Carrier 48MA-50ME016-040 User Manual

0 (0)

48MA/50ME016-040 Combination Multizone Heating/Cooling Units Gas, Electric, or Glycol Heat

Installation, Start-Up

and Service Instructions

CONTENTS

Page

SAFETY CONSIDERATIONS . . . . . . . . . . . . . . . . . . . 2

INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-34

General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2

Unit Clearances . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2

Roof Curb . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2

Roof Openings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2

Rigging Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5

Unit Positioning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5

Removing Shipping Shields . . . . . . . . . . . . . . . . . . 5

Field-Fabricated Ductwork . . . . . . . . . . . . . . . . . . . . 5

Condensate Drains . . . . . . . . . . . . . . . . . . . . . . . . . . . 9

Gas Piping (48MA) . . . . . . . . . . . . . . . . . . . . . . . . . . . 9

Optional Glycol Connections (50ME) . . . . . . . . . 10

Field Power Supply Wiring . . . . . . . . . . . . . . . . . . 10

· UNIT COMMON FEED MINIMUM CIRCUIT AMPS

Field Control Wiring . . . . . . . . . . . . . . . . . . . . . . . . . 14

·ZONE THERMOSTATS

·ZONE MODULE CONNECTIONS

·ACCESSORY REMOTE CONTROL PANEL

Reheat Humidity Control . . . . . . . . . . . . . . . . . . . . 34

Optional Economizer . . . . . . . . . . . . . . . . . . . . . . . . 34

Optional Exhaust Damper . . . . . . . . . . . . . . . . . . . 34

START-UP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34-39

Evaporator Fan . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34

Compressor Rail Shipping Bolts . . . . . . . . . . . . . 34

Refrigerant Valves . . . . . . . . . . . . . . . . . . . . . . . . . . 34

Zone Module Gas Valves (48MA) . . . . . . . . . . . . . 34

Gas Heat Lighting Procedure (48MA) . . . . . . . . . 35

· TO SHUT OFF GAS HEAT

Intermittant Pilots (48MA) . . . . . . . . . . . . . . . . . . . 35

·ADJUSTMENT

·PRESSURE ADJUSTMENT (NATURAL GAS)

Main Burner Adjustment (48MA) . . . . . . . . . . . . . 36

·ORIFICE ALIGNMENT

·PRIMARY AIR ADJUSTMENT

Outdoor-Air Thermostat Adjustment

(50ME With Electric Heat) . . . . . . . . . . . . . . . . . . 36

·UNITS WITH 2-ELEMENT HEATERS

·UNITS WITH 3-ELEMENT HEATERS

Optional Glycol Heating Coils . . . . . . . . . . . . . . . . 38

Zone Air¯ow Adjustment . . . . . . . . . . . . . . . . . . . . 38

Sequence of Operation . . . . . . . . . . . . . . . . . . . . . 38

·COOLING

·HEATING (48MA)

·HEATING (50ME WITH ELECTRIC HEAT)

·HEATING (50ME WITH GLYCOL HEATING COILS)

·OUTDOOR-AIR DAMPER

SERVICE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39-43

Cabinet Panels and Grilles . . . . . . . . . . . . . . . . . . 39

·SIDE PANELS

·TOP PANELS

·HEATER ACCESS PANELS

Cleaning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39

·EVAPORATOR COILS (ZONE COOLING COILS) AND GLYCOL HEATING COILS

·CONDENSER AND OUTDOOR-AIR COOLING COILS

·CONDENSATE DRAINS

·INDOOR-AIR FILTERS

·OUTDOOR-AIR INLET SCREENS

·GAS HEATING SECTION

·COMBUSTION AIR FAN

Air¯ow Switches . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39

·INDOOR AIRFLOW SWITCH (AFS1)

·COMBUSTION AIRFLOW SWITCH (AFS2)

Service Switch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39

Time GuardT Control Circuit . . . . . . . . . . . . . . . . . 39

Capacity Control Pressure Switches (CCP)

(2-Compressor Units Only) . . . . . . . . . . . . . . . . 39

Compressor Oil . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39

· TO ADD OR REMOVE OIL

Compressor Capacity Control Unloader(s) . . . . 40

·CONTROL SET POINT

·PRESSURE DIFFERENTIAL

Crankcase Heater(s) . . . . . . . . . . . . . . . . . . . . . . . . . 40

Refrigerant Charge . . . . . . . . . . . . . . . . . . . . . . . . . . 40

·NO CHARGE

·LOW CHARGE

Head Pressure Control . . . . . . . . . . . . . . . . . . . . . . 40

·MOTORMASTERt HEAD PRESSURE CONTROL DEVICE

·FAN CYCLING PRESSURESTAT

Condenser Fans . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41

·ADJUSTMENT

·FAN MOTOR REMOVAL

·LUBRICATION

Evaporator Fans and Motor . . . . . . . . . . . . . . . . . . 41

·MOTOR REMOVAL

·FAN SHAFT BEARING REMOVAL

·FAN SPEED ADJUSTMENT

·PULLEY REMOVAL

·PULLEY ALIGNMENT

·BELT TENSION ADJUSTMENT

·LUBRICATION

Forced-Draft Blower (48MA) . . . . . . . . . . . . . . . . . 42

·LUBRICATION

·AIR SHUTTER ADJUSTMENT

Zone Module Transformers . . . . . . . . . . . . . . . . . . 42

Optional Economizer . . . . . . . . . . . . . . . . . . . . . . . . 42

·THERMOSTAT SETTINGS

·DAMPER POSITION

·OPERATION

Optional Exhaust Damper . . . . . . . . . . . . . . . . . . . 42

Replacement Parts . . . . . . . . . . . . . . . . . . . . . . . . . . 42

START-UP CHECKLIST . . . . . . . . . . . . . . . . . . . . . CL-1

Manufacturer reserves the right to discontinue, or change at any time, speci®cations or designs without notice and without incurring obligations.

Book

1

1

 

PC 111

Catalog No. 564-840

Printed in U.S.A.

Form 48MA/50ME-3SI

Pg 1

4-96

Replaces: 48MA/50ME-1SI

Tab

1c

1d

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SAFETY CONSIDERATIONS

Installation and servicing of air-conditioning equipment can be hazardous due to system pressure and electrical components. Only trained and quali®ed service personnel should install, repair, or service air-conditioning equipment.

