Carrier HFC-134A User Manual

0 (0)

EVERGREEN® 23XRV High-Efficiency Variable Speed Screw Chiller with Foxfire™ Compression Technology and PIC III Controls 50/60 Hz HFC-134a

Installation Instructions

SAFETY CONSIDERATIONS

Screw liquid chillers are designed to provide safe and reliable service when operated within design specifications. When operating this equipment, use good judgment and safety precautions to avoid damage to equipment and property or injury to personnel.

Be sure you understand and follow the procedures and safety precautions contained in the machine instructions, as well as those listed in this guide.

DO NOT VENT refrigerant relief devices within a building. Outlet from rupture disc or relief valve must be vented outdoors in accordance with the latest edition of ANSI/ASHRAE 15 (American National Standards Institute/American Society of Heating, Refrigeration and Air-Conditioning Engineers) (Safety Code for Mechanical Refrigeration). The accumulation of refrigerant in an enclosed space can displace oxygen and cause asphyxiation.

PROVIDE adequate ventilation in accordance with ANSI/ ASHRAE 15, especially for enclosed and low overhead spaces. Inhalation of high concentrations of vapor is harmful and may cause heart irregularities, unconsciousness, or death. Intentional misuse can be fatal. Vapor is heavier than air and reduces the amount of oxygen available for breathing. Product causes eye and skin irritation. Decomposition products are hazardous.

DO NOT USE OXYGEN to purge lines or to pressurize a machine for any purpose. Oxygen gas reacts violently with oil, grease, and other common substances.

DO NOT USE air to leak test. Use only refrigerant or dry nitrogen.

NEVER EXCEED specified test pressures. VERIFY the allowable test pressure by checking the instruction literature and the design pressures on the equipment nameplate.

DO NOT VALVE OFF any safety device.

BE SURE that all pressure relief devices are properly installed and functioning before operating any machine.

RISK OF INJURY OR DEATH by electrocution. High voltage is present on motor leads even though the motor is not running. Open the power supply disconnect before touching motor leads or terminals.

DO NOT WELD OR FLAMECUT any refrigerant line or vessel until all refrigerant (liquid and vapor) has been removed from chiller. Traces of vapor should be displaced with dry air or nitrogen and the work area should be well ventilated. Refrigerant in contact with an open flame produces toxic gases.

DO NOT USE eyebolts or eyebolt holes to rig heat exchangers or the entire assembly.

DO NOT work on high-voltage equipment unless you are a qualified electrician.

DO NOT WORK ON electrical components, including control panels, switches, starters, or oil heater until you are sure ALL POWER IS OFF and no residual voltage can leak from capacitors or solid-state components.

LOCK OPEN AND TAG electrical circuits during servicing. IF WORK IS INTERRUPTED, confirm that all circuits are deenergized before resuming work.

AVOID SPILLING liquid refrigerant on skin or getting it into the eyes. USE SAFETY GOGGLES. Wash any spills from the skin with soap and water. If liquid refrigerant enters the eyes, IMMEDIATELY FLUSH EYES with water and consult a physician.

NEVER APPLY an open flame or live steam to a refrigerant cylinder. Dangerous over pressure can result. When it is necessary to heat refrigerant, use only warm (110 F [43 C]) water.

DO NOT REUSE disposable (nonreturnable) cylinders or attempt to refill them. It is DANGEROUS AND ILLEGAL. When cylinder is emptied, evacuate remaining gas pressure, loosen the collar, and unscrew and discard the valve stem. DO NOT INCINERATE.

CHECK THE REFRIGERANT TYPE before adding refrigerant to the machine. The introduction of the wrong refrigerant can cause machine damage or malfunction.

Operation of this equipment with refrigerants other than those cited herein should comply with ANSI/ASHRAE 15 (latest edition). Contact Carrier for further information on use of this machine with other refrigerants.

DO NOT ATTEMPT TO REMOVE fittings, covers, etc., while machine is under pressure or while machine is running. Be sure pressure is at 0 psig (0 kPa) before breaking any refrigerant connection.

CAREFULLY INSPECT all relief valves, rupture discs, and other relief devices AT LEAST ONCE A YEAR. If machine operates in a corrosive atmosphere, inspect the devices at more frequent intervals.

DO NOT ATTEMPT TO REPAIR OR RECONDITION any relief valve when corrosion or build-up of foreign material (rust, dirt, scale, etc.) is found within the valve body or mechanism. Replace the valve.

DO NOT install relief devices in series or backwards.

USE CARE when working near or in line with a compressed spring. Sudden release of the spring can cause it and objects in its path to act as projectiles.

DO NOT STEP on refrigerant lines. Broken lines can whip about and release refrigerant, causing personal injury.

DO NOT climb over a machine. Use platform, catwalk, or staging. Follow safe practices when using ladders.

USE MECHANICAL EQUIPMENT (crane, hoist, etc.) to lift or move inspection covers or other heavy components. Even if components are light, use mechanical equipment when there is a risk of slipping or losing your balance.

BE AWARE that certain automatic start arrangements CAN ENGAGE THE STARTER, TOWER FAN, OR PUMPS. Open the disconnect ahead of the starter, tower fan, and pumps. Shut off the machine or pump before servicing equipment.

USE only repaired or replacement parts that meet the code requirements of the original equipment.

DO NOT VENT OR DRAIN waterboxes containing industrial brines, liquid, gases, or semisolids without the permission of your process control group.

DO NOT LOOSEN waterbox cover bolts until the waterbox has been completely drained.

DOUBLE-CHECK that coupling nut wrenches, dial indicators, or other items have been removed before rotating any shafts.

DO NOT LOOSEN a packing gland nut before checking that the nut has a positive thread engagement.

PERIODICALLY INSPECT all valves, fittings, and piping for corrosion, rust, leaks, or damage.

PROVIDE A DRAIN connection in the vent line near each pressure relief device to prevent a build-up of condensate or rain water.

Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.

Book

2

Catalog No. 532-309

Printed in U.S.A.

