INDUSTRIAL & HAZARDOUS LOCATION Emergency Lights
660
COOPER LIGHTING - SURE-LITES®
UMB SERIES
W e t L o c a t i o n
E M E R G E N C Y L I G H T I N G
•NEMA 4X
•Dual-voltage input 120/277VAC, 60Hz
•Grey fiberglass housing
•Two top mounted, fully adjustable, grey, highimpact thermoplastic heads standard
•Glare-free lens with PAR36 sealed beam lamps
•Watertight and corrosion resistant
•Wet location listed (32˚F or 0˚C and above)
•Gasketed, internally hinged front cover
•Remote capability
•Line-latching, Solid-State voltage limited charger, Solid-State switching, lowvoltage disconnect, brownout circuit, overload/short-circuit protection, test switch/power indicator light
•UL 924 Listed, Life Safety NFPA 101, NEC/OSHA, most state and local codes
D E S C R I P T I O N
The ideal unit for wet environments where an emergency lighting unit will be exposed to water spray,
penetrating steam, or dampness. The UMB Series is best suited for use in areas like waste water treatment plants, food processing facilities and most industrial applications.
D I M E N S I O N S
12 1/4" (311mm)
CHARGE |
|
|
6 1/2" |
|
(165mm) |
TEST |
|
6" (152mm) |
10" (254mm) |
E L E C T R I C A L R AT I N G S
|
Rated Wattage to 87 1/2% of Rated D.C. Voltage |
|
|
Lamp Information |
|
|
|||
Model |
DC Voltage |
Battery |
1 1/2 Hours |
2 Hours |
3 Hours |
4 Hours |
Type |
Wattage |
Number |
UMB1 |
6 |
LC |
18 |
15 |
10 |
8 |
Incandescent |
8 |
29-03 |
UMB6 |
6 |
LC |
27 |
24 |
18 |
14 |
Incandescent |
8 |
29-03 |
UMB7 |
6 |
LC |
54 |
48 |
36 |
28 |
Incandescent |
8 |
29-03 |
UMB8 |
12 |
LC |
36 |
30 |
20 |
16 |
Halogen |
8 |
29-16 |
UMB9 |
12 |
LC |
54 |
48 |
36 |
28 |
Halogen |
8 |
29-16 |
UMB14 |
6 |
NC |
15 |
12 |
8 |
6 |
Incandescent |
7.2 |
29-75 |
UMB15 |
6 |
NC |
24 |
18 |
12 |
10 |
Incandescent |
7.2 |
29-75 |
UMB16 |
12 |
NC |
30 |
24 |
16 |
12 |
Halogen |
8 |
29-16 |
UMB17 |
12 |
NC |
48 |
36 |
24 |
20 |
Halogen |
8 |
29-16 |
O R D E R I N G I N F O R M AT I O N
S A M P L E N U M B E R : U M B 6 T H
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Model Number |
Options (add as Suffix) |
Accessories |
|||||||
|
UMB1 |
TDM=Time Delay Monitor |
(Order separately) |
|||||||
|
UMB6 |
TH=Thermal Heater |
WG7=Wire Guard |
|||||||
|
UMB7 |
Alternate Lamps(1) |
VS2WP=Polycarbonate |
|||||||
|
UMB8 |
Other Options(1) |
Vandal/Weather Shield |
|||||||
|
UMB9 |
|
|
|
|
|
|
|
||
|
UMB14 |
|
|
|
|
|
|
|
||
|
UMB15 |
|
|
|
|
|
|
|
||
|
UMB16 |
|
|
|
|
|
|
|
||
|
UMB17 |
|
|
|
|
|
|
|
||
|
|
|
|
|
|
|
|
E n e r g y D a t a
|
Input Current (Max.): |
|
Model No. |
120V |
277V |
UMB1, UMB6, UMB7 |
.12A |
.05A |
UMB8, UMB9 |
.30A |
.13A |
UMB14 |
.06A |
.03A |
UMB15 |
.07A |
.04A |
UMB16 |
.13A |
.06A |
UMB17 |
.15A |
.07A |
(1) Consult your Cooper Lighting Representative.