Carrier 40RMS008-034, 40RMQ008-028, 40RM007-034 User Manual

0 (0)

40RM007-034 40RMQ008-028 40RMS008-034 Packaged Air-Handling Units 50/60 Hz

Installation, Start-Up and

Service Instructions

CONTENTS

Page

SAFETY CONSIDERATIONS . . . . . . . . . . . . . . . . . . . . . . 1

PRE-INSTALLATION. . . . . . . . . . . . . . . . . . . . . . . . . . . . .1,2

Moving and Storage. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2

Rigging . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2

INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-25

General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2

Uncrating . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2

Accessories. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2

Unit Positioning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13

Unit Isolation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13

Refrigerant and Chilled Water

Piping Access. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13

Refrigerant Piping. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13

Chilled Water Piping . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19

Condensate Drain . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20

Fan Motors and Drives . . . . . . . . . . . . . . . . . . . . . . . . . . 20

Power Supply and Wiring . . . . . . . . . . . . . . . . . . . . . . . 21

Connecting Ductwork . . . . . . . . . . . . . . . . . . . . . . . . . . . 24

Return-Air Filters. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24

START-UP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25

SERVICE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25-45

Panels. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25

Fan Motor Lubrication. . . . . . . . . . . . . . . . . . . . . . . . . . . 25

Fan Shaft Bearings. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25

Centering Fan Wheel . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26

Fan Shaft Position Adjustment . . . . . . . . . . . . . . . . . . 26

Individual Fan Wheel Adjustment . . . . . . . . . . . . . . . 26

Fan Belts. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26

Fan Rotation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26

Fan Pulley Alignment . . . . . . . . . . . . . . . . . . . . . . . . . . . 27

Pulley and Drive Adjustment . . . . . . . . . . . . . . . . . . . . 27

Condensate Drains. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27

Return-Air Filters. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27

Chilled Water Coil Freeze Protection . . . . . . . . . . . . 27

Coil Removal. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27

Cleaning Cooling Coil . . . . . . . . . . . . . . . . . . . . . . . . . . . 27

Cleaning Insulation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27

Replacing Filters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28

START-UP CHECKLIST . . . . . . . . . . . . . . . . . . . CL-1,CL-2

SAFETY CONSIDERATIONS

Improper installation, adjustment, alteration, service, maintenance, or use can cause explosion, fire, electric shock, or other occurrences which may injure you or damage your property. Consult qualified installer or service agency for information or assistance. The qualified installer or agency must use only factory-authorized kits or accessories when modifying this product.

Recognize safety information. This is the safety-alert symbol (). When you see this symbol on the unit and in instructions or manuals, be alert to the potential for personal injury.

Understand the signal words — DANGER, WARNING, and CAUTION. These words are used with the safety-alert symbol. Danger identifies the most serious hazards which will result in severe personal injury or death. Warning indicates a condition that could result in personal injury. Caution is used to identify unsafe practices which would result in minor personal injury or product and property damage.

Installing, starting up, and servicing this equipment can be hazardous due to system pressures, electrical components and equipment location (elevated structures, etc.).

Only trained, qualified installers and service mechanics should install, start up, and service this equipment.

Untrained personnel can perform basic maintenance functions such as cleaning coils, and cleaning and replacing filters. All other operations should be performed by trained service personnel.

When working on the equipment, observe precautions in the literature and on tags, stickers, and labels attached to the equipment.

Follow all safety codes.

Wear safety glasses and work gloves.

Use care in handling, rigging, and setting bulky equipment.

Be sure all power to equipment is shut off before performing maintenance or service. More than one disconnect may be present. Failure to do so may result in personal injury or damage to the unit.

PRE-INSTALLATION

1.The power supply (v, ph, and Hz) must correspond to that specified on unit rating plate.

2.The electrical supply provided by the utility must be sufficient to handle load imposed by this unit.

3. Refer to Installation, General section (page 2) and Fig. 1A-1C for locations of electrical inlets, condensate drain, duct connections, and required clearances before setting unit in place.

