Carrier 50HG014-028 User Manual

0 (0)

50HG014-028 Single Package Rooftop Units Electric Cooling with Electric Heat Option

Installation Instructions

CONTENTS

Page

SAFETY CONSIDERATIONS . . . . . . . . . . . . . . . . . . . . . . 1

INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-23

Step 1 — Provide Unit Support . . . . . . . . . . . . . . . . . . . 1

ROOF CURB

ALTERNATE UNIT SUPPORT

Step 2 — Remove Shipping Rails . . . . . . . . . . . . . . . . 3

Step 3 — Rig and Place Unit . . . . . . . . . . . . . . . . . . . . . 3

POSITIONING

ROOF MOUNT

INSTALLATION ONTO CURB

Step 4 — Field Fabricate Ductwork. . . . . . . . . . . . . . . 8 Step 5 — Make Unit Duct Connections . . . . . . . . . . . 8 Step 6 — Trap Condensate Drain . . . . . . . . . . . . . . . . . 9 Step 7 — Make Electrical Connections . . . . . . . . . . . 9

FIELD POWER SUPPLY

FIELD CONTROL WIRING

Step 8 — Install Outdoor-Air Hood . . . . . . . . . . . . . . 20

Step 9 — Position Optional Power Exhaust

or Barometric Relief Damper Hood. . . . . . . . . . . . 22 Step 10 — Non-Fused Disconnect. . . . . . . . . . . . . . . 22 Step 11 — Install All Accessories . . . . . . . . . . . . . . . 23

SAFETY CONSIDERATIONS

Installation and servicing of air-conditioning equipment can be hazardous due to system pressure and electrical components. Only trained and qualified service personnel should install, repair, or service air-conditioning equipment.

Untrained personnel can perform the basic maintenance functions of replacing filters. All other operations should be performed by trained service personnel. When working on air-conditioning equipment, observe precautions in the literature, tags and labels attached to the unit, and other safety precautions that may apply.

Follow all safety codes. Wear safety glasses and work gloves. Use quenching cloth for unbrazing operations. Have fire extinguishers available for all brazing operations.

Before performing service or maintenance operations on unit, turn off main power switch to unit. Electrical shock could cause personal injury.

IMPORTANT: Units have high ambient operating limits. If limits are exceeded, the units will automatically lock the compressor out of operation. Manual reset will be required to restart the compressor.

INSTALLATION

Step 1 — Provide Unit Support

ROOF CURB — Assemble or install accessory roof curb in accordance with instructions shipped with this accessory. See Fig. 1. Install insulation, cant strips, roofing, and counter flashing as shown. Ductwork can be installed to roof curb before unit is set in place. Curb must be level. This is necessary to permit unit drain to function properly. Unit leveling tolerance is

± 1/16 in. per linear ft in any direction. Refer to Accessory Roof Curb Installation Instructions for additional information as required. When accessory roof curb is used, unit may be installed on class A, B, or C roof covering material.

IMPORTANT: The gasketing of the unit to the roof curb is critical for a watertight seal. Install gasket with the roof curb as shown in Fig. 1. Improperly applied gasket can also result in air leaks and poor unit performance.

ALTERNATE UNIT SUPPORT — When a curb cannot be used, install unit on a noncombustible surface. Support unit with sleepers, using unit curb support area. If sleepers cannot be used, support long sides of unit with a minimum of 3 equally spaced 4-in. x 4-in. pads on each side.

Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.

Book

1

4

PC 111

Catalog No. 535-00092

Printed in U.S.A.

Form 50HG-7SI

Pg 1

11-03

Replaces: 50HG-3SI

Tab

1b

6b

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Fig. 1 — Roof Curb Details

2

Step 2 — Remove Shipping Rails — Remove shipping rails prior to lowering unit onto roof curb. See Fig. 2. The rails are attached to the unit at both the return end and condenser end. Remove the screws from both ends of each rail. Be careful not to drop the rails onto any surface that could be damaged. Discard the rails. It is important to replace the screws into the unit to avoid any air or water leakage.

Do not allow the shipping rail to drop on the roof surface. Damage to the roof surface may result.

Step 3 — Rig and Place Unit — Inspect unit for transportation damage. See Table 1 for physical data. File any claim with transportation agency.

