Carrier 48TJ016-028 User Manual

0 (0)
Carrier 48TJ016-028 User Manual

48TJ016-028

Single-Package Rooftop Units Electric Cooling/Gas Heating

Installation, Start-Up and

Service Instructions

 

CONTENTS

 

 

 

Page

SAFETY CONSIDERATIONS............................................

I

INSTALLATION.............................................................

2-31

Step 1 — Provide Unit Support............................................

2

ROOF CURB

 

ALTERNATE UNIT SUPPORT

 

Step 2 —- Rig and Place Unit...............................................

2

POSITIONING

 

ROOF MOUNT

 

Step 3 — Field Fabricate Ductwork.....................................

9

Step 4 — Make Unit Duct Connections...............................

9

Step 5 — Install Flue Hood and Wind Baffle.....................

9

Step 6 — Trap Condensate Drain........................................

9

Step 7 — Orifice Change....................................................

10

Step 8 — Install Gas Piping................................................

11

Step 9 — Make Electrical Connections.............................

11

FIELD POWER SUPPLY

 

FIELD CONTROL WIRING

 

• OPTIONAL NON-FUSED DISCONNECT

 

OPTIONAL CONVENIENCE OUTLET

 

 

Step 10 — Make Outdoor-Air Inlet Adjustments,. 14

Step 11 — Install Outdoor-Air Hood................................

14

Step 12 — Install All Accessories.......................................

15

 

MOTORMASTER® I CONTROL INSTALLATION

 

MOTORMASTER V CONTROL INSTALLATION

Step 13 — Adjust Factory-Installed Options....................

17

 

PREMIERLINKTM CONTROL

 

 

ENTHALPY SWITCH/RECEIVER

 

 

OUTDOOR ENTHALPY CONTROL

 

 

DIFFERENTIAL ENTHALPY CONTROL

 

 

ENTHALPY SENSORS AND CONTROL

 

 

OPTIONAL ECONOMISERIV AND

 

 

ECONOMI$ER2

 

 

ECONOMI$ERIV STANDARD SENSORS

 

 

ECONOMI$ERIV CONTROL MODES

 

Step 14 — Install Humidlstat for

 

 

Optional MoistureMISer’'“ Package............................

29

START-UP......................................................................

31-38

SERVICE........................................................................

39-47

TROUBLESHOOTING................................................

48 52

INDEX...................................................................................

53

START-UP CHECKLIST..............................................

CL 1

SAFETY CONSIDERATIONS

Installation and seiTicing of air-conditioning equipment can be hazardous due to system pressure and electrictil compo­ nents, Only triiined and qualified service personnel should in­ stall, repair, or service air-conditioning equipment.

Untrained personnel can perform basic maintenance func­ tions of cleaning coils and filters and replacing filters. All other operations should be performed by trained service personnel. When working on air-conditioning equipment, observe

precautions in the literature, tags and labels attached to the unit, and other safety precautions that may apply.

Follow all siifety codes. Wear safety glasses and work gloves. Use quenching cloth for unbrazing operations. Have fire extinguishers available for till brazing operations.

A WARNING

Before performing service or maintenance operations on unit, turn off main power switch to unit. Electrical shock could cause personal injuiy.

AWARNING

1.Improper instiillation, adjustment, alteration, service, or maintenance can cause properfy ckimage, personal injuiy, or loss of life. Refer to the User's Information Manual provided with this unit for more details.

2, Do not store or use gasoline or other flammable vapors and liquids in the vicinity of tliis or any otlier appliance.

What to do if you smell gas:

1.DO NOT tiy to light any appliance.

2.DO NOT touch any electrical switch, or use any phone in your building,

3.IMMEDIATELY call your gas supplier from a neigh­ bor’s phone. Follow the gas supplier’s instmctions.

4.If you cannot reach your gas supplier, cttll the fire deparfment.

A WARNING

Disconnect gas piping from unit when pressure testing at pressure greater than 0.5 psig. Pressures greater than 0.5 psig will cause gas valve damage resulting in haziu'dous condition. If gas valve is subjected to pressure greater than 0.5 psig, it must be replaced before use. When pressure testing field-supplied gas piping at pressures of 0.5 psig or less, a unit connected to such piping must be isolated by closing the manual gas valve(s).

IMPORTANT: Units have high ambient operating lim­ its. If limits are exceeded, the units will automatically lock the compressor out of operation. Manuiil reset will be required to restiuf the compressor.

Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.

Book 1 |4

Catalog No. 04-53480009-01

Printed in U.S.A.

Form 48TJ-22SI

Pg 1

3-06

Replaces: 48TJ-21SI

Tab lajca

INSTALLATION

Inspect unit for transportation danage. If cktmage is found, file claim with transportation agency.

Step 1 — Provide Unit Support

ROOF CURB — Assemble and install accessoiy roof curb or horizontiil adapter roof cuifi in accordance witli instinctions shipped with this accessoiy. See Fig. 1 and 2. Install insulation, cant strips, roofing, and counter flashing as shown. Ductwork can be installed to roof curb or horizontal adapter roof curb be­ fore unit is set in place. Curb or adapter roof curb should be level. Tills is necessaiy to permit unit drain to function proper­ ly. Unit leveling tolerance is ± Vu, in. per linear ft in any direc­ tion. Refer to Accessoiy Roof Curb or Horizontal Adapter Roof Curb Installation Instmctions for additional information as required. When accessoiy roof curb or horizontal adapter roof curb is used, unit may be installed on class A, B, or C roof covering material.

IMPORTANT: The gasketing of the unit to the roof curb or adapter roof curb is critical for a watertight setil. InstiJI gasket with the roof curb or adapter as shown in Fig. 2. Improperly applied gasket can also result in air leaks and poor unit performance.

ALTERNATE UNIT SUPPORT ^ When the curb or adapter cannot be used, install unit on a noncombustible surface. Sup­ port unit with sleepers, using unit curb support area. If sleepers cannot be used, support long sides of unit with a minimum of 3 equally spaced 4-in. x 4-in. pads on each side.

Step 2 — Rig and Place Unit — Do not di'op unit; keep upright. Use spreader biu's over unit to prevent sling or cable diimage. Rollers may be used to move unit across a roof. Level by using unit frame as a reference; leveling tolerance is ±V](i in. per linear ft in any direction. See Fig. 3 for additional information. Unit operating weight is shown in Table 1.

Four lifting holes are provided in ends of unit base rails as shown in Fig. 3. Refer to rigging instmctions on unit.

POSITIONING — Maintain clearance, per Fig. 4 and 5, around and above unit to provide minimum distance from combustible materials, proper airflow, and service access.

Do not install unit in an indoor location. Do not locate unit air inlets near exhaust vents or other sources of contaminated air. For proper unit operation, adequate combustion and venti­ lation ail' must be provided in accordance with Section 5.3 (Air for Combustion and Ventilation) of the National Fuel Gas Code, ANSI Z223.1 (American National Standards Institute).

Although unit is weatlierproof, guard against water from higher level mnoff and overhangs.