Form 23XRV-1SI

Pg 1

309 6-06

Replaces: New

Tab

5e

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CONTENTS

Page

SAFETY CONSIDERATIONS . . . . . . . . . . . . . . . . . . . . . . 1

INTRODUCTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2

General. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2

Job Data. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2

INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-42

Receiving the Machine . . . . . . . . . . . . . . . . . . . . . . . . . . . 2

INSPECT SHIPMENT

IDENTIFY MACHINE

INSTALLATION REQUIREMENTS

PROVIDE MACHINE PROTECTION

Rigging the Machine . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3

RIG MACHINE ASSEMBLY

RIG MACHINE COMPONENTS

Separate Machine Components . . . . . . . . . . . . . . . . . 13

SEPARATE COOLER AND CONDENSER

REMOVE THE CONTROLS/DRIVE ENCLOSURE FROM THE CONDENSER

REMOVE THE DISCHARGE PIPE ASSEMBLY FROM THE CONDENSER

SEPARATE THE COMPRESSOR FROM THE CONDENSER

SEPARATE THE VAPORIZER FROM THE

CONDENSER

VFD Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19

Install Machine Supports . . . . . . . . . . . . . . . . . . . . . . . . 22

INSTALL STANDARD ISOLATION

INSTALL ACCESSORY ISOLATION

INSTALL SPRING ISOLATION

Connect Piping. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24

INSTALL WATER PIPING TO HEAT EXCHANGERS

INSTALL VENT PIPING TO RELIEF VALVES

Make Electrical Connections . . . . . . . . . . . . . . . . . . . . 30

GROUNDING THE CONTROLS/DRIVE ENCLOSURE

INSTALLING INPUT POWER WIRING

WIRING THE FIELD WIRING TERMINAL STRIPS

CONNECT CONTROL INPUTS

CONNECT CONTROL OUTPUTS

CONNECT STARTER

COMPLETING THE INSTALLATION . . . . . . . . . . . 43-47

Checking the Installation . . . . . . . . . . . . . . . . . . . . . . . . 43

Oil Pump and Oil Heater . . . . . . . . . . . . . . . . . . . . . . . . . 43

Connect Control Wiring . . . . . . . . . . . . . . . . . . . . . . . . . 43

Carrier Comfort Network Interface. . . . . . . . . . . . . . . 43

Lead-Lag Control Wiring . . . . . . . . . . . . . . . . . . . . . . . . 44

Install Field Insulation and Lagging . . . . . . . . . . . . . 44

INSTALLATION START-UP REQUEST

CHECKLIST . . . . . . . . . . . . . . . . . . . . . . . . . . . CL-1, CL-2

INTRODUCTION

General — The 23XRV machine is factory assembled, wired, and leak tested. Installation (not by Carrier) consists primarily of establishing water and electrical services to the machine. The rigging, installation, field wiring, field piping, and insulation of waterbox covers are the responsibility of the contractor and/or customer. Carrier has no installation responsibilities for the equipment.

Job Data — Necessary information consists of:

job contract or specifications

machine location prints

rigging information

piping prints and details

field wiring drawings

starter manufacturer’s installation details

Carrier certified print

INSTALLATION

Receiving the Machine

INSPECT SHIPMENT

Do not open any valves or loosen any connections. The 23XRV machine may be shipped with a full refrigerant charge. Some machines may be shipped with a nitrogen holding charge as an option.

1.Inspect for shipping damage while machine is still on shipping conveyance. If machine appears to be damaged or has been torn loose from its anchorage, have it examined by transportation inspectors before removal. Forward claim papers directly to transportation company. Manufacturer is not responsible for any damage incurred in transit.

2.Check all items against shipping list. Immediately notify the nearest Carrier representative if any item is missing.

3.To prevent loss or damage, leave all parts in original packages until beginning installation. All openings are closed with covers or plugs to prevent dirt and debris from entering machine components during shipping. A full operating oil charge is placed in the oil sump before shipment.

IDENTIFY MACHINE (Fig. 1-4) — Refer to machine nameplate in Fig. 1. The machine model number, serial number, and heat exchanger sizes are stamped on the Refrigeration Machine nameplate located on the side of the VFD (variable frequency drive) enclosure. Check this information against shipping papers and job data.

a23-1547

Fig. 1 — Refrigeration Machine Nameplate

2

 

S –Special

 

23XRV – High Efficiency

Not Used

 

Variable Speed Screw Chiller

 

 

 

 

Cooler Size*

Voltage Code

 

3 – 380-3-60

 

30-32

 

4 – 416-3-60

 

35-37

 

5 – 460-3-60

 

40-42

 

9 – 400-3-50

 

45-47

 

 

 

50-52

Drive

Rectifier Max

Inverter Max

55-57

Frame

Input Amps†

Output Amps†

 

Condenser Size*

AA

440

442

BA

520

442

30-32

BB

520

520

35-37

CC

608

608

40-42

 

 

 

45-47

Motor Code

Max Motor Amps

50-52

55-57

P

265

 

Q

283

 

 

 

Economizer Option

R

306

 

S

334

 

E – With Economizer

T

368

 

N – No Economizer

U

421

a23-1533

 

V

440

 

R – Compressor

*First number denotes frame size.

†Maximum limits only. Additional application limits apply that may reduce these ampacities.

Fig. 2 — Model Number Identification

Identifying the Drive by Part Number — Each LiquiFlo™ 2.0 AC drive can be identified by its part number. See Fig. 5. This number appears on the shipping label and on the VFD nameplate.

Drive Input Component Location — Figure 6 identifies the control center components.

Identifying the Power Module by I.D. Number — Each LiquiFlo 2.0 AC power module can be identified by its I.D. number. See Fig. 5. This number appears on the shipping label and on the power module’s nameplate. Power ratings are provided in Table 1.

INSTALLATION REQUIREMENTS — Certain requirements should be checked before continuing with the chiller’s electrical installation. Input power wire sizes, branch circuit protection, and control wiring are all areas that need to be evaluated.

Determining Wire Size Requirements — Wire size should be determined based on the size of the conduit openings, and applicable local, national, and international codes (e.g., NEC [National Electric Code]/CEC [California Energy Commission] regulations). General recommendations are included in the Carrier field wiring drawing.

Conduit Entry Size — It is important to determine the size of the conduit openings in the enclosure power entry plate so that the wire planned for a specific entry point will fit through the opening. Do NOT punch holes or drill into the top surface of the control center enclosure for field wiring. Do not punch holes or drill into the top surface of the control center enclosure for field wiring. Knockouts are provided in the back of the control center for field control wiring connections.

Recommended Control and Signal Wire Sizes — The recommended minimum size wire to connect I/O signals to the control terminal blocks is 18 AWG (American Wire Gage). Recommended terminal tightening torque is 7 to 9 in.-lb (0.79 to 1.02 N-m).

Recommended Air Flow Clearances — Be sure there is adequate clearance for air circulation around the enclosure. A 6-in. (152.4 mm) minimum clearance is required wherever vents are located in the VFD enclosure.

Match Power Module Input and Supply Power Ratings — It is important to verify that building power will meet the input power requirements of the Machine Electrical Data nameplate

input power rating. Be sure the input power to the chiller corresponds to the chiller’s nameplate voltage, current, and frequency. Refer to machine nameplate in Fig. 7. The machine electrical data nameplate is located on the right side of the control center.

PROVIDE MACHINE PROTECTION — Protect machine and VFD enclosure from construction dirt and moisture. Keep protective shipping covers in place until machine is ready for installation.

If machine is exposed to freezing temperatures after water circuits have been installed, open waterbox drains and remove all water from cooler and condenser. Leave drains open until system is filled.

