = Delta

 

 

 

 

 

 

 

 

Analog Input Reading 1

30275

1

100

1, 2, 3, 4, 5, 6

 

 

 

 

 

 

 

Analog Input Reading 2

30276

1

100

1, 2, 3, 4, 5, 6

 

 

 

 

 

 

 

Analog Input Reading 3

30277

1

100

1, 2, 3, 4, 5, 6

 

 

 

 

 

 

 

Analog Input Reading 4

30278

1

100

1, 2, 3, 4, 5, 6

 

 

 

 

 

 

 

System Control Mode

30280

1

0 = Internal (Auto)

1, 2, 3, 4, 5, 6

1 = External (Manual)

 

 

 

 

 

 

 

 

 

 

 

0 = Reason Unknown

 

 

 

 

 

 

1 = Network Display

 

 

 

 

 

 

2 = Alarm

 

System Operating State Reason

30281

1

3 = Schedule

1, 2, 3, 4, 5, 6

 

 

 

 

 

4 = Remote System

 

 

 

 

 

 

5 = External Input

 

 

 

 

 

 

6 = Local Display

 

Maintenance Ramp

30282

1

%

1, 2, 3, 4, 5, 6

 

 

 

 

 

 

 

Calculated Next Maintenance Month

30283

1

 

1, 2, 3, 4, 5, 6

 

 

 

 

 

 

 

Calculated Next Maintenance Year

30284

1

 

1, 2, 3, 4, 5, 6

 

 

 

 

 

 

 

Hot Water / Hot Gas Valve Open Position

30285

1

%

1, 2, 3, 4, 5, 6

 

 

 

 

 

 

 

Maintenance Tracking State

30286

1

0 = off

1, 2, 3, 4, 5, 6

1 = on

 

 

 

 

 

 

Customer Input 1 - Event Control

30287

40287

1

0 = disabled

1, 2, 3, 4, 5, 6

1 = enabled

 

 

 

 

 

 

 

 

 

 

 

0 = Message

 

Customer Input 1 - Event Type

30288

40288

1

1 = Warning

1, 2, 3, 4, 5, 6

 

 

 

 

 

2 = Alarm

 

Customer Input 2 - Event Control

30289

40289

1

0 = disabled

1, 2, 3, 4, 5, 6

1 = enabled

 

 

 

 

 

 

 

 

 

 

 

0 = Message

 

Customer Input 2 - Event Type

30290

40290

1

1 = Warning

1, 2, 3, 4, 5, 6

 

 

 

 

 

2 = Alarm

 

Customer Input 3 - Event Control

30291

40291

1

0 = disabled

1, 2, 3, 4, 5, 6

1 = enabled

 

 

 

 

 

 

 

 

 

 

 

0 = Message

 

Customer Input 3 - Event Type

30292

40292

1

1 = Warning

1, 2, 3, 4, 5, 6

 

 

 

 

 

2 = Alarm

 

Customer Input 4 - Event Control

30293

40293

1

0 = disabled

1, 2, 3, 4, 5, 6

1 = enabled

 

 

 

 

 

 

 

 

 

 

 

0 = Message

 

Customer Input 4 - Event Type

30294

40294

1

1 = Warning

1, 2, 3, 4, 5, 6

 

 

 

 

 

2 = Alarm

 

Ext Free Cooling Lockout - Event Control

30295

40295

1

0 = disabled

1, 2, 3, 4, 5, 6

1 = enabled

 

 

 

 

 

 

 

 

 

 

 

0 = Message

 

Ext Free Cooling Lockout - Event Type

30296

40296

1

1 = Warning

1, 2, 3, 4, 5, 6

 

 

 

 

 

2 = Alarm

 

Liebert® IntelliSlot® Modbus/BACnet IP

16

Modbus 485 and Modbus IP Protocols - Thermal Management Products

Table 8 Liebert Challenger 3000, Liebert Challenger ITR, Liebert CW, Liebert Deluxe System/3, Liebert DS, Liebert DSE, Liebert HPM, Liebert PeX- Input and Holding (continued)

Controller

Liebert iCOM v4

 

 

 

 

 

 

 

 

 

 

 

 

Input

Holding

# of

 

 

Extra

Data Label

Register

Register

Reg.

Scale

Notes / Units

Notes

Ext Condenser Pump High Water - Event

30297

40297

1

0 = disabled

1, 2, 3, 4, 5, 6

Control

1 = enabled

 

 

 

 

 

Ext Condenser Pump High Water - Event

 

 

 

 

0 = Message

 

30298

40298

1

1 = Warning

1, 2, 3, 4, 5, 6

Type

 

 

 

 

2 = Alarm

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Ext Standby Glycol Pump On - Event

30299

40299

1

0 = disabled

1, 2, 3, 4, 5, 6

Control

1 = enabled

 

 

 

 

 

 

 

 

 

 

0 = Message

 

Ext Standby Glycol Pump On - Event Type

30300

40300

1

1 = Warning

1, 2, 3, 4, 5, 6

 

 

 

 

 

2 = Alarm

 

Ext Standby Unit On - Event Control

30301

40301

1

0 = disabled

1, 2, 3, 4, 5, 6

1 = enabled

 

 

 

 

 

 

 

 

 

