Desa GCP10TGCN20T, GCP6 GCN10T, GCP20T, GCN6 User Manual

0 (0)
Desa GCP10TGCN20T, GCP6 GCN10T, GCP20T, GCN6 User Manual

VENT-FREE BLUE FLAME

GAS HEATER

SAFETY INFORMATION AND

INSTALLATION MANUAL

Forvisit..com

CR94-001 UNVENTED

ROOM HEATER

GCN20T, GCP20T

GCN6, GCP6

GCN10T, GCP10T

WARNING: If the information in this manual is not followed exactly, a fire or explosion may result causing property damage, personal injury, or loss of life.

Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance.

WHAT TO DO IF YOU SMELL GAS

Do not try to light any appliance.

Do not touch any electrical switch; do not use any phone in your building.

Immediately call your gas supplier from a neighbor’s phone. Follow the gas supplier’s instructions.

If you cannot reach your gas supplier, call the fire department.

Installation and service must be performed by a qualified installer, service agency, or the gas supplier.

Unvented room heaters are for installation in SINGLE FAMILY TYPE RESIDENCES ONLY, and the installation is limited to ONE (1) unit per residence.

WARNING: Improper installation, adjustment, alteration, service, or maintenance can cause injury or property damage. Refer to this manual for correct installation and operational procedures. For assistance or additional information consult a qualified installer, service agency, or the gas supplier.

WARNING: This is an unvented gas-fired heater. It uses air (oxygen) from the room in which it is installed. Provisions for adequatecombustionandventilationairmust be provided. Refer to Air For Combustion and Ventilation on page 4 of this manual.

This appliance is only for use with the type of gas indicated on the rating plate. This appliance is not convertible for use with other gases.

*Aftermarket: Completion of sale, not for purpose of resale, from the manufacturer

Save thisfor.

TABLE OF CONTENTS 2 SAFETY INFORMATION

TABLE OF CONTENTS

 

SAFETY INFORMATION ............................................................

2

UNPACKING ...............................................................................

3

PRODUCT IDENTIFICATION .....................................................

3

PRODUCT FEATURES ..............................................................

3

LOCAL CODES ...........................................................................

4

AIR FOR COMBUSTION AND VENTILATION ...........................

4

INSTALLATION ...........................................................................

6

OPERATING HEATER ..............................................................

14

INSPECTING BURNER ............................................................

15

CLEANING AND MAINTENANCE ............................................

16

TROUBLESHOOTING ..............................................................

17

ILLUSTRATED PARTS BREAKDOWN AND PARTS LIST .......

20

SPECIFICATIONS .....................................................................

 

26

SERVICE CENTER/PARTS CENTRAL ....................................

 

26

OWNER’S REGISTRATION FORM ..........................................

 

27

REPLACEMENT PARTS ..........................................................

 

29

SERVICE HINTS .......................................................................

 

29

TECHNICAL SERVICE .............................................................

 

29

SERVICE PUBLICATIONS .......................................................

 

29

ACCESSORIES ........................................................................

 

29

WARRANTY INFORMATION ......................................

Back Cover

SAFETY INFORMATION

WARNINGS

IMPORTANT: Read this owner’s manual carefully and completely before trying to assemble, operate, or service this heater. Improper use of this heater can cause serious injury or death from burns, fire, explosion, electrical shock, and carbon monoxide poisoning.

DANGER: Carbon monoxide poisoning may lead to death!

Carbon Monoxide Poisoning: Early signs of carbon monoxide poisoning resemble the flu, with headaches, dizziness, or nausea. If you have these signs, the heater may not be working properly. Get fresh air at once! Have heater serviced. Some people are more affected by carbon monoxide than others. These include pregnant women, persons with heart or lung disease or anemia, those under the influence of alcohol, and those at high altitudes.

Natural and Propane/LP Gas: Natural and propane/LP gases are fuel gases. Fuel gases are odorless. An odor-making agent is added to fuel gases. The odor helps you detect a fuel gas leak. However, the odor added to fuel gas can fade. Fuel gas may be present even though no odor exists.

Make certain you read and understand all warnings. Keep this manual for reference. It is your guide to safe and proper operation of this heater.

WARNING: Any change to this heater or its controls can be dangerous.

WARNING: Do not use any accessory not approved for use with this heater.

WARNING: Do not use a blower insert, heat exchanger insert or other accessory not approved for use with this heater.

Children and adults should be alerted to the hazard of high surface temperature and should stay away to avoid burns or clothing ignition.

Surface of heater becomes very hot when running heater. Heater will remain hot for a time after shutdown. Allow surface to cool before touching.

Any safety screen or guard removed for servicing the appliancemustbereplacedpriortooperationtheheater.

Due to high temperatures, the appliance should be located out of traffic and away from furniture and draperies.

Do not place clothing or other flammable material on or near the appliance. Never place any objects on the heater.

Carefully supervise young children when they are in the same room with heater.

Make sure grill guard is in place before running heater.

Keep the appliance area clear and free from combustible materials, gasoline, and other flammable vapors and liquids.

For morevisit www..com

112157-01A

SAFETY INFORMATION UNPACKING 3

PRODUCT IDENTIFICATION PRODUCT FEATURES

SAFETY INFORMATION

Continued

Installation and repair should be done by a qualified service person. The appliance should be inspected and serviced before use and at least annually by a professional service person. More frequent cleaning may be required due to excessive lint from carpeting, etc. It is imperative that control compartments, burners and circulating air passageways of the appliance be kept clean.

1.This appliance is only for use with the type of gas indicated on the rating plate. This appliance is not convertible for use with other gases.

2.Do not place propane/LP supply tank(s) inside any structure. Locate propane/LP supply tank(s) outdoors.

3.Do not install in a bedroom or a bathroom.

4.If you smell gas

Shut off gas supply

Do not try to light any appliance

Do not touch any electrical switch; do not use any phone in your building

Immediately call your gas supplier from a neighbor’s phone. Follow the gas supplier’s instructions

If you cannot reach your gas supplier, call the fire department

5.This heater needs fresh, outside air ventilation to run properly. This heater has an Oxygen Depletion Sensing (ODS) safety shutoff system. The ODS shuts down the heater if not enough fresh air is available. See Air for Combustion and Ventilation, pages 4 through 6.

6.Keep all air openings in the front and bottom of heater clear and free of debris. This will insure enough air for proper combustion.

7.If heater and pilot shuts off unexpectedly, do not relight the pilot until you provide fresh, outside air. If heater keeps shutting off, have it serviced.

8.Do not run heater

where flammable liquids or vapors are used or stored

under dusty conditions

9.Before using furniture polish, wax, carpet cleaner, or similar products, turn heater off. If heated, the vapors from these products may create a white powder residue within burner box or on adjacent walls or furniture.

10.Do not use heater if any part has been under water. Immediately call a qualified service technician to inspect the room heater and to replace any part of the control system and any gas control which has been under water.

11.Turn off heater and let cool before servicing. Only a qualified service person should service and repair heater.

12.Operating heater above elevations of 4,500 feet (1 370 m) could cause pilot outage due to lower levels of oxygen in the air.

