Carrier 48TC-16 User Manual

0 (0)
48TC**16
Single Package Rooftop Gas Heating/Electric Cooling Unit with Puronr (R---410A) Refrigerant Size 16
Installation Instructions
NOTE: Read the entire instruction manual before starting the installation
SAFETY CONSIDERATIONS 2....................
INSTALLATION 4...............................
Jobsite Survey 4................................
Step 1 -- Plan for Unit Location 4..................
Roof Mount 5...............................
Step 2 -- Plan for Sequence of Unit Installation 5......
Curb--Mount Installation 5.....................
Pad--Mount Installation 5......................
Frame--Mount Installation 5....................
Step 3 -- Inspect Unit 5...........................
Step 4 -- Provide Unit Support 5...................
Roof Curb Mount 5..........................
Slab Mount (Horizontal Units Only) 5...........
Alternate Unit Support
(In Lieu of Curb or Slab Mount) 5..............
Step 5 -- Field Fabricate Ductwork 7................
Step 6 -- Rig and Place Unit 7.....................
Positioning on Curb 8........................ Step 7 -- Convert to Horizontal and Connect Ductwork 8...
Step 8 -- Install Outside Air Hood 9................
Economizer Hood Removal and Setup —
Factory Option 9............................
Two Position Damper Hood Removal and Setup —
Factory Option 9............................
Economizer Hood and Two--Position Hood 10.....
Step 9 -- Install Flue Hood 10.....................
Step 10 -- Install Gas Piping 11....................
Factory--Option Thru--Base Connections
(Gas Connections) 11......................... Step 11 -- Install External Condensate Trap and Line 13..
Step 12 -- Make Electrical Connections 14...........
Field Power Supply 14........................
All Units 15................................
Units without Factory--Installed Disconnect 15....
Units with Factory--Installed Disconnect 15.......
Convenience Outlets 16....................... Factory--Option Thru--Base Connections
(Electrical Connections) 18....................
Units without Thru--Base Connections 18.........
Field Control Wiring 18.......................
Thermostat 18...............................
Unit without Thru--Base Connection Kit 19.......
Heat Anticipator Settings 19...................
Humidi--MiZer
Humidi--MiZer -- Space RH Controller 20........
PremierLinkt (Factory Option) 21.................
Supply Air Temperature (SAT) Sensor 25.........
Outdoor Air Temperature (OAT) Sensor 25.......
EconoMi$er2 25.............................
Field Connections 25..........................
Space Sensors 27............................
Connect Thermostat 27.......................
Configure the Unit for Thermostat Mode 27......
Economizer Controls 28........................
Indoor Air Quality (CO
Outdoor Air Quality Sensor 28................. Space Relative Humidity Sensor or
Humidistat Connections 29....................
Smoke Detector/Fire Shutdown (FSD) 30.........
Filter Status Switch 30........................
Supply Fan Status Switch 30...................
Remote Occupied Switch 30...................
Power Exhaust (output) 30.....................
CCN Communication Bus 31..................
RTU Open Control System 32.....................
Supply Air Temperature (SAT) Sensor 35.........
Outdoor Air Temperature (OAT) Sensor 35.......
EconoMi$er2 35.............................
Field Connections 35..........................
Space Temperature (SPT) Sensors 36............ Indoor Air Quality (CO
R
Control Connections 20..........
sensor) 28.............
2
)Sensor 36.............
2
Outdoor Air Quality Sensor 37.................
Space Relative Humidity Senor or Humidistat 37..
Smoke Detector/Fire Shutdown (FSD) 38.........
Connecting Discrete Inputs 38..................
Communication Wiring -- Protocols 39............
General 39.................................
Local Access 40.............................
RTU Open Troubleshooting 40.................
Outdoor Air Enthalpy Control 41.................
Differential Enthalpy Control 41................
Return Air Enthalpy Sensor 41.................
Smoke Detectors 42.............................
System 42..................................
Controller 42...............................
Sensor Module 42...........................
48TC**16
Smoke Detector Locations 43....................
Supply Air 43...............................
Return Air without Economizer 43..............
Return Air with Economizer 43.................
Step 13 -- Adjust Factory--Installed Options 46........
Step 14 -- Install Accessories 46...................
!
WARNING
FIRE, EXPLOSION HAZARD
Failure to follow this warning could result in personal injury or death.
Disconnect gas piping from unit when leak testing at pressure greater than 0.5 psig (3450 Pa). Pressures greater than 0.5 psig (3450 Pa) will cause gas valve damage resulting in hazardous condition. If gas valve is subjected to pressure greater than 0.5 psig (3450 Pa), it must be replaced before use. When pressure testing field--supplied gas piping at pressures of 0.5 psig (3450 Pa) or less, a unit connected to such piping must be isolated by closing the manual gas valve.
!
