Carrier TJF005-007, 48TJD, TJE, TJF004, 48TJE User Manual

0 (0)

48TJE,TJF004 48TJD,TJE,TJF005-007 Single-Package Rooftop Heating/Cooling Units

Installation, Start-Up and

Service Instructions

CONTENTS

Page

SAFETY CONSIDERATIONS . . . . . . . . . . . . . . . . . . . . . . 1

INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-36

Step 1 — Provide Unit Support . . . . . . . . . . . . . . . . . . . 1

ROOF CURB

SLAB MOUNT

Step 2 — Field Fabricate Ductwork . . . . . . . . . . . . . . . 2

Step 3 — Install External Trap for

Condensate Drain . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 Step 4 — Rig and Place Unit . . . . . . . . . . . . . . . . . . . . . 2

• POSITIONING

 

Step 5

— Install Flue Hood . . . . . . . . . . . . . . . . . . . . . . .

4

Step 6

— Install Gas Piping . . . . . . . . . . . . . . . . . . . . . .

4

Step 7

— Make Electrical Connections . . . . . . . . . . .

5

DISCONNECT BOX LOCATION

FIELD POWER SUPPLY

FIELD CONTROL WIRING

HEAT ANTICIPATOR SETTINGS

Step 8 — Make Outdoor-Air Adjustment and

Install Outdoor-Air Hood . . . . . . . . . . . . . . . . . . . . . . 12

MANUAL OUTDOOR-AIR DAMPER

OPTIONAL DURABLADE ECONOMIZER

OPTIONAL ECONOMI$ER

Step 9 — Adjust Evaporator-Fan Speed . . . . . . . . . 20

DIRECT-DRIVE MOTORS

BELT-DRIVE MOTORS

START-UP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37-39 SERVICE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40-44 TROUBLESHOOTING. . . . . . . . . . . . . . . . . . . . . . . . . 45-50 START-UP CHECKLIST . . . . . . . . . . . . . . . . . . . . . . . . CL-1

SAFETY CONSIDERATIONS

Installation and servicing of air-conditioning equipment can be hazardous due to system pressure and electrical components. Only trained and qualified service personnel should install, repair, or service air-conditioning equipment.

Untrained personnel can perform basic maintenance functions of cleaning coils and filters and replacing filters. All other operations should be performed by trained service personnel. When working on air-conditioning equipment, observe precautions in the literature, tags and labels attached to the unit, and other safety precautions that apply.

Follow all safety codes. Wear safety glasses and work gloves. Use quenching cloth for unbrazing operations. Have fire extinguishers available for all brazing operations.

Ensure voltage listed on unit data plate agrees with electrical supply provided for the unit.

Disconnect gas piping from unit when leak testing at pressure greater than 1/2 psig. Pressures greater than 1/2 psig will cause gas valve damage resulting in hazardous condition. If gas valve is subjected to pressure greater than 1/2 psig, it must be replaced before use. When pressure testing field-supplied gas piping at pressures of 1/2 psig or less, a unit connected to such piping must be isolated by manually closing the gas valve.

Before performing service or maintenance operations on unit, turn off main power switch to unit and install lockout tag. Electrical shock could cause personal injury.

INSTALLATION

Unit is shipped in the vertical discharge configuration. To convert to horizontal configuration, remove screws from side duct opening covers and remove covers. Using the same screws, install covers on vertical duct openings with the insulation side down. Seals around duct openings must be tight. See Fig. 1.

Step 1 — Provide Unit Support

ROOF CURB — Assemble and install accessory roof curb in accordance with instructions shipped with curb. See Fig. 2. Install insulation, cant strips, roofing felt, and counter flashing as shown. Ductwork must be attached to curb, not to the unit. The accessory thru-the-bottom power and gas connection package must be installed before the unit is set on the roof curb. If fieldinstalled (thru-the-roof curb) gas connections are desired, use factory-supplied 3/4 in. pipe coupling and gas plate assembly to mount the thru-the-roof curb connection to the roof curb. Gas connections and power connections to the unit must be field installed after the unit is installed on the roof curb.

If electric and control wiring is to be routed through the basepan, attach the accessory thru-the-bottom service connections to the basepan in accordance with the accessory installation instructions.

IMPORTANT: The gasketing of the unit to the roof curb is critical for a watertight seal. Install gasket supplied with the roof curb as shown in Fig. 2. Improperly applied gasket can also result in air or water leaks and poor unit performance.

Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.

Book

1

4

PC 111

Catalog No. 534-774

Printed in U.S.A.

Form 48TJ-18SI

Pg 1

10-00

Replaces: 48TJ-16SI

Tab

1a

6a

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Fig. 1 — Horizontal Conversion Panels

(Viewed from Duct End)

Curb should be level. Unit leveling tolerances are shown in Fig. 3. This is necessary for unit drain to function properly. Refer to Accessory Roof Curb Installation Instructions for additional information as required.

SLAB MOUNT (Horizontal Units Only) — Provide a level concrete slab that extends a minimum of 6 in. beyond unit cabinet. Install a gravel apron in front of condenser coil air inlet to prevent grass and foliage from obstructing airflow.

NOTE: Horizontal units may be installed on a roof curb if required.

Step 2 — Field Fabricate Ductwork — Secure all ducts to roof curb and building structure on vertical units. Do not connect ductwork to unit. For horizontal applications, fieldsupplied flanges should be attached to horizontal discharge openings and all ductwork should be secured to the flanges. Insulate and weatherproof all external ductwork, joints, and roof openings with counter flashing and mastic in accordance with applicable codes.

Ducts passing through an unconditioned space must be insulated and covered with a vapor barrier.

If a plenum return is used on a vertical unit, the return should be ducted through the roof deck to comply with applicable fire codes.

A minimum clearance is not required around ductwork. Cabinet return air static shall not exceed –.30 in. wg with EconoMi$er, or –.35 in. wg with Durablade Economizer, or –.45 in. wg without economizer.

These units are designed for a minimum continuous returnair temperature of 50 F (dry bulb), or an intermittent operation down to 45 F (dry bulb) (in heating mode), such as when used with a night set-back thermostat.

Step 3 — Install External Trap for Condensate Drain — The unit’s 3/4-in. condensate drain connections are located on the bottom and side of the unit. Unit discharge connections do not determine the use of drain connections; either drain connection can be used with vertical or horizontal applications.

When using the standard side drain connection, make sure the plug (Red) in the alternate bottom connection is tight before installing the unit.

To use the bottom drain connection for a roof curb installation, relocate the factory-installed plug (Red) from the bottom connection to the side connection. See Fig. 4. The piping for the condensate drain and external trap can be completed after the unit is in place.

