Desa GWP6, GWRN10, GWP10T, GWRP10, GWN6 User Manual

...
0 (0)
Desa GWP6, GWRN10, GWP10T, GWRP10, GWN6 User Manual

VENT-FREE GAS HEATER

TM SAFETY INFORMATION AND

INSTALLATION MANUAL

Forvisit..com

GWN6, GWP6

GWN10, GWP10

GWN10T, GWP10T

GWRN10 AND GWRP10

WARNING: If the information in this manual is not followed exactly, a fire or explosion may result causing property damage, personal injury, or loss of life.

Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance.

WHAT TO DO IF YOU SMELL GAS

Do not try to light any appliance.

Do not touch any electrical switch; do not use any phone in your building.

Immediately call your gas supplier from a neighbor’s phone. Follow the gas supplier’s instructions.

If you cannot reach your gas supplier, call the fire department.

Installation and service must be performed by a qualified installer, service agency, or the gas supplier.

WARNING: Improper installation, adjustment, alteration, service, or maintenance can cause injury or property damage. Refer to this manual for correct installation and operational procedures. For assistance or additional information consult a qualified installer, service agency, or the gas supplier.

WARNING: This is an unvented gas-fired heater. It uses air (oxygen) from the room in which it is installed.Provisionsforadequate combustion and ventilation air must be provided. Refer to Air For Combustion and Ventilation on page 4 of this manual.

This appliance may be installed in an aftermarket*, permanently located, manufactured (mobile) home, where not prohibited by local codes.

This appliance is only for use with the type of gas indicated on the rating plate. This appliance is not convertible for use with other gases.

*Aftermarket: Completion of sale, not for purpose of resale, from the manufacturer

Save thisfor.

TABLE OF CONTENTS 2 SAFETY INFORMATION

TABLE OF CONTENTS

 

SAFETY INFORMATION ............................................................

2

UNPACKING ...............................................................................

3

PRODUCT IDENTIFICATION .....................................................

3

PRODUCT FEATURES ..............................................................

3

LOCAL CODES ...........................................................................

3

AIR FOR COMBUSTION AND VENTILATION ...........................

4

INSTALLATION ...........................................................................

6

OPERATING HEATER ...............................................................

11

INSPECTING BURNER ............................................................

15

CLEANING AND MAINTENANCE ............................................

16

TROUBLESHOOTING ..............................................................

17

ILLUSTRATED PARTS BREAKDOWN AND PARTS LIST .......

20

SPECIFICATIONS ....................................................................

 

26

REPLACEMENT PARTS ..........................................................

 

27

SERVICE HINTS .......................................................................

 

27

TECHNICAL SERVICE .............................................................

 

27

SERVICE PUBLICATIONS .......................................................

 

27

ACCESSORY ............................................................................

 

27

PARTS CENTRALS ..................................................................

 

28

OWNER’S REGISTRATION FORM ..........................................

 

29

WARRANTY INFORMATION ......................................

Back Cover

SAFETY INFORMATION

WARNINGS

IMPORTANT: Read this owner’s manual carefully and completely before trying to assemble, operate, or service this heater. Improper use of this heater can cause serious injury or death from burns, fire, explosion, electrical shock, and carbon monoxide poisoning.

DANGER: Carbon monoxide poisoning may lead to death!

Carbon Monoxide Poisoning: Early signs of carbon monoxide poisoning resemble the flu, with headaches, dizziness, or nausea. If you have these signs, the heater may not be working properly. Get fresh air at once! Have heater serviced. Some people are more affected by carbon monoxide than others. These include pregnant women, persons with heart or lung disease or anemia, those under the influence of alcohol, and those at high altitudes.

Natural and Propane/LP Gas: Natural and propane/LP gases are fuel gases. Fuel gases are odorless. An odor-making agent is added to fuel gases. The odor helps you detect a fuel gas leak. However, the odor added to fuel gas can fade. Fuel gas may be present even though no odor exists.

Make certain you read and understand all warnings. Keep this manual for reference. It is your guide to safe and proper operation of this heater.

WARNING: Any change to this heater or its controls can be dangerous.

WARNING: Do not use any accessory not approved for use with this heater.

Due to high temperatures, the appliance should be located out of traffic and away from furniture and draperies.