13.To prevent performance problems, do not use propane/LP fuel tank of less than 100 lbs. (45 kg) capacity.

14.Provide adequate clearances around air openings.

15.Before using the heater, provide adequate ventilation. An area of 10 square inches (65 cm2) of opening of a window or roof vent is needed for adequate combustion and ventilation air.

UNPACKING

1.Remove heater from carton.

2.Remove all protective packaging applied to heater for shipment.

3.Check heater for any shipping damage. If heater is damaged, promptly inform dealer where you bought heater.

PRODUCT IDENTIFICATION

Piezo Ignitor

 

Control Knob

Button

Control Knob

Piezo Ignitor

 

Button

 

 

 

 

 

Grill

 

 

 

Guard

 

 

 

Glass

 

 

 

Panel

 

 

 

Front

 

 

 

Panel

 

 

 

Heater

 

6,000/10,000 Btu/Hr

Cabinet

20,000 Btu/Hr

Figure 1 - Vent-Free Gas Heater

PRODUCT FEATURES

SAFETY DEVICE

This heater has a pilot with an Oxygen Depletion Sensing (ODS) safety shutoff system. The ODS/pilot is a required feature for ventfree room heaters. The ODS/pilot shuts off the heater if there is not enough fresh air.

PIEZO IGNITION SYSTEM

This heater has a piezo ignitor. This system requires no matches, batteries, or other sources to light heater.

THERMOSTATIC HEAT CONTROL

Thermostat models have a thermostat sensing bulb and a control valve. This results in the greatest heater comfort. This can also result in lower gas bills.

For more information, visit www.desatech.com

112157-01A

LOCAL CODES

4 AIR FOR COMBUSTION AND VENTILATION

Providing Adequate Ventilation

LOCAL CODES

Install and use heater with care. Follow all local codes. In the absence of local codes, use the latest edition of CAN/CGA B149.1 Natural Gas Installation Code or CAN/CGA B149.2 Propane Installation Code*.

*Available from www.csa.ca or 1-800-463-6727 (call your local gas company for your local codes).

AIR FOR COMBUSTION AND VENTILATION

WARNING: This heater shall not be installed in a confined space or unusually tight construction unless provisions are provided for adequate combustion and ventilation air. Read the following instructions to insure proper fresh air for this and other fuelburning appliances in your home.

Today’s homes are built more energy efficient than ever. New materials, increased insulation, and new construction methods help reduce heat loss in homes. Home owners weather strip and caulk around windows and doors to keep the cold air out and the warm air in. During heating months, home owners want their homes as airtight as possible.

While it is good to make your home energy efficient, your home needs to breathe. Fresh air must enter your home. All fuel-burning appliances need fresh air for proper combustion and ventilation.

Exhaust fans, fireplaces, clothes dryers, and fuel burning appliances draw air from the house to operate. You must provide adequate fresh air for these appliances. This will insure proper venting of vented fuel-burning appliances.

PROVIDING ADEQUATE VENTILATION

The following are excerpts from CAN/CGA B149.1 Natural Gas Installation Code or CAN/CGA B149.2 Propane Installation Code.

All spaces in homes fall into one of the three following ventilation classifications:

1.Unusually Tight Construction

2.Unconfined Space

3.Confined Space

The information on pages 4 through 6 will help you classify your space and provide adequate ventilation.

For more

Unusually Tight Construction

The air that leaks around doors and windows may provide enough fresh air for combustion and ventilation. However, in buildings of unusually tight construction, you must provide additional fresh air.

Unusually tight construction is defined as construction where:

a.walls and ceilings exposed to the outside atmosphere have a continuous water vapor retarder with a rating of one perm (6 x 10-11 kg per pa-sec-m2) or less with openings gasketed or sealed and

b.weather stripping has been added on openable windows and doors and

c.caulking or sealants are applied to areas such as joints around window and door frames, between sole plates and floors, between wall-ceiling joints, between wall panels, at penetrations for plumbing, electrical, and gas lines, and at other openings.

If your home meets all of the three criteria above, you must provide additional fresh air. See Ventilation Air From Outdoors, page 6.

If your home does not meet all of the three criteria above, proceed to Determining Fresh-Air Flow For Heater Location, page 5.

Confined and Unconfined Space

The Canadian Gas Association Certification Requirement, CGA CR94-001 REV. 2 states that when combustion air supply is for the unvented room heater only, it shall be sized at the rate of one (1) square inch per 5000 BTU/HR (1.5 KW) from outdoors or the manufacturer’s specification (whichever is greater). However, combustion air is acceptable when available from the principal heat source and sized to the current CAN/CGA-B149.1 or .2 requirements. Where unvented equipment is installed in an area separated from a combustion air supply by a door, then permanent openings, grills or louvers shall be provided. One shall be within 18 inches (46 cm) from the ceiling and one 18 inches (46 cm) from the floor, sized to one (1) square inch per 1000 BTU/HR (0.29 KW) to allow free movement of air with the source of combustion air supply.

visit www..com

112157-01A

AIR FOR COMBUSTION AND VENTILATION

5

Determining Fresh-Air Flow For Heater Location

AIR FOR COMBUSTION AND VENTILATION

Continued

DETERMINING FRESH-AIR FLOW FOR HEATER LOCATION

Determining if You Have a Confined or Unconfined Space

Use this work sheet to determine if you have a confined or unconfined space.

Space: Includes the room in which you will install heater plus any adjoining rooms with doorless passageways or ventilation grills between the rooms.

1.Determine the volume of the space (length x width x height). Length x Width x Height = ___________ cu. ft. (m3) (volume of space)

Example: Space size 20 ft. (6.1 m) (length) x 16 ft. (4.88 m) (width) x 8 ft. (2.44 m) (ceiling height) = 2560 cu. ft. (72.6m3) (volume of space)

If additional ventilation to adjoining room is supplied with grills or openings, add the volume of these rooms to the total volume of the space.

2.Multiply the space volume by 20 to determine the maximum Btu/Hr (kW) the space can support.

__________ (volume of space) x 20 = [Maximum Btu/Hr (kW) the space can support]

Example: 2560 cu. ft. (72.6m3) (volume of space) x 20 = 51,200 [maximum Btu/Hr (kW) the space can support]

3.Add the Btu/Hr of all fuel burning appliances in the space.

Vent-free heater

 

_____________ Btu/Hr (kW)

Gas water heater*

 

_____________ Btu/Hr (kW)

Gas furnace

 

_____________ Btu/Hr (kW)

Vented gas heater

 

_____________ Btu/Hr (kW)

Gas fireplace logs

 

_____________ Btu/Hr (kW)

Other gas appliances* +

_____________ Btu/Hr (kW)

Total

=

_____________ Btu/Hr (kW)

* Do not include direct-vent gas appliances. Direct-vent draws combustion air from the outdoors and vents to the outdoors.

The space in the above example is a confined space because the actual Btu/Hr (kW) used is more than the maximum Btu/Hr (kW) the space can support. You must provide additional fresh air. Your options are as follows:

A.Rework worksheet, adding the space of an adjoining room. If the extra space provides an unconfined space, remove door to adjoining room or add ventilation grills between rooms. See Ventilation Air From Inside Building, page 6.