It is important to properly plan before installing a 23XRV unit to ensure that the environment and operating conditions are satisfactory. The installation must comply with all requirements in the certified prints.

Rigging the Machine — The 23XRV machine can be rigged as an entire assembly. Large interconnecting piping has flanged connections that allow the compressor, cooler, and condenser sections to be separated and rigged individually. In addition, the VFD can be removed and rigged separately.

RIG MACHINE ASSEMBLY — See rigging instructions on label attached to machine. Also refer to rigging guide (Fig. 8), physical data in Fig. 9, and Tables 2-9B. Lift machine only from the points indicated in rigging guide. Each lifting cable or chain must be capable of supporting the entire weight of the machine.

Lifting machine from points other than those specified may result in serious damage to the unit and personal injury. Rigging equipment and procedures must be adequate for machine weight. See Fig. 8 for machine weights.

NOTE: These weights are broken down into component sections for use when installing the unit in sections. For the complete machine weight, add all component sections and refrigerant charge together. See Tables 5-9B for machine component weights.

3

1

21

20

19

-1548

41 40 39 38

37

-1549

4

2 3

5

6

7

8

9

10

12 11

13

14

16 15

18 17

22

23

24

25

26

36 35 34

27

33

28

32 31 30 29

45

42 43 44

46

47

48

49

50

a23-1550 51

1Motor Terminal Cover Plate

2Variable Frequency Drive

3International Chiller Visual Controller (ICVC)

4Discharge Pipe Relief Valve

5Condenser

6Oil Reclaim Actuator

7Vaporizer Sight Glass

8Oil Filter Assembly (Hidden)

9Vaporizer

10Oil Charging/Drain Valve

11Oil Sump

12Condenser Refrigerant Pumpout Valve

13Condenser Float Chamber

14Cooler Inlet Isolation Valve

15ASME Nameplate, Economizer (Hidden)

16Filter Drier

17Oil Sump Heater

18Condenser Supply/Return End Waterbox

19Cooler Supply/Return End Waterbox

20Motor Cooling Supply Line

21VFD Disconnect

22Discharge Pipe

23Compressor Discharge Check Valve Access Cover

24Condenser Relief Valves

25Refrigerant Charging Valve

26Cooler Relief Valve

27Tubesheet Mounting Brackets

28Typical Waterbox Drain Coupling

29ASME Nameplate, Condenser

30Oil Pump

31Oil Pump Inlet Strainer

32Strainer Housing Sight Glass

33Discharge Isolation Valve (Option or Accessory)

34Refrigeration Machine Nameplate

35Machine Electrical Data Nameplate

36Oil Sump Sight Glass

37Filter Drier Isolation Valve with Schrader

38Economizer

39Motor Cooling Sight Glass

40Motor Cooling Isolation Valve

41Vaporizer Drain Sight Glass

42VFD Cold Plate Refrigeration Inlet Connection (Outlet Hidden)

43VFD Cold Plate Solenoid

44Compressor Nameplate

45Compressor Lubrication Block

46Economizer Muffler

47Vaporizer Condenser Gas Isolation Valve

48Hot Gas Bypass Isolation and Trim Valve

49VFD Cooling Refrigerant Strainer

50Cooler Refrigerant Pumpout Valve

51ASME Nameplate, Cooler

Fig. 3 — Typical 23XRV Components

4

6

4 5

2 3

1

9

7

a23-1551 8

10

12 13

11

14

 

15

20

16

 

 

17

a23-1552

19

 

18

1Condenser Pressure

2Evaporator Pressure

3Compressor Discharge Temperature

4Compressor Discharge Pressure

5Compressor Discharge High Pressure Switch

6Compressor Motor Winding Temperature (Hidden)

7Evaporator Refrigerant Liquid Temperature (Hidden)

8Condenser Liquid Temperature

9Condenser Liquid Flow (Optional)

10 — Inductor Temperature Switch

(Inside VFD Enclosure)

11 — VFD Rectifier Temperature

(Inside Power Module)

12 — VFD Cold Plate Temperature

(Inside VFD Enclosure)

13 — VFD Inverter Temperature

(Inside Power Module)

14 — Humidity Sensor (Inside VFD Enclosure)

15 — Oil Pressure Leaving Filter (Hidden)

16 — Oil Sump Pressure (Hidden)

17 — Oil Sump Temperature (Hidden)

18 — Vaporizer Temperature

19 — Evaporator Liquid Temperature

20 — Evaporator Liquid Flow (Optional)

Fig. 4 — Typical 23XRV Installation (Sensor Locations)

a23-1553

Fig. 5 — VFD Nameplate

5

6

-a23

 

 

1554

21

1

 

 

19

18

17

16

1Input Inductor Assembly

2Capacitor Bank Assembly

3Pre-Charge Resistor Assembly

4AC Contactor (3)

5Power Module Assembly

6Terminal Block, 10-Position (2)

7Power Module Nameplate

8Fuse Black, 30A, 600V, Class CC

9Fuse, Class CC, 600V, 15A (2)

10Fuse, Class CC, 600V, 5A (1)

11Fuse, Class CC, 600V, 20A (3)

10

 

11

 

9

 

20

 

 

 

 

 

2

8

13

8

5

6

 

16

8

14

3

4

7

6

 

 

 

12

15

 

 

 

 

12Fuse, Class CC, 600V, 1A (3)

13Transformer, 3kVA

14Line Sync PC Board Assembly

15Line Sync Board Cover

16Fan, 115V (3)

17Circuit Breaker, 600V, 15A

18Circuit Breaker, 600V

19Lug, Ground, 2-600 MCM

20Communications Interface Board

21Input Power Wiring Panel

Fig. 6 — Control Center Components

a23-1555

Fig. 7 — Machine Electrical Data Nameplate

HEAT EXHANGER

COMPRESSOR

MAXIMUM WEIGHT

VESSEL

DIM.

CHAIN LENGTH

DIM.

DIM.

CODE

FRAME SIZE*

(lb)

LENGTH

“A”

“B”

“C”

“D”

“E”

“F”

30-32

 

19,187

12′

6′-10″

13′- 5″

13′-0″

12′- 5″

3′-11″

3′- 8″

35-37

 

20,589

14′

7′- 8″

13′-10″

13′-5″

12′-10″

3′-11″

3′- 8″

40-42

R

23,928

12′

6′-10″

13′- 6″

12′-8″

12′- 3″

4′- 1″

3′-11″

45-47

25,167

14′

7′- 8″

13′-11″

13′-2″

12′- 8″

4′- 1″

3′-11″

 

50-52

 

26,950

12′

6′-10″

13′-10″

12′-7″

12′- 9″

4′- 0″

4′- 4″

55-57

 

28,479

14′

7′- 8″

14′- 4″

13′-1″

13′- 1″

4′- 0″

4′- 4″

*The 11th character of the chiller model number indicates the frame size of the compressor.