 

 

0 = Message

 

Ext Standby Unit On - Event Type

30302

40302

1

1 = Warning

1, 2, 3, 4, 5, 6

 

 

 

 

 

2 = Alarm

 

Ext Humidifier Lockout - Event Control

30303

40303

1

0 = disabled

1, 2, 3, 4, 5, 6

1 = enabled

 

 

 

 

 

 

 

 

 

 

 

0 = Message

 

Ext Humidifier Lockout - Event Type

30304

40304

1

1 = Warning

1, 2, 3, 4, 5, 6

 

 

 

 

 

2 = Alarm

 

Ext Loss of Flow - Event Control

30305

40305

1

0 = disabled

1, 2, 3, 4, 5, 6

1 = enabled

 

 

 

 

 

 

 

 

 

 

 

0 = Message

 

Ext Loss of Flow - Event Type

30306

40306

1

1 = Warning

1, 2, 3, 4, 5, 6

 

 

 

 

 

2 = Alarm

 

Ext Over Temperature - Event Control

30307

40307

1

0 = disabled

1, 2, 3, 4, 5, 6

1 = enabled

 

 

 

 

 

 

 

 

 

 

 

0 = Message

 

Ext Over Temperature - Event Type

30308

40308

1

1 = Warning

1, 2, 3, 4, 5, 6

 

 

 

 

 

2 = Alarm

 

Ext Reheat Lockout - Event Control

30309

40309

1

0 = disabled

1, 2, 3, 4, 5, 6

1 = enabled

 

 

 

 

 

 

 

 

 

 

 

0 = Message

 

Ext Reheat Lockout - Event Type

30310

40310

1

1 = Warning

1, 2, 3, 4, 5, 6

 

 

 

 

 

2 = Alarm

 

High Power Shutdown - Event Control

30311

40311

1

0 = disabled

1, 2, 3, 4, 5, 6

1 = enabled

 

 

 

 

 

 

 

 

 

 

 

0 = Message

 

High Power Shutdown - Event Type

30312

40312

1

1 = Warning

1, 2, 3, 4, 5, 6

 

 

 

 

 

2 = Alarm

 

Humidifier Issue - Event Control

30313

40313

1

0 = disabled

1, 2, 3, 4, 5, 6

1 = enabled

 

 

 

 

 

 

 

 

 

 

 

0 = Message

 

Humidifier Issue - Event Type

30314

40314

1

1 = Warning

1, 2, 3, 4, 5, 6

 

 

 

 

 

2 = Alarm

 

Master Unit Communication Lost - Event

30315

40315

1

0 = disabled

1, 2, 3, 4, 5, 6

Control

1 = enabled

 

 

 

 

 

Master Unit Communication Lost - Event

 

 

 

 

0 = Message

 

30316

40316

1

1 = Warning

1, 2, 3, 4, 5, 6

Type

 

 

 

 

2 = Alarm

 

 

 

 

 

 

 

 

 

 

 

 

 

 

17

Liebert® IntelliSlot® Modbus/BACnet IP

Modbus 485 and Modbus IP Protocols - Thermal Management Products

Table 8 Liebert Challenger 3000, Liebert Challenger ITR, Liebert CW, Liebert Deluxe System/3, Liebert DS, Liebert DSE, Liebert HPM, Liebert PeX- Input and Holding (continued)

Controller

Liebert iCOM v4

 

 

 

 

 

 

 

 

 

 

 

 

Input

Holding

# of

 

 

Extra

Data Label

Register

Register

Reg.

Scale

Notes / Units

Notes

Service Required - Event Control

30317

40317

1

0 = disabled

1, 2, 3, 4, 5, 6

1 = enabled

 

 

 

 

 

 

 

 

 

 

 

0 = Message

 

Service Required - Event Type

30318

40318

1

1 = Warning

1, 2, 3, 4, 5, 6

 

 

 

 

 

2 = Alarm

 

Shutdown - Loss Of Power - Event Control

30319

40319

1

0 = disabled

1, 2, 3, 4, 5, 6

1 = enabled

 

 

 

 

 

 

 

 

 

 

 

0 = Message

 

Shutdown - Loss Of Power - Event Type

30320

40320

1

1 = Warning

1, 2, 3, 4, 5, 6

 

 

 

 

 

2 = Alarm

 

Smoke Detected - Event Control

30321

40321

1

0 = disabled

1, 2, 3, 4, 5, 6

1 = enabled

 

 

 

 

 

 

 

 

 

 

 

0 = Message

 

Smoke Detected - Event Type

30322

40322

1

1 = Warning

1, 2, 3, 4, 5, 6

 

 

 

 

 

2 = Alarm

 

Water Under Floor - Event Control

30323

40323

1

0 = disabled

1, 2, 3, 4, 5, 6

1 = enabled

 

 

 

 

 

 

 

 

 

 

 

0 = Message

 

Water Under Floor - Event Type

30324

40324

1

1 = Warning

1, 2, 3, 4, 5, 6

 

 

 

 

 

2 = Alarm

 

Ext Compressor Lockout - Event Control

30325

40325

1

0 = disabled

1, 2, 3, 4, 5, 6

1 = enabled

 

 

 

 

 

 

 

 

 

 

 

