DELTA MCS-1800Power Shelf

Installation, Operation and

Maintenance Manual

www.deltaww.com

Delta MCS 1800 3U

Power Shelf

Installation, Operations and

Maintenance Manual

DELTA ELECTRONICS, INC.

DELTA MCS 1800 3U Power Shelf

Installation, Operations and

Maintenance Manual

Table of Contents

1.

General

----------------------------------------------

1-1

 

1.1

Using This Manual

----------------------------------------------

1-1

 

1.2

Safety Notice

----------------------------------------------

1-1

2.

Product Description

----------------------------------------------

2-1

 

2.1

Product Description

----------------------------------------------

2-1

 

2.2

Product Main Features

----------------------------------------------

2-1

 

2.3

System Specifications

----------------------------------------------

2-1

3.

Power Supply Unit (PSU)

----------------------------------------------

3-1

 

3.1

Description

----------------------------------------------

3-1

 

3.2

Specifications

----------------------------------------------

3-1

 

3.3

Operation and Adjustment

----------------------------------------------

3-4

 

3.4

System Alarm

----------------------------------------------

3-5

 

3.5

PSU Block Diagram

----------------------------------------------

3-5

 

3.6

PSU Operating Principle

----------------------------------------------

3-5

4.

Alarm Control Unit

----------------------------------------------

4-1

 

4.1

Description

----------------------------------------------

4-1

 

4.2

Specifications

----------------------------------------------

4-1

 

4.3

Alarm Control Unit Block Diagram

----------------------------------------------

4-4

 

4.4

Settings and Control

----------------------------------------------

4-4

5.DC Distribution

5.1DC Cabling

5.2Low Voltage Battery Disconnect (System equipped with PDU)

5.3Battery Connections (System equipped with PDU)

5.4Battery Temperature Probe Connection (System equipped with PDU)

6.Installation

6.1Preliminary Inspection

6.2System Mounting

6.3Module Installation

6.4Shelf Wiring

6.5AC Input Connections

----------------------------------------------

5-1

----------------------------------------------

5-1

----------------------------------------------

5-1

----------------------------------------------

5-1

----------------------------------------------

5-1

----------------------------------------------

6-1

----------------------------------------------

6-1

----------------------------------------------

6-1

----------------------------------------------

6-1

----------------------------------------------

6-1

----------------------------------------------

6-1

INDEX i

DELTA MCS 1800 3U Power Shelf

Installation, Operations and

Maintenance Manual

Table of Contents

6.6Battery String Connections (System equipped with PDU)

6.7Temperature and Alarm Connections

6.8EXT. Breaker trip signal I/P Connector Wiring

6.9AC High Voltage Aux. Relay Output Wiring

7.System Start –UpProcedure

7.1Initial Start-UpPreparation

7.3Basic Functional Verification 7.2 No Load Start-Up

7.4DC Load Connections

7.5System Functionality Check

7.6System Operation

----------------------------------------------

6-1

----------------------------------------------

6-2

----------------------------------------------

6-2

----------------------------------------------

6-2

----------------------------------------------

7-1

----------------------------------------------

7-1

----------------------------------------------

7-1

----------------------------------------------

7-1

----------------------------------------------

7-1

----------------------------------------------

7-1

8. System Alarms and Troubleshooting

----------------------------------------------

8-1

8.1

AC Fail Voltage Alarm Description

----------------------------------------------

8-1

8.2

High Voltage Shutdown Alarm

----------------------------------------------

8-1

8.3

High Voltage Alarm Description

----------------------------------------------

8-1

8.4

Low Voltage Alarm

----------------------------------------------

8-2

8.5

Low Voltage Disconnect Alarm (System

----------------------------------------------

8-2

 

equipped with PDU)

 

 

8.6

Fuse Fail Alarm (System equipped with PDU)

----------------------------------------------

8-2

8.7

Alarm Unit Fail

----------------------------------------------

8-3

8.8

Rectifier Fail Alarm

----------------------------------------------

8-3

9. Maintenance

----------------------------------------------

9-1

9.1

Cleaning and Maintenance

----------------------------------------------

9-1

9.2

Removing and Replacing a Rectifier Unit

----------------------------------------------

9-1

10.

Acronyms and Abbreviations

----------------------------------------------

10-1 ~3

ATTACHMENT

INDEX ii

DELTA MCS-18003U Power Shelf

Installation, Operations and

Maintenance Manual

1 General

1.1 Using This Manual

This manual contains specifications and instructions to properly install and maintain the power supply system. Component specifications and drawings are also included.