WARNING
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could cause personal injury or death.
Before performing service or maintenance operations on unit, always turn off main power switch to unit and install lock(s) and lockout tag(s). Unit may have more than one power switch.
SAFETY CONSIDERATIONS
Improper installation, adjustment, alteration, service, maintenance, or use can cause explosion, fire, electrical shock or other conditions which may cause personal injury or property damage. Consult a qualified installer, service agency, or your distributor or branch for information or assistance. The qualified installer or agency must use factory--authorized kits or accessories when modifying this product. Refer to the individual instructions packaged with the kits or accessories when installing.
Follow all safety codes. Wear safety glasses and work gloves. Use quenching cloths for brazing operations and have a fire extinguisher available. Read these instructions thoroughly and follow all warnings or cautions attached to the unit. Consult local building codes and appropriate national electrical codes (in USA, ANSI/NFPA70, National Electrical Code (NEC); in Canada, CSA C22.1) for special requirements.
It is important to recognize safety information. This is the safety--alert symbol
unit and in instructions or manuals, be alert to the potential for personal injury.
Understand the signal words DANGER, WARNING, CAUTION, and NOTE. These words are used with the safety--alert symbol. DANGER identifies the most serious hazards which will result in severe personal injury or death. WARNING signifies hazards which could result in personal injury or death. CAUTION is used to identify unsafe practices, which may result in minor personal injury or product and property damage. NOTE is used to highlight suggestions which will result in enhanced installation, reliability, or operation.
. When you see this symbol on the
!
WARNING
UNIT OPERATION AND SAFETY HAZARD
Failure to follow this warning could cause personal injury, death and/or equipment damage.
Puronr (R--410A) refrigerant systems operate at higher pressures than standard R--22 systems. Do not use R--22 service equipment or components on Puron refrigerant equipment.
!
WARNING
PERSONAL INJURY AND ENVIRONMENTAL HAZARD
Failure to follow this warning could cause personal injury or death.
Relieve pressure and recover all refrigerant before system repair or final unit disposal.
Wear safety glasses and gloves when handling refrigerants. Keep torches and other ignition sources away from refrigerants and oils.
!
CAUTION
CUT HAZARD
Failure to follow this caution may result in personal injury. Sheet metal parts may have sharp edges or burrs. Use care and wear appropriate protective clothing, safety glasses and gloves when handling parts and servicing air conditioning equipment.
2
Vertical Connections / Economizer
48TC**16
Horizontal Connections / Economizer
Fig. 1 -- Unit Dimensional Drawing – 16 Size Unit
3
C10864A
48TC**16
Fig. 1 -- Unit Dimensional Drawing – 16 Size Unit (cont.)
INSTALLATION
Jobsite Survey
Complete the following checks before installation.
1. Consult local building codes and the NEC (National Electrical Code) ANSI/NFPA 70 for special installa­tion requirements.
2. Determine unit location (from project plans) or select unit location.
3. Check for possible overhead obstructions which may interfere with unit lifting or rigging.
Step 1 — Plan for Unit Location
Select a location for the unit and its support system (curb or other) that provides for at least the minimum clearances required for safety. This includes the clearance to combustible surfaces, unit performance and service access below, around and above unit as specified in unit drawings. See Fig. 2.
NOTE: Consider also the effect of adjacent units. Unit may be installed directly on wood flooring or on Class
A, B, or C roof--covering material when roof curb is used Do not install unit in an indoor location. Do not locate air
inlets near exhaust vents, relief valves, or other sources of contaminated air.
C10862A
18” (457)
*
42" (1067)
Required bottom condensate drain connection.
*
Otherwise, 36” (914mm) for condensate connection.
42" (1067)
42" (1067)
C09897
Fig. 2 -- Service Clearance Dimensional Drawing
Although unit is weatherproof, avoid locations that permit water from higher level runoff and overhangs to fall onto the unit.
Select a unit mounting system that provides adequate height to allow for removal and disposal of frost and ice that will form during the heating--defrost mode as well as allow installation of condensate trap per requirements. Refer to Step 11 — Install External Condensate Trap and Line – for required trap dimensions.
4
Roof Mount —
Check building codes for weight distribution requirements. Unit operating weight is shown in Table 1.
Step 3 — Inspect Unit
Inspect unit for transportation damage. File any claim with transportation agency.
Table 1 – Operating Weights
48TC**16
COMPONENT UNITS LB (KG)
Base Unit 1380 (627)
Economizer
Vertical 100 (45)
Horizontal 115 (52)
H u m i di --- M i Ze rRSystem 62 (28)
Powered Outlet 32 (15)
Curb
14--- in/356 mm 180 (82)
24--- in/610 mm 235 (107)
Step 2 — Plan for Sequence of Unit Installation
The support method used for this unit will dictate different sequences for the steps of unit installation. For example, on curb--mounted units, some accessories must be installed on the unit before the unit is placed on the curb. Review the following for recommended sequences for installation steps.