4.This installation must conform with local building codes and with the NEC (National Electrical Code) or ANSI (American National Standards Institute)/NFPA (National Fire Protection Association) latest revision. Refer to provincial and local plumbing or wastewater codes and other applicable local codes.

Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.

Book

1

4

PC 111

Catalog No. 534-00003

Printed in U.S.A.

Form 40RM-23SI

Pg 1

12-04

Replaces: 40RM-22SI

Tab

3c

2e

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Moving and Storage — To transfer unit from truck to storage site, use a fork truck. Do not stack units more than 2 high during storage. If unit is to be stored for more than 2 weeks before installation, choose a level, dry storage site free from vibration. Do not remove plastic wrap or skid from unit until final installation.

Rigging — All 40RM Series units can be rigged by using the shipping skid. Units are shipped fully assembled. Do not remove shipping skids or protective covering until unit is ready for final placement; damage to bottom panels can result. Use slings and spreader bars as applicable to lift unit.

INSTALLATION

General — Allow 21/2 ft at front and side of unit for service clearance and airflow. For units equipped with an economizer, refer to the accessory installation instructions for additional clearance requirements. Be sure floor, wall, or ceiling can

support unit weight (Tables 1A-1F). See Fig. 1A-1C for dimensions.

Uncrating — Move unit as near as possible to final location before removing shipping skid.

Remove metal banding, top skid, and plastic wrap. Examine unit for shipping damage. If shipping damage is evident, file claim with transportation agency. Remove base skid just prior to actual installation.

Check nameplate information against available power supply and model number description in Fig. 2.

NOTE: Be sure to remove the styrofoam shipping pad from the thermostatic expansion valve (TXV). Verify that it has been removed. See Fig. 3.

Accessories — Refer to instructions shipped with each accessory for specific information.

2

Table 1A — 40RM Physical Data, English — Cooling Units

UNIT 40RM

007

 

 

008

 

 

012

 

 

014

 

 

016

 

 

 

 

024

 

 

028

 

 

 

034

NOMINAL CAPACITY (Tons)

6

 

 

71/2

 

 

10

 

 

121/2

 

 

15

 

 

 

 

20

 

 

25

 

 

 

30

OPERATING WEIGHT (lb)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Base Unit with TXV

381

 

 

385

 

 

405

 

 

670

 

 

685

 

 

 

 

690

 

 

1020

 

 

 

1030

Plenum

175

 

 

175

 

 

175

 

 

225

 

 

225

 

 

 

 

225

 

 

325

 

 

 

325

FANS

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Qty...Diam. (in.)

1...15

 

 

1...15

 

 

1...15

 

2...15

 

 

2...15

 

 

 

2...15

 

2...18

 

 

2...18

Nominal Airflow (cfm)

2400

 

 

3000

 

 

4000

 

5000

 

 

6000

 

 

 

 

8,000

 

10,000

 

 

12,000

Airflow Range (cfm)

1800-

 

 

2250-

 

 

3000-

 

3750-

 

 

4500-

 

 

 

6,000-

 

7,500-

 

 

9,000-

3000

 

 

3750

 

 

5000

 

6250

 

 

7500

 

 

 

10,000

 

12,500

 

 

15,000

Nominal Motor Hp (Standard Motor)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

208/230-1-60

1.3

 

 

2.4

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

208/230-3-60 and 460-3-60

2.4

 

 

2.4

 

 

2.4

 

 

2.9

 

 

3.7

 

 

 

 

5.0

 

 

7.5

 

 

 

10.0

575-3-60

1.0

 

 

2.0

 

 

2.0

 

 

3.0

 

 

3.0

 

 

 

 

5.0

 

 

7.5

 

 

 

10.0

230-3-50, 400-3-50

2.4

 

 

2.4

 

 

2.9

 

 

2.9

 

 

2.9

 

 

 

 

5.0

 

 

7.5

 

 

 

10.0

Motor Speed (rpm)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

208/230-1-60

1725

 

 