This manual contains information related to the operation and maintenance of the Alarm Control Unit (ALU), the –48V/+24VPower Supply Unit (PSU), and the Distribution Module. Additional information is provided on system status and alarms, troubleshooting, and system maintenance. Appendix figures of this manual contains drawings, simple block diagram for different functional blocks and systems schematic.

Step-by-stepprocedures required for the installation andturn-upare detailed. All equipment parameter setting, adjustments, and confirmation, as well as system monitoring, operations, and maintenance procedures, are included.

Warnings are printed in bold, italic lettering. They alert the installation or maintenance craftsperson of a potential hazard to either the equipment or the craftsperson if the warning is not followed.

1.2 Safety Notice

Delta Energy Systems is not liable for any hazards incurred by not following proper safety procedures. Installation, operation, and maintenance personnel should always follow these safety rules:

1.Before installing the system, verify the AC input voltage and frequency, the AC breaker rating and type, and other environmental conditions as noted in the specifications.

2.The system has passed stringent system testing prior to shipment. To avoid electrical shock. The rectifier system requires a single ground point permanently connected to earth ground.

3.An AC breaker must provide adequate isolation between the system input and commercial AC main.

4.The environment should be dust free and controlled by an AC system. The area must be free of any flammable vapors or fluids.

5.To avoid electrical hazard, the covers must not be removed on any component, including the ALU and the rectifier.

6.Circuit breakers or fuses must be replaced with approved replacement circuit breakers meeting the original design specification.

7.All connections must be made per the latest issue of the applicable national and local codes.

1-1

DELTA MCS-18003U Power Shelf

Installation, Operations and

Maintenance Manual

2 Product Description

2.1Product Description

This power Shelf consists of modular rectifiers, an Alarm Control Unit (ALU), and a DC distribution module. Up to four rectifiers and an alarm unit can be equipped on a shelf containing an integrated distribution module. The rectifiers can operate from a universal range of AC line voltages. The High Line (HL) operations are defined at an AC line input range of 165VAC~ 264VAC. The Low Line (LL) operations are defined at an AC line input range of 90 VAC-130VAC.

The system is controlled and monitored by the ALU. System level rectifier voltage settings, system status, and alarms are displayed on the ALU. The system float voltage, equalize voltage, and alarm thresholds are set from RMS. The ALU also provides automatic derating of the output power over the whole operating line voltages. Figure 1 shows different functional blocks of the system.

2.2Product Main Features

The Power Shelf has the following main features:

-48VDC/120 Amps, or +24VDC/200Amps, N+1 redundancy Modular design for scalable, cost effective expansion

Front access for simple installation and maintenance High power density

Active Power Factor Correction (>. 99PFC) High efficiency

Temperature compensated float voltage control Alarm Control Unit

Low Voltage Battery Disconnect (LVBD) (System equipped with PDU) Remote Monitoring and control

2.3System Specifications

The system specifications are provided in the following sections.

2.3.1 -48VStandard Power Shelf Configuration(MODUL NAME:ES48/120-JAAxx)

(1)

AC Input:

175VAC ~ 275VAC, 48Amps. Max

(2)

System Capacity:

120Amps. Max.

(3)

Rectifier:

-48V/30A×1~4

(4)

Control and Supervisory Unit

 

Figure 1 shows a front view of shelf.

2-1

DELTA MCS-18003U Power Shelf

Installation, Operations and

Maintenance Manual

Environmental Data

System Environmental Data

Specification

Value

Operating temperature

0 to +50

Storage temperature

-40to +70

Humidity

0% to 95% RH

Altitude

-300ft. to 10,000 ft.

Weight

Approximately 48 lbs.

EMI/FRI

FCC Part 15, Class B and CISPR 22, Class B

Lightning/surge

ANSI/IEEE C62.41-1,and IEC1000-4-5

Seismic

Bellcore GR-63-CORE,Zone 4

Safety

CUL and UL Listed and Marked

2.3.2 +24V Standard Power Shelf Configuration(MODUL NAME: ES24/200-JAAxx)

(1)

AC Input:

175VAC ~ 275VAC, 48Amps. Max

(2)

System Capacity:

200Amps. Max.

(3)

Rectifier:

+24V/50A×1~4

(4)Control and Supervisory

Figure 1 shows a front view of shelf.

Environmental Data

System Environmental Data

Specification

Value

Operating temperature

0 to +50

Storage temperature

-40to +70

Humidity

0% to 95% RH

Altitude

-300ft. to 10,000 ft.

Weight

Approximately 48 lbs.