Untrained personnel can perform basic maintenance functions of cleaning coils and ®lters and replacing ®lters. All other operations should be performed by trained service personnel. When working on air-conditioning equipment, observe precautions in the literature, tags and labels attached to the unit, and other safety precautions that may apply.

Follow all safety codes, including ANSI (American National Standards Institute) Z223.1. Wear safety glasses and work gloves. Use quenching cloth for unbrazing operations. Have ®re extinguisher available for all brazing operations.

Before performing service or maintenance operations on unit, turn off main power switch to unit. Electrical shock could cause personal injury.

Do not try to light any appliance. Do not touch any electrical switch; do not use any phone in your building. Immediately call your gas supplier from a neighbor's phone. Follow the gas supplier's instructions. If you cannot reach your gas supplier, call the ®re department.

Do not store or use gasoline or other ¯ammable vapors and liquids in the vicinity of the 48MA unit or any other gas-®red appliance.

Improper installation, adjustment, alteration, service, or maintenance can cause injury or property damage. Refer to this manual. For assistance or additional information, consult a quali®ed installer, service agency, or the gas supplier.

Disconnect gas piping from 48MA unit when leak testing at pressures greater than 0.5 psig. Pressures greater than 0.5 psig will cause gas valve damage resulting in a hazardous condition. If gas valve is subjected to pressure greater than 0.5 psig, it must be replaced. When pressure testing ®eld-supplied gas piping at pressures of 0.5 psig or less, the unit connected to such piping must be isolated by manually closing the gas valve.

INSTALLATION

General Ð Install unit on rooftop, outdoor site only. Install unit, electrical wiring, gas supply line (48MA) and condensate drain lines in accordance with all applicable codes.

Unit Clearances Ð See Fig. 1 and 2 for service and air¯ow clearances. For 48MA gas-®red units, provide not less than 36-in. clearance to combustibles from top and all sides. Keep burner end free from any obstruction.

Locate exit terminals of mechanical draft system (48MA ¯ue outlet) as follows:

·Not less than 12 in. from any opening through which combustion products could enter the building.

·Not less than 2 ft from any adjacent building.

·Not less than 7 ft above grade when unit is adjacent to public walkways.

Roof Curb Ð Assemble and install per instructions shipped with this accessory. Information required to ®eld fabricate a roof curb and other curb data are shown in Fig. 3-5.

Install ®eld-supplied insulation, cant strips, roo®ng and counter ¯ashing as required. Seal all curb joints with mastic or other suitable roof cement to keep out moisture. Be sure that run-off pan at compressor end of curb is completely flashed and sealed.

Seal strip (Fig. 3) is shipped with accessory roof curb. Install as described in the roof curb installation instructions. The seal strip compresses under unit weight so that an airtight seal and vibration isolation are provided between unit base and curb.

Roof Openings Ð Except for the compressor and condenser section, roof area under the unit need not be ®lled in as the curb-mounted unit encloses this space. Leaving this roof section open provides ample clearance for ductwork, piping, and power and control wiring.

If the roof area inside curb is to be ®lled in so that roof deck and bottom of base unit can be used as a return-air plenum, any spaces under the curb ¯anges caused by corrugated roo®ng or roof irregularities must be sealed to prevent water seepage. If spaces are not sealed, the negative pressure of return air may draw water under the unit and into the building structure.

If openings are cut in a ®nished roof, provide at least 6-in. space on each of the longer sides of the supply and return air openings. Due to interference from the roof curb structure, this additional clearance may not be possible on the short sides.

2

CONDENSER SECTION AIRFLOW

CONN Ð Connection

NOTES:

1.Space required for service and air¯ow all around and above unit is 36 inches.

2.For additional information see Fig. 4.

3.Center of gravity is within 6 in. radius of geometric center of unit.

4.Maximum allowable pitch of unit is 1¤2 in. per 10 ft in any direction.

Certi®ed dimension drawings available on request.

UNIT

 

 

 

 

DIMENSIONS (ft-in.)

 

 

 

 

48MA

A

B

C

D

E

F

G

H

J

K

L

016-030

7- 23¤4

3-05¤8

17-115¤16

2-215¤16

13-51¤2

0- 91¤16

2-10

7-33¤16

0-31¤8

0-31¤8

0-31¤8

034,040

7-11

3-915¤16*

21- 91¤16

4-25¤8

13-51¤2

0-111¤16

3- 45¤16

8-63¤4

0-31¤32

0-215¤16

0-71¤4

*Overall height; includes 13¤4-in. for fan guards.

Fig. 1 Ð Base Unit Physical Data and Dimensions; 48MA Units

3

CONDENSER SECTION AIRFLOW

CONN Ð Connection

NOTES:

1.Space required for service and air¯ow all around and above unit is 36 inches.

2.For additional information see Fig. 5.

3.Center of gravity is within 6 in. radius of geometric center of unit.

4.Maximum allowable pitch of unit is 1¤2 in. per 10 ft in any direction.

Certi®ed dimension drawings available on request.

UNIT

 

 

 

DIMENSIONS (ft-in.)

 

 

 

 

50ME

A

B

C

D

E

 

F

G

H

J

016-030

7- 23¤4

3-09¤16

17-115¤16

2-215¤16

13-51¤2

 

3-71¤16

7-33¤16

0-31¤8

0-31¤8

034,040

7-11

3-915¤16*

21-91¤16

4-25¤8

13-51¤2

 

4-4

8-63¤4

0-215¤16

0-71¤4

*Overall height; includes 13¤4-in. for fan guards.

Fig. 2 Ð Base Unit Physical Data and Dimensions; 50ME Units

4

AIRFLOW

*Factory supplied (with accessory roof curb). ²Field supplied (when using accessory roof curb).

NOTE: Dimensions are in inches.

Fig. 3 Ð Roof Curb Detail

Rigging Unit Ð Inspect unit for shipping damage, and ®le any damage claim immediately with transportation company.

Lift unit with cables and spreader bars, using lifting brackets provided (Fig. 1 and 2). Lift one unit at a time, keep unit upright, and do not drop. Unit weights are given in Table 1. Unit center of gravity is within 6 in. of unit's geometric center. Eyebolts may be removed after unit is in ®nal position.