0 = Message

 

Ext Compressor Lockout - Event Type

30326

40326

1

1 = Warning

1, 2, 3, 4, 5, 6

 

 

 

 

 

2 = Alarm

 

Clogged Air Filter - Event Control

30327

40327

1

0 = disabled

1, 2, 3, 4, 5, 6

1 = enabled

 

 

 

 

 

 

 

 

 

 

 

0 = Message

 

Clogged Air Filter - Event Type

30328

40328

1

1 = Warning

1, 2, 3, 4, 5, 6

 

 

 

 

 

2 = Alarm

 

Ext Loss of Air Blower - Event Control

30329

40329

1

0 = disabled

1, 2, 3, 4, 5, 6

1 = enabled

 

 

 

 

 

 

 

 

 

 

 

0 = Message

 

Ext Loss of Air Blower - Event Type

30330

40330

1

1 = Warning

1, 2, 3, 4, 5, 6

 

 

 

 

 

2 = Alarm

 

Compressor High Head Pressure - Event

30331

40331

1

0 = disabled

1, 2, 3, 4, 5, 6

Control 1

1 = enabled

 

 

 

 

 

Compressor High Head Pressure - Event

30332

40332

1

0 = disabled

1, 2, 3, 4, 5, 6

Control 2

1 = enabled

 

 

 

 

 

Compressor High Head Pressure - Event

 

 

 

 

0 = Message

 

30333

40333

1

1 = Warning

1, 2, 3, 4, 5, 6

Type 1

 

 

 

 

2 = Alarm

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Compressor High Head Pressure - Event

 

 

 

 

0 = Message

 

30334

40334

1

1 = Warning

1, 2, 3, 4, 5, 6

Type 2

 

 

 

 

2 = Alarm

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Compressor Low Suction Pressure - Event

30335

40335

1

0 = disabled

1, 2, 3, 4, 5, 6

Control 1

1 = enabled

 

 

 

 

 

Compressor Low Suction Pressure - Event

30336

40336

1

0 = disabled

1, 2, 3, 4, 5, 6

Control 2

1 = enabled

 

 

 

 

 

Liebert® IntelliSlot® Modbus/BACnet IP

18

Modbus 485 and Modbus IP Protocols - Thermal Management Products

Table 8 Liebert Challenger 3000, Liebert Challenger ITR, Liebert CW, Liebert Deluxe System/3, Liebert DS, Liebert DSE, Liebert HPM, Liebert PeX- Input and Holding (continued)

Controller

Liebert iCOM v4

 

 

 

 

 

 

 

 

 

 

 

 

Input

Holding

# of

 

 

Extra

Data Label

Register

Register

Reg.

Scale

Notes / Units

Notes

Compressor Low Suction Pressure - Event

 

 

 

 

0 = Message

 

30337

40337

1

1 = Warning

1, 2, 3, 4, 5, 6

Type 1

 

 

 

 

2 = Alarm

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Compressor Low Suction Pressure - Event

 

 

 

 

0 = Message

 

30338

40338

1

1 = Warning

1, 2, 3, 4, 5, 6

Type 2

 

 

 

 

2 = Alarm

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Compressor Pump Down Issue - Event

30339

40339

1

0 = disabled

1, 2, 3, 4, 5, 6

Control 1

1 = enabled

 

 

 

 

 

Compressor Pump Down Issue - Event

30340

40340

1

0 = disabled

1, 2, 3, 4, 5, 6

Control 2

1 = enabled

 

 

 

 

 

Compressor Pump Down Issue - Event

 

 

 

 

0 = Message

 

30341

40341

1

1 = Warning

1, 2, 3, 4, 5, 6

Type 1

 

 

 

 

2 = Alarm

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Compressor Pump Down Issue - Event

 

 

 

 

0 = Message

 

30342

40342

1

1 = Warning

1, 2, 3, 4, 5, 6

Type 2

 

 

 

 

2 = Alarm

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Compressor Short Cycle - Event Control 1

30343

40343

1

0 = disabled

1, 2, 3, 4, 5, 6

1 = enabled

 

 

 

 

 

 

Compressor Short Cycle - Event Control 2

30344

40344

1

0 = disabled

1, 2, 3, 4, 5, 6

1 = enabled

 

 

 

 

 

 

 

 

 

 

 

0 = Message

 

Compressor Short Cycle - Event Type 1

30345

40345

1

1 = Warning

1, 2, 3, 4, 5, 6

 

 

 

 

 

2 = Alarm

 

 

 

 

 

 

0 = Message

 

Compressor Short Cycle - Event Type 2

30346

40346

1

1 = Warning

1, 2, 3, 4, 5, 6

 

 

 

 

 

2 = Alarm

 

Compressor Thermal Overload - Event

30347

40347

1

0 = disabled

1, 2, 3, 4, 5, 6

Control 1

1 = enabled

 

 

 

 

 

Compressor Thermal Overload - Event

30348

40348

1

0 = disabled

1, 2, 3, 4, 5, 6

Control 2

1 = enabled

 

 

 

 

 

Compressor Thermal Overload - Event

 

 

 

 

0 = Message

 

30349

40349

1

1 = Warning

1, 2, 3, 4, 5, 6

Type 1

 

 

 

 