Do not place clothing or other flammable material on or near the appliance. Never place any objects on the heater.

Surface of heater becomes very hot when running heater. Keep children and adults away from hot surface to avoid burns or clothing ignition. Heater will remain hot for a time after shutdown. Allow surface to cool before touching.

Carefully supervise young children when they are in the same room with heater.

Make sure grill guard is in place before running heater.

Keep the appliance area clear and free from combustible materials, gasoline, and other flammable vapors and liquids.

1.This appliance is only for use with the type of gas indicated on the rating plate. This appliance is not convertible for use with other gases.

2.Do not place propane/LP supply tank(s) inside any structure. Locate propane/LP supply tank(s) outdoors.

3.Do not install 10,000 Btu units in a bathroom.

For morevisit www..com

107902-01D

SAFETY INFORMATION UNPACKING 3

PRODUCT IDENTIFICATION PRODUCT FEATURES LOCAL CODES

SAFETY INFORMATION

Continued

4.If you smell gas

Shut off gas supply

Do not try to light any appliance

Do not touch any electrical switch; do not use any phone in your building

Immediately call your gas supplier from a neighbor’s phone. Follow the gas supplier’s instructions

If you cannot reach your gas supplier, call the fire department

5.This heater needs fresh, outside air ventilation to run properly. This heater has an Oxygen Depletion Sensing (ODS) safety shutoff system. The ODS shuts down the heater if not enough fresh air is available. See Air for Combustion and Ventilation, pages 4 and 5.

6.Keep all air openings in the front and bottom of heater clear and free of debris. This will insure enough air for proper combustion.

7.If heater shuts off, do not relight until you provide fresh, outside air. If heater keeps shutting off, have it serviced.

8.Do not run heater

where flammable liquids or vapors are used or stored

under dusty conditions

9.Before using furniture polish, wax, carpet cleaner, or similar products, turn heater off. If heated, the vapors from these products may create a white powder residue within burner box or on adjacent walls or furniture.

10.Do not use heater if any part has been under water. Immediately call a qualified service technician to inspect the room heater and to replace any part of the control system and any gas control which has been under water.

11.Turn off heater and let cool before servicing. Only a qualified service person should service and repair heater.

12.Operating heater above elevations of 4,500 feet could cause pilot outage.

13.To prevent performance problems, do not use propane/LP fuel tank of less than 100 lbs. capacity.

UNPACKING

1.Remove heater from carton.

2.Remove all protective packaging applied to heater for shipment.

3.Check heater for any shipping damage. If heater is damaged, promptly inform dealer where you bought heater.

PRODUCT IDENTIFICATION

Piezo Ignitor

Piezo Ignitor

Button

Control Knob

Button

Control Knob

 

 

Grill

 

Guard

 

Glass

Burners

Panel

 

Front

 

Panel

 

Heater

 

Cabinet

 

Blue Flame Heater

Infrared Heater

Figure 1 - Vent-Free Gas Heater

 

PRODUCT FEATURES

SAFETY DEVICE

This heater has a pilot with an Oxygen Depletion Sensing (ODS) safety shutoff system. The ODS/pilot is a required feature for ventfree room heaters. The ODS/pilot shuts off the heater if there is not enough fresh air.

PIEZO IGNITION SYSTEM

This heater has a piezo ignitor. This system requires no matches, batteries, or other sources to light heater.

LOCAL CODES

Install and use heater with care. Follow all local codes. In the absence of local codes, use the latest edition of National Fuel Gas Code ANSI Z223.1/NFPA 54*.

*Available from:

American National Standards Institute, Inc.

1430 Broadway

New York, NY 10018

National Fire Protection Association, Inc.

Batterymarch Park

Quincy, MA 02269

For more information, visit www.desatech.com

107902-01D

4

AIR FOR COMBUSTION AND VENTILATION

Providing Adequate Ventilation

 

Determining Fresh-Air Flow For Heater Location

 

 

AIR FOR COMBUSTION AND VENTILATION

WARNING: This heater shall not be installed in a confined space or unusually tight construction unless provisions are provided for adequate combustion and ventilation air. Read the following instructions to insure proper fresh air for this and other fuelburning appliances in your home.

Today’s homes are built more energy efficient than ever. New materials, increased insulation, and new construction methods help reduce heat loss in homes. Home owners weather strip and caulk around windows and doors to keep the cold air out and the warm air in. During heating months, home owners want their homes as airtight as possible.