Curb--mounted installation —
Install curb, making sure to position the common cross rail (see Fig. 3) for large duct opening.
Install field--fabricated ductwork inside curb Complete installation of the factory--installed
thru--the--base service connection option Prepare bottom condensate drain connection to suit
planned condensate line routing (refer to Step 9 for details)
Rig and place unit Install outdoor air hood Install condensate line trap and piping Make electrical connections Install other accessories
Pad--mounted installation —
Prepare pad and unit supports Check and tighten the bottom condensate drain
connection plug Rig and place unit Convert unit to side duct connection arrangement Install field--fabricated ductwork at unit duct openings Install outdoor air hood Install condensate line trap and piping Make electrical connections Install other accessories
Frame--mounted installation —
Frame--mounted applications generally follow the sequence for a curb installation. Adapt as required to suit specific installation plan.
Confirm before installation of unit that voltage, amperage and circuit protection requirements listed on unit data plate agree with power supply provided.
Step 4 — Provide Unit Support
Roof Curb Mount —
Accessory roof curb details and dimensions are shown in Fig. 3. Assemble and install accessory roof curb in accordance with instructions shipped with the curb.
NOTE: The gasketing of the unit to the roof curb is critical for a watertight seal. Install gasket supplied with the roof curb as shown in Fig. 3. Improperly applied gasket can also result in air leaks and poor unit performance.
Curb should be level. This is necessary for unit drain to function properly. Unit leveling tolerances are show in Fig. 4. Refer to Accessory Roof Curb Installation Instructions for additional information as required.
Install insulation, cant strips, roofing felt, and counter flashing as shown. Ductwork must be attached to curb and
not to the unit.
IMPORTANT: If the unit’s gas connection and/or electric and control
wiring is to be routed through the basepan and the unit is equipped with the factory--installed Thru--the--Base service option see the following sections:
S Factory--Option Thru--Base Connections
(Gas Connection) on page 11
S Factory--Option Thru--Base Connections
(Electrical Connections) on page 17
If using the field--installed Thru--the--Base accessory follow the instructions provided with the accessory kit.
NOTE: If gas and/or electrical connections are not going to occur at this time, tape or otherwise cover the fittings so that moisture does not get into the building or conduit in the interim.
Slab Mount (Horizontal Units Only) —
Provide a level concrete slab that extends a minimum of 6 in. (150 mm) beyond unit cabinet. Install a gravel apron in front of condenser coil air inlet to prevent grass and foliage from obstructing airflow.
NOTE: Horizontal units may be installed on a roof curb if required.
Alternate Unit Support (InLieuofCurborSlabMount)—
A non--combustible sleeper rail can be used in the unit curb support area. If sleeper rails cannot be used, support the long sides of the unit with a minimum of 3 equally spaced 4--in. x 4--in. (102 mm x 102 mm) pads on each side.
48TC**16
5
48TC**16
Fig. 3 -- Roof Curb Details
6
C10772
!
CAUTION
C
A
B
MAXIMUM ALLOWABLE
DIFFERENCE IN. (MM)
A-B
0.5” (13)
B-C
1.0” (25)
A-C
1.0” (25)
C10001
Fig. 4 -- Unit Leveling Tolerances
Step 5 — Field Fabricate Ductwork
NOTE: Cabinet return-air static pressure (a negative
condition) shall not exceed 0.35 in. wg (87 Pa) with economizer or 0.45 in. wg (112 Pa) without economizer.
For vertical ducted applications, secure all ducts to roof curb and building structure. Do not connect ductwork to unit.
Fabricate supply ductwork so that the cross sectional dimensions are equal to or greater than the unit supply duct opening dimensions for the first 18 in. (458 mm) of duct length from the unit basepan.
Insulate and weatherproof all external ductwork, joints, and roof openings with counter flashing and mastic in accordance with applicable codes.
Ducts passing through unconditioned spaces must be insulated and covered with a vapor barrier.
If a plenum return is used on a vertical unit, the return should be ducted through the roof deck to comply with applicable fire codes.
PROPERTY DAMAGE HAZARD
Failure to follow this caution may result in damage to roofing materials.
Membrane roofs can be cut by sharp sheet metal edges. Be careful when placing any sheet metal parts on such roof.
Step 6 — Rig and Place Unit
When the unit is ready to be rigged and no longer will be lifted by a fork truck, the wood protector under the basepan must be removed. Remove 4 screws from each base rail. Wood protector will drop to the ground. See instructions on the unit base rails.
Keep unit upright and do not drop. Spreader bars are required. Rollers may be used to move unit across a roof. Level by using unit frame as a reference. See Table 1 and Fig. 5 for additional information.
