B-VENT DECORATIVE ELECTRONIC IGNITION GAS FIREPLACE OWNER’S OPERATION AND INSTALLATION MANUAL

MODELS M36E(B,H), M42E(B,H), VM36E(B,H) AND VM42E(B,H)

NATURAL GAS

MODELS M36EP(B,H), M42EP(B,H), VM36EP(B,H) AND

VM42EP(B,H) PROPANE/LP GAS

WARNING: If the information in these instructions is not followed exactly, a fire or explosion may result causing property damage, personal injury or death.

FOR YOUR SAFETY

Do not store or use gasoline or any other flammable vapors or liquids in the vicinity of this or any other appliance.

WHAT TO DO IF YOU SMELL GAS :

Do not try to light any appliance.

Do not touch any electrical switch;

Do not use any phone in your building.

Immediatelycallyourgassupplierfromaneighbor’s phone. Follow the gas supplier’s instructions.

If you cannot reach your gas supplier, call the fire department.

Installationandservicemustbeperformedbyaqualified installer, service agency or the gas supplier.

Save this manual for future reference. For more information, visit www.desatech.com

WARNING: Improper installation, adjustment, alteration, service or maintenance can cause injury or propertydamage.Refertothismanualforcorrectinstallation and operational procedures. For assistance or additional information consult a qualified installer, service agency or the gas supplier.

NOT FOR USE WITH SOLID FUEL

CHECK LOCAL CODES PRIOR TO INSTALLATION

SAVE THIS BOOK

This book is valuable. In addition to instructing you on how to install and maintain your appliance, it also contains information that will enable you to obtain replacement parts or optional accessory items when needed. Keep it with your

other important papers.

This appliance may be installed in an aftermarket*, permanently located, manufactured (mobile) home, where not prohibited by state or local codes.

This appliance is only for use with the type of gas indicated on the rating plate.

This appliance is not convertible for use with other gases, unless a certified kit is used.

*Aftermarket: Completion of sale, not for purpose of resale, from the manufacturer.

TABLE OF CONTENTS

Safety Information ...............................................

3

Cleaning and Maintenance

................................

20

Unpacking ...........................................................

4

Service Hints .....................................................

 

20

Introduction..........................................................

4

Technical Service ..............................................

 

20

Selecting Location...............................................

5

Replacement Parts............................................

 

20

Product Specifications.........................................

6

Wiring Diagram..................................................

 

21

Pre-Installation Preparation.................................

7

Troubleshooting.................................................

 

22

Venting Installation ..............................................

9

Illustrated Parts Breakdown .......and Parts List

24

Installation ..........................................................

11

Accessories.......................................................

 

29

Operating Fireplace...........................................

18

Warranty Information............................

Back Page

Inspecting Burners ............................................

19

 

 

 

2

www.desatech.com

108796-01K

SAFETY INFORMATION

WARNING: This product contains and/or generates chemicals known to the State of California to cause cancer or birth defects or other reproductive harm.

IMPORTANT:Readthisowner’s manualcarefullyandcompletely before trying to assemble, operate or service this fireplace.

Improper use of this fireplace cancauseseriousinjuryordeath from burns, fire, explosions, electrical shock and carbon monoxide poisoning.

DANGER:Carbonmonoxide poisoning may lead to death!

This fireplace is a vented product. This fireplace willnot produceany gas leakage into yourhome if properly installed.This fireplace must be properly installedbyaqualifiedserviceperson.Ifthisunitis notproperlyinstalledbyaqualifiedserviceperson, gas leakage can occur.

Carbon Monoxide Poisoning: Early signs of carbon monoxide poisoning resemble the flu, with headaches, dizziness or nausea. If you have these signs, the fireplace may not have been installed properly. Get fresh air at once! Have fireplace inspected and serviced by a qualified service person. Some people are more affected by carbon monoxide than others. These include pregnant women, people with heart or lung disease or anemia, those under the influence of alcohol and those at high altitudes.

Propane/LP gas and natural gas are both odorless. An odor-making agent is added to each of these gases. The odor helps you detect a gas leak. However, the odor added to these gases can fade. Gas may be present even though no odor exists.