B.Vent room directly to the outdoors. See Ventilation Air From Outdoors, page 6.

C.Install a lower Btu/Hr (kW) heater, if lower Btu/Hr (kW) size makes room unconfined.

If the actual Btu/Hr used is less than the maximum Btu/Hr (kW) the space can support, the space is an unconfined space. You will need no additional fresh air ventilation.

WARNING: If the area in which the heater may be operated is smaller than that defined as an unconfined space or if the building is of unusually tight construction, provide adequate combustion and ventilation air by one of the methods described in CAN/CGA B149.1 Natural Gas Installation Code or CAN/CGA B149.2 Propane Installation Code or applicable local code.

Example:

 

 

Gas water heater

 

40,000 (11.7)

 

_____________ Btu/Hr (kW)

Vent-free heater

+

20,000 (5.9)

_____________ Btu/Hr (kW)

Total

=

60,000 (17.6)

_____________ Btu/Hr (kW)

4.Compare the maximum Btu/Hr the space can support with the actual amount of Btu/Hr used.

__________________ Btu/Hr (kW) (maximum the space can support)

__________________ Btu/Hr (kW) (actual amount of Btu/Hr used)

Example: 51,200 Btu/Hr (15kW) (maximum the space can support)

60,000 Btu/Hr (17.6kW) [actual amount of Btu/Hr (kW) used]

For more information, visit www.desatech.com

112157-01A

6

AIR FOR COMBUSTION AND VENTILATION

Ventilation Air

 

INSTALLATION

 

Check Gas Type

 

 

AIR FOR COMBUSTION AND VENTILATION

Continued

VENTILATION AIR

Ventilation Air From Inside Building

Ventilated

Outlet Attic

Air

This fresh air would come from an adjoining unconfined space. When ventilating to an adjoining unconfined space, you must provide two permanent openings: one within 18" (45 cm) of the ceiling and one within 18" (45 cm) of the floor on the wall connecting the two spaces (see options 1 and 2, Figure 2). You can also remove door into adjoining room (see option 3, Figure 2). Follow CAN/CGA B149.1 Natural Gas Installation Code or CAN/ CGA B149.2 Propane Installation Code for required size of ventilation grills or ducts.

Outlet

Air

To Attic

To

Crawl

Space

Inlet

Air

 

 

Inlet Air

 

Ventilated

 

 

 

 

 

Crawl Space

 

 

 

 

 

 

 

 

Ventilation Air From Outdoors

Provide extra fresh air by using ventilation grills or ducts. You must provide two permanent openings: one within 18" (45 cm) of the ceiling and one within 18" (45 cm) of the floor. Connect these items directly to the outdoors or spaces open to the outdoors. These spaces include attics and crawl spaces. Follow CAN/CGA B149.1 Natural Gas Installation Code or CAN/CGA B149.2 Propane Installation Code for required size of ventilation grills or ducts.

IMPORTANT: Do not provide openings for inlet or outlet air into attic if attic has a thermostat-controlled power vent. Heated air entering the attic will activate the power vent.

 

18"

 

12"

 

(45 cm)

 

Ventilation Grills

Ventilation

Into Adjoining Room,

Option 2

Grills

Or

into Adjoining

Remove

Room,

Door into

Option 1

Adjoining

 

Room,

 

Option 3

18"

12"

(45 cm)

Figure 2 - Ventilation Air from Inside Building

For more

Figure 3 - Ventilation Air from Outdoors

INSTALLATION

Installation must conform with local codes or, in the absence of local codes, with the current standard

CAN/CGA B149.1 Natural Gas Installation Code or CAN/CGA B149.2 Propane Installation Code

NOTICE: This heater is intended for use as supplemental heat. Use this heater along with your primary heating system. Do not install this heater as your primary heat source. If you have a central heating system, you may run system’s circulating blower while using heater. This will help circulate the heat throughout the house. In the event of a power outage, you can use this heater as your primary heat source.

WARNING: A qualified service person must install heater. Follow all local codes.

CHECK GAS TYPE

Use only the correct type of gas (natural or propane/LP). If your gas supply is not the correct gas type, do not install heater. Call dealer where you bought heater for proper type heater.

visit www..com

112157-01A

INSTALLATION

7

Installation Items

Locating Heater

 

 

 

INSTALLATION

Continued

INSTALLATION ITEMS

Before installing heater, make sure you have the items listed below.

for propane/LP gas, external regulator (supplied by installer)

piping (check local codes)

sealant (resistant to propane/LP gas)

equipment shutoff valve *

ground joint union

sediment trap

tee joint

pipe wrench

for natural gas, test gauge connection*

* A CSA design-certified equipment shutoff valve with 1/8" NPT tap is an acceptable alternative to test gauge connection. Purchase the optional CSA design-certified equipment shutoff valve from your dealer. See Accessories, page 29.

LOCATING HEATER

This heater is designed to be mounted on a wall.

WARNING: Maintain the minimum clearances shown in Figure 4. If you can, provide greater clearances from floor, ceiling, and joining wall.

Models GCN20T and GCP20T only: You can locate heater on floor, away from a wall. An optional floor mounting stand is needed. Purchase the floor mounting stand from your dealer. See Accessories, page 29.

WARNING: Never install the heater

in a bedroom or bathroom

in a recreational vehicle

where curtains, furniture, clothing, or other flammable objects are less than 36 inches (92 cm) from the front, top, or sides of the heater

as a fireplace insert

in high traffic areas

in windy or drafty areas

CAUTION: This heater creates warm air currents. These currents move heat to wall surfaces next to heater. Installing heater next to vinyl or cloth wall coverings or operating heater where impurities (such as but not limited to, tobacco smoke, aromatic candles, cleaning fluids, oil or kerosene lamps, etc.) in the air exist, may discolor walls or cause odors.

IMPORTANT: Vent-free heaters add moisture to the air. Although this is beneficial, installing heater in rooms without enough ventilation air may cause mildew to form from too much moisture. See

Air for Combustion and Ventilation, pages 4 through 6. If high humidity is experienced, a dehumidifier may be used to help lower the water vapor content in the air.

CAUTION: If you install the heater in a home garage

heater pilot and burner must be at least 18 inches (46 cm) above floor

locate heater where moving vehicle will not hit it

For convenience and efficiency, install heater

where there is easy access for operation, inspection, and service

in coldest part of room

For 20,000 Btu/hr (5.9 kW) models, an optional fan kit is available from your dealer. See Accessories, page 29. If planning to use fan, locate heater near a grounded electrical outlet. Outlet must be grounded in accordance with local codes, with the current Canadian Electrical Code Part 1 CSA C22.1.

 

CEILING

6"

36" (91.5 cm)

Minimum

(15.3 cm)

Minimum

6,000 Btu/Hr

From

(1.8 kW)

Sides Of

Model Shown

Heater

 

Right

Left

Side

Side

Minimum To Top Surface

Of Carpeting, Tile Or Other

Combustible Material

3" (7.7 cm)

Figure 4 - Mounting Clearances As Viewed From Front of Heater

For more information, visit www.desatech.com

112157-01A

INSTALLATION

8 Thermostat Sensing Bulb (Thermostat Models Only)

Installing Heater To Wall 6,000 and 10,000 Btu/Hr Models (1.8 and 2.9 kW)

INSTALLATION

Continued

THERMOSTAT SENSING BULB

(Thermostat Models Only)

The thermostat sensing bulb has been placed inside the heater for protection during shipping.