Locate mechanical di'aft system flue assembly at least 4 ft from any opening through which combustion products could enter the building, and at least 4 ft from any adjacent building. When unit is located adjacent to public walkways, flue assem­ bly must be at least 7 ft above grade.

ROOF MOUNT — Check building codes for weight distri­ bution requirements. Unit operating weight is shown in Table 1.

Instructions continued cm page 9.

NOTE: CRRFCURB013A00 is a fuliy

factory prsassembied

hori­

zontal adapter and includes an insulated

transition duct. The

pres­

sure drop through the adapter curb is negligible.

 

 

For horizontal return applications; The power exhaust and baro­ metric relief dampers must be installed in the return air duct.

ACCESSORY

CURB

DESCRIPTION

PACKAGE NO.

HEIGHT

 

CRRFCURB013AOO

 

Pre-Assembled, Roof Curb,

(584)

Horizontal Adapter

 

Fig. 1 — Horizontal Supply/Return Adapter Installation

PKG. NO. REF.

CURB

DESCRIPTION

HEIGHT

 

 

CRRFCURB010A00

2" (305)

Standard Curb 14" High

CRRFCURB011A00

2'- 0"(610)

Standard Curb for Units Requiring High Installation

CRRFCURB012A00

2'- 0"(610)

Side Supply and Return Curb for High Installation

NOM. 5/4 K A (323 X (1023 TYP. 4 PLC5

<CRRFCURB012AOO ONLY)

CRRFCURB012A00'0NLY) 0

NOTES:

K ROOF CURB ACCESSORY 15 SHIPPED D15AS5EHBLED.

2.INSULATED PANELS: 1* THICK NEOPRENE COATED 1-1/2 LB DENSITY

3.DIMENSIONS IN C ) ARE IN MILLIMETERS.

4.c=i> DIRECTION OF AIR FLOW

5.ROOFCURB: 16 GA. CVA03-56) STL.

S. A 30 DEGREE ELBOW MUST BE INSTALLED ON THE SUPPLY DUCT WORK BELOW THE UNIT DISCHARGE FOR UNITS EQUIPPED WITH ELECTRIC HEATERS.

NOTE;

TO PREVENT THE HAZARD OF STAGNANT WATER

BUllD-UP IN THE DRAIN PAN OF THE INDOOP SECTION, UNIT CAN ONLY BE PITCHED AS SHOWN.

.... .

CONDENSER

 

AND

 

COMPRESSOR

A-

END

DIMENSIONS (degrees ond inches)

UNIT

 

A

 

B

 

 

 

 

 

 

 

DEG.

 

IN.

DEG.

 

IN.

 

 

 

 

 

 

 

ALL

.26

 

.45

.28

 

.43

 

 

 

 

 

 

 

UNIT LEVELING TOLERANCES

- nom edge oF unit to horizcntoL .

COUNTER FLASHING;

(FIELD SUPPLIED)

•ROOFING FELT (FIELD SUPPLIED)

■CANT STRIP (FIELD SUPPLIED)

ROOFING MATERIAL (FIELD SUPPLIED)

Fig. 2 — Roof Curb Details

NOTES;

1.Dimensions in ( ) are in millimeters.

2.Refer to Fig. 4 and 5 for unit operating weights.

3.Remove boards at ends of unit and runners prior to rigging.

4.Rig by inserting hooks into unit base rails as shown. Use corner post from packaging to protect coil from damage. Use bumper boards for spreader bars on all units.

5.Weights do not include optional economizer. Add 90 lb (41 kg) for economizer weight.

6.Weights given are for aluminum evaporator and condenser coil plate fins.

A CAUTION

All panels must be in place when rigging.

UNIT

MAXIMUM

 

 

 

DIMENSIONS

 

 

SHIPPING WEIGHT

 

A

 

B

48TJ

 

 

lb

 

kg

Ft-in.

 

mm

Ft-in.

 

mm

 

 

 

 

016

1775

 

805

6-11V2

 

2121

3-5

 

1041

020

1875

 

850

6-11 Vg

 

2121

3-3

 

991

024

1985

 

900

6-11 Vg

 

2121

3-2

 

965

028

2135

 

968

6-11 Vg

 

2121

3-2

 

965

Fig. 3 — Rigging Detaiis

HP m PLCS

0 ' ■ 3 T3S“^ Í

1993 I

 

STD UNIT

ECONOMIZER

CORNER

CORNER

CORNER

CORNER

DIMA

DIM B

DIM C

UNIT

WEIGHT

WEIGHT

 

A

 

B

 

C

 

D

 

 

 

 

 

 

 

 

 

 

 

lb

kg

lb

kg

lb

 

kg

lb

 

kg

lb

 

kg

lb

 

kg

ft-in.

mm

ft-in.

mm

ft-in.

mm

48TJD,

1650

748

90

41

423

 

192

386

 

175

403

 

183

438

 

199

3-5

1041

3-5

1041

1-10

559

TJF016

 

 

 

 

48TJD,

1800

816

90

41

432

 

196

410

 

186

461

 

209

472

 

214

3-3

991

3-7

1092

1-8

508

TJF020

 

 

 

 

NOTES:

1.Refer to print for roof curb accessory dimensions.

2.Dimensions in ( ) are in miiiimeters.

Center of Gravity,

o Direction of airflow.

5.Ductwork to be attached to accessory roof curb only.

6.Minimum clearance:

Rear: 7'-0" (2134) for coil removal. This dimension can be reduced to 4'-0" (1219) if conditions permit coil removal from the top.

4'-0" (1219) to combustible surfaces, all four sides (includes between units).

Left side; 4'-0" (1219) for proper condenser coil airflow.

Front: 4'-0" (1219) for control box access.

Right side: 4'-0" (1219) for proper operation of damper and power exhaust if so equipped.

Top: 6'-0" (1829) to assure proper condenser fan operation.

Bottom: 14" (356) to combustible surfaces (when not using curb).

Control box side; 3'-0" (914) to ungrounded surfaces, non-combustible.

Control box side: 3'-6" (1067) to block or concrete walls, or other grounded surfaces.

Local codes or jurisdiction may prevail.

7.With the exception of clearance for the condenser coil and the damper/

power exhaust as stated in Note #6, a removable fence or barricade requires no clearance.

8.Dimensions are from outside of corner post. Allow O'-s/ie" (8) on each side for top cover drip edge.

SECTION A-A

Fig. 4— Base Unit Dimensions; 48TJ016,020

 

 

STD UNIT

ECONOMIZER

CORNER

CORNER

CORNER

CORNER

DIMA

DIM B

DIMC

 

UNIT

WEIGHT

WEIGHT

 

A

 

B

C

 

 

D

 

 

 

 

 

 

 

 

 

 

 

 

 

lb

kg

lb

kg

lb

 

kg

lb

 

kg

lb

 

kg

lb

 

kg

ft-in.

mm

ft-in.

mm

tt-in.

mm

 

48TJD,

1850

839

90

41

443

 

201

406

 

184

476

 

216

525

 

238

3-2

965

3-5

1041

1-8

508

 

TJF024

 

 

 

 

 

48TJD,

2000

907

90

41

471

 

214

428

 

194

526

 

239

574

 

260

3-2

965

3-5

1041

1-8

508

1 3/8* 8iA. 08AIM HOLE

TJF028

 

 

 

 

TTP (41 PLCS^

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0 ' - 3 ? / 8 '

 

 

 

 

 

 

 

NOTES:

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1. Refer to print for roof curb accessory dimensions.