All panels must be in place when rigging. Unit is not designed for handling by fork truck. Damage to unit can result.

Do not drop unit; keep upright. Use spreader bars over unit to prevent sling or cable damage. Rollers may be used to move unit across a roof. Level by using unit frame as a reference; leveling tolerance is ± 1/16 in. per linear ft in any direction. See Fig. 3 for additional information. Unit rigging weight is shown in Fig. 3.

Four lifting holes are provided in the unit base rails as shown in Fig. 3. Refer to rigging instructions on unit.

POSITIONING — Maintain clearance, per Fig. 4, around and above unit to provide minimum distance from combustible materials, proper airflow, and service access.

Do not install unit in an indoor location. Do not locate air inlets near exhaust vents or other sources of contaminated air.

Although unit is weatherproof, guard against water from higher level runoff and overhangs.

ROOF MOUNT — Check building codes for weight distribution requirements. Unit operating weight is shown in Table 1.

INSTALLATION ONTO CURB — The 50HG units are designed to fit on either the accessory full perimeter curb or onto existing 48/50TJ,HJ or 48/50DP,DR curbs. In either case, correct placement of the unit onto the curb is critical to operating performance. To aid in correct positioning, 3/8-in. diameter locating holes have been added to the unit base rails. When placing the unit, these holes should line up with the roof curb edge as shown in Fig. 5 and 6, to assure proper duct opening alignment. Select the alignment holes suited for the curb being used. For installation on the HJ/TJ/DP/DR curb use the alignment holes located approximately 20 in. from the end of the base rail on the return end of the unit. For placement on the HG curb, use the alignment holes located approximately 2-in. from the end of the base rail on the return end of the unit. See labels on the side of the unit for more details.

SHIPPING RAILS

Fig. 2 — Shipping Rail Removal

3

Fig. 3 — Rigging Details

4

Carrier 50HG014-028 User Manual

Fig. 4 — Base Unit Dimensions

5

Table 1 — Physical Data

UNIT 50HG

 

 

 

 

 

014

 

 

 

 

 

 

016

 

 

 

 

 

 

020

 

 

VOLTAGE

 

 

208/230

 

575

 

208/230

 

575

 

 

208/230

 

 

575

 

 

 

and 460

 

 

and 460

 

 

 

and 460

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NOMINAL CAPACITY (Tons)

 

 

12.5

 

12.5

 

 

15

 

 

 

15

 

 

 

17.5

 

 

 

17.5

 

OPERATING WEIGHT (lb)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

50 SERIES (Cooling Only)

 

 

2017

 

2017

 

2111

 

2111

 

2139

 

 

2139

 

COMPRESSOR

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Quantity

 

 

 

 

2

 

 

 

2

 

 

 

3

 

 

 

3

 

 

 

3

 

 

 

3

 

Number of Refrigerant Circuits

 

 

 

2

 

 

 

2

 

 

 

3

 

 

 

3

 

 

 

3

 

 

 

3

 

Oil (ounces) Ckt A...Ckt B...Ckt C

 

72...

 

72...

NA

72...

 

72...

NA

68...

68...

68

68...

 

68...

68

 

68...

68...

72

 

68...

68...

72

REFRIGERANT TYPE

 

 

 

 

 

 

 

 

 

 

 

 

R-22

 

 

 

 

 

 

 

 

 

 

 

Expansion Device

 

 

TXV

 

TXV

 

TXV

 

TXV

 

 

TXV

 

 

 

TXV

 

 

 

 

 

 

 

 

 

 

 

 

Operating Charge (lb)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Circuit A

 

 

19.6

 

19.6

 

13.2

 

13.2

 

 

13.1

 

 

 

13.1

 

Circuit B

 

 

18.3

 

18.3

 

12.2

 

12.2

 

 

12.7

 

 

 

12.7

 

Circuit C

 

 

 

NA

 

 

 

NA

 

 

15.4

 

15.4

 

 

15.2

 

 

 

15.2

 

CONDENSER COIL

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Rows...Fins/inch

 

 

2

...17

 

2

...17

 

2...

17

 

2

...17

 

2 17...

 

2 17...

 

Total Face area (sq. ft)

 

 

57.78

 

57.78

 

57.78

 

57.78

 

57.78

 

57.78

 

CONDENSER FAN

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Nominal Cfm (Total, all fans)

 

14,000

14,000

 

14,000

14,000

 

14,000

 

14,000

Quantity...