2 = Alarm

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Compressor Thermal Overload - Event

 

 

 

 

0 = Message

 

30350

40350

1

1 = Warning

1, 2, 3, 4, 5, 6

Type 2

 

 

 

 

2 = Alarm

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Dig Scroll Comp Discharge Over Temp -

30351

40351

1

0 = disabled

1, 2, 3, 4, 5, 6

Event Ctrl 1

1 = enabled

 

 

 

 

 

Dig Scroll Comp Discharge Over Temp -

30352

40352

1

0 = disabled

1, 2, 3, 4, 5, 6

Event Ctrl 2

1 = enabled

 

 

 

 

 

Dig Scroll Comp Discharge Over Temp -

 

 

 

 

0 = Message

 

30353

40353

1

1 = Warning

1, 2, 3, 4, 5, 6

Event Type 1

 

 

 

 

2 = Alarm

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Dig Scroll Comp Discharge Over Temp -

 

 

 

 

0 = Message

 

30354

40354

1

1 = Warning

1, 2, 3, 4, 5, 6

Event Type 2

 

 

 

 

2 = Alarm

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Ext Air Sensor A High Humidity - Event

30355

40355

1

0 = disabled

1, 2, 3, 4, 5, 6

Control

1 = enabled

 

 

 

 

 

Ext Air Sensor A High Humidity - Event

 

 

 

 

0 = Message

 

30356

40356

1

1 = Warning

1, 2, 3, 4, 5, 6

Type

 

 

 

 

2 = Alarm

 

 

 

 

 

 

 

 

 

 

 

 

 

 

19

Liebert® IntelliSlot® Modbus/BACnet IP

Modbus 485 and Modbus IP Protocols - Thermal Management Products

Table 8 Liebert Challenger 3000, Liebert Challenger ITR, Liebert CW, Liebert Deluxe System/3, Liebert DS, Liebert DSE, Liebert HPM, Liebert PeX- Input and Holding (continued)

Controller

Liebert iCOM v4

 

 

 

 

 

 

 

 

 

 

 

 

Input

Holding

# of

 

 

Extra

Data Label

Register

Register

Reg.

Scale

Notes / Units

Notes

Ext Air Sensor A Low Humidity - Event

30357

40357

1

0 = disabled

1, 2, 3, 4, 5, 6

Control

1 = enabled

 

 

 

 

 

 

 

 

 

 

0 = Message

 

Ext Air Sensor A Low Humidity - Event Type

30358

40358

1

1 = Warning

1, 2, 3, 4, 5, 6

 

 

 

 

 

2 = Alarm

 

Ext Air Sensor A Over Temp - Event Control

30359

40359

1

0 = disabled

1, 2, 3, 4, 5, 6

1 = enabled

 

 

 

 

 

 

 

 

 

 

 

0 = Message

 

Ext Air Sensor A Over Temp - Event Type

30360

40360

1

1 = Warning

1, 2, 3, 4, 5, 6

 

 

 

 

 

2 = Alarm

 

Ext Air Sensor A Under Temp - Event

30361

40361

1

0 = disabled

1, 2, 3, 4, 5, 6

Control

1 = enabled

 

 

 

 

 

 

 

 

 

 

0 = Message

 

Ext Air Sensor A Under Temp - Event Type

30362

40362

1

1 = Warning

1, 2, 3, 4, 5, 6

 

 

 

 

 

2 = Alarm

 

High Return Humidity - Event Control

30363

40363

1

0 = disabled

1, 2, 3, 4, 5, 6

1 = enabled

 

 

 

 

 

 

 

 

 

 

 

0 = Message

 

High Return Humidity - Event Type

30364

40364

1

1 = Warning

1, 2, 3, 4, 5, 6

 

 

 

 

 

2 = Alarm

 

Low Return Humidity - Event Control

30365

40365

1

0 = disabled

1, 2, 3, 4, 5, 6

1 = enabled

 

 

 

 

 

 

 

 

 

 

 

0 = Message

 

Low Return Humidity - Event Type

30366

40366

1

1 = Warning

1, 2, 3, 4, 5, 6

 

 

 

 

 

2 = Alarm

 

Return Air Over Temp - Event Control

30367

40367

1

0 = disabled

1, 2, 3, 4, 5, 6

1 = enabled

 

 

 

 

 

 

 

 

 

 

 

0 = Message

 

Return Air Over Temp - Event Type

30368

40368

1

1 = Warning

1, 2, 3, 4, 5, 6

 

 

 

 

 

2 = Alarm

 

Return Air Under Temp - Event Control

30369

40369

1

0 = disabled

1, 2, 3, 4, 5, 6

1 = enabled

 

 

 

 

 

 

 

 

 

 

 

0 = Message

 

Return Air Under Temp - Event Type

30370

40370

1

1 = Warning

1, 2, 3, 4, 5, 6

 

 

 

 

 

2 = Alarm

 

Fan Hours Exceeded - Event Control

30371

40371

1

0 = disabled

1, 2, 3, 4, 5, 6

1 = enabled

 

 

 

 

 

 

 

 

 

 

 

0 = Message

 

Fan Hours Exceeded - Event Type

30372

40372

1

1 = Warning

1, 2, 3, 4, 5, 6

 