IMPORTANT: Do not drill or punch holes in unit frame or panels; damage to internal components or wiring may result.

Unit Positioning Ð When lowering unit onto roof curb, do not exceed the out-of-symmetry tolerances given in Fig. 4 and 5. Be sure unit is level or is pitched within speci- ®ed tolerances. Units have drains on both sides and may be pitched to either side.

Removing Shipping Shields (Fig. 6)

1.Remove shield over ¯ue outlet grille (48MA only).

2.Remove shields (sheet metal covers) located in the outdoorair inlet screen tracks behind the louvers. If the screens are removed for this procedure, be sure to replace them before replacing the louvered assembly.

Field-Fabricated Ductwork Ð Supplyand returnair openings are shown in Fig. 4 and 5. To simplify supplyair connection, a zone duct plenum may be ®eld fabricated as shown in Fig. 7. It is recommended that this plenum be installed prior to unit positioning.

It is recommended that the unit be supported on blocks temporarily while the duct plenum is installed, rather than installing the plenum while the unit is suspended. The duct plenum may be installed once the unit is located in its ®nal position, but it is much easier to install the plenum prior to unit ®nal placement.

Zone supply-air duct openings on the base unit have tab slot connections similar to those shown in Fig. 7 except that the end partitions are hemmed. Hem is positioned so that the 1-in. ¯ange at entering end of ®eld-fabricated plenum will force-®t between hem and adjacent unit frame.

Standard ¯exible duct connections between duct plenum and duct system may be used. Follow applicable codes.

Insulate any supply-air ducts passing through unconditioned spaces and cover with a vapor barrier. Separate ducts with insulation if they run parallel for more than 5 ft. This will prevent heat transfer between zones.

Install a manual balancing damper in each zone duct to provide the required zone air¯ow.

The return-air duct connection consists of 4 sheet metal ¯anges as shown in Fig. 1, 2, 4, and 5.

5

Table 1 Ð Physical Data

 

UNIT 48MA/50ME

 

016

024

 

028

 

030

034

 

040

 

Zone Modules (Quantity)

 

8

8

 

10

 

10

12

 

12

 

Nominal Cooling Capacity (tons)

15

20

 

25

 

28

30

 

37

 

OPERATING WEIGHT (lb)

 

 

 

 

 

 

 

 

 

 

 

Base Unit 48MA

 

3395

3815

 

4075

 

4080

5340

 

5710

 

Base Unit 50ME (with electric heat)

2995

3415

 

3675

 

3680

4900

 

5270

 

Roof Curb

 

506

506

 

506

 

506

630

 

630

 

REFRIGERANT CHARGE Ð R-22 (lb)

28

32

 

43

 

43

57

 

66.1

 

COMPRESSOR

 

 

 

Reciprocating Hermetic, 1725 Rpm

 

 

 

 

No. 1 Type

 

06DE537

06DE824

 

06DE537

 

06DE537

06DE537

 

06EE250

 

Cylinders...Unloaders

 

6...2

6...2

 

6...2

 

6...2

6...2

 

4...1

 

No. 2 Type

 

Ð

06DA824

 

06DA824

 

06DA537

06DA537

 

06EA250

 

Cylinders (have no unloaders)

Ð

6

 

6

 

6

6

 

4

 

System Oil Charge (pints)

 

11

18

 

18

 

18

18

 

31

 

Unloader Settings (psig)

Loads

 

 

 

Compressor No. 1 Only

 

 

 

 

Unloader No. 2

 

 

71.0 ± 1.5

 

 

 

 

Ð

 

Unloads

 

 

57.5 ± 2.5

 

 

 

 

Ð

 

 

 

 

 

 

 

 

 

Unloader No. 1

Loads

 

 

75.0 ± 1.5

 

 

 

 

75.5 ± 1.5

 

Unloads

 

 

62.5 ± 2.5

 

 

 

 

58.0 ± 2.5

 

 

 

 

 

 

 

 

 

Capacity Steps (%)

 

100,67,33

100,83,67

 

100,80,60

 

100,80,60

100,83,67

 

100,75,

 

 

50,33,17

 

40,20

 

40,20

50,33,17

 

50,25

 

 

 

 

 

 

 

 

CONDENSER FANS

 

 

 

 

Propeller, Direct Drive

 

 

 

 

Motor Hp...Rpm...Frame (NEMA)

 

 

 

 

 

 

 

 

 

 

 

No. 1

 

 

 

1...1075...56 (Single phase)

 

 

 

 

 

No. 2

 

 

 

1...1140...56 (3 phase)

 

 

 

 

Nominal Cfm

No. 3

Ð

Ð

 

Ð

 

Ð

1...1140...56 (3 phase)

 

 

16,500

15,000

 

15,000

 

15,000

24,000

 

23,000

 

EVAPORATOR FANS*

 

 

 

 

Centrifugal, Belt Drive

 

 

 

 

Number...Size (in.)

 

2...15 × 15

2...15 × 15

 

2...15 × 15

 

2...15 × 15

3...15 × 9

 

3...15 × 9

 

Cfm (Nominal)

Std

6000

8000

 

10,000

 

10,000

12,000

 

12,000

 

Motor Hp...Rpm

5...1725

71¤2...1725

 

10...1725

 

10...1725

15...1725

 

15...1725

 

Alt

Ð

Ð

 

Ð

 

Ð

20...1725

 

20...1725

 

Fan Pulley

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Outside Diameter (in.)

 

10.6

10.6

 

8.0

 

8.0

8.0

 

8.0

 

Bore (in.)

Std

13¤16

13¤16

 

13¤16

 

13¤16

111¤16

 

111¤16

 

Fan Belt Number...Size

1...3V630

1...3V630

 

2...3V560

 

2...3V560

2...3V630

 

2...3V630

 

Alt

Ð

Ð

 

Ð

 

Ð

3...3V670

 

3...3V670

 

 

 

 

 

 

Motor Pulley

Std

 

 

 

Factory Installed

 

 

 

 

Outside Diameter (in.)

5.3

6.0

 

5.0

 

5.0

5.0

 

5.0

 

Alt

Ð

Ð

 

Ð

 

Ð

6.0

 

6.0

 

Bore (in.)