Locating Thermostat Sensing Bulb (for thermostat applications)

1.Remove front panel of heater [for 10,000 Btu/Hr (2.9 KW) heater, see Figure 11 page 9 or for 20,000 Btu/Hr (5.9 KW) heater see Figure 14, page 10].

2.Locate thermostat sensing bulb just under burner assembly.

IMPORTANT: Attach thermostat sensing bulb to back of heater for proper operation.

Attaching Thermostat Sensing Bulb

1.Remove thermostat sensing bulb from holders inside heater. Route through slot opening in bottom of heater.

2.Place clamp on thermostat sensing bulb as shown in Figure 5. Clamp is provided in hardware package.

3.Snap clamp into upper mounting hole as shown in Figure 5. Mounting hole is located on lower left edge on back of heater. Make sure the thermostat sensing bulb is pointing up.

Thermostat

Sensing Bulb

Clamp

Figure 5 - Attaching Thermostat Sensing Bulb

INSTALLING HEATER TO WALL 6,000 AND 10,000 BTU/HR MODELS (1.8 AND 2.9 KW)

Marking Screw Locations

1.Determine where you will locate heater.

WARNING: Maintain minimum clearances shown in Figure 6. If you can, provide greater clearances from floor and joining wall.

2.Mark two mounting screw locations on wall (see Figure 6).

 

 

8 7/8"

 

 

 

7 3/4"

 

 

 

 

 

 

 

 

 

 

 

 

(22.5 cm)

(19.7 cm)

 

 

 

Blue Flame

 

 

 

 

 

 

 

Minimum To

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Maintain 6"

 

 

 

 

 

 

WALL

Clearance

Mounting 20 1/4" (51.4 cm)

From Wall

 

 

 

 

 

 

 

JOINING

 

 

 

 

Screw

From Floor

 

 

 

 

 

Locations

Minimum To

 

 

 

 

 

Maintain 3" (7.6

 

 

 

 

 

 

 

 

 

cm) Clearance

FLOOR

Figure 6 - Mounting Screw Locations

Installing Two Mounting Screws

Note: Wall anchors and mounting screws are in hardware package. The hardware package is provided with heater.

Attaching to wall stud method

For attaching mounting screw to wall stud

1.Drill hole at marked location using 9/64" drill bit.

2.Insert mounting screw into wall stud.

3.Tighten screw until 1/16" (1.6 mm) space (thickness of penny) is between screwhead and wall.

Attaching to wall anchor method

Follow instructions below to attach mounting screws to hollow walls (wall areas between studs) or solid walls (concrete or masonry).

1.Drill holes at marked locations using 5/16" drill bit. For solid walls (concrete or masonry), drill at least 1 1/4" (3.2 cm) deep.

2.Fold wall anchor (see Figure 7).

3.Insert wall anchor (wings first) into hole. Tap anchor flush to wall.

4.For thin walls [1/2" (1.27 cm) or less], insert red key into wall anchor. Push red key to “pop” open anchor wings (see Figure 8). IMPORTANT: Do not hammer key! For thick walls [over 1/2" (1.27 cm) thick] or solid walls, do not pop open wings.

Thin Walls (1/4" to 1/2" thick) (1.6 to 1.2 cm)

Figure 7 - Folding Anchor

Figure 8 - Popping Open Anchor

 

Wings For Thin Walls

For morevisit www..com

112157-01A

INSTALLATION

9

Installing Heater To Wall 6,000 and 10,000 Btu/Hr Models (1.8 and 2.9 kW) (Cont.)

Installing Heater To Wall 20,000 Btu/Hr Models (5.9 kW)

 

 

 

INSTALLATION

Continued

5.Tighten two screws until 1/16" (1.6 mm) space (thickness of penny) is between screwheads and wall (see Figure 9).

Thin or

Thick Wall

(thick wall shown)

1/16" Space (1.6 mm)

Solid

Wall

Figure 9 - Tightening Anchors

Placing Heater On Mounting Screws

1.Locate two keyhole slots on back panel of heater (see Figure 10).

2.Place large openings of slots over screwheads. Slide heater down until screws are in small portion of slots.

Installing Bottom Mounting Screw

1.Locate bottom mounting hole. This hole is near bottom on back panel of heater (see Figure 12).

2.Mark screw location on wall.

3.Remove heater from wall.

4.If installing bottom mounting screw into hollow or solid wall, install wall anchor. Follow steps 1 through 5 under Attaching To Wall Anchor Method, page 10. If installing bottom mounting screw into wall stud, drill hole at marked location using 9/64" drill bit.

5.Replace heater on wall.

6.Insert bottom anchor screw through back panel into bottom anchor or drilled hole (see Figure 12).

7.Tighten screw until heater is firmly secured to wall. Do not over tighten.

Note: Do not replace front panel at this time. Replace front panel after making gas connections and checking for leaks (see pages 11 and 12).

Keyhole Slots

Figure 10 - Location Of Keyhole Slots On Back Panel Of Heater

Removing Front Panel Of Heater

1.Remove two screws near bottom corners of front panel.

2.Lift straight up on grill guard until it stops. Grill guard will slide up about 1/4" (6 mm).

3.Pull bottom of front panel forward, then down.

Figure 12 - Installing Bottom Mounting Screw

INSTALLING HEATER TO WALL 20,000 BTU/HR MODELS (5.9 KW)

Mounting Bracket

Locate mounting bracket in heater carton. Remove mounting bracket from heater carton.

Figure 13 - Mounting Bracket

Figure 11 - Removing Front Panel Of Heater

For more information, visit www.desatech.com

112157-01A

INSTALLATION

10 Installing Heater To Wall 20,000 Btu/Hr Models (5.9 kW) (Cont.)

INSTALLATION

Continued

Removing Front Panel Of Heater (20,000 Btu/Hr Models Only) (5.9 kW)

1.Remove the four painted screws, two on each side of front panel.

2.Pull bottom of front panel forward, then out.

3.Remove any remaining packaging materials.

Figure 14 - Removing Front Panel Of Heater

Methods For Attaching Mounting Bracket To Wall

Only use last hole on each end of mounting bracket to attach bracket to wall. These two holes are 14 inches (35.5 cm) apart from their centers. Attach mounting bracket to wall in one of two ways:

1.Attaching to wall stud

2.Attaching to wall anchor

Attaching to Wall Stud: This method provides the strongest hold. Insert mounting screws through mounting bracket and into wall studs.

Attaching to Wall Anchor: This method allows you to attach mounting bracket to hollow walls (wall areas between studs) or to solid walls (concrete or masonry).

Decide which method better suits your needs. Either method will provide a secure hold for the mounting bracket.

Marking Screw Locations

1.Tape mounting bracket to wall where heater will be located. Make sure mounting bracket is level.

WARNING: Maintain minimum clearances shown in Figure 15. If you can, provide greater clearances from floor and joining wall.

2.Mark screw locations on wall (see Figure 15).