All units must have an external trap for condensate drainage. Install a trap at least 4-in. deep and protect against freezeup. If drain line is installed downstream from the external trap, pitch the line away from the unit at 1 in. per 10 ft of run. Do not use a pipe size smaller than the unit connection (3/4 in.).

Step 4 — Rig and Place Unit — Inspect unit for transportation damage. File any claim with transportation agency. Keep unit upright and do not drop. Spreader bars are not required if top crating is left on unit. Rollers may be used to move unit across a roof. Level by using unit frame as a reference. See Table 1 and Fig. 5 for additional information.

Lifting holes are provided in base rails as shown in Fig. 6. Refer to rigging instructions on unit.

All panels must be in place when rigging and lifting.

2

‘‘B’’

‘‘C’’

 

‘‘D’’ ALT

 

 

 

‘‘E’’

 

 

“F”

 

 

 

“G”

 

 

 

 

 

CONNECTOR

 

DRAIN HOLE

 

 

 

Gas

 

Power

 

 

 

Control

 

 

 

 

 

 

PKG ACY

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3/4

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CRBTMPWR001A00

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3/4

 

[19] NPT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

[19] NPT

 

11/4

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CRBTMPWR002A00

 

1′-911/16

1′-4″

 

 

 

13/4

 

 

 

 

 

 

 

 

 

 

[31.7]

 

 

 

 

1/2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

[551]

 

 

[406]

[44.5]

 

 

 

 

 

1/2

 

 

3/4

 

[12.7] NPT

 

CRBTMPWR003A00

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

[12.7] NPT

 

[19] NPT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3/4

 

11/4

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CRBTMPWR004A00

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

[19] NPT

 

[31.7]

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ROOF CURB

‘‘A’’

UNIT SIZE

ACCESSORY

48TJ

 

CRRFCURB001A00

1′-2″

 

[356]

 

 

004-007

CRRFCURB002A00

2′-0″

 

[610]

 

 

 

NOTES:

1.Roof curb accessory is shipped disassembled.

2.Insulated panels:

3. Dimensions in [ ] are in millimeters.

4.Roof curb: galvanized steel.

5.Attach ductwork to curb (flanges of duct rest on curb).

6.Service clearance 4′ on each side.

7. Direction of airflow.

8.Connector packages CRBTMPWR001A00 and 2A00 are for thru-the-curb type. Packages CRBTMPWR003A00 and 4A00 are for the thru- the-bottom type connections.

TO ENSURE AIRTIGHT CONNECTION

PLACE UNIT AS CLOSE TO

END AS POSSIBLE.

TO ENSURE AIRTIGHT CONNECTION

PLACE UNIT AS CLOSE TO

END AS POSSIBLE.

Fig. 2 — Roof Curb Dimensions

3

MAXIMUM ALLOWABLE

DIFFERENCE (in.)

A-B

B-C

A-C

0.5

1.0

1.0

Fig. 3 — Unit Leveling Tolerances

CONDENSATE PAN (SIDE VIEW)

DRAIN PLUG

NOTE: Drain plug is shown in factory-installed position.

Fig. 4 — Internal Trap Condensate Drain

POSITIONING — Maintain clearance around and above unit to provide minimum distance from combustible materials, proper airflow, and service access. See Fig. 6. A properly positioned unit will have the following clearances between unit and roof curb: 1/4-in. clearance between roof curb and base rails on each side and duct end of unit; 1/4-in. clearance between roof curb and condenser coil end of unit. (See Fig. 2, section C-C.)

Do not install unit in an indoor location. Do not locate unit air inlets within 10 ft of exhaust vents or other sources of contaminated air or as local codes require.

Be sure that unit is installed so that snow will not block the combustion intake or flue outlet.

Unit may be installed directly on wood flooring or on Class A, B, or C roof-covering material when roof curb is used.

Although unit is weatherproof, guard against water from higher level runoff and overhangs.

Flue vent discharge must have a minimum horizontal clearance of 4 ft from electric and gas meters, gas regulators, and gas relief equipment.

Minimum distance between unit and other electrically live parts is 48 inches.

Flue gas can deteriorate building materials. Orient unit such that flue gas will not affect building materials.

Adequate combustion-air space must be provided for proper operation of this equipment. Be sure that installation complies with all local codes and Section 5.3, Air for Combustion and Ventilation, NFGC (National Fuel Gas Code), and ANSI (American National Standards Institute) Z223.1, and NFPA (National Fire Protection Association) 54 TIA-54-84-1. In Canada, installation must be in accordance with the CAN1B149 installation codes for gas burning appliances.

After unit is in position, remove rigging skids and shipping materials.

Step 5 — Install Flue Hood — Flue hood is shipped screwed to the burner compartment access panel. Remove from shipping location and using screws provided, install flue hood and screen in location shown in Fig. 7.

For units size 004-006 being installed in California Air Quality Management Districts, which require NOx emissions of 40 nanograms/joule or less, a field-installed low NOx kit must be used.

Step 6 — Install Gas Piping — Unit is equipped for use with type of gas shown on nameplate. Refer to local building codes, or in the absence of local codes, to ANSI Z223.1 entitled National Fuel Gas Code. In Canada, installation must be in accordance with the CAN1.B149.1 and CAN1.B149.2 installation codes for gas burning appliances.

For natural gas applications, gas pressure at unit gas connection must not be less than 4 in. wg or greater than 13.0 in. wg while unit is operating. On 48TJ005,006,007 high heat units, the gas pressure at unit gas connection must not be less than 5 in. wg or greater than 13 in. wg while the unit is operating. For propane applications, the gas pressure must not be less than 5 in. wg or greater than 13 in. wg at the unit connection.

Size gas sully piping for 0.5 in. wg maximum pressure drop. Do not use supply pipe small than unit gas connection. Support gas piping as shown in the table in Fig. 8. For example, a 3/4-in. gas pipe must have one field-fabricated support beam every 8 ft. Therefore, an 18-ft long gas pipe would have a minimum of 2 support beams, a 48-ft long pipe would have a minimum of 6 support beams.

See Fig. 8 for typical pipe guide and locations of external manual main shutoff valve.

4

NOTES:

1. Dimension in ( ) is in millimeters.

2.Hook rigging shackles through holes in base rail, as shown in detail ‘‘A.’’ Holes in base rails are centered around the unit center of gravity. Use wooden top skid when rigging to prevent rigging straps from damaging unit.

3.Unit weights do not include economizer. See Table 1 for economizer weights.

All panels must be in place when rigging.