 

 

 

 

2 = Alarm

 

Fan Issue - Event Control

30373

40373

1

0 = disabled

1

1 = enabled

 

 

 

 

 

 

 

 

 

 

 

0 = Message

 

Fan Issue - Event Type

30374

40374

1

1 = Warning

1

 

 

 

 

 

2 = Alarm

 

Main Fan Overload - Event Control

30375

40375

1

0 = disabled

1, 2, 3, 4, 5, 6

1 = enabled

 

 

 

 

 

 

 

 

 

 

 

0 = Message

 

Main Fan Overload - Event Type

30376

40376

1

1 = Warning

1, 2, 3, 4, 5, 6

 

 

 

 

 

2 = Alarm

 

Liebert® IntelliSlot® Modbus/BACnet IP

20

Modbus 485 and Modbus IP Protocols - Thermal Management Products

Table 8 Liebert Challenger 3000, Liebert Challenger ITR, Liebert CW, Liebert Deluxe System/3, Liebert DS, Liebert DSE, Liebert HPM, Liebert PeX- Input and Holding (continued)

Controller

Liebert iCOM v4

 

 

 

 

 

 

 

 

 

 

 

 

Input

Holding

# of

 

 

Extra

Data Label

Register

Register

Reg.

Scale

Notes / Units

Notes

Condenser Issue - Event Control 1

30377

40377

1

0 = disabled

1, 2, 3, 4, 5, 6

1 = enabled

 

 

 

 

 

 

Condenser Issue - Event Control 2

30378

40378

1

0 = disabled

1, 2, 3, 4, 5, 6

1 = enabled

 

 

 

 

 

 

 

 

 

 

 

0 = Message

 

Condenser Issue - Event Type 1

30379

40379

1

1 = Warning

1, 2, 3, 4, 5, 6

 

 

 

 

 

2 = Alarm

 

 

 

 

 

 

0 = Message

 

Condenser Issue - Event Type 2

30380

40380

1

1 = Warning

1, 2, 3, 4, 5, 6

 

 

 

 

 

2 = Alarm

 

System Event Acknowledge/Reset

40381

1

2 = Reset

1, 2, 3, 4, 5, 6

4 = Acknowledge

 

 

 

 

 

 

 

 

 

 

 

0 = Supply

 

Air Temperature Control Sensor

30481

40481

1

1 = Remote

2, 3, 4, 5, 6

 

 

 

 

 

2 = Return

 

Supply Air Over Temp Threshold

30482

40482

1

10

deg C

2, 3, 4, 5, 6

 

 

 

 

 

 

 

Supply Air Over Temp Threshold

30755

40755

1

10

deg F

2, 3, 4, 5, 6

 

 

 

 

 

 

 

Supply Air Under Temp Threshold

30483

40483

1

10

deg C

2, 3, 4, 5, 6

 

 

 

 

 

 

 

Supply Air Under Temp Threshold

30756

40756

1

10

deg F

2, 3, 4, 5, 6

 

 

 

 

 

 

 

Outside Air Temperature

30484

1

10

deg C

2, 3, 4, 5, 6

 

 

 

 

 

 

 

Outside Air Temperature

30757

1

10

deg F

2, 3, 4, 5, 6

 

 

 

 

 

 

 

 

 

 

 

 

0 = Relative

 

Humidity Proportional Control Type

30485

40485

1

1 = Compensated

2, 3, 4, 5, 6

2 = Predictive

 

 

 

 

 

 

 

 

 

 

 

3 = Dew Point

 

 

 

 

 

 

 

 

Ext Air Sensor A Dew Point Temp

30486

-

1

10

deg C

2, 3, 4, 5, 6

 

 

 

 

 

 

 

Ext Air Sensor A Dew Point Temp

30758

-

1

10

deg F

2, 3, 4, 5, 6

 

 

 

 

 

 

 

Ext Dew Point Over Temp Threshold

30487

40487

1

10

deg C

2, 3, 4, 5, 6

 

 

 

 

 

 

 

Ext Dew Point Over Temp Threshold

30759

40759

1

10

deg F

2, 3, 4, 5, 6

 

 

 

 

 

 

 

Ext Dew Point Under Temp Threshold

30488

40488

1

10

deg C

2, 3, 4, 5, 6

 

 

 

 

 

 

 

Ext Dew Point Under Temp Threshold

30760

40760

1

10

deg F

2, 3, 4, 5, 6

 

 

 

 

 

 

 

Compressor Lockout

30489

40489

1

0 = disabled

2, 3, 4, 5, 6

1 = enabled

 

 

 

 

 

 

Main Chilled Water Valve

30491

40491

1

0 = Valve 1

2, 3, 4, 5, 6

1 = Valve 2

 

 

 

 

 

 

Reheater Lockout

30492

40492

1

0 = disabled

2, 3, 4, 5, 6

1 = enabled

 

 

 

 

 

 

Humidifier Lockout

30493

40493

1

0 = disabled

2, 3, 4, 5, 6

1 = enabled

 

 

 

 

 

 

 

 

 

 

 

0 = Supply

 

Fan Control Sensor

30494

40494

1

1 = Remote

2, 3, 4, 5, 6

2 = Return

 

 

 

 

 

 

 

 