Makecertainyoureadandunderstandallwarnings. Keep this manual for reference. It is your guide to safe and proper operation of this fireplace.

WARNING: Any change to this fireplace or its controls can be dangerous.

1.This appliance is only for use with the type of gas indicated on the rating plate. This appliance is not convertible for use with other gases unless a certified kit is used.

2.Forpropane/LPfireplace,donotplacepropane/ LP supply tank(s) inside any structure. Locate propane/LPsupplytank(s)outdoors.Toprevent performance problems, do not use propane/LP fuel tank of less than 100 lbs. capacity.

3.If you smell gas

shut off gas supply

do not try to light any appliance

do not touch any electrical switch; do not use any phone in your building

immediately call your gas supplier from a neighborʼsphone.Followthegassupplier's instructions

ifyoucannotreachyougassupplier,callthe fire department.

4.Never install the fireplace

in a recreational vehicle

wherecurtains,furniture,clothingorother flammable objects are less than 42" from the front, top or sides of the fireplace

in high traffic areas

in windy or drafty areas

5.Thisfireplacereacheshightemperatures.Keep children and adults away from hot surfaces to avoidburnsorclothingignition.Fireplacewill remain hot for a time after shutdown. Allow surfaces to cool before touching.

6.Carefullysuperviseyoungchildrenwhenthey are in the room with fireplace.

7.A hearth extension is not required with this appliance. If one is installed, it is for aesthetic purposes only and does not have to meet the standard requirements.

8.Turnfireplaceoffandletcoolbeforeservicing or repairing. Only a qualified service person should install, service or repair this fireplace. Have fireplace inspected annually by a qualified service person.

9.You must keep control compartments, burners and circulating air passages clean. More frequent cleaning may be needed due to excessive lint and dust from carpeting, bedding material, etc. Turn off the gas valve and pilot light before cleaning fireplace.

10.Have venting system inspected annually by a qualified service person. If needed, have venting system cleaned or repaired. See Cleaning and Maintenance, page 20.

108796-01K

www.desatech.com

3

SAFETY INFORMATION

Continued

11.Keep the area around your fireplace clear of combustible materials, gasoline and other flammable vapor and liquids. Do not run fireplace where these are used or stored. Do not place items such as clothing or decorations on or around fireplace.

12.Do not use this fireplace to cook food or burn paper or other objects.

13.Do not use any solid fuels (wood, coal, paper, cardboard, etc.) in this fireplace. Use only the gas type indicated on fireplace nameplate.

14.Thisappliance,wheninstalled,mustbeelectrically grounded in accordance with local codes or, in the absence of local codes, with the

National Electrical Code, ANSI/NFPA 70 or the Canadian Electrical Code, CSA C22.1.

15.Do not obstruct the flow of combustion and ventilation air in any way. Provide adequate clearancesaroundairopeningsintothecombustion chamber along with adequate accessibility clearance for servicing and proper operation.

16.Do not install fireplace directly on carpeting, vinyl tile or any combustible material other than wood. The fireplace must set on a metal or wood panel extending the full width and depth of the fireplace.

17.Do not use fireplace if any part has been exposed to or under water. Immediately call a qualifiedservicepersontoarrangeforreplacement of the unit.

18.Do not operate fireplace if any log is broken.

19.Do not use a blower insert, heat exchanger insert or other accessory not approved for use with this fireplace.

20.Provide adequate clearances around air openings.

UNPACKING

The following items are packed inside the firebox. Remove before positioning firebox into framing.

Transition Collar - For vent connection

Ceramic Log Pack - Shrink-wrapped on cardboard

Three (3) plastic bags containing lava rock, pan and ember materials

Rear Log - Remove the two plastic quick ties from around the burner and grate

Grate Stand - Lift off of burner pan

Check all items for any shipping damage. If damaged, promptly inform dealer or distributor where you bought the product.

Safely retain these items for later installation.