 

MAX

 

DIMENSIONS

 

 

UNIT

WEIGHT

‘‘A’’

‘‘B’’

 

‘‘C’’

 

lb

kg

in.

mm

in.

mm

 

in.

mm

48TJE,TJF004

510

231

 

 

 

 

 

 

 

48TJD,TJE,TJF005

520

236

73.69

1872

37.50

953

 

33.35

847

48TJD,TJE,TJF006

540

245

 

48TJD,TJE,TJF007

615

279

 

 

 

 

 

 

 

Fig. 5 — Rigging Details

Step 7 — Make Electrical Connections

Unit cabinet must have an uninterrupted, unbroken electrical ground to minimize the possibility of personal injury if an electrical fault should occur. This ground may consist of electrical wire connected to unit ground lug in control compartment, or conduit approved for electrical ground when installed in accordance with NEC (National Electrical Code), ANSI/NFPA, latest edition, and local electrical codes. Do not use gas piping as an electrical ground. Failure to follow this warning could result in the installer being liable for personal injury of others.

FIELD POWER SUPPLY — All units except 208/230-v units are factory wired for the voltage shown on the nameplate. If the 208/230-v unit is to be connected to a 208-v power supply, the transformer must be rewired by disconnecting the black wire from the 230-v terminal wire on the transformer and connecting it to the 200-v red terminal of the transformer.

Refer to unit label diagram for additional information. Wiring leads are provided for field service. Use copper conductors only when splice connectors are used.

When installing units, provide a disconnect per NEC.

All field wiring must comply with NEC and local requirements. In Canada, electrical connections must be in accordance with CSA (Canadian Standards Association) C22.1 Canadian Electrical Code Part One.

DISCONNECT BOX LOCATION — The field-supplied disconnect box may be mounted on the unit’s end panel or on the corner post. Mount disconnect box on the left side of the rating plate when mounting on the unit’s end panel. Do not mount the disconnect box over the unit rating plate. When mounting disconnect box on corner post, secure disconnect box to corner post and condenser coil top cover. See Fig. 7.

A disconnect box mounting space is available when an optional or accessory condenser coil grille is used. Mount the disconnect on the sheet metal provided with the condenser coil grille. The sheet metal is located adjacent to the corner post on the left side of the power wiring access panel.

Install field wiring as follows:

1.Connect ground lead to chassis ground connection when using separate ground ties.

2.Install conduit between disconnect and side panel. Insert conduit through power supply knockout opening. See Fig. 9.

3.Connect power lines to power wiring leads.

4.Pigtails are provided for field power connections and are located inside the burner access panel. See Fig. 10 and 11. Use factory-supplied splices or Underwriters’ Laboratories (UL) approved copper connector.

5

Table 1 — Physical Data

UNIT SIZE 48TJ

 

E/F004

 

 

D/E/F005

 

 

D/E/F006

 

 

D/E/F007

NOMINAL CAPACITY (tons)

 

3

 

 

4

 

 

5

 

 

6

OPERATING WEIGHT (lb)

 

 

 

 

 

 

 

 

 

 

 

Unit

 

 

 

 

 

 

 

 

 

 

 

Al/Al*

 

460

 

 

470

 

 

490

 

 

565

Al/Cu*

 

465

 

 

476

 

 

497

 

 

576

Cu/Cu*

 

468

 

 

482

 

 

505

 

 

587

Economizer

 

 

 

 

 

 

 

 

 

 

 

Durablade

 

34

 

 

34

 

 

34

 

 

34

EconoMi$er

 

47

 

 

47

 

 

47

 

 

47

Roof Curb†

 

115

 

 

115

 

 

115

 

 

115

COMPRESSOR

 

 

 

 

Reciprocating

 

 

 

 

 

Scroll

Quantity

 

1

 

 

1

 

 

1

 

 

1

 

 

 

No. Cylinders (per Circuit)

 

2

 

 

2

 

 

2

 

 

2

Oil (oz)

 

50

 

 

50

 

 

50

 

 

54

REFRIGERANT TYPE

 

 

 

 

 

R-22

 

Expansion Device

 

 

 

 

Acutrol™ Metering Device

 

Operating Charge (lb-oz)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Circuit 1

 

4-4

 

 

6-6

 

 

6-14

 

 

9-0

Circuit 2

 

 

 

 

 

 

 

CONDENSER COIL

 

 

Enhanced Copper Tubes, Aluminum Lanced Fins

 

Rows...Fins/in.

 

1...17

 

 

2...17

 

 

2...17

 

 

2...17

 

 

 

 

Total Face Area (sq ft)

 

8.36

 

 

8.36

 

 

10.42

 

 

10.42

CONDENSER FAN

 

 

 

 

Propeller Type

 

Nominal Cfm

 

3500

 

 

4000

 

 

4000

 

 

4000

 

 

 

 

Quantity...Diameter (in.)

 

1...22.0

 

 

1...22.0

 

 

1...22.0

 

 

1...22.0

Motor Hp...Rpm

 

1/4...1100

 

 

1/4...1100

 

 

1/4...1100

 

 

1/4...1100

Watts Input (Total)

 

325

 

 

325

 

 

325

 

 

325

EVAPORATOR COIL

 

 

Enhanced Copper Tubes, Aluminum Double-Wavy Fins

 

Rows...Fins/in.

 

2...15

 

 

2...15

 

 

3...15

 

 

4...15

 

 

 

 

Total Face Area (sq ft)

 

4.17

 

 

5.5

 

 

5.5

 

 

5.5

EVAPORATOR FAN

 

 

 

 

Centrifugal Type

 

Quantity...Size (in.)

Std

1...10 x 10

 

 

1...10 x 10

 

 

1...11 x 10

 

 

1...10 x 10

 

 

 

 

 

Alt

1...10 x 10

 

 

1...10 x 10

 

 

1...10 x 10

 

 

 

High-Static

1...10 x 10

 

 

1...10 x 10

 

 

1...11 x 10

 

 

1...10 x 10

Type Drive

Std

Direct

 

 

Direct

 

 

Direct

 

 

Belt

 

Alt

Belt

 

 

Belt

 

 

Belt

 

 

Nominal Cfm

High-Static

Belt

 

 

Belt

 

 

Belt

 

 

Belt

 

1200

 

 

1600

 

 

2000

 

 

2400

Maximum Continuous Bhp

Std

.34

 

 

.75

 

 

1.20

 

 

2.40

 

Alt

1.00

 

 

1.00

 

 

1.30/2.40**

 

 

 

High-Static

2.40

 

 

2.40

 

 

2.90

 

 

2.90

Motor Frame Size

Std

48

 

 

48

 

 

48

 

 

56

 

Alt

48

 

 

48

 

 

56

 

 

 

High-Static

56

 

 

56

 

 

56

 

 

56

Nominal Rpm High/Low

Std

860/800

 

 

1075/970

 

 

1075/970

 

 

 

Alt

1620

 

 

1620

 

 

1725

 

 

 

High-Static

1725

 

 

1725

 

 

1725

 

 

1725

Fan Rpm Range

Std

 

 

 

 

 

 

1070-1460

 

Alt

760-1000

 

 

835-1185

 

 

900-1300

 

 

Motor Bearing Type

High-Static

1075-1455

 

 

1075-1455

 

 

1300-1685

 

 

1300-1685

 

Ball

 

 

Ball

 

 

Ball

 

 

Ball

Maximum Allowable Rpm

 

2100

 

 

2100

 

 

2100

 

 

2100

Motor Pulley Pitch Diameter Min/Max (in.)