 

 

 

3 = Manual

 

 

 

 

 

 

 

 

Fan Speed Minimum Set Point

30495

40495

1

%

2, 3, 4, 5, 6

 

 

 

 

 

 

 

Fan Speed Temperature Set Point

30497

40497

1

10

deg C

2, 3, 4, 5, 6

 

 

 

 

 

 

 

Fan Speed Temperature Set Point

30761

40761

1

10

deg F

2, 3, 4, 5, 6

 

 

 

 

 

 

 

Standby Units

30498

40498

1

2, 3, 4, 5, 6

 

 

 

 

 

 

 

21

Liebert® IntelliSlot® Modbus/BACnet IP

Modbus 485 and Modbus IP Protocols - Thermal Management Products

Table 8 Liebert Challenger 3000, Liebert Challenger ITR, Liebert CW, Liebert Deluxe System/3, Liebert DS, Liebert DSE, Liebert HPM, Liebert PeX- Input and Holding (continued)

Controller

Liebert iCOM v4

 

 

 

 

 

 

 

 

 

 

 

 

Input

Holding

# of

 

 

Extra

Data Label

Register

Register

Reg.

Scale

Notes / Units

Notes

Adjusted Humidity

30499

1

10

% RH

2, 3, 4, 5, 6

 

 

 

 

 

 

 

Return Dew Point

30500

1

10

deg C

2, 3, 4, 5, 6

 

 

 

 

 

 

 

Return Dew Point

30762

1

10

deg F

2, 3, 4, 5, 6

 

 

 

 

 

 

 

Actual Air Temperature Set Point

30501

1

10

deg C

2, 3, 4, 5, 6

 

 

 

 

 

 

 

Actual Air Temperature Set Point

30763

1

10

deg F

2, 3, 4, 5, 6

 

 

 

 

 

 

 

Actual Humidity Set Point

30502

1

-

% RH

2, 3, 4, 5, 6

 

 

 

 

 

 

 

Dew Point Set Point

30503

40503

1

10

deg C

2, 3, 4, 5, 6

 

 

 

 

 

 

 

Dew Point Set Point

30764

40764

1

10

deg F

2, 3, 4, 5, 6

 

 

 

 

 

 

 

Supply Air Over/Under Temperature - Event

30504

40504

1

0 = disabled

2, 3, 4, 5, 6

Control

1 = enabled

 

 

 

 

 

Remote Sensor Over Temp Threshold

30505

40505

1

10

deg C

2, 3, 4, 5, 6

 

 

 

 

 

 

 

Remote Sensor Over Temp Threshold

30765

40765

1

10

deg F

2, 3, 4, 5, 6

 

 

 

 

 

 

 

Remote Sensor Under Temp Threshold

30506

40506

1

10

deg C

2, 3, 4, 5, 6

 

 

 

 

 

 

 

Remote Sensor Under Temp Threshold

30766

40766

1

10

deg F

2, 3, 4, 5, 6

 

 

 

 

 

 

 

Remote Sensor Average Temperature

30507

1

10

deg C

2, 3, 4, 5, 6

 

 

 

 

 

 

 

Remote Sensor Average Temperature

30767

1

10

deg F

2, 3, 4, 5, 6

 

 

 

 

 

 

 

Remote Sensor Maximum Temperature

30508

1

10

deg C

2, 3, 4, 5, 6

 

 

 

 

 

 

 

Remote Sensor Maximum Temperature

30768

1

10

deg F

2, 3, 4, 5, 6

 

 

 

 

 

 

 

Remote Sensor System Average

30509

1

10

deg C

2, 3, 4, 5, 6

Temperature

 

 

 

 

 

 

Remote Sensor System Average

30769

1

10

deg F

2, 3, 4, 5, 6

Temperature

 

 

 

 

 

 

Remote Sensor System Maximum

30510

1

10

deg C

2, 3, 4, 5, 6

Temperature

 

 

 

 

 

 

Remote Sensor System Maximum

30770

1

10

deg F

2, 3, 4, 5, 6

Temperature

 

 

 

 

 

 

Remote Sensor Temperature 1

30551

1

10

deg C

2, 3, 4, 5, 6

 

 

 

 

 

 

 

Remote Sensor Temperature 1

30771

1

10

deg F

2, 3, 4, 5, 6

 

 

 

 

 

 

 

Remote Sensor Temperature 2

30552

1

10

deg C

2, 3, 4, 5, 6

 

 

 

 

 

 

 

Remote Sensor Temperature 2

30772

1

10

deg F

2, 3, 4, 5, 6

 

 

 

 

 

 

 

Remote Sensor Temperature 3

30553

1

10

deg C

2, 3, 4, 5, 6

 

 

 

 

 

 

 

Remote Sensor Temperature 3

30773

1

10

deg F

2, 3, 4, 5, 6

 

 

 

 

 

 

 

Remote Sensor Temperature 4

30554

1

10

deg C

2, 3, 4, 5, 6

 

 

 

 

 

 

 

Remote Sensor Temperature 4

30774

1

10

deg F

2, 3, 4, 5, 6

 

 

 

 

 

 

 

Remote Sensor Temperature 5

30555

1

10

deg C

2, 3, 4, 5, 6

 

 

 

 