Lifting holes are provided in base rails as shown in Fig. 5. Refer to rigging instructions on unit.
!
UNIT DAMAGE HAZARD
Failure to follow this caution may result in equipment damage.
All panels must be in place when rigging. Unit is not designed for handling by fork truck.
Before setting the unit onto the curb, recheck gasketing on curb.
CAUTION
48TC**16
PLACE ALL SEAL STRIP IN PLACE BEFORE PLACING UNIT ON ROOF CURB.
“B”
UNIT
48TC**16 2130 968 116.0 2945 60.5 1535 59.5 1510
NOTES:
1. SPREADER BARS REQUIRED — Top damage will occur if spreader bars are not used.
2. Dimensions in ( ) are in millimeters.
3. Hook rigging shackles through holes in base rail, as shown in detail “A.” Holes in base rails are centered around the unit center of gravity . U se wooden top to prevent rigging straps from damaging unit .
914 - 1371
( 36” - 54” )
“C”
“A”
SEE DETAIL “A”
MAX WEIGHT
LB KG IN MM IN MM IN MM
A B C
DUCT END
DIMENSIONS
DETAIL “A”
Fig. 5 -- Rigging Details
7
C10774
PositioningonCurb—
For full perimeter curbs CRRFCURB074A00 and 075A00, the clearance between the roof curb and the front and rear
1
base rails should be the curb and the end base rails should be
/4in (6.4 mm). The clearance between
1
/2in (13 mm). For retrofit applications with curbs CRRFCURB003A01 and 4A01, the unit should be position as shown in Fig. 6.
5
Maintain the 15.5 in (394 mm) and 8
5
clearances and allow the 22
/16in (567 mm) dimension to
/8in (220 mm)
float if necessary.
Fig. 6 -- Retrofit Installation Dimensions
48TC**16
If the alternative condensate drain location through the bottom of the unit is used in conjunction with a retrofit curb, the hole in the curb must be moved 12.5 in (320 mm) towards the duct end of the unit. (See Fig. 7.)
Original Position
New Position (moved 12.5 in.)
C10003
Remove all shipping materials and top skid. Remove extra center post from the condenser end of the unit so that the condenser end of the unit matches Figs. 26 and 27. Recycle or dispose of all shipping materials.
Step 7 — Convert to Horizontal and Connect Ductwork (when required)
Unit is shipped in the vertical duct configuration. Unit without factory--installed economizer or return air smoke detector option may be field--converted to horizontal ducted configuration using accessory CRDUCTCV001A00. To convert to horizontal configuration, remove screws from side duct opening covers and remove covers.
Discard the supply duct cover. Install accessory CRDUCTCV001A00 to cover the vertical supply duct opening. Use the return duct cover removed from the end panel to cover the vertical return duct opening.
Field--supplied flanges should be attached to horizontal duct openings and all ductwork should be secured to the flanges. Insulate and weatherproof all external ductwork, joints, and roof or building openings with counter flashing and mastic in accordance with applicable codes.
Do not cover or obscure visibility to the unit’s informative data plate when insulating horizontal ductwork.
C10904
Fig. 7 -- Alternative Condensate Drain Hole Positions
Although unit is weatherproof, guard against water from higher level runoff and overhangs.
IMPORTANT: If the unit has the factory--installed Thru--the--Base
option, make sure to complete installation of the option before placing the unit on the roof curb.
See the following sections:
S Factory--Option Thru--Base Connections
(Gas Connection) on page 11
S Factory--Option Thru--Base Connections
(Electrical Connections) on page 17
NOTE: If gas and/or electrical connections are not
going to occur at this time, tape or otherwise cover the fittings so that moisture does not get into the building or conduit in the interim.
C06108
Fig. 8 -- Horizontal Conversion Panels
8
Step 8 — Install Outside Air Hood
Economizer Hood Removal and Setup -­Factory Option —
1. The hood is shipped in knock--down form and located in the return air compartment. It is attached to the economizer using two plastic tie--wraps.
2. To gain access to the hood, remove the filter access panel. (See Fig. 9.)
3. Locate and cut the (2) plastic tie--wraps, being careful to not damage any wiring. (See Fig. 10.)
4. Carefully lift the hood assembly through the filter access opening and assemble per the steps outlined in Economizer Hood and Two–Position Hood on page 10.
Two Position Damper Hood Removal and Setup -­Factory Option —
1. The hood is shipped in knock--down form and assembled to a metal support tray using plastic stretch wrap. Located in the return air compartment, the assembly’s metal tray is attached to the basepan and also attached to the damper using two plastic tie--wraps.
2. To gain access to the hood, remove the filter access panel. (See Fig. 9.)
3. Locate the (2) screws holding the metal tray to the basepan and remove. In order to remove the screws, it may be necessary to remove the panel underneath the two--position damper. Remove the two screws. Locate and cut the (2) plastic tie--wraps securing the assembly to the damper. (See Fig. 11.) Be careful to not damage any wiring or cut tie--wraps securing any wiring.