Std

 

 

 

 

 

 

2.8/3.8

 

Alt

1.9/2.9

 

 

1.9/2.9

 

 

2.4/3.4

 

 

 

High-Static

2.8/3.8

 

 

2.8/3.8

 

 

3.4/4.4

 

 

3.4/4.4

Nominal Motor Shaft Diameter (in.)

Std

1/2

 

 

1/2

 

 

1/2

 

 

5/8

 

Alt

1/2

 

 

1/2

 

 

5/8

 

 

Fan Pulley Pitch Diameter (in.)

High-Static

5/8

 

 

5/8

 

 

5/8

 

 

5/8

Std

 

 

 

 

 

 

4.5

 

Alt

4.5

 

 

4.0

 

 

4.5

 

 

 

High-Static

4.5

 

 

4.5

 

 

4.5

 

 

4.5

Belt, Quantity...Type...Length (in.)

Std

 

 

 

 

 

 

1...A...40

 

Alt

1...A...34

 

 

1...A...34

 

 

1...A...39

 

 

 

High-Static

1...A...39

 

 

1...A...39

 

 

1...A...40

 

 

1...A...40

Pulley Center Line Distance (in.)

Std

 

 

 

 

 

 

14.7-15.5

 

Alt

10.0-12.4

 

 

10.0-12.4

 

 

14.7-15.5

 

 

 

High-Static

10.0-12.4

 

 

10.0-12.4

 

 

14.7-15.5

 

 

14.7-15.5

Speed Change per Full Turn of

Std

 

 

 

 

 

 

80

Movable Pulley Flange (rpm)

Alt

48

 

 

70

 

 

80

 

 

 

High-Static

65

 

 

65

 

 

60

 

 

60

Movable Pulley Maximum Full Turns

Std

 

 

 

 

 

 

5

From Closed Position

Alt

5

 

 

5

 

 

5

 

 

 

High-Static

6

 

 

6

 

 

5

 

 

5

Factory Setting

Std

 

 

 

 

 

 

3

 

Alt

3

 

 

3

 

 

3

 

 

Factory Speed Setting (rpm)

High-Static

31/2

 

 

31/2

 

 

31/2

 

 

31/2

Std

 

 

 

 

 

 

1225

 

Alt

856

 

 

975

 

 

1060

 

 

Fan Shaft Diameter at Pulley (in.)

High-Static

1233

 

 

1233

 

 

1396

 

 

1396

 

5/8

 

 

5/8

 

 

5/8

 

 

5/8

 

LEGEND

Al

Aluminum

Bhp

Brake Horsepower

Cu

Copper

*Evaporator coil fin material/condenser coil fin material. Contact your local representative for details about coated fins.

†Weight of 14-in. roof curb. **Single phase/three-phase.

††Rollout switch lockout is manually reset by interrupting power to unit or resetting thermostat.

NOTES:

1.The 48TJ004-007 units have a loss-of-charge (low pressure) switch located in the liquid line.

2.High-static motor not available on single-phase units.

6

Table 1 — Physical data (cont)

UNIT SIZE 48TJ

 

E/F004

D/E/F005

D/E/F006

D/E/F007

FURNACE SECTION

 

 

 

 

 

Rollout Switch Cutout

 

 

 

 

 

Temp (F)††

 

195

195

195

195

Burner Orifice Diameter

 

 

 

 

 

(in. ...drill size)

 

 

 

 

 

Natural Gas

Std

.113...33

.113...33/.113...33/.129...30

.113...33/.113...33/.129...30

.113...33/.113...33/.129...30

Liquid Propane

Alt

.089...43

.089...43/.089...43/.102...38

.089...43/.089...43/.102...38

.089...43/.089...43/.102...38

Thermostat Heat Anticipator

 

 

 

 

 

Setting (amps)

 

 

 

 

 

208/230 v and 575 Stage 1

 

.14

.14

.14

.14

Stage 2

 

.14

.14

.14

.14

460 v Stage 1

 

.14

.14

.14

.14

Stage 2

 

.14

.14

.14

.14

Gas Input (Btuh) Stage 1

 

74,000/82,000

74,000/115,000/120,000

74,000/115,000/120,000

74,000/115,000/120,000

Stage 2

 

—/115,000

—/—/150,000

—/—/150,000

—/—/150,000

Efficiency (Steady State) (%)

 

80

80

80

80

Temperature Rise Range

 

25-55/55-85

25-55/35-65/50-80

25-55/35-65/50-80

25-55/35-65/50-80

Manifold Pressure (in. wg)

 

 

 

 

 

Natural Gas

Std

3.5

3.5

3.5

3.5

Liquid Propane

Alt

3.5

3.5

3.5

3.5

Gas Valve Quantity

 

1

1

1

1

Gas Valve Pressure Range

 

 

 

 

 

Psig

 

0.180-0.487

0.180-0.487

0.180-0.487

0.180-0.487

in. wg

 

5.0-13.5

5.0-13.5

5.0-13.5

5.0-13.5

Field Gas Connection

 

 

 

 

 

Size (in.)

 

1/2

1/2

1/2

1/2

HIGH-PRESSURE SWITCH (psig)

 

 

 

 

 

Standard Compressor

 

 

450 ± 50

 

500 ± 50

Internal Relief (Differential)

 

 

 

 

 

Cutout

 

 

428

 

428

Reset (Auto.)

 

 

320

 

320

LOSS-OF-CHARGE (LOW PRESSURE)

 

 

 

 

 

SWITCH (psig)

 

 

 

 

 

Cutout

 

 

 

7 ± 3

 

Reset (Auto.)

 

 

 

22 ± 7

 

FREEZE PROTECTION THERMOSTAT (F)

 

 

 

 

 

Opens

 

 

 

30 ± 5

 

Closes

 

 

 

45 ± 5

 

OUTDOOR-AIR INLET SCREENS

 

 

 

Cleanable

 

Quantity...Size (in.)

 

 

 

1...20 x 24 x 1

 

RETURN-AIR FILTERS

 

 

 

Throwaway

 

Quantity...Size (in.)

 

 

 

2...16 x 25 x 2

 

 

 

LEGEND

Al

Aluminum

Bhp

Brake Horsepower

Cu

Copper

*Evaporator coil fin material/condenser coil fin material. Contact your local representative for details about coated fins.

†Weight of 14-in. roof curb.