While it is good to make your home energy efficient, your home needs to breathe. Fresh air must enter your home. All fuel-burning appliances need fresh air for proper combustion and ventilation.

Exhaust fans, fireplaces, clothes dryers, and fuel burning appliances draw air from the house to operate. You must provide adequate fresh air for these appliances. This will insure proper venting of vented fuel-burning appliances.

PROVIDING ADEQUATE VENTILATION

The following are excerpts from National Fuel Gas Code, ANSI Z223.1/NFPA 54, Section 5.3, Air for Combustion and Ventilation.

All spaces in homes fall into one of the three following ventilation classifications:

1.Unusually Tight Construction

2.Unconfined Space

3.Confined Space

The information on pages 4 and 5 will help you classify your space and provide adequate ventilation.

Unusually Tight Construction

The air that leaks around doors and windows may provide enough fresh air for combustion and ventilation. However, in buildings of unusually tight construction, you must provide additional fresh air.

Unusually tight construction is defined as construction where:

a.walls and ceilings exposed to the outside atmosphere have a continuous water vapor retarder with a rating of one perm (6 x 10-11 kg per pa-sec-m2) or less with openings gasketed or sealed and

b.weather stripping has been added on openable windows and doors and

c.caulking or sealants are applied to areas such as joints around window and door frames, between sole plates and floors, between wall-ceiling joints, between wall panels, at penetrations for plumbing, electrical, and gas lines, and at other openings.

If your home meets all of the three criteria above, you must provide additional fresh air. See Ventilation Air From Outdoors, page 5.

If your home does not meet all of the three criteria above, proceed to Determining Fresh-Air Flow For Heater Location.

Confined and Unconfined Space

The National Fuel Gas Code, ANSI Z223.1/NFPA 54 defines a confined space as a space whose volume is less than 50 cubic feet per 1,000 Btu per hour (4.8 m3 per kw) of the aggregate input rating of all appliances installed in that space and an unconfined space as a space whose volume is not less than 50 cubic feet per 1,000 Btu per hour (4.8 m3 per kw) of the aggregate input rating of all appliances installed in that space. Rooms communicating directly with the space in which the appliances are installed*, through openings not furnished with doors, are considered a part of the unconfined space.

* Adjoining rooms are communicating only if there are doorless passageways or ventilation grills between them.

DETERMINING FRESH-AIR FLOW FOR HEATER LOCATION

Determining if You Have a Confined or Unconfined Space

Use this work sheet to determine if you have a confined or unconfined space.

Space: Includes the room in which you will install heater plus any adjoining rooms with doorless passageways or ventilation grills between the rooms.

1.Determine the volume of the space (length x width x height). Length x Width x Height = ___________ cu. ft. (volume of space)

Example: Space size 22 ft. (length) x 18 ft. (width) x 8 ft. (ceiling height) = 3168 cu. ft. (volume of space)

If additional ventilation to adjoining room is supplied with grills or openings, add the volume of these rooms to the total volume of the space.

2.Multiply the space volume by 20 to determine the maximum Btu/Hr the space can support.

__________ (volume of space) x 20 = (Maximum Btu/Hr the space can support)

Example: 2560 cu. ft. (volume of space) x 20 = 51,200 (maximum Btu/Hr the space can support)

For morevisit www..com

107902-01D

AIR FOR COMBUSTION AND VENTILATION

Continued

3.Add the Btu/Hr of all fuel burning appliances in the space.

Vent-free heater

 

_____________ Btu/Hr

Gas water heater*

 

_____________ Btu/Hr

Gas furnace

 

_____________ Btu/Hr

Vented gas heater

 

_____________ Btu/Hr

Gas fireplace logs

 

_____________ Btu/Hr

Other gas appliances* +

_____________ Btu/Hr

Total

=

_____________ Btu/Hr

* Do not include direct-vent gas appliances. Direct-vent draws combustion air from the outdoors and vents to the outdoors.