 

 

 

 

 

 

 

 

 

 

 

 

2, Dimensions in ( ) are in millimeters.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3^ Center of Gravity.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Direction of airflow.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

5. Ductwork to be attached to accessory roof curb only.

 

 

 

 

 

 

 

 

 

 

 

6. Minimum clearance:

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

• Rear: 7'-0" (2134) for coil removal. This dimension can be reduced to

 

 

 

 

 

 

 

 

 

 

4'-0" (1219) if conditions permit coil removal from the top.

 

 

 

 

 

 

 

 

 

 

4'-0" (1219) to combustible surfaces, all four sides (includes between

 

 

 

 

 

 

 

 

 

 

units).

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

' Left side: 4'-0" (1219) for proper condenser coil airflow.

 

 

 

 

 

 

 

 

 

 

 

' Front: 4'-0" (1219) for control box access.

 

 

 

 

 

 

 

 

 

 

 

 

 

Right side: 4'-0" (1219) for proper operation of damper and power

 

 

 

 

 

 

 

 

 

 

exhaust if so equipped.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Top: 6'-0" (1829) to assure proper condenser fan operation.

 

 

 

 

 

 

 

 

 

 

' Bottom: 14" (356) to combustible surfaces (when not using curb).

 

 

 

 

 

 

 

 

 

' Control box side: 3'-0" (914) to ungrounded surfaces, non-combustible.

 

 

 

 

 

 

 

 

 

Control box side: 3'-6" (1067) to block or concrete walls, or other

 

 

 

 

 

 

 

 

 

 

grounded surfaces.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Local codes or jurisdiction may prevail.

 

 

 

 

 

 

 

 

 

 

 

 

 

7. With the exception of clearance for the condenser coil and the damper/

 

 

 

 

 

 

 

 

power

 

exhaust as

stated in

 

Note

#6, a

removable

fence

or barricade

requires no clearance.

8. Dimensions are from outside of corner post. Allow O'-^/ie" (8) on each side for top cover drip edge.

SECTfON A-A

Fig. 5 — Base Unit Dimensions; 48TJ024,028

Table 1 — Physical Data

 

 

 

UNIT 48TJ

 

 

016D/F

 

020D/F

 

 

024D/F

 

 

 

028D/F

 

 

 

 

208/230, 460 V 1 575 V

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NOMINAL CAPACITY (tons)

 

15

 

 

18

 

 

20

 

 

25

 

 

OPERATING WEIGHT (lb)

 

1650

 

1B00

 

 

1850

 

 

2000

 

 

 

Economizer

 

90

 

 

90

 

 

90

 

 

90

 

 

 

Roof Curb

 

200

 

 

200

 

 

200

 

 

200

 

 

COMPRESSOR

 

 

 

 

 

1...SM120,

Scr

3ll

1.. .5M120,

 

 

 

1...5M161,

 

 

Quantity...Model (Ckt 1, Ckt 2)

 

 

 

 

 

 

 

 

 

 

 

 

 

2...SR’'942AE

1...SRV82AE

 

 

1...5M110

 

 

 

1...5M120

 

 

Number of Refrigerant Circuits

 

 

 

 

 

 

 

 

 

2

 

 

2

 

 

2

 

 

2

 

 

 

Oi!(oz)(Ckt1,Ckt 2)

 

90, 90

 

110, 72

 

 

110,110

 

 

112, 110

 

 

 

Stages of Capacity Controi (%)

 

50/50

 

60/40

 

 

52/48

 

 

56/44

 

 

REFRiGERANTTYPE

 

 

 

 

 

 

R-22

 

 

 

 

 

 

 

 

Expansion Device

 

 

 

 

 

 

TXV

 

 

 

 

 

 

 

 

Operating Charge (Ib-oz)

 

10-13 1 15-2 1 16-3 1 21-0

 

 

 

 

 

 

 

 

 

 

Circuit 1*

 

 

 

 

 

 

 

 

 

 

 

Circuit 2

 

10-5 1 11-5 1 14-8 1 15-4

 

 

 

 

 

 

 

 

 

CONDENSER COIL

 

 

 

 

Cross-Hatched %-in. Copper Tubes, Aluminum Lanced,

 

 

 

 

 

 

 

 

 

 

 

Aluminum Pre-Coated, or Copper Plate Fins

 

 

 

 

 

Rows...Fins/in.

 

 

2.,.17 1 3...15 1 3...15 I 4.,,15

 

 

 

 

 

 

 

 

 

 

Total Face Area (sq ft)

 

21.7 1 21.7 1 21.7 1 21.7

 

 

 

 

 

 

 

 

 

CONDENSER FAN

 

 

 

 

 

Propelle

r Type

 

 

 

 

 

 

 

 

Nominal Cfm

 

10,400

 

9300

 

 

13,700

 

 

12,500

 

 

 

Quantity...Diameter (in.)

 

3.. .22

 

3...22

 

 

2,,.30

 

 

2...30

 

 

 

Motor Hp...Rpm

 

f/2..,1050

'/г...1050

 

 

1..,1075

 

 

1.,.1075

 

 

 

Watts Input (Total)

 

1100

 

1100

 

 

3400

 

 

3400

 

 

EVAPORATOR COIL

 

 

 

 

 

Cross-Hatched ^/a-in. Copper Tubes, Aluminum Lanced or

 

 

 

 

 

Rows...Fins/in.

 

 

 

 

 

 

Copper Plate Fins, Face Split

 

 

 

 

 

 

 

 

 

 

2...17

 

 

I 3...15 I

 

 

3...15

I

 

4...15

 

 

 

Total Face Area (sq ft)

 

 

 

17.5

 

 

17.5

 

 

17.5

 

 

 

17.5

 

 

EVAPORATOR FAM

 

 

 

 

 

Centrifugal Type

 

 

 

 

 

 

 

 

Quantity...Size (in.)