**Single phase/three-phase.

††Rollout switch lockout is manually reset by interrupting power to unit or resetting thermostat.

NOTES:

1.The 48TJ004-007 units have a loss-of-charge (low-pressure) switch located in the liquid line.

2.High-static motor not available on single-phase units.

7

Carrier TJF005-007, 48TJD, TJE, TJF004, 48TJE User Manual

 

STANDARD

DURABLADE

ECONOMI$ER

CORNER

CORNER

CORNER

CORNER

UNIT

UNIT

ECONOMIZER

WEIGHT

WEIGHT

WEIGHT

WEIGHT

48TJ

WEIGHT

WEIGHT

WEIGHT

(A)

(B)

 

(C)

 

(D)

 

Lb

Kg

Lb

Kg

Lb

Kg

Lb

Kg

Lb

Kg

Lb

 

Kg

Lb

 

Kg

E/F004

460

209

34

15.4

47

21.3

140

63.5

105

47.6

159

 

72.1

56

 

25.4

D/E/F005

470

213

34

15.4

47

21.3

142

64.4

106

48.1

162

 

73.5

60

 

27.2

D/E/F006

490

222

34

15.4

47

21.3

150

68.0

115

52.2

160

 

72.6

65

 

29.5

D/E/F007

565

256

34

15.4

47

21.3

165

74.8

136

61.7

200

 

90.7

64

 

29.0

CONNECTION SIZES

A11/16Dia [27] Field Power Supply Hole

B3/4-14 NPT Condensate Drain

C1/2-14 NPT Gas Connection

NOTES:

1. Dimensions in [ ] are in millimeters.

2. Center of gravity.

3. Direction of airflow.

4.On vertical discharge units, ductwork to be attached to accessory roof curb only. For horizontal discharge units, field-supplied flanges should be attached to horizontal discharge openings, and all ductwork should be attached to the flanges.

5.Minimum clearance (local codes or jurisdiction may prevail):

a.Between unit, flue side and combustible surfaces, 36 inches.

b.Bottom of unit to combustible surfaces (when not using curb), 1 inch. Bottom of base rail to combustible surfaces (when not using curb) 0 inches.

c.Condenser coil, for proper airflow, 36 in. one side, 12 in. the other. The side getting the greater clearance is optional.

d.Overhead, 60 in. to assure proper condenser fan operation.

e.Between units, control box side, 42 in. per NEC.

f.Between unit and ungrounded surfaces, control box side, 36 in. per NEC.

g.Between unit and block or concrete walls and other grounded surfaces, control box side, 42 in. per NEC.

h.Horizontal supply and return end, 0 inches.

6.With the exception of the clearance for the condenser coil and combustion side as stated in notes 5a, b and c, a removable fence or barricade requires no clearance.

7.Units may be installed on combustible floors made from wood or Class A, B, or C roof covering material if set on base rail.

8.The vertical center of gravity is 1′-6″ [457] up from the bottom of the base rail.

BOTTOM POWER CHART, THESE HOLES REQUIRED FOR USE WITH ACCESSORY PACKAGES — CRBTMPWR001A00, (POWER AND CONTROL) AND CRBTMPWR003A00 (POWER, CONTROL, AND GAS)

 

 

 

 

 

 

 

 

 

 

 

 

THREADED

 

 

 

 

WIRE

 

 

 

 

 

 

 

 

 

 

REQURED

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CONDUIT SIZE

 

 

 

 

 

USE

 

 

 

 

 

 

 

HOLE SIZES (MAX.)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1/2

 

 

 

 

 

24 V

 

 

 

 

 

 

 

 

 

 

7/8[22.2]

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3/4

 

 

 

 

Power

 

 

 

 

 

 

 

 

 

 

11/8[28.4]

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1/2″ FPT

 

 

 

 

 

Gas

 

 

 

 

 

 

 

 

 

 

11/4[31.8]

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Fig. 6 — Base Unit Dimensions

8

CONDENSER

INTAKE

COIL

LOUVERS

TOP COVER

 

CORNER POST

FLUE HOOD

END PANEL

Fig. 7 — Flue Hood Details

LEGEND

NFGC — National Fuel Gas Code *Field supplied.

NOTE: Follow all local codes.

SPACING OF SUPPORTS

STEEL PIPE

X

NOMINAL

DIMENSIONS

DIAMETER

(in.)

(feet)

 

1/2

6

3/4 or 1

8

11/4 or larger

10

Fig. 8 — Gas Piping Guide (With Accessory Thru-the-Curb Service Connections)

Voltage to compressor terminals during operation must be within voltage range indicated on unit nameplate (see Table 2). On 3-phase units, voltages between phases must be balanced within 2% and the current within 10%. Use the formula shown in the legend for Table 2, Note 2 to determine the percent of voltage imbalance. Operation on improper line voltage or excessive phase imbalance constitutes abuse and may cause damage to electrical components. Such operation would invalidate any applicable Carrier warranty.

FIELD CONTROL WIRING — Install a Carrier-approved accessory thermostat assembly according to installation instructions included with the accessory. Locate thermostat assembly on a solid wall in the conditioned space to sense average temperature in accordance with thermostat installation instructions. Connect thermostat wires to terminal board.

Route thermostat cable or equivalent single leads of colored wire from subbase terminals through connector on unit to lowvoltage connections (shown in Fig. 12).

Fig. 9 — Conduit Installation

LEGEND

IGC — Integrated Gas Unit Controller

LED — Light-Emitting Diode

Fig. 10 — Component Location

NOTE: For wire runs up to 50 ft, use no. 18 AWG (American Wire Gage) insulated wire (35 C minimum). For 50 to 75 ft, use no. 16 AWG insulated wire (35 C minimum). For over 75 ft, use no. 14 AWG insulated wire (35 C minimum). All wire larger than no. 18 AWG cannot be directly connected to the thermostat and will require a junction box and splice at the thermostat.

Feed control wires through the raceway located between the condenser coil top cover and burner side panel. See Fig. 10. Connect control wires to corresponding screw terminals, the low-voltage connections located inside low-voltage access panel. See Fig. 12 for connections. The low-voltage connections provide the UL required clearance between highand low-voltage wiring.

HEAT ANTICIPATOR SETTINGS — Set heat anticipator settings at .14 amp for the first stage and .14 amp for secondstage heating, when available.