 

 

 

Remote Sensor Temperature 5

30775

1

10

deg F

2, 3, 4, 5, 6

 

 

 

 

 

 

 

Remote Sensor Temperature 6

30556

1

10

deg C

2, 3, 4, 5, 6

 

 

 

 

 

 

 

Remote Sensor Temperature 6

30776

1

10

deg F

2, 3, 4, 5, 6

 

 

 

 

 

 

 

Remote Sensor Temperature 7

30557

1

10

deg C

2, 3, 4, 5, 6

 

 

 

 

 

 

 

Remote Sensor Temperature 7

30777

1

10

deg F

2, 3, 4, 5, 6

 

 

 

 

 

 

 

Remote Sensor Temperature 8

30558

1

10

deg C

2, 3, 4, 5, 6

 

 

 

 

 

 

 

Remote Sensor Temperature 8

30778

1

10

deg F

2, 3, 4, 5, 6

 

 

 

 

 

 

 

Liebert® IntelliSlot® Modbus/BACnet IP

22

Modbus 485 and Modbus IP Protocols - Thermal Management Products

Table 8 Liebert Challenger 3000, Liebert Challenger ITR, Liebert CW, Liebert Deluxe System/3, Liebert DS, Liebert DSE, Liebert HPM, Liebert PeX- Input and Holding (continued)

Controller

Liebert iCOM v4

 

 

 

 

 

 

 

 

 

 

 

 

Input

Holding

# of

 

 

Extra

Data Label

Register

Register

Reg.

Scale

Notes / Units

Notes

Remote Sensor Temperature 9

30559

1

10

deg C

2, 3, 4, 5, 6

 

 

 

 

 

 

 

Remote Sensor Temperature 9

30779

1

10

deg F

2, 3, 4, 5, 6

 

 

 

 

 

 

 

Remote Sensor Temperature 10

30560

1

10

deg C

2, 3, 4, 5, 6

 

 

 

 

 

 

 

Remote Sensor Temperature 10

30780

1

10

deg F

2, 3, 4, 5, 6

 

 

 

 

 

 

 

Air Economizer Availability

30561

1

0 = Not Available

2, 3, 4, 5, 6

1 = Available

 

 

 

 

 

 

 

 

 

 

 

0 = disabled

 

Air Economizer Control Source

30562

40562

1

1 = internal

2, 3, 4, 5, 6

 

 

 

 

 

2 = external

 

Chilled Water Valve Hours

30563

40563

1

hr

2, 3, 4, 5, 6

 

 

 

 

 

 

 

Cooling Capacity

30564

1

%

2, 3, 4, 5, 6

 

 

 

 

 

 

 

Cooling Control Temperature

30565

1

10

deg C

2, 3, 4, 5, 6

 

 

 

 

 

 

 

Cooling Control Temperature

30781

1

10

deg F

2, 3, 4, 5, 6

 

 

 

 

 

 

 

Fan Speed Control Temperature

30566

1

10

deg C

2, 3, 4, 5, 6

 

 

 

 

 

 

 

Fan Speed Control Temperature

30782

1

10

deg F

2, 3, 4, 5, 6

 

 

 

 

 

 

 

 

 

 

 

 

0 = Disabled

 

Free Cooling Internal Control Mode

30567

40567

1

1 = Contact

2, 3, 4, 5, 6

2 = Temperature

 

 

 

 

 

 

 

 

 

 

 

3 = Set Point

 

 

 

 

 

 

 

 

 

 

 

 

 

0 = Supply

 

Humidity Control Sensor

30667

40667

1

1 = Remote

3, 4, 5, 6

 

 

 

 

 

2 = Return

 

Digital Scroll Compressor Loading 1

30668

1

%

3, 4, 5, 6

 

 

 

 

 

 

 

Digital Scroll Compressor Loading 2

30669

1

%

3, 4, 5, 6

 

 

 

 

 

 

 

Static Pressure Set Point

30672

40672

1

10

Pa

3, 6

 

 

 

 

 

 

 

Unit Static Pressure

30673

1

10

Pa

3, 6

 

 

 

 

 

 

 

System Static Pressure

30674

1

10

Pa

3, 6

 

 

 

 

 

 

 

 

 

 

 

 

0 = Inactive

 

Condenser Low Noise Mode State

30675

1

1 = Active (Interval)

3, 4, 5, 6

 

 

 

 

 

2 = Active (Full Day)

 

Condenser Low Noise Mode Schedule

30676

40676

1

0 = disabled

3, 4, 5, 6

Control

1 = enabled

 

 

 

 

 

Condenser Low Noise Mode Max Fan

30677

40677

1

%

3, 4, 5, 6

Speed

 

 

 

 

 

 

Condenser Normal Mode Max Fan Speed

30678

40678

1

%

3, 4, 5, 6

 

 

 

 

 

 

 

 

 

 

 

 

1 = Monday

 

 

 

 

 

 

2 = Tuesday

 

 

 

 

 

 

4 = Wednesday

3, 4, 5, 6

Condenser Low Noise Mode - Interval Days

30679

40679

1

8 = Thursday

 

 

 

 

 

16 = Friday

 

 

 

 

 

 

32 = Saturday

 

 

 

 

 

 