 

 

 

 

Std

11¤8

13¤8

 

13¤8

 

13¤8

15¤8

 

15¤8

 

Resulting Fan Rpm

880

995

 

1095

 

1095

1095

 

1095

 

Alt

Ð

Ð

 

Ð

 

Ð

1320

 

1320

 

 

 

 

 

 

Shaft Center Line Distance (in.)

18 ± 2.5

18 ± 2.5

 

18 ± 2.5

 

18 ± 2.5

21 ± 2.5

 

21 ± 2.5

 

Maximum Fan Rpm

 

1300

1300

 

1300

 

1300

1550

 

1550

 

CONDENSER COOLING COIL

 

Thermostatic Expansion Valve, Hot Gas Bypass

 

 

 

Face Area (sq ft)

 

6.8

6.8

 

6.8

 

6.8

10.2

 

10.2

 

Corrugated Fins/in. ...Rows

13...2

13...2

 

13...2

 

13...2

13...2

 

13...3

 

EVAPORATOR COILS (zone)

 

 

Solenoid Valve and Capillary Tube for each

 

 

 

Number...Face Area (sq ft/ea)

8...2.12

8...2.12

 

10...2.12

 

10...2.12

12...2.01

 

12...2.01

 

Corrugated Fins/in. ...Rows

13...3

13...3

 

13...3

 

13...3

12...3

 

15...3

 

HEATING SECTION (48MA)

 

 

One Heat Assembly in Each Zone Module

 

 

 

Rise Range

Total

 

 

 

25 F to 55 F at 0.75 in. wg ESP

 

 

 

 

Input (1000 Btuh)

432

432

 

540

 

540

648

 

648

 

Each Module

54

54

 

54

 

54

54

 

54

 

 

 

 

 

 

Bonnet Cap.² (1000 Btuh)

Total

324

324

 

405

 

405

486

 

486

 

Each Module

40.5

40.5

 

40.5

 

40.5

40.5

 

40.5

 

Burner Spud Qty...Size

 

2...38

2...38

 

2...38

 

2...38

2...38

 

2...38

 

OPTIONAL HEATING SECTION (50ME Electric)

 

 

 

 

 

 

 

 

 

 

Electric Heaters

 

 

Nichrome, Open-Wire Resistance Element in Each Zone Module

 

Qty...Elements (each)**

 

8...2 or 3

8...2 or 3

 

10...2 or 3

 

10...2 or 3

12...2 or 3

 

12...2 or 3

 

OPTIONAL HEATING SECTION

 

 

One Heating Coil in Each Zone Module

 

 

 

(50ME Glycol Coil)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Maximum Allowable Inlet Temperature (F)

 

 

 

 

200

 

 

 

 

Maximum Allowable Flow, Each Coil (Gpm)

 

 

 

 

6

 

 

 

 

 

Solution Mixture

 

 

 

 

20% Glycol

 

 

 

 

Maximum Allowable Working Pressure (Psig)

 

 

 

 

30

 

 

 

 

Total Internal Volume (Gal)

 

2.61

2.61

 

3.15

 

3.15

3.76

 

3.76

 

PRESSURE SWITCHES

Cutout

 

 

 

 

29 ± 5

 

 

 

 

Low-Pressure (Psig)

 

 

 

 

 

 

 

 

Cut-in

 

 

 

 

39 ± 5

 

 

 

 

 

 

 

 

 

 

 

 

 

High-Pressure (Psig)

Cutout

 

 

400 ± 5

 

 

 

 

Cut-in

 

 

300 ± 5

 

 

 

 

 

 

 

 

 

 

 

Indoor Air¯ow Switch (AFS1)

 

 

 

 

 

 

 

 

 

 

Factory Setting (cfm)

 

 

 

6000

 

 

 

9000

 

Adjustment Range (cfm)

 

 

4000-6000

 

 

6000-9000

 

INDOOR AIR FILTERS

 

 

 

 

 

 

 

 

 

 

 

Standard Qty...Size (in.)

 

 

 

12...20 × 25 × 2

 

 

 

 

High Efficiency (optional)

 

 

 

 

12...20 × 2 5 × 2 (36.5% Efficient)

 

 

 

 

Qty...Size (in.)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OUTDOOR AIR FILTERS

 

 

 

 

 

 

 

 

 

 

 

Qty...Size (in.)

 

 

2...20 × 25 × 1

 

 

2...32 × 35 × 1

 

LEGEND

ESP Ð

External Static Pressure

NEMA Ð

National Electrical Manufacturers Association

*Standard unit shipped with standard motor, pulley, and belt(s); alternate unit shipped with alternate motor, pulley, and belt(s).

²The heating efficiency rating is a product thermal efficiency rating determined under continuous operating conditions independent of any installed system. **See Field Power Supply Wiring section on page 10 and Table 4 for details.

6

Carrier 48MA-50ME016-040 User Manual

EVAPORATOR (ZONE MODULE) AIRFLOW

CONN Ð Connection

*Not used on 48MA016,024 (8 zone module units).

NOTES:

1. For additional information, see Table 1 and Fig. 1.

2. Maximum allowable unit pitch is 1¤2 in. per 10 ft in any direction. 3. Remove shipping brace before assembling curb section (location

shown).

UNIT

 

 

 

DIMENSIONS (ft-in.)

 

 

 

48MA

A

B

C

D

E

F

G

H

J

016-030

18-21¤8

7- 3

11-9

5-61¤4

7-27¤8

1-109¤16

2-29¤16

6-03¤8

0- 71¤2

034,040

21-97¤8

7-113¤4

14-13¤4

6-77¤16

8-43¤16

2- 91¤8

3-1

6-81¤2

0-105¤16

Fig. 4 Ð Roof Curb Physical Data and Dimensions; 48MA Units

7

END DETAIL

(034,044 12-ZONE MODULES)

EVAPORATOR (ZONE MODULE) AIRFLOW

CONN Ð Connection

*Not used on 50ME016,024 (8 zone module units).

NOTES:

1.For additional information, see Table 1 and Fig. 2.

2.Maximum allowable unit pitch is 1¤2 in. per 10 ft in any direction.

3.Remove shipping brace before assembling curb section (location shown).

UNIT

 

 

 

DIMENSIONS (ft-in.)