 

2...10 X 10

 

2...10 X 10

2...12X 12

 

 

2...12 X 12

 

 

 

2...12X 12

 

 

Type Drive

 

Belt

 

Belt

Belt

 

 

Belt

 

 

 

Belt

 

 

Nominal Cfm

 

6000

 

 

6000

7200

 

 

8000

 

 

10,000

 

 

 

Motor Hp

 

3.7

 

 

3.0

5

 

 

7.5

 

 

10

 

 

 

Motor Nominal Rpm

 

1725

 

 

1725

1745

 

 

1745

 

 

1740

 

 

 

Maximum Continuous Bhp

 

4.25

 

 

3.45

5.90

 

8.7 [208/230, 575 v]

 

10.2 [208/230, 575 v[

 

 

 

 

 

 

 

9.5 [460 v[

 

 

 

11.8 [460 v]

 

 

Motor Frame Size

 

 

 

 

 

 

 

 

 

 

 

 

 

 

56H

 

56H

184T

 

 

213T

 

 

 

215T

 

 

Nominal Rpm High/Low

 

 

 

 

 

 

 

 

 

Fan r/s Range

Low-Medium Static

891-1179

 

1159-1429

910-1095

 

 

1002-1225

 

 

1066-1283

 

 

 

Motor Bearing Type

High Static

1227-1550

 

1069-1287

 

 

1193-1458

 

 

1332-1550

 

 

 

 

Ball

 

Ball

Ball

 

 

Ball

 

 

 

Ball

 

 

Maximum Allowable Rpm

 

1550

 

 

1550

1550

 

 

1550

 

 

1550

 

 

 

Motor Pulley Pitch Diameter

Low-Medium Static

3.1/4.1

 

 

4.3/5,3

4.9/5.9

 

 

5.4/6.6

 

 

4,9/5.9

 

 

 

Min/Max (in.)

High Static

3.7/4.7

 

 

_

4.9/5.9

 

 

5.4/6.6

 

 

4,9/5.9

 

 

 

Nomina! Motor Shaft Diameter (in.)

Low-Medium Static

%

 

 

VH

1'/8

 

 

1%

 

 

13/8

 

 

 

Fan Pulley Pitch Diameter (in.)

6.0

 

 

6.4

9.4

 

 

9.4

 

 

8.0

 

 

 

Nominal Fan Shaft Diameter (in.)

High Static

5.2

 

 

8.0

 

 

7.9

 

 

6.4

 

 

 

Low-Medium Static

1"/,6

 

 

13/16

1"/16

 

 

1"/i6

 

 

 

1Vi6

 

 

Belt, Quantity..,Type...Length (in.)

1...BX...42

 

1...BX...45

1...BX...50

 

 

1...BX...54

 

 

 

2...BX...50

 

 

Pulley Center Line Distance (in.)

High Static

1...BX...42

 

1...BX...48

 

 

1..,BX,..50

 

 

 

2..,BX,..47

 

 

 

13.5-15,5

 

13.5-15,5

13.3-14.8

 

 

14.6-15.4

 

 

14,6-15.4

 

 

 

Speed Change per Full Turn of

Low-Medium Static

48

 

 

44

37

 

 

37

 

 

36

 

 

 

Movable Pulley Flange (rpm)

High Static

55

 

 

34

 

 

44

 

 

45

 

 

 

Movable Pulley Maximum Full Turns

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

From Closed Position

 

5

 

 

5

5

 

 

5

 

 

5

 

 

 

Factory Speed

 

3.5

 

 

3,5

3.5

 

 

3.5

 

 

3.5

 

 

 

Factory Speed Setting (rpm)

Low-Medium Static

1035

 

 

1296

1002

 

 

1120

 

 

1182

 

 

 

Fan Shaft Diameter at Pulley (in.)

High Static

1389

 

 

1178

 

 

1328

 

 

1470

 

 

 

 

1"/i6

 

13/16

1^16

 

 

1 Vi 6

 

 

 

1 Vi6

 

 

 

LEGEND

 

 

 

 

"'"'The 48TJ028 units requires 2-in. industrial-grade filters capable of handling

 

Bhp ™ Brake Horsepower

 

 

 

 

face velocities of up to 625 ft/min

{such as

American

Air Filter no. 5700 or

TXV — Thermostatic Expansion Valve

equivalent).

 

NOTE: The 48TJ016-028 units have a low-pressure switch (standard) located Xircuit 1 uses the lower portion of condenser coil and lower portion of evap­ on the suction side.

orator coils; and Circuit 2 uses the upper portion of both coils. fRollout switch is manual reset.

Table 1 — Physical Data (cent)

UNIT 48TJ

 

016D/F

020D/F

024D/F

028D/F

FURNACE SECTION

 

 

 

 

 

Rollout Switch Cutout Temp (F)+

 

190

190

190

190

Burner Orifice Diameter (in... .drill size)

 

 

 

 

Natural Gas

 

0.1285...30/0.136...29

0.1285...30/0.136...29

0.1285...30/0.136...29

0.1285...30/0.136...29

Thermostat Heat Anticipator Setting (amps)

 

 

 

 

208/230, 575

Stage 1

0.98

0.98

0.98

0.98

 

Stage 2

0.44

0.44

0.44

0,44

460 V

stage 1

0.80

0.80

0.80

0,80

 

Stage 2

0.44

0.44

0.44

0,44

Gas Input

Stage 1

172,000/225,000

206,000/270,000

206,000/270,000

206,000/270,000

Efficiency (Steady State) {%)

Stage 2

230,000/300,000

275,000/360,000

275,000/360,000

275,000/360,000

 

81

81

81

81

Temperature Rise Range

 

15-45/20-50

15-45/20-50

15-45/20-50

15-45/20-50

Manifold Pressure (in. wg)

 

 

 

 

 

Natural Gas

 

3.3

3.3

3.3

3.3

Gas Valve Quantity

 

1

1

1

1

Field Gas Connection Size (in

.-FPT)

3/4

3/4

3/4

3/4

 

 

 

 

 

 

HIGH-PRESSURE SWITCH (psig)

 

Cutout

426

Reset (Auto)__________________

 

320

LOW-PRESSURE SWITCH (psig)

 

Cutout

27

Reset (Auto)__________________

44

FREEZE PROTECTION THERMOSTAT (F)

 

Opens

30 ±5

Closes

45 ±5

OUTDOOR-AIR INLET SCREENS

Cleanable

Quantity...Size (in.)

2.. .20x25x 1

 

 

1.. .20x 20 x1

RETURN-AIR FILTERS

Throwaway*’'

Quantity...Size (in.)

4.. .20x20x2

 

 

4.. .16x20x2

POWER EXHAUST

V2

LEGEND

Bhp ™ Brake Horsepower

TXV — Thermostatic Expansion Valve

'Circuit 1 uses the lower portion of condenser coil and lower portion of evap­ orator coils; and Circuit 2 uses the upper portion of both coils.

fRollout switch is manual reset.

Hp, 208/230-460 V Motor Direct Drive, Propeller-Fan (Factory-Wired for 460 v)

**The 48TJ028 units requires 2-in. industrial-grade filters capable of handling face velocities of up to 625 ft/min (such as American Air Filter no, 5700 or equivalent).

NOTE: The 48TJ016-028 units have a low-pressure switch (standard) located on the suction side.

step 3 — Field Fabricate Ductwork — Secure all ducts to building stnjcture. Use flexible duct connectors be­ tween unit and ducts as required. Insulate and weatlierproof all external ductwork, joints, and roof openings with counter flashing and mastic in accordance with applicable codes.

Ducts passing through an unconditioned space must be in­ sulated and covered with a vapor barrier.