Diameter (in.)

 

 

4

...22

 

4

...22

 

4...

22

 

4

...22

 

4 22...

 

4 22...

 

Motor Hp...

Rpm

 

1/4...

1100

1/4...

1100

1/4...

1100

1/4...

1100

 

1/4

...1100

 

1/4

...1100

Watts input (Total)

 

 

1400

 

1400

 

1400

 

1400

 

1400

 

 

1400

 

EVAPORATOR COIL

 

 

 

 

 

 

 

 

 

 

 

Face

Split

 

 

 

 

 

 

 

 

 

 

 

Rows Fins/inch

 

 

3

15

 

3

15

 

3

15

 

3

15

 

3 15

 

3 15

 

 

 

 

 

 

 

 

 

Total Face area (sq. ft)

 

 

23.33

 

23.33

 

23.33

 

23.33

 

23.33

 

23.33

 

EVAPORATOR FAN

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Quantity...

Size

 

2...

 

15x11

2...

 

15x11

2...

15x11

2...

 

15x11

 

2...

15x11

 

2...

15x11

Type Drive

 

 

Belt

 

 

Belt

 

 

Belt

 

 

Belt

 

 

 

Belt

 

 

 

Belt

 

Nominal Cfm

 

 

5000

 

5000

 

6000

 

6000

 

7000

 

 

7000

 

Std Motor Hp

 

 

 

3.7

 

 

 

3

 

 

 

3.7

 

 

 

3

 

 

 

5

 

 

 

5

 

Alt Motor Hp

 

 

 

5

 

 

 

5

 

 

 

5

 

 

 

5

 

 

 

71/2

 

 

 

71/2

 

Motor Nominal Rpm

 

 

1725

 

1725

 

1725

 

1725

 

1725

 

 

1725

 

Std Maximum Continuous Bhp

 

 

4.25

 

3.45

 

4.25

 

3.45

 

 

5.75

 

 

 

5.75

 

Std Maximum Continuous Watts

 

 

3171

 

2574

 

3171

 

2574

 

4290

 

 

4290

 

Alt Maximum Continuous Bhp

 

 

5.75

 

5.75

 

5.75

 

5.75

 

 

8.63

 

 

 

8.63

 

Alt Maximum Continuous Watts

 

 

4290

 

4290

 

4290

 

4290

 

6438

 

 

6438

 

Motor Frame Size

Standard

 

56HZ

 

56H

 

56HZ

 

56H

 

S184T

 

184T

 

Motor Frame Size

Alternate

S184T

 

184T

 

S184T

 

184T

 

S213T

 

S213T

Fan Drive Rpm Range

Std motor/Std drive

485-613

472-619

618-789

609-778

 

658-808

 

658-808

 

 

Std motor/Alt drive

618-789

609-778

485-613

472-619

 

794-974

 

794-974

 

 

Alt motor/Std drive

778-1021

778-1021

778-1021

778-1021

 

949-1145

 

949-1145

Motor Bearing Type

Alt motor/Alt drive

1000-1227

1000-1227

1000-1227

1000-1227

 

1126-1328

 

1126-1328

 

 

Ball

 

 

Ball

 

 

Ball

 

 

Ball

 

 

 

Ball

 

 

 

Ball

 

Maximum Allowable Rpm

 

 

1400

 

1400

 

1400

 

1400

 

1400

 

 

1400

 

Motor Pulley Pitch Diameter

Std motor/Std drive

3.7-4.7

3.1-4.1

 

3.4-4.4

3.4-4.4

 

4.3-5.3

 

4.3-5.3

 

 

Std motor/Alt drive

3.4-4.4

3.4-4.4

 

3.7-4.7

3.1-4.1

 

4.3-5.3

 

4.3-5.3

 

 

Alt motor/Std drive

3.1-4.1

3.1-4.1

 

3.1-4.1

3.1-4.1

 

5.4-6.6

 

5.4-6.6

 

 

Alt motor/Alt drive

4.3-5.3

4.3-5.3

 

4.3-5.3

4.3-5.3

 

5.5-6.5

 

5.5-6.5

Motor Shaft Diameter (in.)