 

 

 

50ME

A

B

C

D

E

F

G

H

J

016-030

18-21¤8

7- 3

11-9

5-61¤4

7-27¤8

1-109¤16

2-29¤16

6-03¤8

0- 71¤2

034,040

21-97¤8

7-113¤4

14-13¤4

6-77¤16

8-43¤16

2- 91¤8

3-1

6-81¤2

0-105¤16

Fig. 5 Ð Roof Curb Physical Data and Dimensions; 50ME Units

8

Condensate Drains Ð Pipe nipples covered with foam rubber insulation are shipped in unit return air ®lter section (6 nipples in units 48MA, 4 nipples in units 50ME). Install a nipple in each drain connection on both sides of unit. See Fig. 1 and 2 for drain locations. Be sure foam rubber seals space between nipple and base rail opening to prevent rain leaks.

Connect a drain line to drain connection under outdoor air inlet grilles on both sides of unit. These drains need not be trapped.

Install a trapped drain line on remaining connections on lowest side of unit depending on unit pitch. If unit is level, a trapped drain may be installed at each connection if desired. Cap or plug unused connections on high side of unit to prevent air¯ow between unit interior and outdoors.

OUTDOOR AIR INLET

 

(ONE ON EACH SIDE OF UNIT)

FLUE OUTLET

SHIPPING SHIELD

COVER

(BEHIND LOUVERS)

(48MA ONLY)

 

Fig. 6 Ð Shipping Shield Locations

(016-030 Units Shown)

Do not interconnect drains. Make each trap a minimum of 4 in. deep. Insulate trap against freeze-up or use ¯exible material.

Gas Piping (48MA) Ð Unit is equipped for use with type of gas shown on nameplate. Refer to latest edition of ANSI Z223.1. Unit main gas connection and alternate gas connection locations are shown in Fig. 1, 4, and 8. Do not use gas supply pipe smaller than unit gas connection. Maximum allowable natural gas supply pressure is 10.0 in. wg; minimum allowable natural gas supply pressure for full rate input is 5.0 in. wg.

Pitch pipe 1¤4 in. per 15 ft. Pitch all horizontal pipe runs upward to risers and from risers upward to meter. Install a dirt and moisture pocket (drip leg) at each section of vertical pipe run. Use only ground joint unions to ensure leakfree joints. Use only pipe joint compounds that are resistant to the action of lique®ed petroleum gases.

NOTE: Dimension to suit job requirements. Twelve inches will bring duct plenum to bottom of roof curb.

DIMENSIONS (in.)

UNIT

016,024

028,030

034,040

48MA,50ME

 

 

 

A*

75¤8

75¤8

75¤16

B*

75¤8

73¤4

53¤4

*Typical; both ends.

Fig. 7 Ð Field-Fabricated Zone Duct Plenum Detail

9

*Shutoff valve not used except where required by code.

Properly cap any gas connection not being used.

Fig. 8 Ð Suggested Gas Piping (48MA)

Unit has factory-installed gas shutoff valves. Install gas shutoff valve external to unit if required by code (Fig. 8). After piping is complete, pressurize gas line and check for leaks with soap and water solution.

Do not use an open ¯ame when checking for gas leaks.

Optional Glycol Connections (50ME) Ð Each zone module has its own glycol heating coil and 115-v solenoid valve. Heating coils are connected in parallel to common supply and return manifolds. Supply manifolds are equipped with bleed cocks. Supply and return connections are shown in Fig. 2 and 5. Unit does not have internal pressure relief for part-load operation. Maximum allowable system working pressure is 30 psig. Unit ratings are based on 20% glycol solutions. Install solution supply apparatus in accordance with application requirements, and mix glycol solution percentage in accordance with glycol manufacturer's recommendations. Freeze-up protection is not factory installed.

Field Power Supply Wiring Ð When installed, unit must be electrically grounded in accordance with local codes or, in the absence of local codes, with the National Electrical Code (NEC).

Unit has a circuit breaker for each compressor, each fan motor, and for each 50ME electric resistance heater assembly (if unit is so equipped). If required by local code, provide an additional disconnect switch in accordance with code being followed.

All units have a main power supply terminal board in the power and condensing control box. The electric resistance heater power supply terminal board(s) (if unit is so equipped) on 50ME units is located in the heater control box at front of unit. See Fig. 2, 5, and 9.

All terminal boards are suitable for use with copper or aluminum wire.

Connect electrical conduit (a threaded pipe nipple) shipped with unit to threaded ®tting in roof curb and bottom of main power and condensing section control box. Route main power wires through conduit to terminal board in box as shown on unit label wiring diagram and in Fig. 9.

When installing 48MA,50ME040 units with optional 20-hp motor, the electrical conduit interconnecting the curb and control box power wire openings will not accommodate aluminum wire of the size that may be required. If aluminum wire cannot be accommodated, an external transition box and short lengths of no. 300 kcmil, 75 C copper wire from the transition box to the unit main power connection are recommended.

Voltage to compressor terminals during compressor operation must be within voltage range indicated on unit nameplate. Phases must be balanced within 2%.

 

LEGEND

EQUIP

Ð Equipment

GND

Ð Ground

TB

Ð Terminal Board

*208/230 v units only.

Fig. 9 Ð Field Power Supply Details

10

Use the following formula to determine the percent voltage imbalance.

% Voltage Imbalance:

= 100 ×

max voltage deviation from average voltage

average voltage

 

EXAMPLE: Supply voltage is 460-3-60.

AB = 452 v

BC = 464 v

AC = 455 v

452 + 464 + 455

Average Voltage =

3

1371

=

3

= 457

Determine maximum deviation from average voltage.

(AB) 457 − 45 2 = 5 v (BC) 464 − 45 7 = 7 v (AC) 457 − 45 5 = 2 v

Maximum deviation is 7 v.

Determine percent voltage imbalance:

7

% Voltage Imbalance = 100 x

457

= 1.53%

This amount of phase imbalance is satisfactory as it is below the maximum allowable 2%.

IMPORTANT: If the supply voltage phase imbalance is more than 2%, contact your local electric utility company immediately.

Unit failure as a result of operation on improper line voltage or excessive phase imbalance constitutes abuse and may cause damage to electrical components. See Tables 2-5 for unit, electric heater, and 50ME electrical application electrical data.