4. Carefully lift the hood assembly (with metal tray) through the filter access opening and assemble per the steps outlined in Economizer Hood and Two–Position Hood on page 10.
5. If removed, reattach the panel under the damper.
48TC**16
FILTER ACCESS PANEL
INDOOR COIL ACCESS PANEL
Fig. 9 -- Typical Access Panel Locations
Remove Hood Parts
Cut Plastic Ties (2) Places
Economizer
Hood Parts
C10004
Plastic Tie Wrap Qty (2)
Screws for Metal Tray Qty (2)
C10006
Fig. 11 -- Two--Position Damper Hood Package Location
Fig. 10 -- Economizer Hood Package Location
C10005
9
Economizer Hood and Two--Position Hood — NOTE: If the power exhaust accessory is to be installed
on the unit, the hood shipped with the unit will not be used and must be discarded. Save the aluminum filter for use in the power exhaust hood assembly.
1. The indoor coil access panel will be used as the top of the hood. If the panel is still attached to the unit, re­move the screws along the sides and bottom of the panel. See Fig. 12.
SIDE PAN EL
5. Attach the post that separates the filters with the screws provided.
6. Open the filter clips which are located underneath the hood top. Insert the aluminum filters into the bottom filter rack (hood divider). Push the filter into position past the open filter clips. Close the filter clips to lock the filters into place. See Fig. 14.
7. Install the two rain deflectors on the edge of the hood topasshowninFig.12.
RAIN DEFLECTORS
48TC**16
CAULK
INDOOR COIL ACCESS PAN EL
HERE
Fig. 12 -- Indoor Coil Access Panel Relocation
2. Swing out indoor coil access panel and insert the
hood sides under the panel (hood top). Be careful not to lift the panel too far as it might fall out. Use the screws provided to attach the hood sides to the hood top. Use screws provided to attach the hood sides to the unit. See Fig. 13.
TOP PAN EL
TOP PAN EL
INDOOR COIL ACCESS PAN EL
C10007
BAROMETRIC RELIEF
DIVIDER
CLEANABLE ALUMINUM FILTER
FILTER
OUTSIDE AIR
HOOD
FILTER CLIP
C10009
Fig. 14 -- Economizer Filter Installation
8. Caulk the ends of the joint between the unit top panel and the hood top as shown in Fig. 12.
9. Replace the filter access panel.
Step 9 — Install Flue Hood
The flue hood is shipped screwed to the basepan beside the burner compartment access panel. Remove the panel below the control box access panel to access the flue hood shipping location. Using screws provided, install flue hood and screen in location shown in Fig. 15.
INDOOR COIL ACCESS PANEL
SCREW
LEFT HOOD SIDE
HOOD DIVIDER
C10008
Fig. 13 -- Economizer Hood Construction
3. Remove the shipping tape holding the economizer barometric relief damper in place.
4. Insert the hood divider between the hood sides. See Figs. 13 and 14. Secure hood divider with 3 screws on each hood side. The hood divider is also used as the bottom filter rack for the aluminum filter.
CONTROL BOX ACCESS PANEL
FLUE HOOD
C10804
Fig. 15 -- Flue Hood Details
10
Step 10 — Install Gas Piping
R
Installation of the gas piping must be accordance with local building codes and with applicable national codes. In U.S.A., refer to NFPA 54/ANSI Z223.1 National Fuel Gas Code (NFGC). In Canada, installation must be accordance with the CAN/CSA B149.1 and CAN/CSA B149.2 installation codes for gas burning appliances.
This unit is factory equipped for use with Natural Gas fuel at elevations up to 2000 ft (610 m) above sea level. Unit may be field converted for operation at elevations above 2000 ft (610 m) and/or for use with liquefied petroleum fuel. See accessory kit installation instructions regarding these accessories.
NOTE: In U.S.A. the input rating for altitudes above 2000 ft (610 m) must be derated by 4% for each 1000 ft (305 m) above sea level. In Canada the input rating must be derated by 10% for altitudes of 2000 ft (610 m) to 4500 ft. (1372 m) above sea level.
For natural gas applications, gas pressure at unit gas connection must not be less than 5 in. wg (1250 Pa) or greater than 13 in. wg (3240 Pa) while the unit is operating. For liquified petroleum applications, the gas pressure must not be less than 11 in. wg (2740 Pa) or greater than 13 in. wg (3240 Pa) at the unit connection.
The gas supply pipe enters the unit at the burner access panel on the front side of the unit, through the long slot at the bottom of the access panel. The gas connection to the unit is made to the valve.