CHAIN “D” CHAIN “B” (SEE NOTE #2) (SEE NOTE #2)

CHAIN “C” (SEE NOTE #2)

15´-0´´ MIN. HEIGHT ABOVE FLOOR

“E”

“A”

“F”

a23-1556

MACHINE RIGGING GUIDE

NOTES:

1.Each chain must be capable of supporting the entire weight of the machine. See chart for maximum weights.

2.Chain lengths shown are typical for 15′ lifting height. Some minor adjustments may be required.

Fig. 8 — Machine Rigging Guide (Cooler Size 30 Through 57)

7

TUBE REMOVAL SPACE FOR EITHER END SIZES 30-32, 40-42, 50-52

12’-7½” (3848 mm) SIZES 35-37, 45-47, 55-57

14’-4” (4369 mm)

0’-3”

0’-3”

4’-10” 0’-5”

MOTOR SERVICE

 

CLEARANCE

 

1’ - 10” (559 mm)

FRAME R COMPRESSOR 3’ - 0” (915mm)

 

 

RECOMMENDED OVERHEAD SERVICE CLEARANCE

C

2’ MIN

(610 mm)

B

 

A

(WIDEST POINT)

 

 

SERVICE AREA

 

4’ - 10” MIN

a23-1557

 

(1219 mm)

 

 

Fig. 9 — 23XRV Dimensions (Refer to Tables 2 and 3)

Table 1 — Drive Assembly and Power Module Ratings

 

 

ENCLOSURE

INPUT

MAX INPUT

MAX OUTPUT

CARRIER PART NUMBER

FRAME SIZE

VOLTAGE (V)

CURRENT

CURRENT* at 4kHZ

TYPE

 

 

RANGE

(AMPS)

(AMPS)

 

 

 

23XRA2AA_ _ _ _ _ _ _ _ _ _ _

Frame 2AA

NEMA 1

380 to 460

440

442

23XRA2BA_ _ _ _ _ _ _ _ _ _ _

Frame 2BA

NEMA 1

380 to 460

520

442

23XRA2BB_ _ _ _ _ _ _ _ _ _ _

Frame 2BB

NEMA 1

380 to 460

520

520

23XRA2CC_ _ _ _ _ _ _ _ _ _ _

Frame 2CC

NEMA 1

380 to 460

608

608

*110% output current capability for one minute, 150% output current for 5 seconds.

Table 2 — 23XRV Dimensions (Nozzle-In-Head Waterbox)

HEAT EXCHANGER

 

A (Length, with Nozzle-in-Head Waterbox)

 

 

B (Width)

C (Height)

1 Pass

2-Pass*

3 Pass†

 

SIZE

 

 

 

 

 

 

ft-in.

mm

ft-in.

mm

ft-in.

mm

ft-in.

mm

ft-in.

mm

30 to 32

14- 31/4

4350

13- 81/4

4172

14- 31/4

4350

6-

4

1930

7-25/8

2200

35 to 37

15-113/4

4870

15- 43/4

4693

15-113/4

4870

6-

4

1930

7-25/8

2200

40 to 42

14- 9

4496

14- 31/8

4347

14- 6

4420

6- 8½

2045

7-6½

2299

45 to 47

16- 51/2

5017

15-115/8

4867

16- 21/2

4940

6- 8½

2045

7-6½

2299

50 to 52

14-10

4521

14- 41/2

4382

14- 61/2

4432

6-113/4

2127

7-63/4

2305

55 to 57

16- 61/2

5042

16- 1

4902

16- 3

4953

6-113/4

2127

7-63/4

2305

*Assumes both cooler and condenser nozzles on same end of chiller.

†1 or 3 pass length applies if either (or both) cooler or condenser is a 1 or 3 pass design. NOTES:

1.Service access should be provided per American Society of Heating, Refrigeration, and Air Conditioning Engineers (ASHRAE) 15, latest edition, National Fire Protection Association (NFPA) 70, and local safety code.

2.Allow at least 3 ft (915 mm) overhead clearance for service rigging for frame R compressor.

3.Certified drawings available upon request.

4.Marine waterboxes may add 6 in. to the width of the machine. See certified drawings for details.

5.‘A’ length dimensions shown are for standard 150 psi design and victaulic connections. The 300 psi design and/or flanges will add length. See certified drawings.

6.Dished head waterbox covers not available for 3 pass design.

8

Table 3 — 23XRV Dimensions (Marine Waterbox)

HEAT EXCHANGER

A (Length, Marine Waterbox — not shown)

MAXIMUM

MAXIMUM

2-Pass*

 

1 or 3 Pass†

 

B WIDTH

C HEIGHT

SIZE

 

 

 

ft-in.

 

mm

ft-in.

mm

ft-in.

 

mm

ft-in.

mm

30 to 32

14- 9

 

4496

16-43/4

4997

6-93/8

 

2067

7-25/8

2200

35 to 37

16- 51/2

 

5017

18-11/4

5518

6-93/8

 

2067

7-25/8

2200

40 to 42

15- 23/4

 

4642

16-81/4

5086

6-93/4

 

2076

7-61/2

2299

45 to 47

16-111/4

 

5163

18-43/4

5607

6-93/4

 

2076

7-61/2

2299

50 to 52

15- 31/2

 

4661

16-81/2

5093

7-1

 

2159

7-63/4

2305

55 to 57

17- 0

 

5182

18-5

5613

7-1

 

2159

7-63/4

2305

*Assumes both cooler and condenser nozzles on same end of chiller. †1 or 3 pass length applies if cooler is a 1 or 3 pass design.

NOTES:

1.Service access should be provided per American Society of Heating, Refrigeration, and Air Conditioning Engineers (ASHRAE) 15, latest edition, National Fire Protection Association (NFPA) 70, and local safety code.

2.Allow at least 3 ft (915 mm) overhead clearance for service rigging for frame R compressor.

3.Certified drawings available upon request.

4.Marine waterboxes may add 6 in. to the width of the machine. See certified drawings for details.

5.‘A’ length and ‘B’ width dimensions shown are for standard 150 psi design and victaulic connections. The 300 psi design and/ or flanges will add length. See certified drawings.

Table 4 — 23XRV Waterbox Nozzle Sizes

FRAME

PRESSURE

PASS

NOMINAL PIPE SIZE (in.)

ACTUAL PIPE ID (in.)