INTRODUCTION

Models M36E(P)(B,H), VM36E(P)(B,H), M42E(P)(B,H) and VM42E(P)(B,H) are vented gas fireplaces that use an electronic control valve and electronic ignition system. A 6" B-Type venting system and a listed type vent cap are not supplied but are required for proper operation. See venting instructions on pages 9 and 10.

WARNING: This gas appliance must not be connected to a chimney flue servicing a solid fuel burning appliance.

Models M36E(B,H), VM36E(B,H), M42E(B,H) and VM42E(B,H) are factory equipped for use with natural gas and must be converted when intended for use with propane/LP gas. A respective model PCBE-36 or PCBE-42 conversion kit may be purchasedforsimpleconversion topropane/LP gas. See Accessories, page 29.

BEFORE YOU BEGIN

Before beginning the installation of your appliance, read these instructions through completely.

This DESA appliance and its approved components are safe when installed according to this installation manual and are operated as recommendedbyDESA.UnlessyouuseDESAapproved components tested for this appliance, YOU MAY

CAUSE A FIRE HAZARD!

TheDESAwarrantywillbevoidedbyandDESAdisclaims any responsibility for the following actions :

A)Modification of the appliance or any of the components.

B)Use of any component part not approved by DESA in combination with this appliance.

C)Installationand/oroperationinamannerother than instructed in this manual.

D)The burning of anything other than the type of gas approved for use in this gas appliance.

Theinstallationmustconformwithlocalcodesor,in theabsenceoflocalcodes,withthecurrentNational Fuel Gas Code, ANSI Z223.1/NFPA 54 or with the current CAN/CGA B149 Installation Codes.

This appliance complies with ANSI Z21.50-2000 and CSA 2.22-2000 as Vented Gas Fireplaces and is listed and tested by the Canadian Standards Association to the above test standards.

4

www.desatech.com

108796-01K

INTRODUCTION

Continued

WARNING: Installation of this appliance should be done by a qualified service person well trained in the installation of such appliances. You will alsoneedabuildingpermitfrom your local Building and Safety Commissioner before installing this appliance; otherwise your insuranceco.maynotcoverthis appliance.

NOTICE: This appliance is not intendedtobeusedasaprimary source of heat.

CAUTION: Do not connect appliance before pressure testing gas piping. Damage to gas valve may result and an unsafe condition may be caused.

The appliance and itʼs individual shutoff valve must be disconnected from the gas supply piping systemduringanypressuretestingofthatsystemat test pressures in excess of 1/2 psig (3.5 kPa).

The appliance must be isolated from the gas supply piping system by closing its individual manual shutoffvalveduringanypressuretestingofthegas supply piping system at test pressures equal to or less than 1/2 psig (3.5 kPa).

For the purpose of input adjustment two pressure taps (for IN and OUT pressures) are provided on the gas control valve for test gauge connections to the appliance.

SELECTING LOCATION

To determine the safest and most efficient location for your appliance, you must take into consideration the following guidelines:

1.The location must allow for proper clearances (see Clearances, page 7).

2.Consider a location where heat output would not be affected by drafts, air conditioning ducts, windows or doors.

3.A location that avoids the cutting of joists or roof rafters will make installation easier. Figure 1 shows a plan view of a few common locations.

Flush installations are recommended where living space is limited or at a premium and since the space required to enclose the appliance would be located beyond an outside wall, this would also reduce the cutting of joists, roof rafters and such. Check local codes for any restrictions.

Projectedinstallationscanextendanydistance into the room. A projection may be ideal for a new addition on an existing, finished wall.

Corner installations make use of space that may not normally be used and provides a wider and more efficient range for radiant heat transference.

Internal wall installations provide a discreet option for room separation and can also be ideal as an addition to an existing wall.