Note: Only mark last hole on each end of mounting bracket. Insert mounting screws through these holes only.

3.Remove tape and mounting bracket from wall.

 

8"

14"

 

 

(20.3 cm)

 

 

Min.

(35.6 cm)

 

AdjoiningWall

Only Insert Mounting

18 3/4"

Screws Through Last

(47.7 cm)

 

Hole On Each End

Min.

 

 

 

Floor

Figure 15 - Mounting Bracket Clearances

Attaching Mounting Bracket To Wall

Note: Wall anchors, mounting screws, and spacers are in hardware package. The hardware package is provided with heater.

Attaching To Wall Stud Method

For attaching mounting bracket to wall studs

1.Drill holes at marked locations using 9/64" drill bit.

2.Place mounting bracket onto wall. Line up last hole on each end of bracket with holes drilled in wall.

3.Insert mounting screws through bracket and into wall studs.

4.Tighten screws until mounting bracket is firmly fastened to wall studs.

Attaching To Wall Anchor Method

For attaching mounting bracket to hollow walls (wall areas between studs) or solid walls (concrete or masonry)

1.Drill holes at marked locations using 5/16" drill bit. For solid walls (concrete or masonry), drill at least 1" (2.5 cm) deep.

2.Fold wall anchor as shown in Figure 16.

3.Insert wall anchor (wings first) into hole. Tap anchor flush to wall.

4.For thin walls [1/2" (1.27 cm) or less], insert red key into wall anchor. Push red key to “pop” open anchor wings. IMPORTANT: Do not hammer key!

For thick walls [over 1/2" (1.27 cm) thick] or solid walls, do not pop open wings.

5.Place mounting bracket onto wall. Line up last hole on each end of bracket with wall anchors.

6.Insert mounting screws through bracket and into wall anchors.

7.Tighten screws until mounting bracket is firmly fastened to wall.

Figure 16 - Folding Anchor

Figure 17Popping Open

 

Anchor Wings For Thin Walls

For morevisit www..com

112157-01A

INSTALLATION

11

Installing Heater To Wall 20,000 Btu/Hr Models (5.9 kW) (Cont.)

Mounting Heater To Floor With Optional Floor Kit [20,000 Btu/Hr (5.9 kW) Only]

INSTALLATION

Continued

Placing Heater On Mounting Bracket

1.Locate two horizontal slots on back panel of heater.

2.Place heater onto mounting bracket. Slide horizontal slots onto stand-out tabs on mounting bracket.

Horizontal Slots

Stand-Out Tab

 

Mounting Bracket

 

 

(attached to wall)

 

 

 

 

 

Figure 18 - Mounting Heater Onto Mounting Bracket

Installing Bottom Mounting Screws

1.Locate two bottom mounting holes. These holes are near bottom on back panel of heater (see Figure 19).

2.Mark screw locations on wall.

3.Remove heater from mounting bracket.

4.If installing bottom mounting screws into hollow or solid wall, install wall anchors. Follow steps 1 through 4 under Attaching To Wall Anchor Method, page 10.

If installing bottom mounting screw into wall stud, drill holes at marked locations using 9/64" drill bit.

5.Replace heater onto mounting bracket.

6.Place spacers between bottom mounting holes and wall anchor or drilled hole.

7.Hold spacer in place with one hand. With other hand, insert mounting screw through bottom mounting hole and spacer. Place tip of screw in opening of wall anchor or drilled hole.

8.Tighten both screws until heater is firmly secured to wall. Do not over tighten.

Note: Do not replace front panel at this time. Replace front panel after making gas connections and checking for leaks (see

pages 11 and 12).

Heater

Wall

Spacer

Front View

Side View

 

Figure 19 - Installing Bottom Mounting Screws

MOUNTING HEATER TO FLOOR WITH OPTIONAL FLOOR KIT [20,000 BTU/HR (5.9 KW) ONLY]

Mounting Base Feet to Heater

1.Lay heater cabinet on its back on a table with the heater bottom overhanging the table edge.

2.Align holes in base foot with mounting holes on bottom of cabinet (see Figure 20).

3.Secure base foot to heater using sheet metal screws.

4.Repeat for other side.

Mounting Base Feet to Floor (Where required by local code)

If heater is being installed directly on carpeting, tile or other combustible material (other than wood flooring), the heater shall be installed on a metal or wood panel extending the full width and depth of the appliance.

1.Remove front cover (see Removing Front Panel of Heater, page 10).

2.Position heater with base feet in desired location. Mark holes for drilling. Remove heater with base.

3.If mounting base to a wood floor, drill 1/8 inch diameter hole, 3/4 inch (2 cm) deep. (Do not use anchors in wood floors).

If mounting base to a concrete floor, drill with 1/4 inch diameter concrete drill bit, 13/8 inches (3.5 cm) into floor. Insert anchors completely into holes.

4.Reposition heater with base feet over holes. Secure base to floor with wood screws. See Figure 20.

Wood

Screw

Base Foot

Sheet Metal Screw

Figure 20 - Installing Base Feet (Heater may vary from illustration)

For more information, visit www.desatech.com

112157-01A

12

INSTALLATION

Connecting To Gas Supply

INSTALLATION

Continued

CONNECTING TO GAS SUPPLY

WARNING: This appliance requires a 3/8" NPT (National Pipe Thread) inlet connection to the pressure regulator.

WARNING: A qualified service person must connect heater to gas supply. Follow all local codes.

Installation must include equipment shutoff valve, union, and plugged 1/8" NPT tap. Locate NPT tap within reach for test gauge hook up. NPT tap must be upstream from heater (see Figure 22).

IMPORTANT: Install an equipment shutoff valve in an accessible location. The equipment shutoff valve is for turning on or shutting off the gas to the appliance.

Apply pipe joint sealant lightly to male NPT threads. This will prevent excess sealant from going into pipe. Excess sealant in pipe could result in clogged heater valves.

WARNING: For natural gas, never connect heater to private (non-utility) gas wells. This gas is commonly known as wellhead gas.

IMPORTANT: For natural gas, check gas line pressure before connecting heater to gas line. Gas line pressure must be no greater than 10.5 inches (26.6 cm) of water. If gas line pressure is higher, heater regulator damage could occur.

CAUTION: For propane/LP gas, never connect heater directly to the propane/LP supply. This heater requires an external regulator (not supplied). Install the external regulator between the heater and propane/LP supply.

WARNING: Use pipe joint sealant that is resistant to liquid petroleum (LP) gas.

We recommend that you install sediment trap in supply line as shown in Figure 22. Locate sediment trap where it is within reach for cleaning. Install in piping system between fuel supply and heater. Locate sediment trap where trapped matter is not likely to freeze. A sediment trap traps moisture and contaminants. This keeps them from going into heater controls. If sediment trap is not installed or is installed wrong, heater may not run properly.

IMPORTANT: Hold pressure regulator with wrench when connecting it to gas piping and/or fittings. Do not over tighten pipe connection to regulator. The regulator body could be damaged.