1725

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

208/230-3-60 and 460-3-60

1725

 

 

1725

 

 

1725

 

1725

 

 

1725

 

 

 

 

1745

 

 

1745

 

 

 

1745

575-3-60

1725

 

 

1725

 

 

1725

 

1725

 

 

1725

 

 

 

 

1745

 

 

1755

 

 

 

1755

230-3-50, 400-3-50

1425

 

 

1425

 

 

1425

 

1425

 

 

1425

 

 

 

 

1425

 

 

1425

 

 

 

1425

REFRIGERANT

 

 

 

 

 

 

 

 

 

 

R-22

 

 

 

 

 

 

 

 

 

 

 

 

Operating charge (lb)

3.0

 

 

3.0

 

 

1.5/1.5

 

2.0/2.0

 

 

2.5/2.5

 

 

3.5/3.5

 

4.5/4.5

 

 

5.0/5.0

 

 

 

 

 

 

 

 

 

 

 

 

(approx per circuit)*

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

DIRECT-EXPANSION COIL

 

 

 

 

Enhanced Copper Tubes, Aluminum Sine-Wave Fins

 

 

 

 

Max Working Pressure (psig)

 

 

 

 

 

 

 

 

 

 

435

 

 

 

 

 

 

 

 

 

 

 

 

Face Area (sq ft)

6.67

 

 

8.33

 

 

10.0

 

 

13.25

 

 

17.67

 

 

 

19.88

 

24.86

 

 

29.83

 

 

 

 

 

 

 

 

 

 

No. of Splits

1

 

 

1

 

 

2

 

 

2

 

 

2

 

 

 

 

2

 

 

2

 

 

 

2

No. of Circuits per Split (3 Row/4 Row)

12/12

 

 

15/15

 

 

9/9

 

 

9/12

 

 

12/16

 

 

 

13/18

 

15/20

 

 

18/24

Split Type...Percentage

 

 

 

 

 

 

 

 

 

 

Face...50/50

 

 

 

 

 

 

 

Fins/in.

15

 

 

15

 

 

17

 

 

15

 

 

15

 

 

 

 

17

 

 

15

 

 

 

15

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

STEAM COIL

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Max Working Pressure (psig at 260 F)

 

 

 

 

 

 

 

 

 

 

20

 

 

 

 

 

 

 

 

 

 

 

 

Total Face Area (sq ft)

6.67

 

 

6.67

 

 

6.67

 

 

13.33

 

 

13.33

 

 

 

13.33

 

15.0

 

 

 

15.0

 

 

 

 

 

 

 

 

 

 

 

 

Rows...Fins/in.

1...9

 

 

1...9

 

 

1...9

 

 

1...10

 

 

1...10

 

 

 

1...10

 

1...10

 

 

1...10

HOT WATER COIL

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Max Working Pressure (psig)

 

 

 

 

 

 

 

 

 

 

150

 

 

 

 

 

 

 

 

 

 

 

 

Total Face Area (sq ft)

6.67

 

 

6.67

 

 

6.67

 

 

13.33

 

 

13.33

 

 

 

13.33

 

15.0

 

 

 

15.0

 

 

 

 

 

 

 

 

 

 

 

 

Rows...Fins/in.

2...8.5

 

 

2...8.5

 

 

2...8.5

 

2...8.5

 

 

2...8.5

 

 

2...8.5

 

2...12.5

 

 

2...12.5

Water Volume

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(gal)

 

 

 

8.3

 

 

 

 

 

 

 

 

13.9

 

 

 

 

 

 

 

 

14.3

 

(ft3)

 

 

 

1.1

 

 

 

 

 

 

1.85

 

 

 

 

 

 

 

 

1.90

 

PIPING CONNECTIONS,

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Quantity...Size (in.)

1...11/

 

 

1...11/

 

 

2...11/

 

 

2...11/

 

 

2...11/

 

 

 

2...11/

 

 

2...13/

 

 

 

2...13/

DX Coil — Suction (ODF)

 

 

 

 

8

 

 

 

8

 

 

8

 

8

 

 

DX Coil — Liquid Refrigerant (ODF)

8

 

5/

8

 

 

 

 

8

 

 

 

 

5/

 

 

 

 

 

 

8

1...