Step 4 Make Unit Duct Connections — Unit is shipped for thra-the-bottom duct connections. Ductwork openings are shown in Fig. 1, 4, and 5. Duct connections are shown in Fig. 6. Field-fabricated concentric ductwork may be connected as shown in Fig. 7 and 8. Attach all ductwork to roof curb and roof cuit) basepans.

Step 5 — Install Flue Hood and Wind Baffle —

Flue hood and wind baffle are shipped secured under main control box. To install, secure flue hood to access panel. See Fig. 9. The wind baffle is then installed over the flue hood.

NOTE: When properly installed, flue hood will line up with combustion tan housing. See Fig. 10.

Step 6 Trap Condensate Drain — See Fig. 1 1 for drain location. One ^4 -in. half coupling is provided inside unit evaporator section for condensate drain connection. An S'A-in. X ^4 -in. diameter and 2-in. x diameter pipe nip­ ple, coupled to standard V4 -in. diameter elbows, provide a straight path down through hole in unit base rtiils (see Fig. 12). A trap at least 4-in. deep must be used.

NOTE: Do not drill in this area; damage to basepan may result in water leak.

Fig. 6 — Air Distribution — Thru-the-Bottom

NOTE:

Dimensions A, A', and B' are obtained trom field-supplied

ceiling diffuser.

I

 

r| Shaded area indicates block-off panels.

 

 

 

 

Fig. 8 — Concentric Duct Details

AIR OUT

AIR IN

AIR OUT

NOTE: Do not drill in

this area;

damage to basepan may result in

water leak.

 

 

Fig. 7 — Concentric Duct Air Distribution

INDUCED DRAFT

MOTOR

COMBUSTION MAIN BURNER HEAT EXCHANGER

FAN HOUSING SECTION SECTION

Pig -|o — Combustion Fan Housing Location

Fig. 11 — Condensate Drain Details

(48TJ016 Shown)

Fig. 12 — Condensate Drain Piping Details

Step 7 — Orifice Change — This unit is factoiy as­ sembled for heating operation using natural gas at an elevation from sea level to 2000 ft. Tliis unit uses orifice type LH32RFnnn, where “nnn” indicates the orifice size based on drill size diameter in thousands of an inch.

HIGH ELEVATION (Above 2000 ft) — Use accessoiy high altitude kit when installing tliis unit at an elevation of 2000 to 7000 ft. For elevations above 7000 ft, refer to Table 2 to identi­ fy the correct orifice size for fhe elevafion. See Table 3 for the number of orifices required for each unit size. Purchase these orifices from your local Carrier dealer. Follow instmctions in accessoiy Installation Instmctions to install the correct orifices.

Table 2 — Altitude Compensation*

ELEVATION (ft)

NATURAL GAS ORIFICEf

Low Heat

 

High Heat

 

 

0-1,999

30

 

29

2,000

30

 

29

3,000

31

 

30

4,000

31

 

30

5,000

31

 

30

6,000

31

 

30

7,000

32

 

31

8,000

32

 

31

9,000

33

 

31

10,000

35

 

32

*As the height above sea level Increases, there is less oxygen per

 

cubic foot of air. Therefore, heat input rate should be reduced at

 

higher altitudes. Includes a 4% input reduction per each 1000 ft.

 

fOrifices available through your Carrier dealer.

 

Table 3 — Orifice Quantity

UNIT

ORIFICE QUANTITY

48TJD016

5

48TJD020,

 

48TJD024,

 

48TJD028,

 

48TJF016

 

48TJF020,

7

48TJF024,

48TJF028

 

CONVERSION TO LP (Liquid Propane) GAS -- Use acces­ soiy LP gas conversion kit when converting this unit for use witli LP fuel usage for elevations up to 7000 ft. For elevations above 7000 ft, refer to Table 4 to identify the correct orifice size for tlie elevation. See Table 3 for the number of orifices required for each unit size. Purchase these orifices from your loctil Carrier dealer. Follow instmctions in accessoiy Installa­ tion Instmctions to install the correct orifices.

Table 4 — LP Gas Conversion*

ELEVATION (ft)

LP GAS ORIFICEf

0-1,999

36

2,000

37

3,000

38

4,000

38

5,000

39

6,000

40

7,000

41

8,000

41

9,000

42

10,000

43

*As the height above sea level increases, there is less oxygen per cubic foot of air. Therefore, heat input rate should be reduced at higher altitudes. Includes a 4% input reduction per each 1000 ft.

fOrifices available through your Carrier dealer.

10

step 8 — Install Gas Piping — Unit is equipped for use with natui'iil gas. Installation must conform with local building codes or. in the absence of lociil codes, with the National Fuel Gas Code. ANSI Z22.3.1.

Install field-supplied manual gas shutoff valve with a Vs-in. NPT pressure tap for test gage connection at unit. Field gas pip­ ing must include sediment trap and union. See Fig. 1.1.

A WARNING

Do not pressure test gas supply while connected to unit. Always disconnect union before servicing. Exceeding maximum manifold pressure may cause explosion and injuiy.

IMPORTANT: Natural gas pressure at unit gas connec­ tion must not be less than 5.5 in. wg or greater than 1.3.5 in. wg.

Size gas-supply piping for 0.5-in. wg maximum pressure drop. Do not use supply pipe smiillei' than unit gas connection.

MANUAL SHUTOFF

step 9 — Make Electrical Connections

FIELD POWER SUPPLY — Unit is factoiy wired for volt­ age shown on nameplate.

When instiilling units, provide a disconnect per NEC (Na­ tional Electrical Code) of adequate size (Table 5).

All field wiring must comply with NEC and local requirements.

Route power ground lines through control box end panel or unit basepan (see Fig. 4 and 5) to connections as shown on unit wiring diagram and Fig. 14.

A CAUTION

Tlie correct power phasing is critical in the operation of the scroll compressor. An incorrect phasing will cause the compressor to rotate in the wrong direction. This may lead to premature compressor failure.

A WARNING

Tlie unit must be electrically grounded in accordance with local codes and NEC ANSl/NFPA 70 (National Fire Pro­ tection Association) to protect against fire and electric shock.

Field wiring must confirm to temperature limitations for type “T’ wire. All field wiring must comply with NEC and lo­ cal requirements.

Transformer no. 1 is wired for 230-v unit. If 208/230-v unit is to be nan with 208-v power supply, the transformer must be rewired as follows:

1.Remove cap from red (208 v) wire,

2.Remove cap from orange (230 v) spliced wire.

3.Replace orange wire with red wire.

4.Recap both wires.

A CAUTION

Be certain unused wires are capped. Failure to do so may damage the transformers.

Operating voltage to compressor must be within voltage range indicated on unit nameplate. On 3-phase units, voltages between phases must be balanced within 2%.

Unit failure as a result of operation on improper line voltage or excessive phase imbalance constitutes abuse and may cause damage to electrical components.

FIELD CONTROL WIRING — Install a Carrier-approved accessoiy thermostat assembly according to installation instmctions included with accessoiy. Locate thermostat assembly on a solid interior wall in the conditioned space to sense aver­ age temperature.