Lightning/surge

ANSI/IEEE C62.41-1,and IEC1000-4-5

Seismic

Bellcore GR-63-CORE,Zone 4

Safety

CUL and UL Listed and Marked

2.3.3 -48VSystem with Power Distribution and Rectifiers(MODUL NAME:ES48/90-JBAxx)

(1)

AC Input:

175VAC ~ 275VAC, 36Amps. Max

(2)

System Capacity:

90Amps. Max.

(3)

Rectifier:

-48V/30A×1~3

(4)Control and Supervisory

(5)

Load Distribution:

30A Breaker×5 @ Single Pole

(6)

Low Voltage Disconnect Switch:

100A×1 @ Single Pole at Battery Side

(7)

Battery Breaker:

100A×1

(8)

AC Breaker

 

 

 

 

 

 

2-2

DELTA MCS-18003U Power Shelf

Installation, Operations and

Maintenance Manual

Figure 1-1shows a front view of shelf.

Environmental Data

System Environmental Data

Specification

Value

Operating temperature

0 to +50

Storage temperature

-40to +70

Humidity

0% to 95% RH

Altitude

-300ft. to 10,000 ft.

Weight

Approximately 48 lbs.

Lightning/surge

ANSI/IEEE C62.41-1,and IEC1000-4-5

Seismic

Bellcore GR-63-CORE,Zone 4

2.3.4 -48VSystem with Power Distribution and Rectifiers(MODUL NAME:ES48/90-JFAxx)

(1)

AC Input:

175VAC ~ 275VAC, 36Amps. Max

(2)

System Capacity:

90Amps. Max.

(3)

Rectifier:

-48V/30A×1~3

(4)

Control and Supervisory

 

(5)

Load Distribution:

100A Breaker×4 @ Single Pole

(6)

Low Voltage Disconnect Switch: 100A×1 @ Single Pole at Battery Side

Figure 1-1shows a front view of shelf.

 

Environmental Data

 

 

System Environmental Data

 

 

 

 

 

 

Specification

Value

 

 

Operating temperature

0 to +50

 

 

Storage temperature

-40to +70

 

 

Humidity

0% to 95% RH

 

 

Altitude

-300ft. to 10,000 ft.

 

 

Weight

Approximately 48 lbs.

 

 

EMI/FRI

FCC Part 15, Class B and CISPR 22, Class B

 

 

Lightning/surge

ANSI/IEEE C62.41-1,and IEC1000-4-5

 

 

Seismic

Bellcore GR-63-CORE,Zone 4

 

 

Safety

CUL and UL Listed and Marked

2.4 Electrical Data

The system electrical data is provided in the following tables.

2.4.1 Input

2-3

DELTA MCS-18003U Power Shelf

Installation, Operations and

Maintenance Manual

Table 1 displays the system input specifications.

Table 1 System Input Specifications

 

Specification

Value

 

Nominal range

175 ~ 275VAC

 

 

90 ~ 275VAC Full Load

 

Operational range

150V ~ 175Vac de-ratingto 80% Load

 

 

90V ~ 150Vac de-ratingto 50% Load

 

 

50 ~ 65 de-rating1500W

 

Frequency

45 ~ 65Hz

 

Power Factor

>0.99 @ 220VAC, Full Load

 

THD

<5% @ 220VAC, Full Load

 

Efficiency

>90% @ 220VAC, Full Load

2.4.2 Output

 

Table 2 displays the system output specifications.

Table 2 System Output Specifications

 

Specification

Value

 

 

 

 

DC Volts

38~60 VDC (-48VVersion)

 

20~30 VDC (+24V Version)

 

 

 

Load regulation

<1%

 

 

 

 

Line regulation

<0.2%

 

 

 

 

Current Limit

110%

 

 

 

 

Current share

<5%

 

 

 

 

Noise:

 

 

Audio band

<2mv

 

Wide band

<10 mVrms

 

Acoustic

<55 dBA

2.4.3 Status/Alarm Indicators

 

The Power Shelf has the following status/alarm indicators:

Load Current

AC ON

Rectifier Fail Alarm (RFA)

Current Limit (CL)

Float/Equalize (FL/EQU)

Major Alarm (MAJ)

Minor Alarm (MIN)

High Voltage Alarm (HV)

High Voltage Shutdown (HVSD)

Low Voltage Alarm (LV)

Low Voltage Disconnect Open (LVDS OPEN)

Fuse Blown (FUSE ALM)

AC Fail (AC FAIL)

2-4

DELTA MCS-18003U Power Shelf

Installation, Operations and

Maintenance Manual

2.4.4 Mechanical Data

Dimension

Value

 

 

Height

5.2 in. (132mm)

 

 

Depth

10.35 in. (263mm)

 

 

Width

3.3 in. (83.6mm)

 

 

2-5