SIZE

psig (kPa)

Cooler

Condenser

Cooler

Condenser

 

 

150/300

1

10

10

10.020

10.020

3

2

8

8

7.981

7.981

(1034/2068)

 

3

6

6

6.065

6.065

 

 

 

150/300

1

10

10

10.020

10.020

4

2

8

8

7.981

7.981

(1034/2068)

 

3

6

6

6.065

6.065

 

 

 

150/300

1

10

10

10.020

10.020

5

2

8

10

7.981

10.020

(1034/2068)

 

3

6

8

6.065

7.981

 

 

Table 5 — 23XRV Compressor Weights

 

ENGLISH

SI

MOTOR

Total Compressor

Total Compressor

CODE

Weight*

Weight*

 

(lb)

(kg)

P

 

 

Q

 

 

R

 

 

S

4866

2207

T

 

 

U

 

 

V

 

 

*Compressor weight is comprised of compressor, stator, rotor, and end bell.

Table 6 — 23XRV Component Weights — TR Compressor

 

FRAME 3

 

FRAME 4

 

FRAME 5

 

COMPONENT

HEAT EXCHANGER*

HEAT EXCHANGER*

HEAT EXCHANGER*

 

lb

 

kg

lb

 

kg

lb

 

kg

Suction Elbow

179

 

81

237

 

108

232

 

105

Discharge Pipe Assembly

747

 

339

747

 

339

747

 

339

Control Center

1650

 

749

1650

 

749

1650

 

749

Discharge Pipe Adapter Flange

178

 

81

178

 

81

178

 

81

Optional Isolation Valves

70

 

32

70

 

32

115

 

52

Optional Unit Mounted Pumpout Unit

164

 

75

164

 

75

164

 

75

Vaporizer Oil Sump

700

 

318

700

 

318

700

 

318

Economizer

542

 

246

542

 

246

542

 

246

*To determine compressor frame size, refer to Fig. 2.

9

Table 7 — 23XRV Heat Exchanger Data

 

 

 

ENGLISH

 

 

 

 

SI

 

 

 

 

 

Dry Rigging Weight

 

Machine Charge

 

Dry Rigging Weight

 

 

Machine Charge

 

 

 

 

(lb)*

 

 

 

(kg)*

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CODE

 

 

Refrigerant

Liquid Weight

 

 

Refrigerant

 

Liquid

 

Cooler

Condenser

Weight (lb)

 

(lb)

Cooler

Condenser

Weight (kg)

Weight (kg)

 

Only

Only

With

Without

Cooler

Condenser

Only

Only

With

 

Without

Cooler

 

Condenser

 

 

 

Economizer

Economizer

 

 

Economizer

 

Economizer

 

30

4148

3617

800

650

464

464

1877

1676

363

 

295

210

 

210

31

4330

3818

800

650

531

542

1959

1769

363

 

295

241

 

246

32

4522

4023

800

650

601

621

2046

1860

363

 

295

273

 

282

35

4419

4529

910

760

511

513

2000

2089

413

 

345

232

 

233

36

4627

4758

910

760

587

602

2094

2195

413

 

345

266

 

273

37

4845

4992

910

760

667

692

2193

2299

413

 

345

303

 

314

40

5008

4962

900

750

863

915

2675

2746

408

 

340

391

 

415

41

5178

5155

900

750

930

995

2758

2839

408

 

340

422

 

451

42

5326

5347

900

750

990

1074

2832

2932

408

 

340

449

 

487

45

5463

5525

1015

865

938

998

2882

3001

460

 

392

425

 

453

46

5659

5747

1015

865

1014

1088

2976

3108

460

 

392

460

 

494

47

5830

5967

1015

865

1083

1179

3061

3214

460

 

392

491

 

535

50

5827

6013

1250

1100

1101

1225

3182

3304

567

 

499

499

 

556

51

6053

6206

1250

1100

1192

1304

3294

3397

567

 

499

541

 

591

52

6196

6387

1250

1100

1248

1379

3364

3485

567

 

499

566

 

626

55

6370

6708

1430

1280

1201

1339

3429

3620

649

 

581

545

 

607

56

6631

6930

1430

1280

1304

1429

3556

3726

649

 

581

591

 

648

57

6795

7138

1430

1280

1369

1514

3636

3826

649

 

581

621

 

687

*Rigging weights are for standard tubes of standard wall thickness (Turbo-B3 and Spikefin 2, 0.025-in. [0.635 mm] wall).

NOTES:

1.Cooler includes the suction elbow and 1/2 the distribution piping weight.

2.Condenser includes float valve and sump, discharge stub-out, and 1/2 the distribution piping weight.

3.For special tubes refer to the 23XRV Computer Selection Program.

4.All weights for standard 2-pass NIH (nozzle-in-head) design with victaulic grooves.

Table 8A — 23XRV Additional Data for Cooler Marine Waterboxes*

HEAT EXCHANGER

 

ENGLISH

 

 

SI

 

FRAME, PASS

Psig

Rigging Weight

Water Volume

kPa

Rigging Weight

Water Volume

 

 

(lb) (see Note 2)

(gal)

 

(kg) (see Note 2)

(L)

FRAME 3, 1 AND 3 PASS

150

730

84

1034

331

318

FRAME 3, 2 PASS

150

365

42

1034

166

159

FRAME 4, 1 AND 3 PASS

150

1888

109

1034

856

413

FRAME 4, 2 PASS

150

944

54

1034

428

204

FRAME 5, 1 AND 3 PASS

150

2445

122

1034

1109

462

FRAME 5, 2 PASS

150

1223

61

1034

555

231

FRAME 3, 1 AND 3 PASS

300

860

84

2068

390

318

FRAME 3, 2 PASS

300

430

42

2068

195

159

FRAME 4, 1 AND 3 PASS

300

2162

109

2068

981

413

FRAME 4, 2 PASS

300

1552

47

2068

704

178

FRAME 5, 1 AND 3 PASS

300

2655

122

2068

1204

462

FRAME 5, 2 PASS

300

1965

53

2068

891

201

*Add to heat exchanger data for total weights or volumes.

NOTES:

1.Weight adder shown is the same for cooler and condenser of equal frame size.

2.For the total weight of a vessel with a marine waterbox, add these values to the heat exchanger weights (or volume).

10

Table 8B — 23XRV Additional Data for Condenser Marine Waterboxes*

HEAT EXCHANGER

 

ENGLISH

 

 

SI

 

FRAME, PASS

Psig

Rigging Weight

Water Volume

kPa

Rigging Weight

Water Volume

 

 

(lb) (see Note 2)

(gal)

 

(kg) (see Note 2)

(L)

FRAME 3, 1 AND 3 PASS

150

N/A

N/A

1034

N/A

N/A

FRAME 3, 2 PASS

150

365

42

1034

166

159

FRAME 4, 1 AND 3 PASS

150

N/A

N/A

1034

N/A

N/A

FRAME 4, 2 PASS

150

989

54

1034

449

204

FRAME 5, 1 AND 3 PASS

150

N/A

N/A

1034

N/A

N/A

FRAME 5, 2 PASS

150

1195

60

1034

542

227

FRAME 3, 1 AND 3 PASS

300

N/A

N/A

2068

N/A

N/A

FRAME 3, 2 PASS

300

430

42

2068

195

159

FRAME 4, 1 AND 3 PASS

300

N/A

N/A

2068

N/A

N/A

FRAME 4, 2 PASS

300

1641

47

2068

744

178

FRAME 5, 1 AND 3 PASS

300

N/A

N/A

2068

N/A

N/A

FRAME 5, 2 PASS

300

1909

50

2068

866

189

*Add to heat exchanger data for total weights or volumes.