Each 50ME electric heat unit is ®tted with a heating lockout circuit (if equipped with optional heat). If any zone module is operating on mechanical cooling (compressor is operating), the heating element in each zone module is locked out and cannot be energized.

On 50ME units, cooling power supply wires and electric heater power supply wires (if applicable) must be sized according to the cooling MCA (Minimum Circuit Amps) values and heating MCA values shown on unit nameplate and in Tables 3-5. These wires may be powered by a common power supply (i.e., a pull-box junction), if desired. The common power supply wires from the main power source to the junction must be sized according to the common MCA values shown in Table 5.

UNIT COMMON FEED MINIMUM CIRCUIT AMPS Ð The unit common feed MCA is calculated on the basis of either: the sum of the cooling MCA plus 1¤2 heating MCA on units with 2 heating elements per zone module (or 2¤3 heating MCA on units with 3 heating elements per zone module) or the sum of the evaporator fan motor full load amps, per NEC, plus the full heating MCA, whichever is larger. Field wiring must conform to NEC limitations for Type T wire.

Table 2 Ð Unit 48MA Electrical Data

UNIT

Voltage

VOLTAGE

COMP

COMP

 

OFM

 

COMBUSTION

 

IFM

POWER

RANGE

NO. 1

NO. 2

 

FLA

 

FAN MOTOR

 

SUPPLY

48MA

(3 Ph, 60 Hz)

 

 

 

 

 

Min

Max

RLA

LRA

RLA

LRA

No. 1

No. 2

No. 3

FLA

Hp

 

FLA

MCA

MOCP

 

 

 

 

208/230

187

254

63.6

266

 

 

 

6.6

 

 

 

 

16.2

109.6

125

016

460

414

508

28.6

120

Ð

Ð

6.2

3.0

Ð

1.8

5

 

6.6

49.8

60

 

575

518

632

22.8

96

 

 

 

2.4

 

 

 

 

5.6

39.8

45

 

208/230

187

254

44.4

170

44.4

170

 

6.6

 

 

 

 

24.2

137.5

150

024

460

414

508

19.9

77

19.9

77

6.2

3.0

Ð

1.8

7.5

 

11.0

62.2

70

 

575

518

632

15.7

62

15.7

62

 

2.4

 

 

 

 

9.0

49.4

60

 

208/230

187

254

63.6

266

44.4

170

 

6.6

 

 

 

 

30.8

168.1

200

028

460

414

508

28.6

120

19.9

77

6.2

3.0

Ð

1.8

10

 

13.0

76.1

90

 

575

518

632

22.8

96

15.7

62

 

2.4

 

 

 

 

10.5

60.4

70

 

208/230

187

254

63.6

266

63.6

266

 

6.6

 

 

 

 

30.8

187.3

200

030

460

414

508

28.6

120

28.6

120

6.2

3.0

Ð

1.8

10

 

13.0

84.5

100

 

575

518

632

22.8

96

22.8

96

 

2.4

 

 

 

 

10.5

67.5

90

 

208/230

187

254

63.6

266

63.6

266

 

6.6

6.6

 

15

 

46.2

210.8

225

 

 

 

20

 

61.0

224.6

250

 

 

 

 

 

 

 

 

 

 

 

 

 

034

460

414

508

28.6

120

28.6

120

6.2

3.0

3.0

1.8

15

 

21.0

94.5

100

20

 

26.6

100.5

125

 

 

 

 

 

 

 

 

 

 

 

 

 

 

575

518

632

22.8

96

22.8

96

 

2.4

2.4

 

15

 

16.0

75.6

90

 

 

 

20

 

21.3

80.6

100

 

 

 

 

 

 

 

 

 

 

 

 

 

 

208/230

187

254

80.0

345

80.0

345

 

6.6

6.6

 

15

 

46.2

247.7

300

 

 

 

20

 

61.0

261.5

300

 

 

 

 

 

 

 

 

 

 

 

 

 

040

460

414

508

38.5

150

38.5

150

6.2

3.0

3.0

1.8

15

 

21.0

116.7

150

20

 

27.0

122.7

150

 

 

 

 

 

 

 

 

 

 

 

 

 

 

575

518

632

31.4

120

31.4

120

 

2.4

2.4

 

15

 

16.0

95

125

 

 

 

20

 

21.3

100

125

 

 

 

 

 

 

 

 

 

 

 

 

 

 

LEGEND

COMP Ð Compressor

FLA

Ð Full Load Amps

IFM

Ð Indoor (Evaporator) Fan Motor

LRA

Ð Locked Rotor Amps

MCA

Ð Minimum Circuit Amps

MOCP Ð Maximum Overcurrent Protection

OFM

Ð

Outdoor (Condenser) Fan Motor

RLA

Ð

Rated Load Amps

NOTES:

1.Combustion air fan is a 115-1-60 motor on all units.

2.Condenser fan motor no. 1 is a 208/230-1-60 speed control motor on all units.

11

Table 3 Ð Unit 50ME Electrical Data

UNIT

VOLTAGE

VOLTAGE

COMP

COMP

 

OFM

 

 

IFM

POWER

RANGE

NO. 1

NO. 2

 

FLA

 

 

SUPPLY

50ME

(3 Ph, 60 Hz)

 

 

 

 

 

Min

Max

RLA

LRA

RLA

LRA

No. 1

No. 2

No. 3

Hp

 

FLA

MCA

MOCP

 

 

 

 

208/230

187

254

63.6

266

 

 

 

6.6

 

 

 

16.2

109.6

125

016

460

414

508

28.6

120

Ð

Ð

6.2

3.0

Ð

5

 

6.6

49.5

60

 

575

518

632

22.8

96

 

 

 

2.4

 

 

 

5.6

39.6

45

 

208/230

187

254

44.4

170

44.4

170

 

6.6

 

 

 

24.2

138.0

150

024

460

414

508

19.9

77

19.9

77

6.2

3.0

Ð

7.5

 

11.0

61.9

70

 

575

518

632

15.7

62

15.7

62

 

2.4

 

 

 

9.0

49.2

60

 

208/230

187

254

63.6

266

44.4

170

 

6.6

 

 

 

30.8

168.9

200

028

460

414

508

28.6

120

19.9

77

6.2

3.0

Ð

10

 

13.0

75.8

90

 

575

518

632

22.8

96

15.7

62

 