CORNER

INTERNAL WALL INSTALLATION

INSTALLATION

FLUSH

FULL INSTALLATION

PROJECTION

INSTALLATION

Figure 1 - Possible Locations for Installing Appliance

108796-01K

www.desatech.com

5

PRODUCT SPECIFICATIONS

GAS RATING - NATURAL

 

M36E(B,H),

 

M42E(B,H),

 

VM36E(B,H)

 

VM42E(B,H)

Max. Input Rating:

40,000 Btu/Hr

 

45,000 Btu/Hr

Manifold Pressure:

3.5 in. WC (.87 kPa)

 

3.5 in. WC (.87 kPa)

Minimum Supply Pressure:

4.5 in. WC (1.12 kPa)

 

4.5 in. WC (1.12 kPa)

Maximum Supply Pressure:

10.5 in. WC (2.66 kPa)

 

10.5 in. WC (2.66 kPa)

Orifice Size:

# 30

 

# 29

GAS RATING - PROPANE/LP

 

 

M36P(B,H), VM36P(B,H)

 

M42P(B,H), VM42P(B,H)

Max. Input Rating:

40,000 Btu/Hr

 

45,000 Btu/Hr

 

 

 

 

Manifold Pressure:

10 in. WC (2.49 kPa)

 

10 in. WC (2.49 kPa)

Minimum Supply Pressure:

11 in. WC (2.74 kPa)

 

11 in. WC (2.74 kPa)

Maximum Supply Pressure:

13 in. WC (3.23 kPa)

 

13 in. WC (3.23 kPa)

Orifice Size:

# 52

 

# 50

A

For Use With 6"Ø Type B-1 Vent Pipe Only

Stand Off

 

Collar

7"

BC

7"

Alternate

Gas Supply

 

 

Inlet

X

K

Outside Air

Kit Location I

(Optional) J

R

S T

7"

P

Q

F

E HEARTH AREA H

DDIMENSIONS

G

Glass Door

1.5"

13.5"

(Optional)

 

NO

 

W

L

V

M

 

Model 36

Model 42

 

Model 36

Model 42

 

Model 36

Model 42

A

29"

36"

I

40 1/4"

44 1/4"

Q

13 7/8"

14"

B

5/8"

5/8"

J

21"

24"

R

10 1/2"

12 1/2"

C

41"

48"

K

8"

9"

S

2 1/2"

2 1/2"

D

12"

14"

L

34 3/4"

42"

T

8 1/8"

8 1/8"

E

21 1/4"

23"

M

42"

49"

U

11"

12 3/4"

F

22 1/4" (24" w/o Brick)

29 1/4" (31" w/o Brick)

N

36"

40"

V

7"

7"

G

32 5/8" (34" w/o Brick)

39 1/2" (41 1/4" w/o Brick)

O

37"

41"

W

2 1/4"

2 1/4"

H

15 3/4" (16 3/4" w/o Brick)

17 3/4" (18 3/4" w/o Brick)

P

8 5/8"

10 1/2"

X

5"

4 1/2"

Figure 2 - Appliance Dimensions

6

www.desatech.com

108796-01K

Desa M36EP, M42EP, VM42EPB, VM36EP User Manual

PRE-INSTALLATION

PREPARATION

CLEARANCES

Minimum clearances to combustibles are:

Back and Sides of Outer Surround. . .0" min.

Drywall to Sides of Front Face

(Nailing Flanges). . . . . . . . . . . . . .0" min.

“B” Vent Surfaces. . . . . . . . . . . . . . . .1" min.

Ceiling to Opening . . . . . . . . . . . . . .42" min.

Floor . . . . . . . . . . . . . . . . . . . . . . . . . .0" min.

Perpendicular Wall . . . . . . . . . . .See Figure 6

CAUTION: Do not block required air spaces with insulation or any other material. Do not obstruct effective opening of appliance with any type of facing material.

 

Nailing 2 x 4 Stud

Left Side

Flange

 

Back

 

Surround

 

 

 

0" Clearance

 

 

 

0"

 

Front Face

Drywall

 

 

Figure 3 - Minimum Clearances

 

(Top View)

 

 

1" (25mm) Min.