Example:

 

 

Gas water heater

 

40,000

 

_____________ Btu/Hr

Vent-free heater

+

10,000

_____________ Btu/Hr

Total

=

50,000

_____________ Btu/Hr

AIR FOR COMBUSTION AND VENTILATION

5

Determining Fresh-Air Flow For Heater Location

Ventilation Air

 

 

 

VENTILATION AIR

Ventilation Air From Inside Building

This fresh air would come from an adjoining unconfined space. When ventilating to an adjoining unconfined space, you must provide two permanent openings: one within 12" of the ceiling and one within 12" of the floor on the wall connecting the two spaces (see options 1 and 2, Figure 2). You can also remove door into adjoining room (see option 3, Figure 2). Follow the National Fuel Gas Code, ANSI Z223.1/NFPA 54, Section 5.3, Air for Combustion and Ventilation for required size of ventilation grills or ducts.

Ventilation Air From Outdoors

Provide extra fresh air by using ventilation grills or ducts. You must provide two permanent openings: one within 12" of the ceiling and one within 12" of the floor. Connect these items directly to the outdoors or spaces open to the outdoors. These spaces include attics and crawl spaces. Follow the National Fuel Gas Code, ANSI Z223.1/NFPA 54, Section 5.3, Air for Combustion and Ventilation for required size of ventilation grills or ducts.

4.Compare the maximum Btu/Hr the space can support with the actual IMPORTANT: Do not provide openings for inlet or outlet air into

amount of Btu/Hr used.

__________________ Btu/Hr (maximum the space can support)

__________________ Btu/Hr (actual amount of Btu/Hr used)

Example: 51,200 Btu/Hr (maximum the space can support)

50,000 Btu/Hr (actual amount of Btu/Hr used)

The space in the above example is a confined space because the actual Btu/ Hr used is more than the maximum Btu/Hr the space can support. You must provide additional fresh air. Your options are as follows:

A.Rework worksheet, adding the space of an adjoining room. If the extra space provides an unconfined space, remove door to adjoining room or add ventilation grills between rooms. See Ventilation Air From Inside Building.

B.Vent room directly to the outdoors. See Ventilation Air From Outdoors.

C.Install a lower Btu/Hr heater, if lower Btu/Hr size makes room unconfined.

If the actual Btu/Hr used is less than the maximum Btu/Hr the space can support, the space is an unconfined space. You will need no additional fresh air ventilation.

WARNING: If the area in which the heater may be operated is smaller than that defined as an unconfined space or if the building is of unusually tight construction, provide adequate combustion and ventilation air by one of the methods described in the

National Fuel Gas Code, ANSI Z223.1/NFPA 54, Section 5.3 or applicable local codes.

attic if attic has a thermostat-controlled power vent. Heated air entering the attic will activate the power vent.

 

12"

 

Ventilation Grills

Ventilation

Into Adjoining Room,

Option 2

Grills

Or

into Adjoining

Remove

Room,

Door into

Option 1

Adjoining

 

Room,

 

Option 3

 

12"

Figure 2 - Ventilation Air from Inside Building

Ventilated

Outlet Attic

Air

Outlet

Air

To Attic

To

Crawl

Space

Inlet

Air

 

 

Inlet Air

 

Ventilated

 

 

 

 

 

Crawl Space

 

 

 

 

 

 

 

 

Figure 3 - Ventilation Air from Outdoors

For more information, visit www.desatech.com

107902-01D

6

INSTALLATION

Check Gas Type

 

 

INSTALLATION

NOTICE: This heater is intended for use as supplemental heat. Use this heater along with your primary heating system. Do not install this heater as your primary heat source. If you have a central heating system, you may run system’s circulating blower while using heater. This will help circulate the heat throughout the house. In the event of a power outage, you can use this heater as your primary heat source.

WARNING: A qualified service person must install heater. Follow all local codes.

CHECK GAS TYPE

Use only the correct type of gas (natural or propane/LP). If your gas supply is not the correct gas type, do not install heater. Call dealer where you bought heater for proper type heater.

INSTALLATION ITEMS

Before installing heater, make sure you have the items listed below.

for propane/LP gas, external regulator (supplied by installer)

piping (check local codes)

sealant (resistant to propane/LP gas)

equipment shutoff valve *

ground joint union

sediment trap

tee joint

pipe wrench

for natural gas, test gauge connection*

* A CSA design-certified equipment shutoff valve with 1/8" NPT tap is an acceptable alternative to test gauge connection. Purchase the optional CSA design-certified equipment shutoff valve from your dealer. See Accessory, page 29.