For propane/LP gas, the installer must supply an external regulator. The external regulator will reduce incoming gas pressure. You must reduce incoming gas pressure to between 11 and 14 inches (28 and 35.5 cm) of water. If you do not reduce incoming gas pressure, heater regulator damage could occur. Install external regulator with the vent pointing down as shown in Figure 21. Pointing the vent down protects it from freezing rain or sleet.

CAUTION: Use only new, black iron or steel pipe. Internally-tinned copper tubing may be used in certain areas. Check your local codes. Use pipe of large enough diameter to allow proper gas volume to heater. If pipe is too small, undue loss of volume will occur.

Typical inlet pipe diameter for 20,000 btu/hr (5.9 kW) models - 3/8" or greater.

Propane/LP

 

Supply Tank

External Regulator

 

 

Vent Pointing Down

Figure 21 - External Regulator With Vent Pointing Down (Propane/LP Systems Only)

For more

3/8" NPT

 

 

 

Pipe Nipple

 

Pressure

 

 

Ground

 

Regulator

Joint Union

 

 

 

Equipment

 

Heater

 

Cabinet

Shutoff Valve*

 

 

 

 

Natural Gas

 

Tee Joint

 

From Gas Meter

 

Reducer

Test

[6/10,000 Btu/Hr (1.8/2.9 kW)

Bushing to

Gauge

4" (10 cm) W.C. to

 

1/8" NPT

 

Connection*

10.5" (26.7 cm) W.C.

 

1/8" NPT

 

 

Pressure]

 

 

 

Plug Tap

 

20,000 Btu/Hr (5.9 kW)

 

 

 

 

 

5" (12.7 cm) W.C. to 10.5"

 

Tee

 

(26.7 cm) W.C. Pressure] 3"

 

Propane/LP

7.7 cm)

Joint

Sediment

Minimum

Pipe

From External Regulator

Trap

 

Nipple

(11" (27.9 cm) W.C. to

 

 

 

Cap

 

14" (35.6 cm) W.C. Pressure)

 

Figure 22 - Gas Connection

* A CSA design-certified equipment shutoff valve with 1/8" NPT tap is an acceptable alternative to test gauge connection. Purchase the optional CSA design-certified equipment shutoff valve from your dealer. See Accessories, page 29.

visit www..com

112157-01A

INSTALLATION

13

Checking Gas Connections

 

 

INSTALLATION

Continued

CHECKING GAS CONNECTIONS

WARNING: Test all gas piping and connections for leaks after installing or servicing. Correct all leaks at once.

WARNING: Never use an open flame to check for a leak. Apply a noncorrosive leak detection fluid to all joints. Bubbles forming show a leak. Correct all leaks at once.

CAUTION: For propane/LP gas, make sure external regulator has been installed between propane/LP supply and heater. See guidelines under Connecting to Gas Supply, page 12.

Pressure Testing Gas Supply Piping System

Test Pressures In Excess Of 1/2 PSIG (3.5 kPa)

1.Disconnect appliance with its appliance main gas valve (control valve) and equipment shutoff valve from gas supply piping system. Pressures in excess of 1/2 psig (3.5 kPa) will damage heater regulator.

2.Cap off open end of gas pipe where equipment shutoff valve was connected.

3.Pressurize supply piping system by either opening propane/LP supply tank valve for propane/LP gas or opening main gas valve located on or near gas meter for natural gas, or using compressed air.

4.Check all joints of gas supply piping system. Apply a noncorrosive leak detection fluid to all joints. Bubbles forming show a leak.

5.Correct all leaks at once.

6.Reconnect heater and equipment shutoff valve to gas supply. Check reconnected fittings for leaks.

Test Pressures Equal To or Less Than 1/2 PSIG (3.5 kPa)

1.Close equipment shutoff valve (see Figure 23).

2.Pressurize supply piping system by either opening propane/ LP supply tank valve for propane/LP gas or opening main gas valve located on or near gas meter for natural gas, or using compressed air.

3.Check all joints from gas meter for natural gas (see Figure 24) or propane/LP supply tank for propane/LP gas, to equipment shutoff valve (see Figure 25). Apply a noncorrosive leak detection fluid to all joints. Bubbles forming show a leak.

4.Correct all leaks at once.

Pressure Testing Heater Gas Connections

1.Open equipment shutoff valve (see Figure 23).

2.Open main gas valve located on or near gas meter for natural gas or open propane/LP supply tank valve.

3.Make sure control knob of heater is in the OFF position.

4.Check all joints from equipment shutoff valve to control valve (see Figures 24 and 25). Apply a noncorrosive leak detection fluid to all joints. Bubbles forming show a leak.

5.Correct all leaks at once.

6.Light heater (see Operating Heater pages 14 and 15). Check the rest of the internal joints for leaks.

7.Turn off heater (see To Turn Off Gas to Appliance, page 15).

8.Replace front panel.

Equipment Open

ON

POSITI

Shutoff Valve

OF

POSIClosed

Figure 23 - Equipment Shutoff Valve

Control Valve Location

Gas

Meter

Equipment

Shutoff Valve

Figure 24 - Checking Gas Joints for Natural Gas [6,000 Btu/Hr Model (1.8 kW) Shown]

Propane/LP

Supply Tank Control

Valve Location

Equipment

Shutoff Valve

Figure 25 - Checking Gas Joints for Propane/LP Gas [6,000 Btu/Hr Model (1.8 kW) Shown]

For more information, visit www.desatech.com

112157-01A

14

OPERATING HEATER

For Your Safety Read Before Lighting

 

Lighting Instructions

 

 

OPERATING HEATER

FOR YOUR SAFETY READ

BEFORE LIGHTING

WARNING: If you do not follow these instructions exactly, a fire or explosion may result causing property damage, personal injury or loss of life.

A.This appliance has a pilot which must be lighted by hand. When lighting the pilot, follow these instructions exactly.

B.BEFORE LIGHTING smell all around the appliance area for gas. Be sure to smell next to the floor because some gas is heavier than air and will settle on the floor.

WHAT TO DO IF YOU SMELL GAS

Do not try to light any appliance.

Do not touch any electric switch; do not use any phone in your building.

Immediately call your gas supplier from a neighbor’s phone. Follow the gas supplier’s instructions.

If you cannot reach your gas supplier, call the fire department.

C.Use only your hand to push in or turn the gas control knob. Never use tools. If the knob will not push in or turn by hand, don’t try to repair it, call a qualified service technician or gas supplier. Force or attempted repair may result in a fire or explosion.

D.Do not use this appliance if any part has been under water. Immediately call a qualified service technician to inspect the appliance and to replace any part of the control system and any gas control which has been under water.

LIGHTING

INSTRUCTIONS

1.STOP! Read the safety information above.

2.Make sure equipment shutoff valve is fully open.

3. Turn control knob clockwise Clockwise to the OFF position

(see Figure 26 or 27).

4.Wait five (5) minutes to clear out any gas. Then smell for gas, including near the floor. If you smell gas, STOP! Follow “B” in the safety information, above. If you don’t smell gas, go to the next step.

5.Press in control knob and turn counterclockwise C-clockwise to the PILOT position. Keep control knob pressed in for five (5) seconds (see Figure 26 or 27).

Note: You may be running this heater for the first time after hooking up to gas supply. If so, the control knob may need to be pressed in for 30 seconds or more. This will allow air to bleed from the gas system.