Standard

 

 

7/8

 

 

 

7/8

 

 

 

7/8

 

 

 

7 /8

 

 

 

11/8

 

 

 

11/8

 

Motor Shaft Diameter (in.)

Alternate

1

11/8

51

1

11/8

48

 

11/8

45

1

11/8

45

 

1

13/8

46

 

1

13/8

46

Belt, Quantity...Type...Length (in.)

Std motor/Std drive

BX...

BX...

1...

A...

...

A

 

BX...

 

BX...

 

 

Std motor/Alt drive

1...

 

A...

45

1...

 

A...

45

1...

BX...

51

1...

BX...

48

 

1...

BX...

42

 

1...

BX...

42

 

 

Alt motor/Std drive

1...

BX...

38

1...

BX...

38

1...

BX...

38

1...

BX...

38

 

1...

BX...

46

 

1...

BX...

46

Pulley center line distance (in.)

Alt motor/Alt drive

1...

 

B...

38

1...

 

B...

38

1...

B...

38

1...

...

B

38

 

1...

BX...

42

 

1...

BX...

42

 

11.3-12.3

11.3-12.3

11.3-12.3

11.3-12.3

 

10.0-12.2

 

10.0-12.2

Speed change per full turn of moveable

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

pulley flange (rpm)

Std motor/Std drive

 

 

21

 

 

 

25

 

 

 

29

 

 

 

28

 

 

 

25

 

 

 

25

 

 

 

Std motor/Alt drive

 

 

29

 

 

 

28

 

 

 

21

 

 

 

25

 

 

 

30

 

 

 

30

 

 

 

Alt motor/Std drive

 

 

41

 

 

 

41

 

 

 

41

 

 

 

41

 

 

 

33

 

 

 

33

 

Moveable pulley maximum (full turns

Alt motor/Alt drive

 

 

38

 

 

 

38

 

 

 

38

 

 

 

38

 

 

 

34

 

 

 

34

 

 

 

 

6

 

 

 

6

 

 

 

6

 

 

 

6

 

 

 

6

 

 

 

6

 

from closed position)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Factory Pulley Setting

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(turns from closed position)

 

 

 

3

 

 

 

3

 

 

 

3

 

 

 

3

 

 

 

3

 

 

 

3

 

Fan Shaft Diameter (in.)

 

 

13/16

 

13/16

 

13/16

 

13/16

 

 

13/16

 

 

 

13/16

 

Factory Speed Setting (rpm)

 

 

549

 

 

546

 

 

704

 

 

694

 

 

 

733

 

 

 

733

 

HIGH PRESSURE SWITCHES (psig)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Cutout

 

 

 

426

 

 

426

 

 

426

 

 

426

 

 

 

426

 

 

 

426

 

Reset (Auto)

 

 

320

 

 

320

 

 

320

 

 

320

 

 

 

320

 

 

 

320

 

OUTDOOR AIR INLET SCREENS

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Quantity...

Size (in.)

 

3...

 

20x25

3...

 

20x25

3...

20x25

3...

 

20x25

 

3...

20x25

 

3...

20x25

RETURN AIR FILTERS

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Quantity...

Size (in.)

 

9...

 

16x25

9...

 

16x25

9...

16x25

9...

 

16x25

 

9...

16x25

 

9...

16x25

LEGEND

Bhp — Brake Horsepower

TXV — Thermostatic Expansion Valve

6

Table 1 — Physical Data (cont)

UNIT 50HG

 

 

024

 

028

VOLTAGE

 

208/230

 

 

575

 

ALL

 

and 460

 

 

 

 

 

 

 

 

 

 

NOMINAL CAPACITY (Tons)

 

20

 

 

20

 

25

OPERATING WEIGHT (lb)

 

 

 

 

 

 

 

50 SERIES (Cooling Only)

 

2187

 

 

2187

 

2446

COMPRESSOR

 

 

 

 

 

 

 

Quantity

 

3

 

 

3

 

2

Number of Refrigerant Circuits

 

3

 

 

3

 

2

Oil (ounces) Ckt A...Ckt B...Ckt C

 

72...72...72

 

 

72...72...72

 

110...110...NA

REFRIGERANT TYPE

 

 

 

 

R-22

 

 

Expansion Device

 

TXV

 

 

TXV

 

TXV

 

 

 

 

Operating Charge (lb)