 

Clearance to

 

 

"B" Vent's Outer Pipe

 

Ceiling

 

42" (1067mm) Min. Clearance from Opening to

Ceiling 0" Clearance

*

0" Clearance to Combustible or Noncombustible Flooring

*

*

DO NOT BLOCK

OR OBSTRUCT

 

OPENINGS

Maintain 2" (51mm) Min. Clearance to the Transition Pipe as Measured at the Outer Vent Collar

*Required Air Spaces are

Indicated with

an "

". Do Not

*

 

Pack with

Insulation or Any

Other Material

Figure 4 - Minimum Clearances

(Front View)

MANTEL CLEARANCES AND WALL

DETAILS

 

A combustible mantle shelf maybe installed a

maximum 12" (229 mm) from the wall. Figures

5 and 6 show the minimum allowable distances

from various combustible mantle components

in relation to the fireplace opening.

12"

Combustible

(229mm)

Materials

 

Header

6" (152mm)

 

A

 

BSpacer

 

3" (76mm)

 

 

 

1

1

/2"

 

 

 

 

 

 

 

(38mm) Max.

 

 

 

M36E(B,H),

 

M42E(B,H),

 

M36EP(B,H)

 

M42EP(B,H)

 

VM36E(B,H),

 

VM42E(B,H),

 

VM36EP(B,H)

 

VM42EP(B,H)

A

14" (356 mm)

15" (381 mm)

B

8" (203 mm)

 

9" (229 mm)

Figure 5 - Mantel Clearances - Side View

 

(Cross Section)

 

 

 

 

TOP VIEW

 

 

 

 

Outer Surround

 

 

 

 

 

Combustible

 

 

 

 

 

Material May

 

 

 

 

 

Be Used

1 1/2" (38 mm)

 

 

 

SAFE

 

 

 

ZONE

Max.

3" (76 mm)

 

 

 

 

 

Max.

 

 

 

 

 

6" (152 mm)

 

 

 

 

 

Max.

 

 

 

 

 

 

 

 

A

Perpendicular

 

 

 

 

 

 

 

 

 

B

Wall

 

M36E(B,H),

 

M42E(B,H),

 

M36EP(B,H)

 

M42EP(B,H)

 

VM3E6(B,H),

 

VM42E(B,H),

 

VM36EP(B,H)

 

VM42EP(B,H)

A

9" (229 mm)

 

6" (152 mm)

B

12" (305 mm)

 

9" (229 mm)

Figure 6 - Side Clearances - Top View

 

(Cross Section)

108796-01K

www.desatech.com

7

PRE-INSTALLATION

PREPARATION

Continued

FRAMING

1.Frame appliance enclosure as illustrated in Figures 7 and 8.

Note: If a wall covering is used to line the enclosure, then all measurements must be from the surface of the covering.

2.Place the appliance into the framing and secure it.

Note: If appliance is to be raised above floor level, a platform must be built to support the appliance.

3.Install the supply line to the appliance using a 1/2" NPT black iron gas line terminating 2 5/16" above the bottom of the appliance. The gas line must be installed through the lower left side accesspointoralternateaccess hole inthebottom of the appliance (see Figure 19, page 13).

4.Repack insulation around the gas lineto cover any remaining openings in the conduit sleeve. Prepare the incoming gas line with teflon tape orpipejointcompoundandhook-upincoming gas line to the flexible gas line.

Note: If 1/2" NPT black iron pipe does not mate withfittingattheendof flexiblegas line, remove fitting and replace with a 37 degree flare 3/4"-12, 1/2" NPT (female) fitting.

WARNING: When finishing appliance, do not overlap combustible material onto the black frontface.Brick,tileorothernoncombustible materials may be applied to the face provided that any gap is between the material usedandthefaceiscaulkedwith a noncombustible caulking.