 

8

 

 

 

 

 

 

 

 

 

2...

 

8

 

 

 

 

 

 

 

 

Steam Coil, In (MPT)

1...21/

 

 

 

 

 

 

 

 

 

1...21/

2

 

 

 

 

 

 

 

Steam Coil, Out (MPT)

1...1/

2

 

 

 

 

 

 

 

 

 

1...11/

 

 

 

 

 

 

 

2

 

 

 

 

 

 

 

 

 

2

 

 

 

 

 

 

 

Hot Water Coil, In (MPT)

1...11/

 

 

1...11/

2

 

 

 

 

 

 

 

 

 

1...2

 

 

 

 

 

 

Hot Water Coil, Out (MPT)

 

 

 

2

 

 

1...11/

 

 

 

 

 

 

 

 

 

1...2

 

 

 

 

 

 

1...11/

 

 

2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Condensate (PVC)

 

 

 

2

 

 

 

 

1...11/4 ODM/1 IDF

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FILTERS

 

 

 

 

 

 

Throwaway — Factory Supplied

 

 

 

 

 

 

 

Quantity...Size (in.)

4...16 x 24 x 2

 

 

 

4...16 x 20 x 2

 

 

 

 

4...20 x 24 x 2

 

 

 

 

 

 

 

 

 

 

4...16 x 24 x 2

 

 

 

 

4...20 x 25 x 2

Access Location

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Either Side

 

 

 

 

 

 

 

 

 

 

 

 

LEGEND

DX — Direct Expansion

TXV — Thermostatic Expansion Valve *Units are shipped without refrigerant charge.

3

Table 1B — 40RMQ Physical Data, English — Heat Pump Units

UNIT 40RMQ

008

 

 

 

012

 

 

016

 

 

024

 

028

 

NOMINAL CAPACITY (Tons)

71/2

 

 

 

10

 

 

15

 

 

20

 

25

 

OPERATING WEIGHT (lb)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Base Unit with TXV

385

 

 

 

427

 

 

713

 

 

720

 

1050

 

Plenum

175

 

 

 

175

 

 

225

 

 

140

 

180

 

FANS

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Qty...Diam. (in.)

1...15

 

 

 

1...15

 

 

2...15

 

 

2...15

 

2...18

 

Nominal Airflow (cfm)

3000

 

 

 

4000

 

 

6000

 

 

8000

 

10,000

 

Airflow Range (cfm)

2250-3750

 

 

 

3000-5000

 

4500-7500

 

 

6000-10,000

 

7500-12,500

Nominal Motor Hp (Standard Motor)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

208/230-1-60

2.4

 

 

 

 

 

 

 

 

 

208/230-3-60 and 460-3-60

2.4

 

 

 

2.4

 

 

3.7

 

 

5.0

 

7.5

 

575-3-60

2.0

 

 

 

2.0

 

 

3.0

 

 

5.0

 

7.5

 

230-3-50, 400-3-50

2.4

 

 

 

2.9

 

 

2.9

 

 

5.0

 

7.5

 

Motor Speed (rpm)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

208/230-1-60

1725

 

 

 

 

 

 

 

 

 

208/230-3-60 and 460-3-60

1725

 

 

 

1725

 

 

1725

 

 

1745

 

1745

 

575-3-60

1725

 

 

 

1725

 

 

1725

 

 

1745

 

1755

 

230-3-50, 400-3-50

1425

 

 

 

1425

 

 

1425

 

 

1425

 

1425

 

REFRIGERANT

 

 

 

 

 

 

 

R-22

 

 

 

 

Operating charge (lb)

3.0

 

 

 

2.0/2.0

 

3.0/3.0

 

 

3.5/3.5

 

4.5/4.5

 

 

 

 

 

 

 

 

 