Table 2 – Natural Gas Supply Line Pressure Ranges
UNIT MIN MAX
48HC**14 5.0 in. wg (1250 Pa) 13.0 in. wg (3240 Pa)
3
/4--in. FPT gas inlet port on the unit gas
X
9” MINIMUM CLEARANCE
BASE UNIT
BASE RAIL
FOR PANEL REMOVAL
MANUAL GAS SHUTOFF VALVE
48” MINIMUM
ROOF CURB
NFGC – National Fuel Gas Code
Field supplied.
*
NOTE: Follow all local codes.
STEEL PIPE
NOMINAL DIAMETER
(in.)
1
/
2
3
/
or 1
4
1
/
or larger
1
4
LEGEND
GAS REGULATOR
*
DRIP LEG
PER NFGC
FABRICATED
SPACINGOFSUPPORTS
X DIMENSION
(ft)
6 8
10
*
*
FIELD-
SUPPORT
FROM GAS METE
*
C11121
Fig. 16 -- Gas Piping Guide
Factory--Option Thru--Base Connections (Gas Connection) —
3
This service connection kit consists ofa
1
fitting (stainless steel), a
1
and a 1
/2--in electrical bulkhead connector, connected to an
/2--in electrical bulkhead connector
/4--in NPT gasadapter
“L” bracket covering the embossed (raised) section of the unit basepan in the condenser section. See Fig. 17.
1
/2” ELECTRICAL BULKHEAD CONNECTOR
3
/4” NPT GAS ADAPTER FITTING
11/2” ELECTRICAL BULKHEAD CONNECTOR
48TC**16
!
CAUTION
EQUIPMENT DAMAGE HAZARD
Failure to follow this caution may result in damage to equipment.
When connecting the gas line to the unit gas valve, the installer MUST use a backup wrench to prevent damage to the valve.
Install a gas supply line that runs to the unit heating section. Refer to the NFPA 54/NFGC or equivalent code for gas pipe sizing data. Size the gas supply line to allow for a maximum pressure drop of 0.5--in wg (124 Pa) between gas regulator source and unit gas valve connection when unit is operating at high--fire flow rate.
The gas supply line can approach the unit in three ways: horizontally from outside the unit (across the roof), thru--curb/under unit basepan (accessory kit required) or through unit basepan (factory--option or accessory kit required). Consult accessory kit installation instructions for details on these installation methods. Observe clearance to gas line components per Fig. 16.
C10905
Fig. 17 -- Thru--the--Base Option, Shipping Position
1. Remove the “L” bracket assembly from the unit (see Fig. 17).
2. Cut and discard the wire tie on the gas fitting. Hand tighten the fitting if it has loosened in transit.
3. Remove connector plate assembly from the “L” bracket and discard the “L” bracket, but retain the washer head screws and the gasket (located between the “L” bracket and the connector plate assembly
NOTE: Take care not to damage the gasket, as it is reused in the following step.
4. Place the gasket over the embossed area in the basepan, aligning the holes in the gasket to the holes in the basepan. See Fig. 18.
5. Install the connector plate assembly to the basepan using 8 of the washer head screws.
11
NOTE: If gas and/or electrical connections are not going to occur at this time, tape or otherwise cover the fittings so that moisture does not get into the building or conduit in the interim.
CONNECTOR PLATE ASSEMBLY
shutoff valve be located upstream of the sediment trap. See Figs. 20 and 21 for typical piping arrangements for gas piping that has been routed through the sidewall of the curb. See Fig. 22 for typical piping arrangement when thru--base is used. Ensure that all piping does not block access to the unit’s main control box or limit the required working space in front of the control box.
9” (229mm) min
GASKET
48TC**16
Fig. 18 -- Completing Installation of Thru--the--Base
Option
The thru--base gas connector has male and female threads. The male threads protrude above the basepan of the unit; the female threads protrude below the basepan.
Check tightness of connector lock nuts before connecting gas piping.
3
Install a thru--base gas fitting. Attach a
/4--in NPT street elbow (field--supplied) on the
3
/4--in pipe nipple with minimum length of 16--in (406 mm) (field--supplied) to the street elbow and extend it through the access panel at the gas support bracket. (See Fig. 19.)