2.4

 

 

 

10.5

60.2

70

 

208/230

187

254

63.6

266

63.6

266

 

6.6

 

 

 

30.8

188.0

200

030

460

414

508

28.6

120

28.6

120

6.2

3.0

Ð

10

 

13.0

84.5

100

 

575

518

632

22.8

96

22.8

96

 

2.4

 

 

 

10.5

67.3

90

 

208/230

187

254

63.6

266

63.6

266

 

6.6

6.6

15

 

46.0

210.8

225

 

 

20

 

61.0

224.6

250

 

 

 

 

 

 

 

 

 

 

 

 

034

460

414

508

28.6

120

28.6

120

6.2

3.0

3.0

15

 

19.8

94.5

100

20

 

26.6

100.5

125

 

 

 

 

 

 

 

 

 

 

 

 

 

575

518

632

22.8

96

22.8

96

 

2.4

2.4

15

 

16.0

75.6

90

 

 

20

 

21.3

80.6

100

 

 

 

 

 

 

 

 

 

 

 

 

 

208/230

187

254

80.0

345

80.0

345

 

6.6

6.6

15

 

46.2

247.7

300

 

 

20

 

61.0

261.5

300

 

 

 

 

 

 

 

 

 

 

 

 

040

460

414

508

39.3

150

39.3

150

6.2

3.0

3.0

15

 

19.8

118.5

150

20

 

26.6

124.5

150

 

 

 

 

 

 

 

 

 

 

 

 

 

575

518

632

31.4

120

31.4

120

 

2.4

2.4

15

 

16.0

95

125

 

 

20

 

21.3

100

125

 

 

 

 

 

 

 

 

 

 

 

 

 

LEGEND

COMP Ð Compressor

FLA

Ð Full Load Amps

IFM

Ð Indoor (Evaporator) Fan Motor

LRA

Ð Locked Rotor Amps

MCA

Ð Minimum Circuit Amps

MOCP

Ð Maximum Overcurrent Protection

OFM

Ð Outdoor (Condenser) Fan Motor

RLA

Ð Rated Load Amps

NOTE: Condenser fan motor no. 1 is a 208/230-1-60 speed control motor on all units.

Table 4 Ð Electric Resistance Heater Data

UNIT

NOMINAL

ELECTRIC

HEATING ELEMENTS

FLA PER

MCA

MOCP

VOLTAGE

HEAT kW

50ME

PER ZONE MODULE

HEATING ELEMENT

(Each Circuit)

(Each Circuit)

(3 Ph, 60 Hz)

(Unit Total)

 

 

 

 

 

 

 

43/

53

2

13.0/14.4

150/166

175/175

 

208/230

57/

70

2

17.3/19.2

200/221

225/225

 

 

87/106

3

17.3/19.2

150/166

175/175

016,024

 

53

2

7.2

83

90

 

460

70

2

9.6

111

125

 

 

106

3

9.6

166

175

 

575

106

3

7.7

133

150

 

 

54/

66

2

13.0/14.4

188/207

200/225

 

208/230

72/

88

2

17.3/19.2

250/276

275/300

 

 

108/132

3

17.3/19.2

188/207

200/225

028,030

 

66

2

7.2

103

110

 

460

88

2

9.6

138

150

 

 

132

3

9.6

207

225

 

575

132

3

7.7

166

175

 

 

65/

79

2

13.0/14.4

225/249

250/250

 

208/230

87/106

2

17.3/19.2

150/165

175/175

 

 

129/158

3

17.3/19.2

225/249

250/250

034,040

 

79

2

7.2

124

125

 

460

106

2

9.6

166

175

 

 

158

3

9.6

249

250

 

575

158

3

7.7

199

200

 

 

 

 

 

 

 

 

 

 

LEGEND

FLA

Ð

Full Load Amps

MCA

Ð

Minimum Circuit Amps

MOCP Ð

Maximum Overcurrent Protection

NOTES:

1.Heaters are rated at 230 v, 460 v, and 575 v.

2.Terminal boards provided for heater power wire connections are suitable for use with copper or aluminum wire.

12

Table 5 Ð Unit 50ME Electrical Application Data

 

UNIT

 

 

 

 

 

MCA

 

 

50ME

NOMINAL

kW

 

 

Heating

Unit

 

(Unit

 

 

Circuit

 

 

 

VOLTAGE

Cooling

 

Common

 

 

 

Total)

 

 

 

Size

 

IFM

 

 

1

 

2

Feed

 

 

 

 

 

 

 

Hp

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

43/

53

 

150.0/165.6

 

Ð

184.8/192.6

 

 

 

208/230

57/

70

109.8/109.8

200.0/220.9

 

Ð

216.7/237.6

 

 

 

 

87/106

 

150.0/165.8

 

150.0/165.8

316.7/348.3

016

 

5

 

53

 

82.9

 

 

90.9

 

 

 

460

70

49.5

110.5

 

Ð

117.1

 

 

 

 

106

 

165.8

 

 

172.4

 

 

 

575

106

39.6

132.5

 

Ð

138.1

 

 

 

 

43/

53

 

150.0/160.6

 

Ð

213.0/220.8

 

 

 

208/230

57/

70

138.0/138.0

200.0/220.9

 

Ð

238.0/248.5

 

 

 

 

87/106

 

150.0/165.8

 

150.0/165.8

342.2/359.0

024

 

7.5

 

53

 

82.9

 

 

103.4

 

 

 

460

70

61.9

110.5

 

Ð

121.5

 

 

 

 

106

 

165.8

 

 

176.8

 

 

 

575

106

49.2

132.5

 

Ð

141.5

 

 

 

 

54/

66

 

188.0/207.1

 

Ð

262.9/272.5

 

 

 

208/230

72/

88

168.9

250.0/276.1

 

Ð

293.9/307.0

 

 

 

 

108/132

 

188.0/207.1

 

188.0/207.1

419.6/445.0

028

 

10

 

66

 

102.8

 

 

127.2

 

 

 

460

88

75.8

138.0

 

Ð

151.0

 

 

 

 

132

 

207.1

 

 

220.1

 

 

 

575

132

60.2

165.6

 

Ð

176.1

 

 

 

 

54/

66

 

188.0/207.1

 

Ð

282.0/291.6

 

 

 