If control knob does not pop up when released, contact a qualified service person or gas supplier for repairs.

6.With control knob pressed in, push down and release ignitor button. This will light pilot. The pilot is attached to the front of burner. The pilot can be seen through the glass panel. If needed, keep pressing ignitor button until pilot lights.

Note: If pilot does not stay lit, refer to Troubleshooting, pages 18 through 20. Also contact a qualified service person or gas supplier for repairs. Until repairs are made, light pilot with a match. To light pilot with amatch, see Manual Lighting Procedure, page 15.

7.Keep control knob pressed in for 30 seconds after lighting pilot. After 30 seconds, release control knob.

If control knob does not pop up when released, contact a qualified service person or gas supplier for repairs.

Note: If pilot goes out, repeat steps 3 through 7. Thermostat model heaters have a safety interlock system. Wait one

(1) minute before lighting pilot again.

8.Manual Controlled Models Only Turn control knob coun-

terclockwise C-clockwise to the HI position. The main burner should light. Set control knob to HI or LO. To turn control knob from HI to LO, press in the control knob and turn counterclockwise C-clockwise .

Note: Both HI and LO are locked positions. You must press in control knob before turning it from these positions.

9.Thermostat Controlled Models Only Turn control knob

counterclockwise C-clockwise to desired heating level. The main burner should light. Set control knob to any heat level between 1 and 5.

CAUTION: Do not try to adjust heating levels by using the equipment shutoff valve.

Ignitor Button

Ignitor Button

Control Knob

Control Knob

 

 

 

 

 

FO

Figure 26 - Control Knob In

Figure 27 - Control Knob In

The OFF Position (Manual

The OFF Position (Thermostat

Controlled Models)

Controlled Models)

Thermocouple

Ignitor Electrode

Pilot Burner

Figure 28 - Pilot

For morevisit www..com

112157-01A

OPERATING HEATER

15

To Turn Off Gas To Appliance

Thermostat Control Operation (Thermostat Models Only)

 

Manual Lighting Procedure

 

INSPECTING BURNER

 

Pilot Flame Pattern

 

Burner Flame Pattern

 

 

OPERATING HEATER

Continued

TO TURN OFF GAS

TO APPLIANCE

Shutting Off Heater

1. Press in and turn control knob clockwise

Clockwise

to the OFF

position.

 

 

2.Turn off all electric power to the appliance if service is to be performed.

Shutting Off Burner Only (pilot stays lit)

Turn control knob clockwise Clockwise to the PILOT position.

THERMOSTAT CONTROL

OPERATION (THERMOSTAT

MODELS ONLY)

The thermostatic control used on these models differs from standard thermostats. Standard thermostats simply turn on and off the burner. The thermostat used on this heater senses the room temperature. The thermostat adjusts the amount of gas flow to the burner. This increases or decreases the burner flame height. At times the room may exceed the set temperature. If so, the burner will shut off. The burner will cycle back on when room temperature drops below the set temperature. The control knob can be set to any heat level between 1 and 5.

Note: The thermostat sensing bulb measures the temperature of air near the heater cabinet. This may not always agree with room temperature (depending on housing construction, installation location, room size, open air temperatures, etc.). Frequent use of your heater will let you determine your own comfort levels.

MANUAL LIGHTING

PROCEDURE

1.Remove front panel [for 6,000 (1.8 kW) and 10,000 (2.9 kW) Btu/Hr heater see Figure 11, page 9, for 20,000 Btu/Hr (5.9 kW) heater, see Figure 14 page 10].

2.Follow steps 1 through 5 under Lighting Instructions, page 14.

3.With control knob pressed in, strike match. Hold match to pilot until pilot lights.

4.Keep control knob pressed in for 30 seconds after pilot is lit. After 30 seconds, release control knob. Follow step 8 under Lighting Instructions, page 14.

5.Replace front panel.

INSPECTING BURNER

Check pilot flame pattern and burner flame pattern often.

PILOT FLAME PATTERN

Figure 29 shows a correct pilot flame pattern. Figure 30 shows an incorrect pilot flame pattern. The incorrect pilot flame is not touching the thermocouple. This will cause the thermocouple to cool. When the thermocouple cools, the heater will shut down.

If pilot flame pattern is incorrect, as shown in Figure 30

turn heater off (see To Turn Off Gas to Appliance, column 1)

see Troubleshooting, pages 18 through 20

Note: The pilot flame on natural gas units will have a slight curve, but flame should be blue and have no yellow or orange color.

Thermocouple

Thermocouple

Yellow Flame

 

Blue Flame

 

 

Pilot Burner

Pilot

 

Burner

 

 

Figure 29 - Correct Pilot

Figure 30 - Incorrect Pilot Flame

Flame Pattern

Pattern

BURNER FLAME PATTERN

WARNING: If yellow tipping occurs, your heater could produce increased levels of carbon monoxide.

NOTICE: Do not mistake orange flames with yellow tipping. Dust or other fine particles enter the heater and burn causing brief patches of orange flame.

Figure 31 shows a correct burner flame pattern. Figure 32 shows an incorrect burner flame pattern. The incorrect burner flame pattern shows yellow tipping of the flame. It also shows the flame higher than 1/2 the glass panel height.

If burner flame pattern is incorrect, as shown in Figure 32

turn heater off (see To Turn Off Gas to Appliance, column 1)

see Troubleshooting, pages 18 through 20

Yellow

Tipping

1/2 GLASS HEIGHT

(Models GCN6 and GCP6 will be lower due to lower input rating)

Figure 31 - Correct Burner

Flame Pattern

Figure 32 - Incorrect Burner

Flame Pattern

For more information, visit www.desatech.com

112157-01A

16

CLEANING AND MAINTENANCE

ODS/Pilot and Burner Orifice

 

Burner Pilot Air Inlet Hole

 

Cabinet

 

 

CLEANING AND

MAINTENANCE

WARNING: Turn off heater and let cool before cleaning.

CAUTION: You must keep control areas, burner, and circulating air passageways of heater clean. Inspect these areas of heater before each use. Have heater inspected yearly by a qualified service person. Heater may need more frequent cleaning due to excessive lint from carpeting, bedding material, pet hair, etc.

WARNING: Failure to keep the primary air opening(s) of the burner(s) clean may result in sooting and property damage.

ODS/PILOT AND BURNER ORIFICE

Use a vacuum cleaner, pressurized air, or small, soft bristled brush to clean.

Pilot Assembly

Pilot Air Inlet

Figure 33 - Pilot Inlet Air Hole

CABINET

Air Passageways

• Use a vacuum cleaner or pressurized air to clean.

Exterior

Use a soft cloth dampened with a mild soap and water mixture. Wipe the cabinet to remove dust.

BURNER PILOT AIR INLET HOLE

The primary air inlet holes allow the proper amount of air to mix with the gas. This provides a clean burning flame. Keep these holes clear of dust, dirt, lint, and pet hair. Clean these air inlet holes prior to each heating season. Blocked air holes will create soot. We recommend that you clean the unit every three months during operation and have fireplace inspected yearly by a qualified service person.