Route thermostat cable or equivalent single leads of colored wire from subbase terminals through conduit in unit to low-voltage connections as shown on unit label wiring diagram and in Fig. 15.

NOTE: For wire nans up to 50 ft, use no. 18 AWG (American Wire Gage) insulated wire (35 C minimum). For 50 to 75 ft, use no. 16 AWG insulated wire (.35 C minimum). For over 75 ft, use no. 14 AWG insulated wire (35 C minimum). All wire larger than no. 18 AWG cannot be directly connected at tlae thermostat and will require a junction box and splice at the tliermostat.

Set heat anticipator settings as follows:

VOLTAGE

W1

W2

208/230,575

0.98

0.44

460

0,80

0.44

Settings may be changed slightly to provide a greater degree of comfort for a particulai' installation.

LEGEND

EQUIP — Equipment

GND — Ground

NEC — National Electrical Code

TB — Terminal Block

NOTE: The maximum wire size for TB1 is 2/0.

Fig. 14 — Field Power Wiring Connections

11

OPTIONAL NON-FUSED DISCONNECT — On units with the optional non-fused disconnect, incoming power will be wired into the disconnect switch. Refer to Fig, 16 for wiring for 100 and 200 amp disconnect switches. Units with an MOCP under 100 will use the 100 amp disconnect switch. Units with an MOCP over 100 will use the 200 amp discon­ nect switch. Refer to the applicable disconnect wiring diagram.

To prevent breakage during shipping, the disconnect handle and shaft aie shipped and packaged inside the unit control box. Install the disconnect handle before unit operation. To install the handle and shaft, perform the following procedure:

1.Open the control box door and remove the handle and shaft from shipping location.

2.Loosen the Allen bolt located on the disconnect switch. Tlie bolt is located on the square hole and is used to hold the shaft in place. Tlie shaft cannot be inserted until the Allen bolt is moved.

3.Insert the disconnect shaft into the sqiuu'e hole on the dis­ connect switch. The end of the shaft is specially cut and the shaft can only be inserted in the correct orientation.

4.Tighten the Allen bolt to lock the shaft into position.

5.Close the control box door.

6.Attach the handle to the external access door with the two screws provided. When the handle is in the ON position, the handle will be vertical. When the handle is in tlie OFF position, the handle will be horizontal.

7.Turn tlie handle to the OFF position and close the door. Tlie handle should fit over the end of the shaft when the door is closed.

8.The handle must be in the OFF position to open the con­ trol box door.

OPTIONAL CONVENIENCE OUTLET--On units with optiontil convenience outlet, a 115-v GFI (ground fault interrttpt) convenience outlet receptacle is provided tor field wiring. Field wiring should be nm through the Vs-in. knockout pro­ vided in the basepan near the return air opening.

THERMOSTAT ASSEMBLY

Fig. 15 — Field Control Thermostat Wiring

6T3 4T2 2Tl LOAD

#11®

■ “È

PI P Pi

5L3 3L2 1L1 LINE

□ □ □

'^N N N

OHO

2 4 E

NOTE: The disconnect takes the place of TB-1 as shown on the unit wiring diagram label and the component arrangement label.

Fig. 16 — Optional Non-Fused Disconnect Wiring

12

Table 5 — Electrical Data

UNIT

NOMINAL

VOLTAGE

 

COMPRESSOR

 

 

OFM

 

IFM

POWER

COMBUSTION

POWER

VOLTAGE

RANGE

No. 1

No. 2

 

 

EXHAUST

FAN MOTOR

SUPPLY

48TJ

 

 

 

 

 

 

(3 Ph, 60 Hz)

Min

Max

RLA

 

LRA

RLA

 

LRA

Qty

Hp

FLA (ea)

Hp

FLA

FLA

LRA

FLA

MCA

MOCP*

 

 

 

 

 

208/230

187

253

25.6

 

190

25.6

 

190

3

0.5

1.7

3.7

10.5/11.0

 

 

0.57

74/74

90/90

 

 

 

4,6

18.8

0.57

79/79

100/100

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

016

460

414

508

13.5

 

95

13.5

 

95

3

0.5

0.8

3.7

4.8

 

 

0.30

38

50

(15 Tons)

 

 

2.3

6.0

0.30

40

50

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

575

5f8

632

10.2

 

75

10.2

 

75

3

0.5

0.8

3.0

3.9

0.57

30

35

 

 

 

2.1

4.8

0.57

32

40

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

208/230

187

253

33

 

237

23

 

184

3

0.5

1.7

5.0

15,8/15.8

0.57

85/85

110/110

020

 

 

4.6

18.8

0.57

90/90

110/110

 

 

 

 

 

 

 

 

 

 

 

 

 

 

460

414

508

16.2

 

130

10.2

 

90

3

0.5

0.8

5.0

7.9

0.30

41

50

(18 Tons)

 

 

2,3

6.0

0,30

43

50

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

575

518

632

12.7

 

85

9

 

73

3

0.5

0.8

5.0

6,0

0.57

33

45

 

 

 

2,1

4.8

0.57

35

45

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

208/230

187

253

33

 

237

29.5

 

237

2

1

6.6

7.5

25.0/25.0

0.57

109/109

125/125

 

 

 

4,6

18.8

0.57

114/114

125/125

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

024

460

414

508

16.2

 

130

14.1

 

130

2

1

3.3

7.5

13.0

0.30

54

70

(20 Tons)

 

 

2,3

6.0

0.30

56

70

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

575

518

632

12.7

 

85

11.3

 

85

2

1

3.4

7.5

10.0

 

 

0.57

44

50

 

 

 

2.1

4.8

0.57

46

50

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

208/230

187

253

47.5

 

265

33

 

237

2

1

6.6

10.0

28.0/28.0

 

0.57

134/134

175/175

 

 

 

4.6

18.8

0.57

138/138

175/175

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

028

460

414

508

22.9

 

145

16.2

 

130

2

1

3.3

10.0

14.6

0.30

66

80

(25 Tons)

 

 

2.3

6.0

0.30

68

90

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

575

518

632

17.9

 

102

12.7

 

85

2

1

3.4

10.0

13.0

0.57

55

70

 

 

 

2,1

4.8

0.57

57

70

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

LEGEND

FLA — Full Load Amps

HACR — Heating, Air Conditioning and Refrigeration

!FH/l

~

Indoor (Evaporator) Fan Motor

LRA

Locked Rotor Amps

MCA

Minimum Circuit Amps

MOCP — Maximum Overcurrent Protection

NEC

National Electrical Code

OFM

Outdoor (Condenser) Fan Motor

RLA

Rated Load Amps

'Fuse or HACR circuit breaker.

NOTES:

1. In compliance with NEC requirements for multimofor and combinafion load equipmenf (refer fo NEC Articles 430 and 440), the overcurrent protective device for the unit shall be fuse or HACR breaker, Canadian units may be fuse or circuit breaker,

2.Unbalanced 3-Phase Supply Voltage

Never operate a motor where a phase imbalance in supply voltage Is greater than 2%. Use the following formula to determine the percent of volt­ age imbalance.

