Emerson 1000VA, 1500VA User Manual

0 (0)
Emerson 1000VA, 1500VA User Manual

Liebert® PSA

Quick-Start Guide - 1000VA/1500VA, 120V

IMPORTANT SAFETY INSTRUCTIONS

SAVE THESE INSTRUCTIONS

This manual contains important instructions that should be followed during installation and maintenance of the UPS.

Intended for installation in a controlled environment.

Maximum ambient temperature 104°F (40°C).

! CAUTION

To reduce the risk of fire, connect only to a circuit provided with 20 amperes maximum branch circuit overcurrent protection in accordance with the national code, ANSI/NFPA 70.

Do not connect equipment that may overload the UPS or demand half-wave rectification, such as a laser printer.

Connect the UPS only to an earthed / grounded outlet that meets national and local electrical safety guidelines.

Locate the UPS near a wall outlet. Do not use an extension cord between the UPS and the outlet.

The Liebert PSA has been designed for small office/home office use only; it is NOT recommended for use in life-support applications.

In the event of an emergency, press the OFF button and disconnect the power cord from the AC power supply to properly disable the UPS.

Do not attach power strips or surge suppressors to the UPS.

Do not attempt to service any parts inside the UPS except the batteries. Failure to adhere to this could cause personal injury or equipment malfunction and void the warranty.

For technical support:

Visit www.liebert.com or

Send an e-mail to upstech@emersonnetworkpower.com.

SETUP

Step 1 Inspect the Package

Inspect the package and the UPS upon receipt. Notify the carrier and dealer of visible damage.

Liebert shutdown

software

CD

Quick-start

guide

USB cable

UPS

Step 2 Decide Where to Place the UPS

Step 5 Check the Site Wiring Fault Indicator

See figure at right for the location of the Site Wiring Indicator on the rear of the UPS.

Check the rear of the UPS to make sure the Site Wiring Fault indicator is NOT illuminated.

Caution: If the Site Wiring Fault indicator is illuminated, have a qualified electrician check the wall receptacle wiring and fix any problems.

Step 6 Connect the Loads

The UPS has three battery backup outlets that provide power when the UPS operates on battery (see Figure 2 below).

Plug the loads into the battery backup outlets on the rear of the UPS.

Caution: Do not connect a laser printer to the

UPS.

USB

SITE WIRING

 

 

FAULT

 

 

IN

OUT

Battery Power Supply

Full Time Surge Protection

AC OUTPUT

 

 

AC INPUT

 

 

The UPS must be placed indoors, protected from water, direct sunlight and excessive heat.

Provide at least 4" (100mm) of clearance on all sides of the unit for proper ventilation.

Step 3 Charge the UPS Battery Before

Use

The UPS battery is not charged before shipping. It MUST be charged before use.

• Connect the UPS power cord to a wall outlet and charge for at least eight hours.

Note: If battery is placed in storage, charge the battery every six months if kept at 5°F to 85°F (-15°C to 29°C)—or every three months if kept at 86°F (30°C) or higher.

Step 4 Start the UPS

After the battery is fully charged:

Turn on the UPS by pressing the On/Off button (see Figure 1 below).

LED 1 should be illuminated (green), indicating the UPS is operating in Normal Mode.

Step 7 Connect the Network Surge Protection

The UPS has two RJ-45 jacks for network lines (see

 

 

 

 

Figure 2 below).

RS232

USB

SITE WIRING

 

 

 

FAULT

 

• Connect a single-line network cable into the RJ-45

 

 

IN

OUT

network surge protection IN jack on the rear of the

 

 

 

 

UPS.

Battery Power Supply

Full Time Surge Protection

 

 

AC OUTPUT

 

 

• Connect an RJ-45 cable from the OUT jack on the

AC INPUT

rear of the UPS to a port on a PC or network device

 

 

such as a router.

 

Step 8 Set Up Liebert shutdown software

To start using the Liebert shutdown software:

• Install the Liebert shutdown software. See the software user manual for installation instructions.

• Connect one end of the USB cable (supplied) to the USB port on the rear of the UPS. Connect the other end to a USB port on the computer. See the software user manual for operating instructions.

UPS CONTROLS AND CONNECTIONS

Figure 1 - Front Panel LEDs Figure 2 - Rear Panel

LED 1 LED 2

On/Off

LED 3

LED 4

USB

(green) (amber)

button

(amber)

(red)

interface

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Utility

 

 

 

!

 

Fault

Battery backup

symbol

 

 

 

symbol

outlets (6)

 

 

 

NEMA 5-15R

 

 

 

 

 

 

 

Battery

 

 

 

Overload

 

symbol

 

 

 

symbol

Input

 

 

 

 

 

 

 

 

EMERSON

 

Liebert

 

breaker

 

 

 

 

 

Network Power

® PSA

 

 

 

 

 

AC Power System

 

NEMA

 

 

 

 

 

 

 

 

 

 

 

 

 

 

5-15P

UPS Status, Alarm Conditions and Alerts

 

USB

SITE WIRING

 

 

 

FAULT

 

 

 

IN

OUT

 

Battery Power Supply

Full Time Surge Protection

AC INPUT

AC OUTPUT

 

 

BREAKER

 

 

 

AC INPUT

 

 

 

Site Wiring Fault indicator

RJ-45 jacks (2) - network protection

Surge outlets (2) NEMA 5-15R

Condition

LED

Color

Solid/Flashing

Audible Alarm

Normal Mode

LED 1

Green

Solid (steady glow)

(None)

Battery Mode

LED 2

Amber

Flashes every 3 seconds

Every 3 seconds

Battery Low

LED 2

Amber

Flashes every 1 second till end of discharge (EOD)

Every 1 second

Overload

LED 3

Amber

Solid (steady glow) until load drops or breaker trips

Continuous

Battery Replacement

LED 4

Red

Flashes every 1 second for 5 seconds only

Every 1 second for 5 seconds only

Fault

LED 4

Red

Solid (steady glow) until UPS shuts down after 5 seconds

Continuous until UPS shuts down