We also recommend that you keep the burner tube and pilot assembly clean and free of dust and dirt. To clean these parts we recommend using compressed air no greater than 30 PSI (207 kPa). Your local computer store, hardware store, or home center may carry compressed air in a can. You can use a vacuum cleaner in the blow position. If using compressed air in a can, please follow the directions on the can. If you don't follow directions on the can, you could damage the pilot assembly.

1.Shut off the unit, including the pilot. Allow the unit to cool for at least thirty minutes.

2.Inspect burner, pilot for dust and dirt.

3.Blow air through the ports/slots and holes in the burner.

4.Never insert objects into the pilot tube.

Clean the pilot assembly also. A yellow tip on the pilot flame indicates dust and dirt in the pilot assembly. There is a small pilot air inlet hole about two inches from where the pilot flame comes out of the pilot assembly (see Figure 33). With the unit off, lightly blow air through the air inlet hole. You may blow through a drinking straw if compressed air is not available.

For morevisit www..com

112157-01A

TROUBLESHOOTING

17

TROUBLESHOOTING

Note: For additional help, visit DESA’s

 

WARNING: Turn off heater

technical service web site at

 

 

and let cool before servicing. Only

www.desatech.com.

 

 

a qualified service person should

 

 

Note: All troubleshooting items are listed in

 

 

service and repair heater.

order of operation.

 

 

 

 

OBSERVED PROBLEM

POSSIBLE CAUSE

CAUTION: Never use a wire, needle, or similar object to clean ODS/pilot. This can damage ODS/ pilot unit.

REMEDY

When ignitor button is pressed, there is no

1.

Ignitor electrode positioned wrong

1.

Replace pilot assembly

spark at ODS/pilot

2.

Ignitor electrode broken

2.

Replace pilot assembly

 

3.

Ignitor electrode not connected to igni-

3.

Reconnect ignitor cable

 

 

tor cable

 

 

 

 

4.

Ignitor cable pinched or wet

4.

Free ignitor cable if pinched by any

 

 

 

 

metal or tubing. Keep ignitor cable dry

 

5.

Broken ignitor cable

5.

Replace ignitor cable

 

6.

Bad piezo ignitor

6.

Replace piezo ignitor

 

 

 

 

 

When ignitor button is pressed, there is

1.

Gas supply turned off or equipment

1.

Turn on gas supply or open equipment

spark at ODS/pilot but no ignition

 

shutoff valve closed

 

shutoff valve

 

2.

Control knob not in PILOT position

2.

Turn control knob to PILOT position

 

3.

Control knob not pressed in while in

3.

Press in control knob while in PILOT

 

 

PILOT position

 

position

 

4.

Air in gas lines when installed

4.

Continue holding down control knob.

 

 

 

 

Repeat igniting operation until air is re-

 

 

 

 

moved

 

5.

Depleted gas supply (propane/LP only)

5.

Contact local propane/LP gas company

 

6.

ODS/pilot is clogged

6.

Clean ODS/pilot (see Cleaning and

 

 

 

 

Maintenance, page 16) or replace ODS/

 

 

 

 

pilot assembly

 

7.

Gas regulator setting is not correct

7.

Replace gas regulator

 

 

 

 

 

 

ODS/pilot lights but flame goes out when

1.

Control knob not fully pressed in

1.

Press in control knob fully

control knob is released

2.

Control knob not pressed in long enough

2.

After ODS/pilot lights, keep control

 

 

 

 

knob pressed in 30 seconds

 

3. Safety interlock system has been

3.

Wait one minute for safety interlock sys-

 

 

triggered

 

tem to reset. Repeat ignition operation

 

4.

Equipment shutoff valve not fully open

4.

Fully open equipment shutoff valve

 

5.

Thermocouple connection loose at con-

5.

Hand tighten until snug, then tighten 1/4

 

 

trol valve

 

turn more

 

6.

Pilot flame not touching thermocouple,

6.

A) Contact local natural or propane/LP

 

 

which allows thermocouple to cool,

 

gas company

 

 

causing pilot flame to go out. This prob-

 

B) Clean ODS/pilot (see Cleaning and

 

 

lem could be caused by one or both of

 

Maintenance, page 16) or replace ODS/

 

 

the following:

 

pilot assembly

 

 

A) Low gas pressure

 

 

 

 

 

B) Dirty or partially clogged ODS/pilot

 

 

 

 

7.

Thermocouple damaged

7.

Replace pilot assembly

 

8.

Control valve damaged

8.

Replace control valve

For more information, visit www.desatech.com

112157-01A

TROUBLESHOOTING

18

TROUBLESHOOTING

Continued

OBSERVED PROBLEM

POSSIBLE CAUSE

REMEDY

Burner does not light after ODS/pilot is lit

1.

Burner orifice is clogged

1.

Clean burner orifice (see Cleaning and

 

 

 

 

Maintenance, page 16) or replace burner

 

 

 

 

orifice

 

2.

Inlet gas pressure is too low

2.

Contact local natural or propane/LP gas

 

 

 

 

company

 

 

 

 

 

Delayed ignition of burner

1.

Manifold pressure is too low

1.

Contact local natural or propane/LP gas

 

 

 

 

company

 

2.

Burner orifice is clogged

2.

Clean burner orifice (see Cleaning and

 

 

 

 

Maintenance, page 16) or replace burner

 

 

 

 

orifice

 

 

 

 

 

Burner backfiring during combustion

1.

Burner orifice is clogged or damaged

1.

Clean burner orifice (see Cleaning and

 

 

 

 

Maintenance, page 16) or replace burner

 

 

 

 

orifice

 

2.

Burner damaged

2.

Replace burner

 

3.

Gas regulator defective

3.

Replace gas regulator

 

 

 

 

 

Yellow flame during burner combustion

1.

Not enough air

1.

Check burner for dirt and debris. If

 

 

 

 

found, clean burner (see Cleaning and

 

 

 

 

Maintenance, page 16)

 

2.

Gas regulator defective

2.

Replace gas regulator

 

3.

Clogged or dirty burner

3.

Clean burner (see Cleaning and Main-

 

 

 

 

tenance, page 16)

 

 

 

 

 

Slight smoke or odor during initial operation

1.

Residues from manufacturing processes

1.

Problem will stop after a few hours of

 

 

 

 

operation

 

 

 

 

 

Heater produces a whistling noise when

1.

Turning control knob to HI position

1.

Turn control knob to LO position and

burner is lit

 

when burner is cold

 

let warm up for a minute

 

2.

Air in gas line

2.

Operate burner until air is removed from

 

 

 

 

line. Have gas checked by local natural

 

 

 

 

or propane/LP gas company

 

3.

Air passageways on heater blocked

3.

Observe minimum installation clear-

 

 

 

 

ances (see Figure 4, page 7)

 

4.

Dirty or partially clogged burner orifice

4.

Clean burner (see Cleaning and Mainte-

 

 

 

 

nance, page 16) or replace burner orifice

Heater produces a clicking/ticking noise just after burner is lit or shut off

1.Metal expanding while heating or contracting while cooling

1.This is common with most heaters. If noise is excessive, contact qualified service person

For morevisit www..com

112157-01A

Loading...
+ 42 hidden pages