LOCATING HEATER

This heater is designed to be mounted on a wall.

WARNING: Maintain the minimum clearances shown in Figure 4. If you can, provide greater clearances from floor, ceiling, and joining wall.

WARNING: Never install the heater

in a bathroom (10,000 Btu/hr only. 6,000 Btu/hr models are allowed in a bathroom. Check local codes.)

in a recreational vehicle

where curtains, furniture, clothing, or other flammable objects are less than 36 inches from the front, top, or sides of the heater

as a fireplace insert

in high traffic areas

in windy or drafty areas

CAUTION: This heater creates warm air currents. These currents move heat to wall surfaces next to heater. Installing heater next to vinyl or cloth wall coverings or operating heater where impurities (such as but not limited to, tobacco smoke, aromatic candles, cleaning fluids, oil or kerosene lamps, etc.) in the air exist, may discolor walls or cause odors.

IMPORTANT: Vent-free heaters add moisture to the air. Although this is beneficial, installing heater in rooms without enough ventilation air may cause mildew to form from too much moisture. See Air for Combustion and Ventilation, pages 4 and 5.

CAUTION: If you install the heater in a home garage

heater pilot and burner must be at least 18 inches above floor

locate heater where moving vehicle will not hit it

For convenience and efficiency, install heater

where there is easy access for operation, inspection, and service

in coldest part of room

 

CEILING

6" Blueflame

36"

Minimum

8" Plaque

 

Minimum

 

From

 

Sides Of

 

Heater

 

 

Right

Left

Side

Side

 

3"Minimum ToTTop Surface

Of

eting,

Of

Carpeting, Tile Or Other

Combustible Material

Figure 4 - Mounting Clearances As Viewed From Front of Heater

For morevisit www..com

107902-01D

INSTALLATION

7

Installation Items

Locating Heater

 

Installing Heater To Wall

 

 

 

INSTALLATION

Continued

INSTALLING HEATER TO WALL

Marking Screw Locations

1.Determine where you will locate heater.

WARNING: Maintain minimum clearances shown in Figure 5. If you can, provide greater clearances from floor and joining wall.

2.Mark two mounting screw locations on wall (see Figure 5).

 

 

8 7/8"

 

 

 

7 3/4"

 

 

 

 

 

 

 

 

 

 

 

 

 

Blue Flame

 

 

 

 

 

 

 

10 7/8" Plaque

 

 

 

 

 

 

 

Minimum To

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Maintain 6"

 

 

 

 

 

 

WALL

Clearance

Mounting

20 1/4"

 

From Wall

 

 

 

 

 

 

 

 

JOINING

 

 

 

 

Screw

Minimum To

 

 

 

 

Locations

 

 

 

 

 

From Floor

 

 

 

 

 

 

 

 

 

Maintain 3"

 

 

 

 

 

 

 

 

 

Clearance

FLOOR

Figure 5 - Mounting Screw Locations

Installing Two Mounting Screws

Note: Wall anchors and mounting screws are in hardware package. The hardware package is provided with heater.

Attaching to wall stud method

For attaching mounting screw to wall stud

1.Drill hole at marked location using 9/64" drill bit.

2.Insert mounting screw into wall stud.

3.Tighten screw until 1/16" space (thickness of penny) is between screwhead and wall.

Attaching to wall anchor method

Follow instructions below to attach mounting screws to hollow walls (wall areas between studs) or solid walls (concrete or masonry).

1.Drill holes at marked locations using 5/16" drill bit. For solid walls (concrete or masonry), drill at least 1 1/4" deep.

2.Fold wall anchor (see Figure 6).

3.Insert wall anchor (wings first) into hole. Tap anchor flush to wall.

4.For thin walls (1/2" or less), insert red key into wall anchor. Push red key to “pop” open anchor wings (see Figure 7). IMPORTANT: Do not hammer key! For thick walls (over 1/2" thick) or solid walls, do not pop open wings.

5.Tighten two screws until 1/16" space (thickness of penny) is between screwheads and wall (see Figure 8).

Thin Walls (1/4" to 1/2" thick)

Figure 6 - Folding Anchor

Figure 7 - Popping Open Anchor

 

Wings For Thin Walls

 

Thin or

 

Thick Wall

 

(thick wall

 

shown)

1/16"

 

Space

 

 

Solid

 

Wall

Figure 8 - Tightening Anchors

Placing Heater On Mounting Screws

1.Locate two keyhole slots on back panel of heater (see Figure 9).