(approx per circuit)*

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

DIRECT-EXPANSION COIL

 

 

 

 

Enhanced Copper Tubes, Aluminum Sine-Wave Fins

 

 

 

Max Working Pressure (psig)

 

 

 

 

 

 

435

 

 

 

 

 

 

Face Area (sq ft)

8.33

 

 

 

10.0

 

 

19.88

 

 

19.88

 

24.86

 

 

 

 

 

 

 

 

No. of Splits

1

 

 

 

2

 

 

2

 

 

2

 

2

 

No. of Circuits per Split

15

 

 

 

9

 

 

18

 

 

18

 

24/16

 

Split Type...Percentage

 

 

 

 

 

 

Face...50/50

 

 

 

 

Face...60/40

Rows...Fins/in.

3...15

 

 

 

4...15

 

 

4...15

 

 

4...15

 

4...15

 

 

 

 

 

 

 

 

STEAM COIL

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Max Working Pressure (psig at 260 F)

 

 

 

 

 

 

20

 

 

 

 

 

 

Total Face Area (sq ft)

6.67

 

 

 

6.67

 

 

13.33

 

 

13.33

 

15.0

 

 

 

 

 

 

 

 

Rows...Fins/in.

1...9

 

 

 

1...9

 

 

1...10

 

 

1...10

 

1...10

 

HOT WATER COIL

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Max Working Pressure (psig)

 

 

 

 

 

 

150

 

 

 

 

 

 

Total Face Area (sq ft)

6.67

 

 

 

6.67

 

 

13.33

 

 

13.33

 

15.0

 

 

 

 

 

 

 

 

Rows...Fins/in.

2...8.5

 

 

 

2...8.5

 

 

2...8.5

 

 

2...8.5

 

2...12.5

 

Water Volume

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(gal)

 

 

8.3

 

 

 

 

 

13.9

 

 

 

(ft3)

 

 

1.1

 

 

 

 

 

1.85

 

 

 

PIPING CONNECTIONS,

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Quantity...Size (in.)

1...11/

 

 

 

2...11/

 

 

2...11/

 

 

2...11/

 

2...13/

 

 

 

 

 

 

 

 

 

 

DX Coil — Vapor (ODF)

8

 

 

8

 

 

 

 

8

DX Coil — Liquid Refrigerant (ODF)

1...5/8

 

 

2...5/8

 

8

 

5/8

8

 

2...5/8

 

 

 

 

 

2...

 

 

 

 

Steam Coil, In (MPT)

1...21/

2

 

 

 

 

 

1...21/

 

 

 

 

1...21/

2

Steam Coil, Out (MPT)

1...11/

 

 

 

 

2

 

 

 

 

1...11/

2

 

 

 

 

1...11/

 

 

 

 

2

 

 

 

 

 

 

2

 

 

 

 

 

Hot Water Coil, In (MPT)

1...11/2

 

 

1...11/2

 

1...2

 

 

1...2

 

Hot Water Coil, Out (MPT)

1...11/2

 

 

1...11/2

 

1...2

 

 

1...2

 

Condensate (PVC)

 

 

 

 

 

 

 

1...11/ ODM/1 IDF

 

 

 

 

 

 

 

 

 

 

 

4

 

 

 

 

 

 

FILTERS

 

 

 

 

 

Throwaway — Factory Supplied

 

 

 

Quantity...Size (in.)

4...16 x 24 x 2

 

 

4...16 x 20 x 2

 

4...20 x 24 x 2

 

 

 

 

 

 

4...16 x 24 x 2

 

4...20 x 25 x 2

Access Location

 

 

 

 

 

 

 

 

 

 

 

 

Either Side

 

 

 

 

Right or

 

Left Side

 

LEGEND

DX — Direct Expansion

TXV — Thermostatic Expansion Valve *Units are shipped without refrigerant charge.