NOTES:

1.Weight adder shown is the same for cooler and condenser of equal frame size.

2.For the total weight of a vessel with a marine waterbox, add these values to the heat exchanger weights (or volume).

Table 9A — 23XRV Waterbox Cover Weights — English (lb)

 

 

 

COOLER

 

 

 

 

CONDENSER

 

 

WATERBOX

Frame 3

Frame 4

Frame 5

Frame 3

Frame 4

Frame 5

DESCRIPTION

Victaulic

Flanged

Victaulic

Flanged

Victaulic

Flanged

Victaulic

Flanged

Victaulic

Flanged

Victaulic

Flanged

 

 

Nozzles

 

Nozzles

 

Nozzles

 

Nozzles

 

Nozzles

 

Nozzles

 

NIH,1 pass Cover 150 PSIG

282

318

148

185

168

229

282

318

148

185

168

229

NIH,2 pass Cover 150 PSIG

287

340

202

256

222

276

287

340

191

245

224

298

NIH,3 pass Cover 150 PSIG

294

310

472

488

617

634

294

310

503

519

628

655

NIH Plain End, 150 PSIG

243

243

138

138

154

154

225

225

138

138

154

154

MWB End Cover, 150 PSIG*

243/315

243/315

138/314

138/314

154/390

154/390

225/234

225/234

138/314

138/314

154/390

154/390

NIH,1 pass Cover 300 PSIG

411

486

633

709

764

840

411

486

633

709

764

840

NIH,2 pass Cover 300 PSIG

411

518

626

733

760

867

411

578

622

729

727

878

NIH,3 pass Cover 300 PSIG

433

468

660

694

795

830

433

468

655

689

785

838

NIH Plain End, 300 PSIG

291

291

522

522

658

658

270

270

522

522

658

658

MWB End Cover, 300 PSIG*

445/619

445/619

522/522

522/522

658/658

658/658

359/474

359/474

522/522

522/522

658/658

658/658

*Rows with two entries list nozzle end and return end weights.

Table 9B — 23XRV Waterbox Cover Weights — SI (kg)

 

 

 

COOLER

 

 

 

 

CONDENSER

 

 

WATERBOX

Frame 3

Frame 4

Frame 5

Frame 3

Frame 4

Frame 5

DESCRIPTION

 

 

 

 

 

 

 

 

 

 

 

 

Victaulic

Flanged

Victaulic

Flanged

Victaulic

Flanged

Victaulic

Flanged

Victaulic

Flanged

Victaulic

Flanged

 

 

Nozzles

 

Nozzles

 

Nozzles

 

Nozzles

 

Nozzles

 

Nozzles

 

NIH,1 pass Cover 150 PSIG

128

144

67

84

76

104

128

144

67

84

76

104

NIH,2 pass Cover 150 PSIG

130

154

92

116

101

125

130

154

87

111

102

135

NIH,3 pass Cover 150 PSIG

133

141

214

221

280

288

133

141

228

235

285

297

NIH Plain End, 150 PSIG

110

110

63

63

70

70

102

102

63

63

70

70

MWB End Cover, 150 PSIG

110/143

110/143

63/142

63/142

70/177

70/177

102/106

102/106

63/142

63/142

70/177

70/177

NIH,1 pass Cover 300 PSIG

186

220

287

322

347

381

186

220

287

322

346

381

NIH,2 pass Cover 300 PSIG

186

235

284

332

344

393

186

235

282

331

330

398

NIH,3 pass Cover 300 PSIG

196

212

299

315

361

376

196

212

297

313

356

380

NIH Plain End, 300 PSIG

132

132

237

237

298

298

122

122

237

237

298

298

MWB End Cover, 300 PSIG

202/281

202/281

237/237

237/237

298/298

298/298

163/215

163/215

237/237

237/237

298/298

298/298

LEGEND

NIH — Nozzle-in-Head

MWB — Marine Waterbox

*Rows with two entries list nozzle end and return end weights.

NOTE: Weight for NIH 2-pass cover, 150 psig (1034 kPa), is included in the heat exchanger weights shown in Table 7.

RIG MACHINE COMPONENTS — Refer to Fig. 10-26 and Carrier Certified Prints for machine component disassembly.

IMPORTANT: Only a qualified service technician should perform this operation.

Do not attempt to disconnect flanges while the machine is under pressure. Failure to relieve pressure can result in personal injury or damage to the unit.

Before rigging the compressor remove control panel and control center.

NOTE: Label each wire before removal when wiring must be disconnected (see Fig. 10 and 11). Clip all wire ties necessary when removing pressure and temperature sensors. Disconnect all pressure transducer wires at the sensor. Temperature sensors cannot be disconnected from their cables; remove temperature sensors from their thermowells and label as required.

11

 

CABLE TRAY CONTAINING

 

VAPORIZER HTR CONDUIT

 

OIL HEATER CONDUIT

 

OIL PUMP CONDUIT

 

OIL SUMP TEMP. CABLE

 

OIL SUMP PRESS. CABLE

 

OIL PRESS. CABLE

OIL RECLAIM ACTUATOR CABLE

 

HGBP CONDUIT (OPTIONAL)

CONDENSER

 

PRESSURE

 

CABLE

 

WATER SENSOR CABLES

 

FOR NOZZLE ARRANGEMENTS

 

A,B,C,E,F,P,Q,R,T,&U

 

(SAME FOR OTHER END

 

OF MACHINE)

 

DISCHARGE END

 

 

CABLE TRAY CONTAINING

DISCH. TEMP. CABLE

ENT/LVG CHILLED LIQUID CABLES

ENT/LVG COND. LIQUID CABLES

DISCH. PRESS. CABLE

COND, PRESS CABLE

DISCH. PRESS. SWITCH

COMP’R DISCH TEMP. CABLE

 

 

EVAP. PRESS. CABLE

COOLER

EVAP. REFRIG. LIQUID TEMP. CABLE

MOTOR TEMP. CABLE

PRESSURE

VFD COOLANT SOLENOID CABLE

CABLE

OIL PRESS. CABLE

DISCH. PRESS. SWITCH CABLE

HGBP CONDUIT (OPTIONAL)

CONTROL

PANEL

MOTOR TEMPERATURE

CABLE

SUCTION END

VFD COOLING

SOLENOID

CABLE

HGBP CONDUIT (OPTIONAL)