C10906
Thru-Curb Adapter
Shut Off
Valve
Burner Access Panel
Thru-Curb Adapter
Union
Unit Base Rail
Drip Leg
C07469
Fig. 20 -- Gas Piping
9” (229mm) min
Union
THRU-BASE GAS FITTING
3
/4-in NPT STREET ELBOW
GAS SUPPORT BRACKET
C10806
Fig. 19 -- Gas Line Piping
Other hardware required to complete the installation of the gas supply line will include a manual shutoff valve, a sediment trap (drip leg) and a ground--joint union. A pressure regulator valve may also be required (to convert gas pressure from pounds to inches of pressure). The manual shutoff valve must be located within 6--ft (1.83 m) of the unit. The union, located in the final leg entering the unit, must be located at least 9--in (230 mm) away from the access panel to permit the panel to be removed for service. If a regulator valve is installed, it must be located a minimum of 4--ft (1220 mm) away from the unit’s flue outlet. Some municipal codes require that the manual
Unit Base Rail
Drip Leg
Shut Off
Val ve
C07470
Fig. 21 -- Gas Piping
C10826
Fig. 22 -- Gas Piping Thru--Base Connections
12
When installing the gas supply line, observe local codes pertaining to gas pipe installations. Refer to the NFPA 54/ANSI Z223.1 NFGC latest edition (in Canada, CAN/CSA B149.1). In the absence of local building codes, adhere to the following pertinent recommendations:
1. Avoid low spots in long runs of pipe. Grade all pipe
1
/4--in. in every 15 ft (7 mm in every 5 m) to prevent traps. Grade all horizontal runs downward to risers. Use risers to connect to heating section and to meter.
2. Protect all segments of piping system against physical and thermal damage. Support all piping with appro­priate straps, hangers, etc. Use a minimum of one hanger every 8 ft (2.4 m). For pipe sizes larger than
3
/4--in., follow recommendations of national codes.
3. Apply joint compound (pipe dope) sparingly and only to male threads of joint when making pipe connec­tions. Use only pipe dope that is resistant to action of liquefied petroleum gases as specified by local and/or national codes. If using PTFE (Teflon) tape, ensure the material is Double Density type and is labeled for use on gas lines. Apply tape per manufacturer’s in­structions.
4. Pressure--test all gas piping in accordance with local and national plumbing and gas codes before connect­ing piping to unit.
NOTE: Pressure test the gas supply system after the gas supply piping is connected to the gas valve. The supply piping must be disconnected from the gas valve during the testing of the piping systems when test pressure is in excess of 0.5 psig (3450 Pa). Pressure test the gas supply piping system at pressures equal to or less than 0.5 psig (3450 Pa). The unit heating section must be isolated from the gas piping system by closing the external main manual shutoff valve and slightly opening the ground--joint union.
Check for gas leaks at the field--installed and factory--installed gas lines after all piping connections have been completed. Use soap--and--water solution (or method specified by local codes and/or regulations).
BURNER
ORIFICE
A93059
Fig. 23 -- Orifice Hole
NOTE: If orifice hole appears damaged or it is suspected
to have been re--drilled, check orifice hole with a numbered drill bit of correct size. Never re--drill an orifice. A burr--free and squarely aligned orifice hole is essential for proper flame characteristics. See Fig. 23.
Step 11 — Install External Condensate Trap and Line
The unit has one3/4-in. condensate drain connection on the end of the condensate pan and an alternate connection on the bottom. See Fig. 24. Unit airflow configuration does not determine which drain connection to use. Either drain connection can be used with vertical or horizontal applications.
48TC**16
!
WARNING
FIRE OR EXPLOSION HAZARD
Failure to follow this warning could result in personal injury, death and/or property damage.
S Connect gas pipe to unit using a backup wrench to
avoid damaging gas controls.
S Never purge a gas line into a combustion chamber. S Never test for gas leaks with an open flame. Use a
commercially available soap solution made specifically for the detection of leaks to check all connections.
S Use proper length of pipe to avoid stress on gas
control manifold.
CONDENSATE PAN (SIDE VIEW)
STANDARD SIDE DRAIN
DRAIN
PLUG
(FACTORY-INSTALLED)
ALTERNATE BOTTOM DRAIN
C08021
Fig. 24 -- Condensate Drain Pan (Side View)
When using the standard side drain connection, ensure the red plug in the alternate bottom connection is tight. Do this before setting the unit in place. The red drain pan can
1
be tightened with a
/2--in. square socket drive extension.
To use the alternate bottom drain connection, remove the red drain plug from the bottom connection (use a
1
/2-- i n . square socket drive extension) and install it in the side drain connection.
13
The piping for the condensate drain and external trap can be completed after the unit is in place. See Fig. 25.
MINIMUM PITCH 1” (25mm) PER 10’ (3m) OF LINE
BASE RAIL
OPEN VENT
2˝ (51) MIN
TO ROOF DRAIN
DRAIN PLUG
NOTE: Trap should be deep enough to offset maximum unit static difference. A 4” (102) trap is recommended.
Fig. 25 -- Condensate Drain Piping Details
48TC**16
All units must have an external trap for condensate drainage. Install a trap at least 4-in. (102 mm) deep and protect against freeze-up. If drain line is installed downstream from the external trap, pitch the line away from the unit at 1-in. per 10 ft (25 mm in 3 m) of run. Do not use a pipe size smaller than the unit connection
3
/4-in.).
(
Step 12 — Make Electrical Connections
!