2.Place large openings of slots over screwheads. Slide heater down until screws are in small portion of slots.

Keyhole Slots

Figure 9 - Location Of Keyhole Slots On Back Panel Of Heater

For more information, visit www.desatech.com

107902-01D

8

INSTALLATION

Installing Heater To Wall (Cont.)

 

Connecting To Gas Supply

 

 

INSTALLATION

Continued

Removing Front Panel Of Heater

1.Remove two screws near bottom corners of front panel.

2.Lift straight up on grill guard until it stops. Grill guard will slide up about 1/4".

3.Pull bottom of front panel forward, then down.

Figure 10 - Removing Front Panel Of Heater

Installing Bottom Mounting Screw

1.Locate bottom mounting hole. This hole is near bottom on back panel of heater (see Figure 11).

2.Mark screw location on wall.

3.Remove heater from wall.

4.If installing bottom mounting screw into hollow or solid wall, install wall anchor. Follow steps 1 through 5 under Attaching To Wall Anchor Method, page 7. If installing bottom mounting screw into wall stud, drill hole at marked location using 9/64" drill bit.

5.Replace heater on wall.

6.Insert bottom anchor screw through back panel into bottom anchor or drilled hole (see Figure 11).

7.Tighten screw until heater is firmly secured to wall. Do not over tighten.

Note: Do not replace front panel at this time. Replace front panel after making gas connections and checking for leaks (see pages 9 and 10).

CONNECTING TO GAS SUPPLY

WARNING: This appliance requires a 3/8" NPT (National Pipe Thread) inlet connection to the pressure regulator.

WARNING: A qualified service person must connect heater to gas supply. Follow all local codes.

WARNING: For natural gas, never connect heater to private (non-utility) gas wells. This gas is commonly known as wellhead gas.

IMPORTANT: For natural gas, check gas line pressure before connecting heater to gas line. Gas line pressure must be no greater than 14 inches of water. If gas line pressure is higher, heater regulator damage could occur.

CAUTION: For propane/LP gas, never connect heater directly to the propane/LP supply. This heater requires an external regulator (not supplied). Install the external regulator between the heater and propane/LP supply.

For propane/LP gas, the installer must supply an external regulator. The external regulator will reduce incoming gas pressure. You must reduce incoming gas pressure to between 11 and 14 inches of water. If you do not reduce incoming gas pressure, heater regulator damage could occur. Install external regulator with the vent pointing down as shown in Figure 12. Pointing the vent down protects it from freezing rain or sleet.

CAUTION: Use only new, black iron or steel pipe. Internally-tinned copper tubing may be used in certain areas. Check your local codes. Use pipe of large enough diameter to allow proper gas volume to heater. If pipe is too small, undue loss of volume will occur.

Propane/LP

 

Supply Tank

External Regulator

 

Vent Pointing Down

 

Figure 12 - External Regulator With Vent Pointing Down

Figure 11 - Installing Bottom Mounting Screw

(propane/LP systems only)

For morevisit www..com

107902-01D

INSTALLATION

9

Connecting To Gas Supply (Cont.)

Checking Gas Connections

 

 

 

INSTALLATION

Continued

Installation must include equipment shutoff valve, union, and plugged 1/8" NPT tap. Locate NPT tap within reach for test gauge hook up. NPT tap must be upstream from heater (see Figure 13).

IMPORTANT: Install an equipment shutoff valve in an accessible location. The equipment shutoff valve is for turning on or shutting off the gas to the appliance.

Apply pipe joint sealant lightly to male NPT threads. This will prevent excess sealant from going into pipe. Excess sealant in pipe could result in clogged heater valves.

WARNING: Use pipe joint sealant that is resistant to liquid petroleum (LP) gas.

We recommend that you install sediment trap in supply line as shown in Figure 13. Locate sediment trap where it is within reach for cleaning. Install in piping system between fuel supply and heater. Locate sediment trap where trapped matter is not likely to freeze. A sediment trap traps moisture and contaminants. This keeps them from going into heater controls. If sediment trap is not installed or is installed wrong, heater may not run properly.