64 = Sunday

 

 

 

 

 

 

1 = Monday

 

 

 

 

 

 

2 = Tuesday

 

 

 

 

 

 

4 = Wednesday

 

Condenser Low Noise Mode - Full Days

30680

40680

1

8 = Thursday

3, 4, 5, 6

 

 

 

 

 

16 = Friday

 

 

 

 

 

 

32 = Saturday

 

 

 

 

 

 

64 = Sunday

 

23

Liebert® IntelliSlot® Modbus/BACnet IP

Modbus 485 and Modbus IP Protocols - Thermal Management Products

Table 8 Liebert Challenger 3000, Liebert Challenger ITR, Liebert CW, Liebert Deluxe System/3, Liebert DS, Liebert DSE, Liebert HPM, Liebert PeX- Input and Holding (continued)

Controller

Liebert iCOM v4

 

 

 

 

 

 

 

 

 

 

 

 

Input

Holding

# of

 

 

Extra

Data Label

Register

Register

Reg.

Scale

Notes / Units

Notes

Condenser Low Noise Mode Start Time

30681

40681

2

Seconds since Midnight

3, 4, 5, 6

 

 

 

 

 

 

 

Condenser Low Noise Mode Stop Time

30683

40683

2

Seconds since Midnight

3, 4, 5, 6

 

 

 

 

 

 

 

Pump Hours 1

30685

40685

2

hr

5

 

 

 

 

 

 

 

Pump Hours 2

30687

40687

2

hr

5

 

 

 

 

 

 

 

System Input RMS A-N 1

30800

1

10

VAC

6

 

 

 

 

 

 

 

System Input RMS A-N 2

30801

1

10

VAC

6

 

 

 

 

 

 

 

System Input RMS A-N 3

30802

1

10

VAC

6

 

 

 

 

 

 

 

System Input RMS A-N 4

30803

1

10

VAC

6

 

 

 

 

 

 

 

System Input RMS A-N 5

30804

1

10

VAC

6

 

 

 

 

 

 

 

System Input RMS A-N 6

30805

1

10

VAC

6

 

 

 

 

 

 

 

System Input RMS B-N 1

30810

1

10

VAC

6

 

 

 

 

 

 

 

System Input RMS B-N 2

30811

1

10

VAC

6

 

 

 

 

 

 

 

System Input RMS B-N 3

30812

1

10

VAC

6

 

 

 

 

 

 

 

System Input RMS B-N 4

30813

1

10

VAC

6

 

 

 

 

 

 

 

System Input RMS B-N 5

30814

1

10

VAC

6

 

 

 

 

 

 

 

System Input RMS B-N 6

30815

1

10

VAC

6

 

 

 

 

 

 

 

System Input RMS C-N 1

30820

1

10

VAC

6

 

 

 

 

 

 

 

System Input RMS C-N 2

30821

1

10

VAC

6

 

 

 

 

 

 

 

System Input RMS C-N 3

30822

1

10

VAC

6

 

 

 

 

 

 

 

System Input RMS C-N 4

30823

1

10

VAC

6

 

 

 

 

 

 

 

System Input RMS C-N 5

30824

1

10

VAC

6

 

 

 

 

 

 

 

System Input RMS C-N 6

30825

1

10

VAC

6

 

 

 

 

 

 

 

System Input RMS Current Phase A 1

30830

1

10

A AC

6

 

 

 

 

 

 

 

System Input RMS Current Phase A 2

30831

1

10

A AC

6

 

 

 

 

 

 

 

System Input RMS Current Phase A 3

30832

1

10

A AC

6

 

 

 

 

 

 

 

System Input RMS Current Phase A 4

30833

1

10

A AC

6

 

 

 

 

 

 

 

System Input RMS Current Phase A 5

30834

1

10

A AC

6

 

 

 

 

 

 

 

System Input RMS Current Phase A 6

30835

1

10

A AC

6

 

 

 

 

 

 

 

System Input RMS Current Phase B 1

30840

1

10

A AC

6

 

 

 

 

 

 

 

System Input RMS Current Phase B 2

30841

1

10

A AC

6

 

 

 

 

 

 

 

System Input RMS Current Phase B 3

30842

1

10

A AC

6

 

 

 

 

 

 

 

System Input RMS Current Phase B 4

30843

1

10

A AC

6

 

 

 

 

 

 

 

System Input RMS Current Phase B 5

30844

1

10

A AC

6

 

 

 

 

 

 

 

System Input RMS Current Phase B 6

30845

1

10

A AC

6

 

 

 

 

 

 

 

System Input RMS Current Phase C 1

30850

1

10

A AC

6

 

 

 

 

 

 

 

System Input RMS Current Phase C 2

30851

1

10

A AC

6

 

 

 

 

 

 

 

System Input RMS Current Phase C 3

30852

1

10

A AC

6

 

 

 

 

 

 

 

System Input RMS Current Phase C 4

30853

1

10

A AC

6

 

 

 

 

 

 

 

System Input RMS Current Phase C 5

30854

1

10

A AC

6

 

 

 

 

 

 

 

System Input RMS Current Phase C 6

30855

1

10

A AC

6

 

 

 

 

 

 

 

Liebert® IntelliSlot® Modbus/BACnet IP

24