9

208/230-1-60

 

575-3-60

 

(SIZE 007 ONLY)

 

LEGEND

C

Contactor

COMP

Compressor

NEC

National Electrical Code

TB

Terminal Block

208/230-3-60 460-3-60

(SIZE 007 ONLY)

208/230-3-60 575-3-60, 460-3-60 (SIZES 004-006)

Fig. 11 — Power Wiring Connections

LEGEND

AHA — Adjustable Heat Anticipator

Field Wiring

Factory Wiring

Fig. 12 — Low-Voltage Connections

10

Table 2 — Electrical Data

UNIT

NOMINAL

IFM

VOLTAGE

COMPRESSOR

 

OFM

 

IFM

COMBUSTION

POWER

DISCONNECT

RANGE

 

(ea)

 

(ea)

 

FAN MOTOR

SUPPLY

SIZE*

48TF

V-Ph-Hz

TYPE

 

 

 

FLA

Min

Max

RLA

 

LRA

Qty

Hp

FLA

FLA

MCA

MOCP†

FLA

LRA

 

208/230-1-60

Std

187

254

16.2

 

96.0

1

1/4

1.4

3.5

.6

24.5/24.5

30/30

23/23

106/106

 

Alt

 

4.9

26.6/26.6

35/35

26/26

111/111

 

 

 

 

 

 

 

 

 

 

 

 

 

Std

 

 

 

 

 

 

 

 

3.5

 

17.7/17.7

25/25

17/17

85/85

 

208/230-3-60

Alt

187

254

10.2

 

75.0

1

1/4

1.4

4.9

.6

19.1/19.1

25/25

19/19

90/90

 

 

High

 

 

 

 

 

 

 

 

5.2

 

19.4/19.4

25/25

19/19

109/109

004

 

Std

 

 

 

 

 

 

 

 

1.3

 

7.6

15

7

48/48

 

460-3-60

Alt

414

508

4.4

 

40.0

1

1/4

0.8

2.1

.3

8.4

15

8

48/48

 

 

High

 

 

 

 

 

 

 

 

2.6

 

8.9

15

9

57/57

 

 

Std

 

 

 

 

 

 

 

 

1.3

 

6.3

15

7

35

 

575-3-60

Alt

518

632

3.7

 

31.0

1

1/4

0.8

2.1

.3

6.9

15

8

37

 

 

High

 

 

 

 

 

 

 

 

2.6

 

7.3

15

7

45

 

208/230-1-60

Std

187

254

23.3

 

118.0

1

1/4

1.4

3.5

.6

34.0/34.0

40/40

32/32

129/129

 

Alt

 

4.9

35.4/35.4

45/45

34/34

133/133

 

 

 

 

 

 

 

 

 

 

 

 

 

Std

 

 

 

 

 

 

 

 

3.5

 

24.2/24.2

30/30

23/23

101/101

 

208/230-3-60

Alt

187

254

15.4

 

90.0

1

1/4

1.4

4.9

.6

25.6/25.6

30/30

25/25

105/105

 

 

High

 

 

 

 

 

 

 

 

5.2

 

25.9/25.9

30/30

25/25

124/124

005

 

Std

 

 

 

 

 

 

 

 

1.8

 

13.0

20

13

51

 

460-3-60

Alt

414

508

8.3

 

45.0

1

1/4

0.8

2.1

.3

13.3

20

13

53

 

 

High

 

 

 

 

 

 

 

 

2.6

 

13.8

20

13

62

 

 

Std

 

 

 

 

 

 

 

 

1.8

 

10.1

15

10

41

 

575-3-60

Alt

518

632

6.4

 

36.0

1

1/4

0.8

2.1

.3

10.3

15

11

42

 

 

High

 

 

 

 

 

 

 

 

2.6

 

10.7

15

10

50

 

208/230-1-60

Std

187

254

28.8

 

147.0

1

1/4

1.4

5.9

.6

43.3/43.3

60/60

42/42

161/161

 

Alt

 

6.6

44.0/44.0

60/60

42/42

184/184

 

 

 

 

 

 

 

 

 

 

 

 

 

Std

 

 

 

 

 

 

 

 

5.9

 

27.3/27.3

35/35

29/29

128/128

 

208/230-3-60

Alt

187

254

16.3

 

114.0

1

1/4

1.4

5.2

.6

26.6/26.6

35/35

26/26

148/148

 

 

High

 

 

 

 

 

 

 

 

7.5

 

28.9/28.9

35/35

29/29

174/174

006

 

Std

 

 

 

 

 

 

 

 

3.1

 

13.2

20

13

72

 

460-3-60

Alt

414

508

7.4

 

64.0

1

1/4

0.8

2.6

.3

12.7

15

12

81

 

 

High

 

 

 

 

 

 

 

 

3.4

 

13.5

20

13

94

 

 

Std

 

 

 

 

 

 

 

 

3.1

 

10.9

15

11

58

 

575-3-60

Alt

518

632

6.2

 

62.0

1

1/4

0.8

3.0

.3

10.5

15

10

66

 

 

High

 

 

 

 

 

 

 

 

3.4

 

12.6

15

11

76

 

208/230-3-60

Std

187

254

23.6

 

146.0

1

1/4

1.4

5.2

.6

30.2/30.2

35/35

29/29

180/180

 

High

 

7.5

32.5/32.5

40/40

32/32

205/205

 

 

 

 

 

 

 

 

 

 

 

007

460-3-60

Std

414

508

10.6

 

73.0

1

1/4

0.6

2.6

.3

15.4

20

15

90

High

 

3.4

16.1

20

16

103

 

 

 

 

 

 

 

 

 

 

 

 

575-3-60

Std

518

632

8.5

 

58.4

1

1/4

0.6

2.6

.3

12.3

15

13

72

 

High

 

3.4

12.9

20

14

82

 

 

 

 

 

 

 

 

 

 

 

 

LEGEND

FLA

Full Load Amps

HACR

Heating, Air Conditioning and Refrigeration

IFM

Indoor (Evaporator) Fan Motor

LRA

Locked Rotor Amps

MCA

Minimum Circuit Amps

MOCP — Maximum Overcurrent Protection

NEC

National Electrical Code

OFM

Outdoor (Condenser) Fan Motor

RLA

Rated Load Amps

*Used to determine minimum disconnect per NEC.

†Fuse or HACR circuit breaker.

NOTES:

1.In compliance with NEC requirements for multimotor and combination load equipment (refer to NEC Articles 430 and 440), the overcurrent protective device for the unit shall be fuse or HACR breaker. Canadian units may be fuse or circuit breaker.

2.Unbalanced 3-Phase Supply Voltage

Never operate a motor where a phase imbalance in supply voltage is greater than 2%. Use the following formula to determine the percent of voltage imbalance.

% Voltage Imbalance

= 100 x

max voltage deviation from average voltage

average voltage

Example: Supply voltage is 460-3-60.

AB = 452 v

BC = 464 v

AC = 455 v

Average Voltage =

452 + 464 + 455

3

=

1371

3

= 457

Determine maximum deviation from average voltage. (AB) 457 – 452 = 5 v

(BC) 464 – 457 = 7 v (AC) 457 – 455 = 2 v

Maximum deviation is 7 v.

Determine percent of voltage imbalance.

