Cooper Lighting UMB16, UMB15, UMB8, UMB14, UMB6 User Manual

...
0 (0)
Cooper Lighting UMB16, UMB15, UMB8, UMB14, UMB6 User Manual

INDUSTRIAL & HAZARDOUS LOCATION Emergency Lights

660

COOPER LIGHTING - SURE-LITES®

UMB SERIES

W e t L o c a t i o n

E M E R G E N C Y L I G H T I N G

NEMA 4X

Dual-voltage input 120/277VAC, 60Hz

Grey fiberglass housing

Two top mounted, fully adjustable, grey, highimpact thermoplastic heads standard

Glare-free lens with PAR36 sealed beam lamps

Watertight and corrosion resistant

Wet location listed (32˚F or 0˚C and above)

Gasketed, internally hinged front cover

Remote capability

Line-latching, Solid-State voltage limited charger, Solid-State switching, lowvoltage disconnect, brownout circuit, overload/short-circuit protection, test switch/power indicator light

UL 924 Listed, Life Safety NFPA 101, NEC/OSHA, most state and local codes

D E S C R I P T I O N

The ideal unit for wet environments where an emergency lighting unit will be exposed to water spray,

penetrating steam, or dampness. The UMB Series is best suited for use in areas like waste water treatment plants, food processing facilities and most industrial applications.

D I M E N S I O N S

12 1/4" (311mm)

CHARGE

 

 

6 1/2"

 

(165mm)

TEST

 

6" (152mm)

10" (254mm)

E L E C T R I C A L R AT I N G S

 

Rated Wattage to 87 1/2% of Rated D.C. Voltage

 

 

Lamp Information

 

 

Model

DC Voltage

Battery

1 1/2 Hours

2 Hours

3 Hours

4 Hours

Type

Wattage

Number

UMB1

6

LC

18

15

10

8

Incandescent

8

29-03

UMB6

6

LC

27

24

18

14

Incandescent

8

29-03

UMB7

6

LC

54

48

36

28

Incandescent

8

29-03

UMB8

12

LC

36

30

20

16

Halogen

8

29-16

UMB9

12

LC

54

48

36

28

Halogen

8

29-16

UMB14

6

NC

15

12

8

6

Incandescent

7.2

29-75

UMB15

6

NC

24

18

12

10

Incandescent

7.2

29-75

UMB16

12

NC

30

24

16

12

Halogen

8

29-16

UMB17

12

NC

48

36

24

20

Halogen

8

29-16

O R D E R I N G I N F O R M AT I O N

S A M P L E N U M B E R : U M B 6 T H

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Model Number

Options (add as Suffix)

Accessories

 

UMB1

TDM=Time Delay Monitor

(Order separately)

 

UMB6

TH=Thermal Heater

WG7=Wire Guard

 

UMB7

Alternate Lamps(1)

VS2WP=Polycarbonate

 

UMB8

Other Options(1)

Vandal/Weather Shield

 

UMB9

 

 

 

 

 

 

 

 

UMB14

 

 

 

 

 

 

 

 

UMB15

 

 

 

 

 

 

 

 

UMB16

 

 

 

 

 

 

 

 

UMB17

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

E n e r g y D a t a

 

Input Current (Max.):

Model No.

120V

277V

UMB1, UMB6, UMB7

.12A

.05A

UMB8, UMB9

.30A

.13A

UMB14

.06A

.03A

UMB15

.07A

.04A

UMB16

.13A

.06A

UMB17

.15A

.07A

(1) Consult your Cooper Lighting Representative.

COOPER LIGHTING