WARNING
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury or death.
Do not use gas piping as an electrical ground. Unit cabinet must have an uninterrupted, unbroken electrical ground to minimize the possibility of personal injury if an electrical fault should occur. This ground may consist of electrical wire connected to unit ground lug in control compartment, or conduit approved for electrical ground when installed in accordance with NEC (National Electrical Code); ANSI/NFPA 70, latest edition (in Canada, Canadian Electrical Code CSA [Canadian Standards Association] C22.1), and local electrical codes.
SEE NOTE
ROOF CURB
C08022
Fig. 26 -- Conduit into Factory Option Disconnect
C10884
C10885
Fig. 27 -- Conduit into Control Box
If the field disconnect is larger than 100A, it must be attached to the unit using accessory CRDISBKT001A00 — disconnect switch bracket — (see Fig. 28). Follow the instructions provided with this accessory. For smaller field
1
disconnects, be sure to use
/2” screws to mount the disconnect directly to the end panel (see Fig. 29). In either case, set the disconnect vertical location on the unit so that a 90_ fitting can be used to connect the conduit to the disconnect.
NOTE: Field--supplied wiring shall conform with the limitations of minimum 63_F(33_C) rise.
Field Power Supply —
For those units without through--the--curb power, conduit must be used to route the main power from the condenser end, via the power entry in the corner post of the unit (see Figs. 26 and 27) to either the factory option disconnect or the bottom of the control box. 1” conduit is provided wrapped around compressor. A second conduit is provided with factory installed powered convenience outlet. For those units that require conduit larger than 1”, it must be field supplied. Figs. 26 and 27 show the wire routings.
C10853
Fig. 28 -- Mounting Position for Field Disconnects
(over 100A)
14
C10854
Fig. 29 -- Mounting Position for Field Disconnects
(up to 100A)
Field power wires are connected to the unit at line--side pressure lugs at the main terminal block (TB1) or at factory--installed option non--fused disconnect switch. Max wire size is #2 AWG (copper only). (See Fig. 31.)
NOTE: TEST LEADS -- Unit may be equipped with short leads (pigtails) on the field line connection points off the optional disconnect switch. These leads are for factory run--test purposes only; remove and discard before connecting field power wires to unit connection points. Make field power connections directly to line connection pressure lugs only.
!
WARNING
FIRE HAZARD
Failure to follow this warning could result in intermittent operation or performance satisfaction. Do not connect aluminum wire between disconnect switch and unit. Use only copper wire. (See Fig. 30.)
All Units —
All field wiring must comply with NEC and all local requirements. Size wire based on MCA (Minimum Circuit Amps) on the unit informative plate. See Fig. 31 and the unit label diagram for power wiring connections to the unit power terminal blocks and equipment ground. Maximum wire size is 2/0 AWG per pole.
Provide a ground--fault and short--circuit over--current protection device (fuse or breaker) per NEC Article 440 (or local codes). Refer to unit informative data plate for MOCP (Maximum Over--current Protection) device size.
Voltage to compressor terminals during operation must be within voltage range indicated on unit nameplate. See Table 10. On 3--phase units, voltages between phases must be balanced within 2% and the current within 10%. Use the formula shown in the legend for Table 10 (see Note 2 on page 45) to determine the percent of voltage imbalance.
All units except 208/230-v units are factory wired for the voltage shown on the nameplate. If the 208/230-v unit is
to be connected to a 208-v power supply, the control transformer must be rewired by moving the black wire
1
with the connection and moving it to the 200-v
/4-in. female spade connector from the 230--v
1
/4-in. male
terminal on the primary side of the transformer. Refer to
unit label diagram for additional information.
!
CAUTION
UNIT DAMAGE HAZARD
Failure to follow this caution may result in equipment damage.
Operation on improper line voltage or excessive phase imbalance constitutes abuse and may cause damage to electrical components. Such operation would invalidate any applicable Carrier warranty.
NOTE: Check all factory and field electrical connections for tightness.
Units Without Factory--Installed Disconnect —
48TC**16
ELECTRIC
DISCONNECT
SWITCH
Fig. 30 -- Disconnect Switch and Unit
COPPER
WIRE ONLY
ALUMINUM
WIRE
A93033
When installing units, provide a disconnect switch of adequate size per NEC (National Electrical Code). Disconnect sizing data is provided on the unit informative plate. Locate on unit cabinet or within sight of the unit per national or local codes. Do not cover unit informative plate if mounting the disconnect on the unit cabinet.
Units with Factory--Installed Disconnect —
The factory--installed option disconnect switch is located in a weatherproof enclosure located under the main control box. The manual switch handle is accessible through an opening in the access panel. Discard the factory test leads (see Fig.
31). The factory disconnect is an 80A disconnect.
15
Loading...
+ 33 hidden pages