EVAP REFRIG. LIQUID

LEGEND

TEMP. CABLE

HGBP

Hot Gas Bypass

HTR

Heater

ENT/LVG — Entering/Leaving

Fig. 10 — Electrical Cable Routing (Top View)

CABLE TRAY CONTAINING

OIL VAPORIZER CONDUIT

OIL HTR CONDUIT

OIL PUMP CONDUIT

OIL RECLAIM ACTUATOR CABLE OIL SUMP PRESS. CABLE OIL DISCH. PRESS. CABLE

OIL SUMP TEMP. CABLE

HGBP CONDUIT (OPTIONAL) COMR’R DISCH. TEMP. CABLE DISCH. PRESS. SWITCH DISCH. PRESS. CABLE

COMP’R DISCHARGE

TEMP. CABLE

DISCH. PRESS. CABLE

DISCH. PRESS. SWITCH

CONDENSER

PRESSURE

CABLE

EVAPORATOR

PRESSURE

CABLE

DISCHARGE END

VFD COOLING

SOLENOID

MOTOR TEMP

CABLE

SUCTION END

 

 

OIL PUMP

 

 

CABLE TRAY CONTAINING

OIL HEATER

 

 

CONDUIT

 

 

VAPORIZER HEATER CONDUIT

CONDUIT

 

LEGEND

 

OIL

OIL SUMP

OIL HTR CONDUIT

EVAPORATOR

 

 

OIL PUMP CONDUIT

REFRIG LIQUID

 

 

TEMPERATURE

 

 

 

PRESSURE

OIL RECLAIM ACTUATOR CABLE

TEMPERATURE

HGBP

Hot Gas Bypass

 

LEAVING

CABLE

OIL SUMP PRESS. CABLE

SENSOR CABLE

OIL RECLAIM

 

HTR

Heater

FILTER

OIL SUMP

OIL PRESS. CABLE

 

ACTUATOR

 

ENT/LVG— Entering/Leaving

CABLE

PRESSURE

OIL SUMP TEMP. CABLE

 

CABLE

 

 

CABLE

HGBP CONDUIT (OPTIONAL)

a23-1559

 

 

 

 

 

 

 

 

 

 

Fig. 11 — Electrical Cable Routing (Back View)

12

Separate Machine Components — The design of the 23XRV allows for disassembly at the job site so that individual components may be moved through existing doorways. Use the following procedures to separate the machine components.

Suggested locations to cut piping will minimize the width of the condenser/economizer assembly.

SEPARATE COOLER AND CONDENSER

IMPORTANT: If the cooler and condenser vessels must be separated, the heat exchangers should be kept level by placing a support plate under the tube sheets. The support plate will also help to keep the vessels level and aligned when the vessels are bolted back together.

NOTE: For steps 1 through 13 refer to Fig. 12. The cooler has been removed from the picture to show the pipes and lines that must be cut.

Check that the holding charge has been removed from the chiller.

1.Place a support plate under each tube sheet to keep each vessel level.

2.Remove cooler relief valve and relief valve vent piping.

3.Cut the motor cooling refrigerant drain line.

4.Rig the suction elbow and disconnect the compressor suction line at the cooler and compressor. Remove bolts from the vaporizer vent line flange.

5.Cut the VFD cooling drain line.

6.Cut the oil reclaim line(s).

7.Cut the hot gas bypass line between the HGBP (hot gas bypass) solenoid valve and the cooler feed line.

8.Unbolt the cooler liquid feed line near the economizer or condenser float chamber at the flanged connection. Temporarily secure the in-line economizer orifice plate (economized chillers only) to the economizer flange (see Fig. 12).

 

17

19

 

 

 

 

18

 

1

 

 

16

 

 

 

 

 

 

 

2

 

 

15

 

 

 

3

 

 

 

 

 

 

14

 

 

 

4

 

 

 

 

 

5

 

5

 

 

 

 

 

 

 

 

 

6

 

 

 

 

 

5

 

13

12

 

 

 

 

 

 

 

 

 

 

11

 

10

7

 

 

 

 

9

 

a23-1560

 

 

 

 

 

 

8

 

1

Suction Elbow (Unbolt)

 

11

VFD Cooling Drain Line

 

2

Vaporizer Vent Line (Unbolt)

 

12

Oil Reclaim Line (Cut)

 

3

Motor Cooling Line (Unbolt)

 

13

Vaporizer Hot Gas Return Line (Cut)

4

Motor Cooling Drain Line (Cut)

14

Discharge Isolation Valve (Optional)

5

Tubesheet Mounting Bracket

 

15

Condenser Relief Valves (Unscrew)

6

Bearing Oil Drain Line

 

16

Discharge Temperature Sensor

7

Support Plate

 

17

Discharge Pipe Assembly Relief Valve (Unscrew)

8

In-Line Economizer Orifice Plate

18

Discharge Pressure Sensor

 

9

Cooler Liquid Feed LIne (Unbolt)

19

Discharge Pressure Switch

 

10

Hot Gas Bypass Line (Cut)

 

 

 

 

Fig. 12 — Cooler/Discharge Pipe Assembly Removal

13

9. Cut the vaporizer refrigerant return line as shown.

10. Disconnect all sensors with cables that cross from the condenser side of the machine to the cooler side including:

a.Evaporator refrigerant liquid temperature sensor. See Fig. 13.

b.Entering and leaving chiller liquid temperature sensors. See Fig. 14.

c.Evaporator pressure sensor.

11.Disconnect the tubesheet mounting brackets from the vessel connectors on the tube cooler tubesheet.

12.Cover all openings.

13.Rig the cooler away from the condenser/compressor.

NOTE: To reassemble, follow steps in reverse order. Connect sensors and cables after major components have been secured to reduce the risk damaging them.

OPTIONAL

HOT GAS

BYPASS LINE

EVAPORATOR

REFRIGERANT

LIQUID

TEMPERATURE

SENSOR

COOLER

REFRIGERANT

PUMPOUT

VALVE

a23-1635

Fig. 13 — Evaporator Refrigerant Liquid Temperature Sensor on Bottom of Cooler

LEAVING CONDENSER

LEAVING CHILLED

LIQUID TEMPERATURE

LIQUID TEMPERATURE

SENSOR

SENSOR

ENTERING CONDENSER

 

ENTERING CHILLED

LIQUID TEMPERATURE

a23-1563

LIQUID TEMPERATURE

SENSOR

SENSOR

 

Fig. 14 — Chiller End View

Do not rig the condenser before the control center and compressor are removed. The condenser/compressor assembly has a high center of gravity and may tip over when lifted at the tubesheet rigging points, which could result in equipment damage and/or serious personal injury.