IMPORTANT: Hold pressure regulator with wrench when connecting it to gas piping and/or fittings. Do not over tighten pipe connection to regulator. The regulator body could be damaged.

3/8" NPT

Pipe Nipple

Ground

Joint Union

Equipment

Shutoff Valve*

Natural Gas

From Gas Meter (4" W.C. to 10.5" W.C. Pressure)

Propane/LP

From External Regulator 3" Minimum

(11" W.C. to 14" W.C. Pressure)

Figure 13 - Gas Connection

Pressure

Regulator

Heater

Cabinet

Tee Joint

 

 

 

Reducer

 

Test

Bushing to

 

 

Gauge

1/8" NPT

 

 

Connection*

1/8" NPT

 

 

 

Plug Tap

 

 

 

 

 

 

Tee

Joint

Pipe Sediment

Nipple Trap

Cap

CHECKING GAS CONNECTIONS

WARNING: Test all gas piping and connections for leaks after installing or servicing. Correct all leaks at once.

WARNING: Never use an open flame to check for a leak. Apply a noncorrosive leak detection fluid to all joints. Bubbles forming show a leak. Correct all leaks at once.

CAUTION: For propane/LP gas, make sure external regulator has been installed between propane/LP supply and heater. See guidelines under Connecting to Gas Supply, pages 8 and 9.

Pressure Testing Gas Supply Piping System

Test Pressures In Excess Of 1/2 PSIG (3.5 kPa)

1.Disconnect appliance with its appliance main gas valve (control valve) and equipment shutoff valve from gas supply piping system. Pressures in excess of 1/2 psig will damage heater regulator.

2.Cap off open end of gas pipe where equipment shutoff valve was connected.

3.Pressurize supply piping system by either opening propane/LP supply tank valve for propane/LP gas or opening main gas valve located on or near gas meter for natural gas, or using compressed air.

4.Check all joints of gas supply piping system. Apply a noncorrosive leak detection fluid to all joints. Bubbles forming show a leak.

5.Correct all leaks at once.

6.Reconnect heater and equipment shutoff valve to gas supply. Check reconnected fittings for leaks.

* A CSA design-certified equipment shutoff valve with 1/8" NPT tap is an acceptable alternative to test gauge connection. Purchase the optional CSA design-certified equipment shutoff valve from your dealer. See Accessory, page 29.

For more information, visit www.desatech.com

107902-01D

10

INSTALLATION

Checking Gas Connections (Cont.)

INSTALLATION

Continued

Test Pressures Equal To or Less Than 1/2 PSIG (3.5 kPa)

1.Close equipment shutoff valve (see Figure 14).

2.Pressurize supply piping system by either opening propane/LP supply tank valve for propane/LP gas or opening main gas valve located on or near gas meter for natural gas, or using compressed air.

3.Check all joints from gas meter for natural or propane/LP supply to equipment shutoff valve (see Figure 15 or 16). Apply a noncorrosive leak detection fluid to all joints. Bubbles forming show a leak.

4.Correct all leaks at once.

Pressure Testing Heater Gas Connections

1.Open equipment shutoff valve (see Figure 14).

Control Valve Location

Gas

Meter

Equipment

Shutoff Valve

Figure 15 - Checking Gas Joints for Natural Gas

2.Open main gas valve located on or near gas meter for natural gas or open propane/LP supply tank valve.

3.Make sure control knob of heater is in the OFF position.

4.Check all joints from equipment shutoff valve to control valve (see Figures 15 and 16). Apply a noncorrosive leak detection fluid to all joints. Bubbles forming show a leak.

5.Correct all leaks at once.

6.Light heater (see Operating Heater pages 11 through 14). Check the rest of the internal joints for leaks.

7.Turn off heater (see To Turn Off Gas to Appliance, pages 12, 13 or 14, depending on your model).

Propane/LP

Supply Tank Control

Valve Location

Equipment

Shutoff Valve

8. Replace front panel.

 

 

Figure 16 - Checking Gas Joints for Propane/LP Gas

 

 

 

Equipment

 

Open

 

 

ON

Shutoff Valve

 

POSITI

 

 

 

O

POSIClosed

Figure 14 - Equipment Shutoff Valve

For morevisit www..com

107902-01D

Loading...
+ 22 hidden pages