% Voltage Imbalance

t o o

max voltage deviation from average voltage

X

 

average voltage

Example: Supply voltage is 460-3-60.

ABC

AB = 452 V

 

BC = 464 V

 

AC = 455 V

 

452 + 464 + 455

 

Average Voltage ;

 

f37f

= 457 Determine maximum deviation from average voltage.

(AB) 457 - 452 = 5 V

(BC) 464 - 457 = 7 v (AC) 457-455 = 2 V

Maximum deviation is 7 v.

Determine percent of voltage imbalance.

7

% Voltage Imbalance = f 00 x

457

= t .53%

This amount of phase imbalance is satisfactory as it is below the maximum allowable 2%.

IMPORTANT: If the supply voltage phase imbalance is more than 2%, contact your local electric utility company immediately.

13

step 10 — Make Outdoor-Air Inlet Adjust­ ments

MANUAL OUTDOOR-AIR DAMPER ^ All units (except those equipped with a factoiy-instiilled economizer) have a manual outdoor-air damper to provide ventilation air.

Damper can be preset to admit up to 25% outdoor air into return-£iir compartment. To adjust, loosen securing screws and move damper to desired setting, tlien retighten screws to secure diunper (see Fig. 17).

25% ADJUSTABLE AIR DAMPER

SECURING SCREWS

Fig. 17 Standard 25% Outdoor-Air

Section Details

Step 11 — Install Outdoor-Air Hood

IMPORTANT: If the unit is equipped with the optional EconoMi$eiTV, move the outdoor air temperature sensor prior to installing the outdoor air hood. See the Optional EconoMi$eiTV and EconoMi$er2 section for more details.

Tlie outdoorair hood is common to 25% air ventilation and economizer. If EconoMi$erIV is used, all electrical connec­ tions have been made and adjusted at the factory. Assemble and install hood in the field.

NOTE: Tlie hood top panel, upper and lower filter rettdners, hood drain pan, baffle (size 024 and 028), and filter support bracket iu'e secured opposite the condenser end of the unit. The screens, hood side panels, remaining section of filter support bracket, seal strip, and hai'dware are in a package located inside the return-air filter access panel (Fig. 18).

1.Attach seal strip to upper filter retainer. See Fig. 19.

2.Assemble hood top panel, side panels, upper filter retain­ er, and drain pan (see Fig. 20).

.2. Secure lower filter retainer and support bracket to unit. See Fig. 20. Leave screws loose on size 024 and 028 units.

4.Slide baffle (size 024 and 028) behind lower filter retainer and tighten screws.

5.Loosen sheet metal screws for top panel of base unit located above outdoor-air inlet opening, and remove screws for hood side panels located on the sides of the outdoor-air inlet opening.

6.Match notches in hood top panel to unit top panel screws. Insert hood flange between top panel flange and unit. Tighten screws.

7.Hold hood side panel flanges flat against unit, and instiill screws removed in Step 5.

8.Inseit outdooi'-air inlet screens and spacer in channel cre­ ated by lower filter retainer and filter support bracket.

Fig. 18 — Outdoor-Air Hood Component Location

HOOD DRAIN

PAN

BAFFLE

14

step 12 — Install All Accessories— install all field-installed accessories. Refer to the accessoiy installation instructions included with each accessoiy.

MOTORMASTER® I CONTROL INSTALLATION (48TJ0I6,020 UNITS)

Install Field-Fabricated Wind Baffles — Wind baffles must be field-fabricated for all units to ensure proper cooling cycle operation at low ambient temperatures. See Fig. 21 for baffle detiiils. Use 20-gage, galvanized sheet metal, or similar coiTosion-resistant metal for baffles. Use field-supplied screws to attach baffles to unit. Screws should be V4 -in. diameter and 5/8-in. long. Drill required screw holes for mounting baffles.

A CAUTION

To avoid diunage to the refrigerant coils and electrical com­ ponents, use recommended screw sizes only. Use care when drilling holes.

NOTE: Dimensions in ( ) are in mm.

Fig. 21 — Wind Baffle Details

Install Motormaster I Controls — Only one Motormaster I control is required per unit. Tlie Motormaster I control must be used in conjunction with the Accessoiy 0° F Low Ambient Kit (purchased separately). Tlie Motonnaster I device controls out­ door fan no. I while outdoor fans no. 2 and ."5 are sequenced off by the Accessoiy 0° F Low Ambient Kit.

Accessory 0° F Low Ambient Kit — Instiill the Accessoiy 0° F Low Ambient Kit per instmction supplied with accessoiy. Sensor Assembly — Install the sensor assembly in the location shown in Fig. 22.

Motor Mount — To ensure proper fan height, replace the exist­ ing motor mount with the new motor mount provided with accessoiy.

Transformer (460 and 575-v Units Only) — On 460 and 575-v units, a transfonner is required. The transformer is provided with the accessoiy and must be field-installed.

Motormaster I Control — Recommended mounting location is on the inside of the panel to the left of the control box. The control should be mounted on the inside of the panel, verti­ cally, with leads protniding from bottom of extinsion.

 

0 0

 

 

0

 

 

ïh-

 

 

 

 

 

 

 

 

 

î î ° o

 

 

 

cp o

 

 

 

cp o

 

 

 

 

0 0 cp o

 

 

i h "

 

 

 

 

 

 

 

 

 

î

i

° °

 

 

i l »

 

 

 

cp 0

 

 

cp 0

 

 

(b 0

 

 

 

i l »

 

 

 

cp 0

 

 

cp 0

 

 

0 0

 

o

 

 

i l »

 

 

 

G )

 

 

cp o

 

 

d )

o

o

 

 

i l "

 

 

 

G )

 

 

cp o

 

 

 

® 0

 

 

i l »

 

 

 

 

 

tp 0

 

 

d >

 

0

 

 

 

i l »

 

 

 

 

 

<p 0

 

 

cp 0

 

 

 

î î

 

°

0

 

 

i l »

 

 

d >

 

0

 

 

 

 

 

 

 

(p 0

 

 

cp 0

 

 

 

 

 

 

Î0 0

 

 

i l »

 

 

 

 

 

(p 0

 

 

 

 

 

 

 

 

 

cp 0

 

 

 

 

cp 0

 

 

i l »

 

 

 

 

 

 

tp 0

 

 

 

 

cp o

 

 

i l »

 

 

 

 

 

 

 

 

SENSOR -

 

cp o

 

SENSOR ----------

 

 

LOCATION

 

 

LOCATION

 

 

 

© 0

 

G) 0

 

 

i l »

 

 

 

 

 

 

 

 

cp 0

 

 

 

è

î

0

 

 

 

i l »

 

 

 

 

i

“ °

 

 

 

 

 

G) 0

 

 

 

cp 0

 

 

0 0

 

 

o

 

 

i l »

 

 

 

G )

 

 

cp o

 

 

© o

 

o

 

 

i l »

 

 

 

G )

 

 

cp o

 

 

 

 

î

i

° °

 

 

i l »

 

 

 

 

cp 0

 

 

tp 0

 

 

 

cbî î0° o

 

 

i l »

 

 

 

 

 

<p 0

 

 

cp 0

 

 

î

i °

°

 

 

 

 

i l »

 

 

0

0

 

 

 

 

 

 

HAiRPIN END

HAIRPIN END

 

48TJ016

 

48TJ020

NOTE: All sensors are located on the eighth hairpin up from the bottom.