REMOVE THE CONTROLS/DRIVE ENCLOSURE FROM THE CONDENSER — Confirm that the power supply disconnect is open and all safety procedures are observed before removing the VFD. This procedure minimizes the number of sensors and cables that need to be disconnected.

Do not attempt to remove the VFD without first isolating the refrigerant charge in the condenser. Damage to one of the motor terminals during VFD removal will result in an uncontrolled refrigerant leak.

1.Close the 2 filter drier isolation valves (Fig. 15) and the 2 VFD isolation valves. Isolate the refrigerant charge into the condenser to prevent a refrigerant leak if one of the motor terminals is accidentally damaged during VFD removal or installation. Evacuate the VFD coldplate through the Schrader valve (Fig. 15) on the VFD drain isolation valve.

2.Remove the shipping bracket between the VFD and the compressor if it is still in place. Remove any conduits that bring power to the VFD. See Fig. 16.

VFD

 

REFRIGERANT

 

COOLING

 

SOLENOID

SCHRADER

VALVE

VFD

VALVE

 

REFRIGERANT

 

COOLING

 

ISOLATION

VFD DRAIN

VALVE

ISOLATION

VFD

VALVE

REFRIGERANT

 

STRAINER

 

 

 

MOTOR

FILTER DRIER

FILTER DRIER

FILTER

COOLING

SIGHT

ISOLATION VALVE

ISOLATION VALVE

DRIER

GLASS

 

 

 

 

a23-1564

Fig. 15 — VFD Refrigerant Isolation Valves

14

Carrier HFC-134A User Manual

SHIPPING

BRACKET

a23-1565

Fig. 16 — VFD Shipping Bracket

3.Remove the nuts that secure the terminal box transition piece to the motor housing.

4.Disconnect the motor leads from the motor terminals (Fig. 17). Note the position of the motor terminal cable lugs so they can be reinstalled with sufficient clearance away from surrounding structure.

5.Remove the motor temperature sensor leads (Fig. 17), the motor ground lead, and the bolts that secure the VFD enclosure to the terminal box transition piece.

6.Disconnect the communication cables from the back of the ICVC (Fig. 18).

7.Disconnect the high pressure switch leads from terminal strip TB1, terminals 15 and 16 (Fig. 19).

8.Unplug connectors CN1A, CN1B, CN2, and CN3 (Fig. 19).

9.Disconnect the control panel ground wire (Fig. 19) that is located next to connectors CN1A and CN1B.

10.Disconnect the VFD cooling lines (Fig. 20) and cover all openings.

11.Remove the 12 screws that secure the control panel to the VFD enclosure. Tilt the control panel away from the back of the control center.

12.Position the control panel on top of the condenser and secure it in place to prevent damage.

MOTOR TERMINALS

MOTOR TERMINAL

BOX FRAME

MOTOR

TEMPERATURE

SENSOR TERMINAL

BLOCK

MOTOR

 

TEMPERATURE

a23-1566

CABLE

Fig. 17 — Motor Terminals

a23-1567

Fig. 18 — ICVC Communication Cables

CONNECTOR CN2

a23-1570

 

CONTROL PANEL

CONNECTOR CN1A

GROUND WIRE

CONNECTOR CN1B

HIGH

PRESSURE

SWITCH

CABLE

LOW VOLTAGE FIELD

WIRING TERMINAL STRIP

CONNECTOR CN3

Fig. 19 — Control Panel Connectors

15

OIL HEATER CONDUIT ASY

OIL PUMP CONDUIT ASY

VAPORIZER HEATER CONDUIT ASY

VFD COOLING LINE

O-RING FACE SEAL

COUPLINGS

OIL RECLAIM

ACTUATOR CABLE

VFD COOLING

SOLENOID CABLE

TEMPERATURE SENSOR CABLES

PRESSURE SENSOR a23-1571 CABLES

Fig. 20 — Control Panel Back

Lifting the Control Center — Care should be used to prevent damage due to dropping or jolting when moving the control center. A fork truck or similar means of lifting and transporting may be used. Sling in a manner that will equalize the load at the pickup points. Use a spreader bar if the angle of the sling is less than 45 degrees relative to horizontal. Do not jolt while lifting.

Use the following procedure to lift the control center.

1.Remove the rubber hole plugs in the top of the control center and fully thread in 4 eyebolts or swivel hoist rings

(see Fig. 21). Lifting hardware must have 3/4 in.-10 x 2 in. long threads and must have a working load limit of at least 6000 lb (2722 kg). Typical eyebolts are Chicago Hardware (size 28) or Grainger (P/N 5ZA63).

2.Attach a sling to the four lifting eyebolts. Make certain that the angle of the sling is not less than 45 degrees relative to horizontal.

3.Using an overhead or portable hoist (minimum 2 ton rated capacity), attach a free-fall chain to the sling secured to the drive. Take up any slack in the chain.

4.Rig the control center and remove the bolts that secure it to the VFD mounting brackets on the condenser (see Fig. 21).

5.Confirm that welding procedures comply with local Pressure Vessel Codes before removing a portion of the VFD support bracket from the condenser. Custom brackets should be fabricated if part of the VFD supports must be cut off of the condenser to reduce the width of the condenser assembly. Clamp ¼-in. plates over both sides of the VFD bracket and drill two pairs of holes that

3/4 IN. - 10 x 2 IN. LIFTING EYEBOLT WITH SHOULDER OR SWIVEL HOIST RING 6000 LB (2722 KG) WORKING LOAD LIMIT TYPICAL — CHICAGO HARDWARE P/N 28 GRAINGER P/N 5ZA63

LIFTING

45° MIN

EYEBOLT

 

a23-1561

Fig. 21 — Control Center Lifting Points

straddle the line along which the VFD brackets will be cut. This will allow the VFD brackets to be reinstalled and welded in their original position.

NOTE: To reassemble, follow steps in reverse order. Connect sensors and cables after major components have been secured to reduce the risk damaging them. (See Fig. 22.)

REMOVE THE DISCHARGE PIPE ASSEMBLY FROM THE CONDENSER

NOTE: For steps 1 through 6 refer to Fig. 12.

The condenser relief valve and relief valve vent piping should be removed if they will interfere with discharge pipe assembly rigging.

1.Remove the discharge pipe assembly relief valve and relief valve vent piping.

2.Disconnect the compressor discharge temperature sensor.

3.Disconnect the compressor discharge pressure sensor and remove the high discharge pressure switch sensor.

4.Rig the discharge pipe assembly and remove the bolts from the compressor discharge and condenser inlet flange. Note the position and orientation of the discharge isolation valve on the condenser inlet flange.

5.Remove the discharge pipe assembly.

6.Cover all openings.

NOTE: To reassemble, follow steps in reverse order. Connect sensors and cables after major components have been secured to reduce the risk of damaging them.

16

Loading...
+ 36 hidden pages