 

 

 

 

 

 

 

Circuit A

 

13.8

 

 

13.8

 

23.9

Circuit B

 

13.9

 

 

13.9

 

21.5

Circuit C

 

15.5

 

 

15.5

 

NA

CONDENSER COIL

 

 

 

 

 

 

 

Rows...Fins/inch

 

2...17

 

 

2...17

 

2...17

Total Face Area (sq. ft)

 

57.78

 

 

57.78

 

66.67

CONDENSER FAN

 

 

 

 

 

 

 

Nominal Cfm (Total, all fans)

 

14,000

 

 

14,000

 

21,000

Quantity...Diameter (in.)

 

4...22

 

 

4...22

 

6...22

Motor Hp...Rpm

 

1/4...1100

 

 

1/4...1100

 

1/4...1100

Watts input (Total)

 

1400

 

 

1400

 

2100

EVAPORATOR COIL

 

 

 

 

Face Split

 

 

Rows...Fins/inch

 

4...15

 

 

4...15

 

4...15

 

 

 

Total Face Area (sq. ft)

 

23.33

 

 

23.33

 

27.22

EVAPORATOR FAN

 

 

 

 

 

 

 

Quantity...Size

 

2...15x11

 

 

2...15x11

 

2...15x11

Type Drive

 

Belt

 

 

Belt

 

Belt

Nominal Cfm

 

8000

 

 

8000

 

10,000

Std Motor Hp

 

5

 

 

5

 

71/2

Alt Motor Hp

 

71/2

 

 

71/2

 

10

Motor Nominal Rpm

 

1725

 

 

1725

 

1725

Std Maximum Continuous Bhp

 

5.75

 

 

5.75

 

8.63

Std Maximum Continuous Watts

 

4290

 

 

4290

 

6438

Alt Maximum Continuous Bhp

 

8.63

 

 

8.63

 

11.50

Alt Maximum Continuous Watts

 

6438

 

 

6438

 

8579

Motor Frame Size

Standard

S184T

 

 

184T

 

S213T

Motor Frame Size

Alternate

S213T

 

 

S213T

 

S215T

Fan Drive Rpm Range

Std motor/Std drive

658-808

 

 

658-808

 

799-965

 

Std motor/Alt drive

794-974

 

 

794-974

 

939-1152

 

Alt motor/Std drive

949-1145

 

 

949-1145

 

945-1187

Motor Bearing Type

Alt motor/Alt drive

1126-1328

 

 

1126-1328

 

1152-1366

 

Ball

 

 

Ball

 

Ball

Maximum Allowable Rpm

 

1400

 

 

1400

 

1400

Motor Pulley Pitch Diameter

Std motor/Std drive

4.3-5.3

 

 

4.3-5.3

 

5.4-6.6

 

Std motor/Alt drive

4.3-5.3

 

 

4.3-5.3

 

4.2-5.2

 

Alt motor/Std drive

5.4-6.6

 

 

5.4-6.6

 

4.2-5.2

 

Alt motor/Alt drive

5.5-6.5

 

 

5.5-6.5

 

5.2-6.2

Motor Shaft Diameter (in.)

Standard

11/8

 

 

11/8

 

13/8

Motor Shaft Diameter (in.)

Alternate

13/8

 

 

13/8

 

13/8

Belt, Quantity...Type...Length (in.)

Std motor/Std drive

1...BX...46

 

 

1...BX...46

 

1...BX...50

 

Std motor/Alt drive

1...BX...42

 

 

1...BX...42

 

2...AX...38

 

Alt motor/Std drive

1...BX...46

 

 

1...BX...46

 

2...BX...38

Pulley center line distance (in.)

Alt motor/Alt drive

1...BX...42

 

 

1...BX...42

 

2...BX...38

 

10.0-12.2

 

 

10.0-12.2

 

9.6-12.0

Speed change per full turn of moveable

 

 

 

 

 

 

 

pulley flange (rpm)

Std motor/Std drive

25

 

 

25

 

28

 

Std motor/Alt drive

30

 

 

30

 

36

 

Alt motor/Std drive

33

 

 

33

 

40

Moveable pulley maximum (full turns

Alt motor/Alt drive

34

 

 

34

 

36

 

6

 

 

6

 

6

from closed position)

 

 

 

 

 

 

 

Factory Pulley Setting

 

 

 

 

 

 

 

(turns from closed position)

 

3

 

 

3

 

3

Fan Shaft Diameter (in.)