A

B

C

M36E(B,H),

M42E(B,H),

M36EP(B,H)

M42EP(B,H)

VM36E(B,H),

VM42E(B,H),

VM36EP(B,H)

VM42EP(B,H)

A

40

3

/

" (1020 mm)

44

3

/ " (1121 mm)

 

 

8

 

 

8

B

21 3/8" (543 mm)

23 1/8" (587 mm)

C

41

1/4" (1048 mm)

48 1/4" (1226 mm)

Figure 7 - Rough Opening for Installing in Wall

These Dimensions Allow for a 3/4" Clearance at Sides and Back of Fireplace. However, 0" Clearance is Permitted

D

C

A

B

3/4" Clearance Not Required at

Nailing Flanges

M36E(B,H),

M42E(B,H),

M36EP(B,H)

M42EP(B,H)

VM36E(B,H),

VM42E(B,H),

VM36EP(B,H)

VM42EP(B,H)

A

24

1

/ "

27

9

/

 

"

 

 

2

 

 

16

 

 

(622.3 mm)

(700.1 mm)

 

 

 

 

 

 

 

 

 

B

73

7

/ "

83

7

/

"

 

 

8

 

8

 

 

 

(1876.4 mm)

(2130.4 mm)

 

 

 

C

52 3/16"

59 5/16"

 

(1326 mm)

(1506.6 mm)

 

 

 

 

 

 

 

 

 

D

17

1

/ "

19

1

/

"

 

 

4

 

2

 

 

 

(438.2 mm)

(495.3 mm)

Figure 8 - Corner Installation Guidelines

8

www.desatech.com

108796-01K

PRE-INSTALLATION PREPARATION Continued

INSTALLING TRANSITION PIPE AND STARTER COLLAR

The transition pipe and starter collar shown in Figure9aresuppliedwiththefireplace,unattached andreadyforinstallation.Removethestartercollar andsetaside.Slidethetransitionpipeoverthevent collar and attach with a minimum of three screws. Replace the starter collar over the transition pipe and attach using four screws located on the leg stands (five used on the model M42E). To install B-vent piping, slide the first piece of B-vent over the transition pipe and attach with either a minimum of two screws or other means approved by the vent manufacturer.

B-Vent Piping

Starter Collar

Transition Pipe

Vent Collar

Figure 9 - Installing Transition Pipe and

Starter Collar VENTING INSTALLATION

A B-type venting system must be connected to the appliance for venting to the outside of the building.

The following section is provided as a guide to a standard B-type vent installation.

Standing codes requirements concerning B-type vent installations may vary within your state, province or local codes jurisdiction. Therefore, it is recommended that you check with your local building codes for specific requirements or in absence of local codes, follow Section 7.0 of the current National Fuel Gas Code ANSI Z223.1/NFPA 54 and in Canada with CAN/CGA B149 for Category I systems using double wall B-1 vent pipe.

This gas appliance must be vented to the outdoors only and may not be terminated into an attic space or into a chimney flue servicing a solid-fuel burning appliance.

This appliance may be vented through a manufacturedchimneysystemoramasonrychimneyusing a B-vent adapter or a chimney liner system if all are listed, inspected and approved by local codes and/or building authorities.

The examples shown in Figure 10, page 10 are typical of most B-vent installations and codes practices.

Example 1: Shows the minimum allowable system height and lateral offset for a 60° degree or greater inclination. Code specifies that offsets at 60° degrees or greater are considered horizontal and must follow the 75% percent rule for lateral to total vertical system height. Codes also allows only one offset in the total system when at 60° degrees or greater. The total vertical height in this example represents the minimum height of 8 feet and therefore the allowable lateral is 6 feet when the 75% percent rule applies. If the lateral length must exceed 75% then the system must be sized in accordance with the Category I venting tables.

Example 2: Shows a multiple offset each at 45° degrees of inclination. Multiple offsets are permittediftheydonotexceed45°degreesofinclination. Thetotallengthsofthetwooffsetsarenotrequired to meet the 75% percent allowable rule.

Example 3: Shows a single offset at 45° degrees of inclination and therefore the lateral length at 10 feet of offset does not have to meet the 75% percent rule.

In each case the offsets must be supported and firestops must be positioned wherever the vent must pass through a sub-floor, ceiling joist or an attic overhang. The vent pipe must terminate vertically into a listed type vent cap and extend a sufficient height through an approved roof flashing, roof jack or a roof thimble. At all points the listed clearances must be maintained.