Fig. 22 — Motormaster I Sensor Locations

15

MOTORMASTER® V CONTROL INSTALLATION (48TJ024,028 UNITS)

Install Lield-Fabricated Wind Baffles — Wind baffles must be field-fabricated for all units to ensure proper cooling cycle operation at low ambient temperatures. See Fig. 21 for baffle details. Use 20-gage, galvanized sheet metal, or similar COITO- sion-resistant metal for baffles. Use field-supplied screws to at­ tach baffles to unit. Screws should be ‘A-in. diameter and 5/s-in. long. Drill required screw holes for mounting baffles.

A 0j|^||Y|Q||

To avoid dmnage to the refrigerant coils and electrical com­ ponents, use recommended screw sizes only. Use cru'e when diilling holes.

Install Motormaster V Controls — Tlie Motormaster V (MMV) control is a motor speed control device which adjusts condenser fan motor speed in response to declining liquid re­ frigerant pressure. A properly applied Motormaster V control extends the operating range of air-conditioning systems and permits operation at lower outdoor ambient temperatures.

Tlie minimum iunbient temperatures at which the unit will operate are:

TEMPERATURE OPERATING LIMÌTS — F°

standard

Unit with

Unit with

Unit

Low Ambient Kit

MMV Control

40

25

-20

To operate down to the ambient temperatures listed, Motomiaster V controls (Fig. 23) must be added. Field-fabricat­ ed and installed wind baffles iu'e also required for iill units (see Fig. 21). The Motormaster V control permits operation of the unit to an ambient temperature of-20 F. Tlie control regulates the speed of 3-phase fan motors that aie compatible with the control. Tliese motors are factoiy installed.

See Table 6 for the Motormaster V control accessoiy pack­ age usage. Table 7 shows applicable voltages and motors. Replacement of motor or fan blade IS NOT REQUIRED ON CURRENT PRODUCTION UNITS since the control is compatible with the factoiy-installed fan motors. Only field wiring control is required

Install the Motormaster V control per instiuctions supplied with accessoiy.

FR<3M FUSE BLOCK

Ó O Ò O Ó

U U L3 G

12I n13Aiio/-\

5

256

IflrtDfVÌÓnrTnhDnrvnfìDITri

/;n 7Î Î3 B-

TO PRESSURE^ O Q O O O

TRANSDUCER

o

C E [3

TO MOTOR(S)

Fig. 23 Motormaster V Control

Table 6 — Motormaster V Control Package Usage

UNIT

VOLTAGE

ITEM DESCRIPTION

 

208/230

CRLOWAIVIB015A00

48TJ024,028

460

CRLOWAÌVIB016A00

 

575

CRLOWAW1B017A00

Table 7 — Applicable Voltages and Motors

VOLTAGE

COMPATIBLE MOTOR

208/230-3-60

HD52AK654

460-3-60

HD52AK654

575-3-60

HD52GE576

16

step 13 — Adjust Factory-Installed Options

PREMIERLINKTM CONTROL — The PremierLink control­ ler is available as a special order from the factoiy and is com­ patible with the CiU'rier Comfort Network® (CCN) system. This control is designed to allow usere the access and ability to change factoiy-defmed settings, thus expanding the function of the standard unit control board. Carrier’s diagnostic standard tier display tools such as Navigator''^' device or Scrolling Marquee can be used witli the PremierLink controller.

Tire PremierLink controller (see Fig. 24) requires the use of a Cai'rier electronic themnostat or a CCN connection for time broadcast to initiate its internal timeclock. This is necessaiy for broadcast of time of day functions (occupied/unoccupied). No sensors are supplied with the field-mounted PremierLink con­ trol. The factoiy-installed PremierLink conti'ol includes only the supply-air temperature (SAT) sensor and the outdoor air temperature (OAT) sensor as standiu'd. An indoor air quality (CO2 ) sensor can be added as an option. Refer to Table 8 for sensor usage. Refer to Fig. 25 for PremierLink controller wir­ ing. The PremierLink control may be mounted in the control panel or an area below the control panel.

NOTE: PremierLink controller version 1.3 and later is shipped in Sensor mode. If used with a thermostat, the PremierLink controller must be configured to Thermostat mode.

Install the Supply Air Temperature (SAT) Sensor — When the unit is supplied with a factoiy-mounted PremierLink con­ trol, the supply-air temperature (SAT) sensor (33ZCSENSAT) is factoiy-supplied and wired. The wiring is routed from the PremierLink control over the control box, through a grommet.

into the fan section, down along the back side of the fan, and along the fan deck over to the supply-air opening.

The SAT probe is wire-tied to tire supply-air opening (on the horizontal opening end) in its shipping position. Remove the sensor for installation. Re-position the sensor in the flange of tire supply-air opening or in the supply air duct (as required by local codes). Drill or punch a ‘/2 -in. hole in the flange or duct.

Use two field-supplied, self-drilling screws to secure the sensor probe in a horizontal orientation.

NOTE: The sensor must be mounted in tire dischiu'ge airstream downstream of the cooling coil and any heating devices. Be sure the probe tip does not come in contact with any of the unit or heat surfaces.

Outdoor Air Temperature (OAT) Sensor — When the unit is supplied with a factoiy-mounted PremierLink control, the outdoor-air temperature sensor (OAT) is factoiy-supplied and wired.

Install the Indoor Air Quality (CQT) Sensor — Mount the optional indoor air quality (CO2 ) sensor according to manufac­ turer specificiitions.

A sepiii'ate field-supplied transformer must be used to power the CO2 sensor.

Wire the CO2 sensor to tlie COM and lAQI terminals of J5 on the PremierLink controller. Refer to the PremierLink Instal­ lation, Start-up, and Configuration Instnictions for detailed wiring and configuration information.

HVAC SENSOR INPUTS

SPACE TEMP

SET POINT ^

SUPPLY AIR TEMP

OUTDOOR TEMP

INDOOR AIR QUALITY

OUTDOOR AIR QUALITY

DUAL MODE SENSOR (STAT)

REMOTE OCCUPANCY (Q)

COMP SAFETY (Y1) ^

FIRE SHUTDOWN (Y2) ^

SUPPLY FAN STATUS (W1)

NOT USED (W2) ^

ENTHALPY STATUS (ENTH)

 

/

4-2OMA

X f M N N

 

CCN/LEN

NAVIGATOR

INDOOR COMPR HEAT EXHAUST

 

PORT

PORT

ECONOMIZER FAN MOTOR 1&2 LOW/HIGH RVS VALVE

 

 

 

-------------------------------

OUTPUTS--------------------------------------------

•-

Fig. 24 — PremierLink Controller

17

Loading...
+ 39 hidden pages