 

13/16

 

 

13/16

 

13/16

Factory Speed Setting (rpm)

 

733

 

 

733

 

882

HIGH PRESSURE SWITCHES (psig)

 

 

 

 

 

 

 

Cutout

 

426

 

 

426

 

426

Reset (Auto)

 

320

 

 

320

 

320

OUTDOOR AIR INLET SCREENS

 

 

 

 

 

 

 

Quantity...Size (in.)

 

3...20x25

 

 

3...20x25

 

3...20x25

RETURN AIR FILTERS

 

 

 

 

 

 

 

Quantity...Size (in.)

 

9...16x25

 

 

9...16x25

 

9...20x25

LEGEND

Bhp — Brake Horsepower

TXV — Thermostatic Expansion Valve

7

ALIGNMENT

HOLE

(IN BASE RAIL)

ALIGNMENT

HOLE SHOULD

LINE UP WITH

ROOF CURB

EDGE FLANGE

EDGE FLANGE

Fig. 5 — Alignment Hole Details

ALIGNMENT

HOLES FOR

HJ, TJ, DP, DR

CURB-BOTH

SIDES

 

RETURN

SUPPLY

 

OPENING

OPENING

 

CURB

CURB

 

RETURN

SUPPLY

ALIGNMENT

OPENING

OPENING

 

 

HOLES FOR HG

 

 

CURB-BOTH

 

 

SIDES

ROOF CURB

Fig. 6 — Alignment Hole Location

Step 4 — Field Fabricate Ductwork — Secure all ducts to building structure. Use flexible duct connectors between unit and ducts as required. Insulate and weatherproof all external ductwork, joints, and roof openings with counter flashing and mastic in accordance with applicable codes.

Ducts passing through an unconditioned space must be insulated and covered with a vapor barrier.

Step 5 — Make Unit Duct Connections

VERTICAL CONFIGURATION — Unit is shipped for thru- the-bottom duct connections. Ductwork openings are shown in Fig. 1 and 4. Duct connections for vertical supply and return configuration are shown in Fig. 7. Field fabricated concentric ductwork may be connected as shown in Fig. 8 and 9. The unit is designed to attach the ductwork to the roof curb. Do not attach duct directly to the unit basepans.

Unit basepans must be supported under the unit and around duct openings in order to prevent air leakage.

For vertical supply and return units, tools or parts could drop into ductwork and cause an injury. Install a 90-degree turn in the return ductwork between the unit and the conditioned space. If a 90-degree elbow cannot be installed, then a grille of sufficient strength and density should be installed to prevent objects from falling into the conditioned space.

Units with electric heat require a 1-in. clearance for the first 24 in. of ductwork. Outlet grilles must not lie directly below unit discharge.

NOTE: A 90-degree elbow must be provided in the supply ductwork to comply with UL (Underwriters’ Laboratories) codes for use with electric heat.

HORIZONTAL APPLICATIONS — Horizontal units are shipped with outer panels that allow for side by side horizontal duct connections. If specified during ordering, the unit will be shipped with the vertical duct openings blocked off from the factory, ready for side supply installation. If the horizontal option was not specified at time of ordering the unit, a fieldinstalled accessory kit is required to convert the vertical unit into a horizontal supply configuration.

Installation of the duct block-off covers should be completed prior to placing the unit unless sufficient side clearance is available. A minimum of 66-in. is required between the unit and any obstruction to install the duct block-off covers. Side supply duct dimensions and locations are shown on Fig. 4. Connect ductwork to horizontal duct flange connections on side of unit.

ECONOMIZER

 

SEE

SEE

 

NOTE

 

NOTE

 

 

AIR

 

AIR

IN

 

OUT

NOTE: Do not drill in this area; damage to basepan may result in water leak.

Fig. 7 — Air Distribution —

Vertical Supply and Return

ECONOMIZER

SEE

 

SEE

NOTE

 

NOTE

AIR OUT

AIR IN

AIR OUT

NOTE: Do not drill in this area; damage to basepan may result in water leak.

Fig. 8 — Air Distribution — Concentric Duct

8

Loading...
+ 16 hidden pages