Vent terminations must be located in accordance withheightandproximityrulesofNFPANo.54or CAN/CGAB149. These rules apply to vents at 12 in. diameter or less and require a minimum height in accordance with the roof pitch and a minimum of 8 ft. distance from a vertical wall or obstruction (see Figure 11, page 10).

If venting horizontally through a side wall becomesnecessary,alistedthimbleapprovedforuse with B-type vent must be used. Check with your local codes before venting through a side wall.

Some codes areas allow the use of existing B-type ventsystemsifthesystemisatorabovetherecommended diameter of the flue; in this case 6".

108796-01K

www.desatech.com

9

VENTING INSTALLATION

Continued

 

 

Listed

 

 

 

 

 

 

Vent Cap

 

 

Listed

Listed

 

 

 

 

 

Vent Cap

 

 

 

 

 

Vent Cap

 

 

 

 

 

 

 

Maintain

 

Maintain

 

 

 

 

 

Listed

 

 

Maintain

 

Listed

 

 

 

 

 

Clearance

 

Maintain

Listed

 

Clearance

 

 

 

 

Support Each

 

Listed

Clearance

 

 

 

 

 

 

 

Lateral At

 

Clearance

 

 

 

 

Least Every

45

 

 

 

 

60

Six (6) Feet

12' Min.

 

 

 

 

 

 

 

 

 

 

 

 

 

8'

6'

 

 

45

10'

12' Min.

Position

 

45

Position

12' Min.

 

Position

 

Firestop

 

Firestop

 

Firestop

 

 

 

Maintain

 

Maintain

 

Maintain

 

 

Listed

 

Listed

 

Listed

 

 

Clearance

 

Clearance

 

Clearance

EXAMPLE 1 EXAMPLE 2 EXAMPLE 3

Figure 10 - Typical B-Vent Configuration

The flue connection must be made using listed B-type connectors and the existing system must be code inspected for damage and proper installation.

It is not recommended that this appliance be commonventedwithanexistinggasburningappliance. However, if it becomes necessary to common vent this appliance, the venting system must be sized and configured in accordance with the common ventingguidesAppendixGofthecurrentNational Fuel Gas Code ANSI Z223.1/NFPA 54 and in Canada with CAN/CGA B149.

Note: Before connecting this appliance to an existing vent system or a common venting system consult with your local architect, planner or building official.

WARNING: This appliance must be properly connected to a system and must not be connected to a chimney flue servicing a separate solid fuel burning appliance.

Lowest

Listed

 

 

 

 

Discharge

Vent Cap

 

 

 

 

Opening

 

 

8 Ft. Min.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Listed Gas

 

 

 

 

 

 

 

 

Vent

 

 

 

 

 

 

x

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

12

 

Roof Pitch x/12

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Listed Clearance

H (Min)

 

 

 

 

 

 

 

 

 

 

 

 

 

Height

 

 

 

 

 

 

 

 

From Roof

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

H (Min.)

 

 

 

Roof Pitch

 

 

Ft.

m

 

 

 

 

 

 

Flat to 6/12

 

1.0

0.30

 

 

 

 

 

 

6/12 to 7/12

 

1.25

0.38

 

 

 

 

 

 

Over 7/12 to 8/12

 

1.5

0.46

 

 

 

 

 

 

Over 8/12 to 9/12

 

2.0

0.61

 

 

 

 

 

 

Over 9/12 to 10/12

 

2.5

0.76

 

 

 

 

 

 

Over 10/12 to 11/12

 

3.25

0.99

 

 

 

 

 

 

Over 11/12 to 12/12

 

4.0

1.22

 

 

 

 

 

 

Over 12/12 to 14/12

 

5.0

1.52

 

 

 

 

 

 

Over 14/12 to 16/12

 

6.0

1.83

 

 

 

 

 

 

Over 16/12 to 18/12

 

7.0

2.13

 

 

 

 

 

 

Over 18/12 to 20/12

 

7.5

2.27

 

 

 

 

 

 

Over 20/12 to 21/12

 

8.0

2.44

 

 

 

 

 

 

 

 

 

 

 

Figure 11 - B-Vent Terminations

10

www.desatech.com

108796-01K