4

Table 1C — 40RMS Physical Data, English — Chilled Water Units

UNIT 40RMS

008

 

 

010

 

 

012

 

014

 

016

 

024

 

028

 

034

NOMINAL CAPACITY (Tons)

71/

 

 

81/

 

 

10

 

121/

2

 

15

 

20

 

25

 

30

 

2

 

 

2

 

 

 

 

 

 

 

 

 

 

 

 

 

OPERATING WEIGHT (lb)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Base Unit

390

 

 

391

 

 

391

 

661

 

677

 

683

 

1035

 

1042

Plenum

175

 

 

175

 

 

175

 

225

 

225

 

225

 

325

 

325

FANS

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Qty...Diam. (in.)

1...15

 

 

1...15

 

 

1...15

 

2...15

 

2...15

 

2...15

 

2...18

 

2...18

Nominal Airflow (cfm)

3000

 

 

3400

 

 

4000

 

5000

 

6000

 

8000

 

10,000

 

12,000

Airflow Range (cfm)

2250-3750

 

2250-4250

 

 

3000-5000

 

3750-6250

 

4500-7500

 

6000-10,000

 

7500-12,500

 

9000-15,000

Nominal Motor Hp

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(Standard Motor)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

208/230-1-60

2.4

 

 

2.4

 

 

 

 

 

 

 

 

208/230-3-60 and 460-3-60

2.4

 

 

2.4

 

 

2.4

 

2.9

 

 

3.7

 

5.0

 

7.5

 

10.0

575-3-60

2.0

 

 

2.0

 

 

2.0

 

3.0

 

 

3.0

 

5.0

 

7.5

 

10.0

230-3-50 and 400-3-50

2.4

 

 

2.4

 

 

2.9

 

2.9

 

 

2.9

 

5.0

 

7.5

 

10.0

Motor Speed (rpm)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

208/230-1-60

1725

 

 

1725

 

 

 

 

 

 

 

 

208/230-3-60 and 460-3-60

1725

 

 

1725

 

 

1725

 

1725

 

1725

 

1745

 

1745

 

1745

575-3-60

1725

 

 

1725

 

 

1725

 

1725

 

1725

 

1745

 

1755

 

1755

230-3-50 and 400-3-50

1425

 

 

1425

 

 

1425

 

1425

 

1425

 

1425

 

1425

 

1425

CHILLED WATER COIL

 

 

 

 

 

 

Enhanced Copper Tubes, Aluminum Sine-Wave Fins

 

 

 

 

Max Working Pressure (psig)

 

 

 

 

 

 

 

 

 

 

435

 

 

 

 

 

 

Face Area (sq ft) — Upper

8.3

 

 

9.0

 

 

9.9

 

8.3

 

 

8.3

 

11.0

 

12.4

 

15.5

 

 

 

 

 

 

 

 

 

Face Area (sq ft) — Lower

 

 

 

 

 

5.5

 

 

8.3

 

8.3

 

12.4

 

12.4

Rows...Fins/in.

 

 

 

 

 

 

 

 

 

 

 

3...15

 

 

 

 

 

 

STEAM COIL

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Max Working Pressure

 

 

 

 

 

 

 

 

 

 

20

 

 

 

 

 

 

(psig at 260 F)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Total Face Area (sq ft)

6.67

 

 

6.67

 

 

6.67

 

13.33

 

13.33

 

13.33

 

15.0

 

15.0

 

 

 

 

 

 

 

 

Rows...Fins/in.

1...9

 

 

1...9

 

 

1...9

 

1...10

 

1...10

 

1...10

 

1...10

 

1...10

HOT WATER COIL

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Max Working Pressure

 

 

 

 

 

 

 

 

 

 

150

 

 

 

 

 

 

(in. wg)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Total Face Area (sq ft)

6.67

 

 

6.67

 

 

6.67

 

13.33

 

13.33

 

13.33

 

15.0

 

15.0

 

 

 

 

 

 

 

 

Rows...Fins/in.