% Voltage Imbalance = 100 x

7

457

= 1.53%

This amount of phase imbalance is satisfactory as it is below the maximum allowable 2%.

IMPORTANT: If the supply voltage phase imbalance is more than 2%, contact your local electric utility company immediately.

11

Step 8 — Make Outdoor-Air Adjustments and Install Outdoor-Air Hood

MANUAL OUTDOOR-AIR DAMPER — The outdoor-air hood and screen are attached to the basepan at the bottom of the unit for shipping.

Assembly:

1.Determine quantity of ventilation required for building. Record amount for use in Step 8.

2.Remove and save outdoor air opening panel and screws. See Fig. 13.

3.Separate hood and screen from basepan by removing the 4 screws securing them. Save all screws.

4.Replace outdoor air opening panel.

OUTDOOR

AIR OPENING

PANEL

3 SCREWS (SIDE)

Fig. 13 — Damper Panel with Manual Outdoor-Air Damper Installed

Fig. 14 — Outdoor-Air Hood Details

5.Place hood on front of outdoor air opening panel. See Fig. 14 for hood details. Secure top of hood with the 4 screws removed in Step 3. See Fig. 15.

6.Remove and save 6 screws (3 on each side) from sides of the manual outdoor-air damper.

7.Align screw holes on hood with screw holes on side of manual outdoor-air damper. See Fig. 14 and 15. Secure hood with 6 screws from Step 6.

8.Adjust minimum position setting of the damper blade by adjusting the manual outdoor-air adjustment screws on the front of the damper blade. See Fig. 13. Slide blade vertically until it is in the appropriate position determined by Fig. 16. Tighten screws.

9.Remove and save screws currently on sides of hood. Insert screen. Secure screen to hood using the screws. See Fig. 15.

Fig. 15 — Outdoor-Air Damper with

Hood Attached

Fig. 16 — Position Setting

12

OPTIONAL DURABLADE ECONOMIZER — The optional economizer hood assembly is packaged and shipped in the filter section. Damper blades and control boards are installed at the factory and the economizer is shipped in the vertical discharge position.

NOTE: Horizontal discharge block-off plate is shipped with the air hood package. If unit is to be used for vertical discharge application, discard this plate.

NOTE: Be sure to engage Durablade economizer flange under tabs in return-air opening of the unit base.

Assembly:

1.Determine if ventilation air is required in building. If so, determine the minimum amount to be supplied by each unit and record quantity of ventilation air needed for use in Step 6.

2.Remove filter access panel by raising panel and swinging panel outward. Panel is now disengaged from track and can be removed. No tools are required to remove filter access panel. Remove outdoor-air opening panel. Save panels and screws. See Fig. 17. Remove optional economizer and outdoor-air damper hood package from filter section.

3.Assemble outdoor-air hood top and side plates as shown in Fig. 18. Install seal strips on hood top and sides. Put aside screen retainer and screws for later assembly. Do not attach hood to unit at this time.

4.To convert to horizontal discharge application:

a.Rotate economizer 90 degrees until the economizer motor faces the condenser section (see Fig. 19).

b.Remove screws and tape from damper then rotate the barometric relief damper hinge 90 degrees. Barometric relief damper should open vertically to operate properly.

c.Install horizontal discharge block-off plate over the opening on the access panel. (Block-off plate MUST be installed before installing hood assembly.) See Fig. 20. Remove 12-pin blue and yellow wire jumper plug and store.

5.Insert economizer plug into economizer harness. Remove tape from barometric relief damper. See Fig. 21. Remove shipping screw (see Fig. 19).

6.If ventilation air is not required, proceed to Step 7. If ventilation air is required, determine the minimum position setting for required airflow. See Fig. 22. Adjust minimum position setting by adjusting the screws on the position setting bracket. Slide bracket until the top screw is in the position determined by Fig. 22. Tighten screws.

7.Remove tape from outdoor-air thermostat (OAT). Fasten OAT to inside of hood using screws and speed clips provided. See Fig. 23. Make sure OAT terminals are positioned up.

8.Replace outdoor-air opening panel using screws from Step 2. Replace filter access panel. Ensure the filter access panel slides along the tracks and is securely engaged.

9.Fasten hood top and side plate assembly (Fig. 18) to outdoor-air opening panel with screws provided.

10.Place knob supplied with economizer on OAT. See Fig. 23. Set OAT for 3° F below indoor room thermostat setting. If accessory enthalpy control (EC) is used in place of OAT, see instructions shipped with EC for installation and adjustment. See Fig. 23.

11.Connect OAT per Fig. 24.

12.Slide outdoor-air inlet screens into screen track on hood side plate. While holding screen in place, fasten screen retainer to hood using screws provided.

NOTE: Refer to Fig. 25 for economizer barometric relief damper characteristics.

Fig. 17 — Typical Access Panel Locations

Fig. 18 — Outdoor-Air Hood Details

ECONOMIZER CONTROL BOARD

BAROMETRIC

RELIEF

DAMPER

ECONOMIZER

PLUG

SHIPPING

SCREW

ECONOMIZER

MOTOR

Fig. 19 — Horizontal Durablade

Economizer Installation

13

BLOCK-OFF PLATE

Fig. 20 — Horizontal Discharge Block-Off Plate

U-SHAPED

ECONOMIZER

 

 

 

 

OAT

HOLE

CONTROL

ECONOMIZER

ECONOMIZER

TOP

 

TOP

(TERMINALS ARE UP)

(NOT

BOARD

PLUG

MOTOR

SCREW

SHOWN)

 

 

 

 

 

 

UNIT

WIRING

OUTSIDE AIR

SCREEN

HARNESS

 

BAROMETRIC

RELIEF DAMPER

SHIPPING

SCREW

POSITION SETTING

ENTHALPY

BRACKET

CONTROL

Fig. 21 — Durablade Economizer Installed in Unit

HOOD

 

OPEN

 

 

 

POSITIONMINIMUM

 

 

 

 

 

 

 

 

S

 

 

 

 

T

 

3

 

 

1

 

 

 

 

 

 

 

P

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

T1

 

4

 

 

2

 

 

5

 

 

 

 

P1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

T ID

 

 

 

 

8 S

CONT

OR

CONT

 

 

 

 

 

 

 

 

 

 

%

 

1 R

 

 

 

 

 

 

 

Y

 

 

IMUH

 

9 U

 

UNPOWERED W

 

 

4

 

 

 

 

 

 

90

 

 

C

 

 

 

 

 

 

30

60

70

 

 

8

T

ACT

 

CTS

3

 

 

ENTHALPY

 

60

 

DAMPER

 

 

1

A

5A

TE H

2

 

 

 

 

 

 

 

 

m

 

 

 

10

 

 

 

 

D

CW

A

2

RA

 

SHO

 

TR

 

 

50

 

 

 

 

C

 

A

 

 

 

 

2

 

 

 

 

 

 

 

V

TINGS:

 

 

 

 

 

 

OUTDOOR

55

 

OPEN

 

 

 

SETPOINTS

 

M

ST

IGH

 

 

C

 

 

 

 

 

 

 

 

 

 

 

AV

 

 

 

 

 

 

 

B

 

 

 

 

 

N

 

 

 

 

 

 

 

 

 

A

 

 

VDC

1

A IN

 

 

 

CONTROL

F

5

 

 

 

CLOSED DAMPER

 

 

 

 

 

1

TR1

 

 

7065

 

 

 

 

 

 

 

A

RUN,

 

 

 

 

 

 

TEMP

 

 

 

 

 

 

.