208/230

72/

88

188.0

250.0/276.1

 

Ð

313.0/326.0

 

 

 

 

108/132

 

188.0/207.1

 

188.0/207.1

438.7/464.0

030

 

10

 

66

 

102.8

 

 

135.9

 

 

 

460

88

84.5

138.0

 

Ð

153.5

 

 

 

 

132

 

207.1

 

 

222.6

 

 

 

575

132

67.3

165.6

 

Ð

177.7

 

 

 

 

65/

79

 

225.0/248.5

 

Ð

323.3/335.1

 

 

 

208/230

87/106

210.8

150.0/165.6

 

150.0/165.1

360.8/376.4

 

 

 

 

129/158

 

225.0/248.5

 

225.0/248.5

510.9/543.2

 

 

15

 

79

 

124.3

 

 

156.7

 

 

 

460

106

94.5

165.1

 

Ð

185.4

 

 

 

 

158

 

248.5

 

 

268.3

034

 

 

575

158

75.6

198.8

 

Ð

214.8

 

 

 

65/

79

 

225.0/248.5

 

Ð

337.1/348.9

 

 

 

 

 

 

 

 

 

208/230

87/106

224.6

150.0/165.1

 

150.0/165.1

374.6/391.2

 

 

 

 

129/158

 

225.0/248.5

 

225.0/248.5

524.6/558.0

 

 

20

 

79

 

124.3

 

 

162.7

 

 

 

460

106

100.5

165.6

 

Ð

192.2

 

 

 

 

158

 

248.5

 

 

275.1

 

 

 

575

158

80.6

198.8

 

Ð

220.1

 

 

 

 

65/

79

 

225.0/248.5

 

Ð

360.2/372.0

 

 

 

208/230

87/106

247.7

150.0/165.1

 

150.0/165.1

397.7/412.8

 

 

 

 

129/158

 

225.0/248.5

 

225.0/248.5

547.7/579.0

 

 

15

 

79

 

124.3

 

 

178.9

 

 

 

460

106

116.7

165.6

 

Ð

199.5

 

 

 

 

158

 

248.5

 

 

282.4

040

 

 

575

158

95.0

198.8

 

Ð

227.5

 

 

 

65/

79

 

225.0/248.5

 

Ð

374.0/385.8

 

 

 

 

 

 

 

 

 

208/230

87/106

261.5

150.0/165.1

 

150.0/165.1

411.5/426.6

 

 

 

 

129/158

 

225.0/248.5

 

225.0/248.5

561.5/592.8

 

 

20

 

79

 

124.3

 

 

148.9

 

 

 

460

106

122.7

165.6

 

Ð

205.5

 

 

 

 

158

 

248.5

 

 

288.4

 

 

 

575

158

100.0

198.8

 

Ð

232.5

 

 

 

 

 

 

 

 

 

 

 

 

 

LEGEND

 

 

 

 

 

 

 

 

IFM Ð

Indoor (Evaporator) Fan Motor

 

 

 

 

 

 

 

MCA Ð Minimum Circuit Amps

 

 

 

 

 

 

 

13

Field Control Wiring

ZONE THERMOSTATS Ð Install a Carrier approved accessory zone thermostat assembly in each zone according to installation instructions included in the accessory. Locate each thermostat assembly in the space where it will sense average zone temperature.

Route thermostat cable or equivalent single leads of no. 18 AWG (American Wire Gage) colored wire from thermostat subbase terminals through opening on base unit (Fig. 1, 2, 4, and 5) to low-voltage thermostat connections on zone control board (Fig. 10). Use no. 16 AWG wire for lengths exceeding 50 ft.

ZONE MODULE CONNECTIONS Ð Any module may be controlled independently or jointly with another module or modules. Modules are combined into nests that form individual Class II circuits (40 va) as follows:

Modules no. 1 and 2, 3 and 4, 5 and 6, 7 and 8, 9 and 10 (028-040 units), 11 and 12 (034,040 units).

The control signal

can

be transferred from one nest

to another nest by

using

factory-supplied jumpers on

quick-connect type multiplexing terminals. This prevents overloading the nest control transformers. Factory-supplied jumpers with quick-connect terminals are shipped in the zone control and thermostat panel compartment.

Under no circumstances shall the transformer power from one Class II circuit be interconnected with any other circuit.

Thermostat heat anticipator settings are indicated for each permitted zone module connection arrangement illustrated in Fig. 11-28.

To Join Modules of the Same Nest Into the Same Zone (i.e., modules no. 1 and 2) Ð Install ®eld-supplied jumpers on thermostat connections (screw terminals) Y to Y and W2 to W2 as shown in Fig. 11. Connect thermostat wires to terminal connections of ®rst module in zone (for consistency). Two-stage cooling may be obtained in this example as shown in Fig. 12 (using a 2-stage thermostat).

To Join Modules Not of the Same Nest Into the Same Zone (i.e., modules no. 2 and 3) Ð Install the factory-supplied jumpers on quick-connect terminals 6 to 1, 7 to 2, and 8 to 3 as shown in Fig. 13. Note that module no. 1 is independently controlled by its own thermostat (in Fig. 13).

 

LEGEND

AFS

Ð Air¯ow Switch

CR

Ð Control Relay

ECR

Ð Economizer Relay

ECT

Ð Economizer Outdoor-Air Thermostat

GV

Ð Gas Valve (not used on 50ME units)

HC

Ð Heater Contactor

HR

Ð Heater Relay

IFC

Ð Indoor (Evaporator) Fan Contactor

LLS

Ð Liquid Line Solenoid

MC

Ð Master Cooling

MCR

Ð Master Cooling Relay

MH

Ð Master Heating

MHR

Ð Master Heating Relay

MU

Ð Master Unit

MUR

Ð Master Unit Relay

NC

Ð Normally Closed

NO

Ð Normally Open

NS

Ð Night Setback

SW

Ð Switch

TRAN Ð Transformer

Quick-Connect Type Terminals (for multiplexing)

Screw-Type Terminals

NOTE: Twelve-zone unit shown. Eight-zone units have modules 1-8 only. Ten-zone units have modules 1-10 only.

Fig. 10 Ð Zone Control Board Component Location

14

Fig. 10 Ð Zone Control Board Component Location (cont)

15

Loading...
+ 33 hidden pages