 

ENTHALPY

 

 

 

 

 

 

 

 

 

 

A

IN

 

 

 

 

 

°

7

 

 

 

 

 

 

1

 

 

 

 

 

 

 

 

 

 

 

 

 

IN

5A

 

 

 

 

 

 

 

 

 

 

 

 

 

CCW

 

1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

T

.

 

 

 

 

 

 

.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

80

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

85

 

 

 

 

2

 

 

 

 

 

 

 

 

 

 

 

REV.

 

97-367

 

 

 

 

 

 

 

 

 

 

B

C

D S

O

RE V .

B

TR

Fig. 23 — Outdoor-Air Thermostat/

Enthalpy Control Installation

Example:

Given — Negative Pressure. . . . . . . . . . . . . . . . . . . . . . . 0.2 in. wg

Outdoor Air . . . . . . . . . .. . . . . . . . . . . . . . . . . . . . . . . . 900 cfm

Determine — Setting = 5 in.

Fig. 22 — Durablade Economizer

Minimum Position Setting

14

LEGEND

OAT — Outdoor-Air Thermostat

NOTE: See unit wiring diagram for details.

Fig. 24 — Wiring Connections for

Outdoor-Air Thermostat

 

0.90

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0.80

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

wg)(in.

0.70

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0.60

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

DROP

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0.50

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

PRESSURE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0.40

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0.30

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0.20

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0.10

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0.00

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

100

200

300

400

500

600

700

800

 

 

 

 

 

 

 

 

 

 

 

CFM

 

 

 

 

 

 

 

 

 

Fig. 25 — Durablade Economizer

Barometric Relief Damper Characteristics

OPTIONAL ECONOMI$ER — See Fig. 26 for EconoMi$er component locations.

1.To remove the existing unit filter access panel, raise the panel and swing the bottom outward. The panel is now disengaged from the track and can be removed. Remove the indoor coil access panel and discard. See Fig. 27.

If installing an optional Power Exhaust Assembly, refer to the EconoMi$er Power Exhaust Installation Instructions.

Controller should be mounted in vertical position as shown in Fig. 26.

2.Assemble the hood assembly as follows:

Remove the EconoMi$er hood from its packaging. Remove shipping brackets holding hood package to EconoMi$er. Locate the outdoor-air opening panel. See Fig. 28. Remove hood assembly shipping brackets located on the back (sloped) side of the EconoMi$er assembly. These brackets are used to retain the hood assembly during shipping only.

3.Install the 1/8 x 3/4-in. seal strip on the exhaust air hood side panels and the bottom bracket. Assemble the exhaust air hood to the outdoor-air opening panel as shown in Fig. 28, using the screws provided. Do not attach hood assembly to unit at this time.

4.Install the 1/8 x 3/4-in. seal strip on the outdoor-air hood top and side panels. Assemble the outdoor-air hood to the outdoor-air opening panel as shown in Fig. 29, using the screws provided. Do not attach hood assembly to the unit at this time.

15

ECONOMI$ER

CONTROLLER

PLUG

GEAR-DRIVEN

 

 

DAMPER

OUTDOOR AIR

TEMPERATURE

SENSOR

ACTUATOR

BAROMETRIC RELIEF DAMPERS

Fig. 26 — EconoMi$er Component Locations

OUTDOOR-AIR

FILTER ACCESS

OPENING PANEL

PANEL

Fig. 27 — Typical Access Panel Locations

OUTDOOR AIR

OPENING PANEL EXHAUST AIR HOOD TOP

SCREEN

RETAINER

 

EXHAUST AIR

SEAL STRIP

HOOD SIDES

 

EXHAUST AIR SCREEN

EXHAUST AIR BOTTOM BRACKET

Fig. 28 — Exhaust Air Hood Assembly

5.Slide the outdoor-air inlet screens into the screen track on the hood side panels. While holding the screens in place, fasten the screen retainer to the hood using the screws provided. Repeat the process for the barometric exhaust air screen. Do not attach completed (Fig. 30) hood assembly to unit at this time.

6.Slide the EconoMi$er assembly into the rooftop unit. See Fig. 31 and 32.

NOTE: Be sure to engage rear EconoMi$er flange under tabs in return-air opening of the unit base. See Fig. 31.

7.Install the outdoor-air block-off plate, then secure the EconoMi$er with the screws provided. See Fig. 32.

8.Remove and discard the 12-pin jumper plug from the unit wiring harness located in the upper left corner and insert the EconoMi$er plug into the unit wiring harness. Refer to wiring diagrams Fig. 33 and 34. Also refer to Fig. 35 if installing an accessory power exhaust.

9.Install the complete hood assembly on the unit and secure using the screws provided.

10.Remove the indoor fan motor access panel. See Fig. 36.

11.Mount the supply-air temperature sensor to the lower

left portion of the indoor

blower housing with the

two (2) screws provided (see Fig. 37). Connect the violet

and pink wires to the corresponding connections on the

supply-air temperature sensor. Replace the indoor fan

motor access panel.

 

OUTDOOR AIR

SEAL STRIP

 

OPENING

 

OUTDOOR AIR

 

 

PANEL

 

 

HOOD TOP

 

 

 

SCREEN

 

 

 

RETAINER

 

 

SEAL STRIP

OUTDOOR AIR

 

 

INLET

 

 

 

SCREENS

ASSEMBLED

 

 

EXHAUST HOOD

 

 

OUTDOOR AIR

 

 

HOOD SIDES

 

Fig. 29 — Outdoor-Air Hood Assembly

Fig. 30 — Completed Hood Assembly

UNIT FILTER

ECONOMI$ER CLIP

RACK

HVAC UNIT

ECONOMI$ER

UNIT BASE

ECONOMI$ER REAR

FLANGE

Fig. 31 — Rear EconoMi$er Flange Installation

WIRING

HARNESS

OUTDOOR

AIR

BLOCK-OFF

PLATE

Fig. 32 — EconoMi$er Installed

16

Loading...
+ 36 hidden pages