2...8.5

 

 

2...8.5

 

 

2...8.5

 

2...8.5

 

2...8.5

 

2...8.5

 

2...12.5

 

2...12.5

Water Volume

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(gal)

 

 

 

8.3

 

 

 

 

 

 

13.9

 

 

 

14.3

(ft3)

 

 

 

1.1

 

 

 

 

 

 

1.85

 

 

 

1.90

PIPING CONNECTIONS,

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Quantity...Size (in.)

1...13/ ODF

 

1...13/ ODF

 

 

2...13/ ODF

 

2...13/ ODM

 

2...13/ ODM

 

2...13/ ODM

 

2...21/ ODM

 

2...21/ ODM

Chilled Water — In

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Chilled Water — Out

8

 

 

8

 

 

8

 

8

 

 

8

 

8

 

8

 

8

1...13/ ODF

 

1...13/ ODF

 

 

2...13/ ODF

 

2...13/ ODM

 

2...13/ ODM

 

2...13/ ODM

 

2...21/ ODM

 

2...21/ ODM

 

8

 

 

8

 

 

8

 

8

 

 

8

 

8

 

8

 

8

Steam Coil, In (MPT)

1...

21/

2

 

 

 

 

 

 

 

1...

 

21/

 

 

 

 

Steam Coil, Out (MPT)

1...11/

 

 

 

 

 

 

 

 

2

 

 

 

 

2

 

 

 

 

 

 

1...11/

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2

 

 

 

 

Hot Water Coil, In (MPT)

1...11/2

 

 

1...11/2

 

 

 

 

 

1...2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Hot Water Coil, Out (MPT)

1...11/2

 

 

1...11/2

 

1...11/4 ODM/1 IDF

1...2

 

 

 

 

Condensate (PVC)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FILTERS

 

 

 

 

 

 

 

 

Throwaway — Factory Supplied

 

 

 

 

Quantity...Size (in.)

 

4...16 x 24 x 2

 

 

 

 

 

4...16 x 20 x 2

 

 

 

4...20 x 24 x 2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4...16 x 24 x 2

 

 

 

4...20 x 25 x 2

Access Location

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Either Side

 

 

 

 

 

 

5

Table 1D — 40RM Physical Data, SI — Cooling Units

UNIT 40RM

007

 

 

 

008

 

012

 

014

 

 

016

 

 

024

 

028

 

034

 

NOMINAL CAPACITY (kW)

21

 

 

 

26

 

35

 

43

 

 

52

 

 

70

 

87

 

105

 

OPERATING WEIGHT (kg)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Base Unit with TXV

173

 

 

 

175

 

184

 

304

 

 

311

 

 

313

 

463

 

467

 

Plenum

80

 

 

 

80

 

80

 

102

 

 

102

 

 

102

 

148

 

148

 

FANS

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Qty...Diam. (mm)

1...381

 

1...381

 

1...381

 

2...381

 

 

2...381

 

 

2...381

 

2...457

 

2...457

Nominal Airflow (L/s)

1133

 

 

 

1604

 

1888

 

2360

 

 

2831

 

 

3775

 

4719

 

5663

 

Airflow Range (L/s)

850-1416

1203-2006

 

1416-2360

 

1770-2949

 

2124-3539

 

 

2831-4719

 

3539-5899

 

4247-7079

Nominal Motor kW (Standard Motor)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

208/230-1-60

0.97

 

 

 

1.79

 

 

 

 

 

 

 

 

 

208/230-3-60 and 460-3-60

1.79

 

 

 

1.79

 

1.79

 

2.16

 

 

2.76

 

 

3.73

 

5.60

 

7.46

 

575-3-60

0.75

 

 

 

1.49

 

1.49

 

2.24

 

 

2.24

 

 

3.73

 

5.60

 

7.46

 

230-3-50, 400-3-50

1.79

 

 

 

1.79

 

2.16

 

2.16

 

 

2.16

 

 

3.73

 

5.60

 

7.46

 

Motor Speed (r/s)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

208/230-1-60

28.8

 

 

 

28.8

 

 

 

 

 

 

 

 

 

208/230-3-60 and 460-3-60

28.8

 

 

 

28.8

 

28.8

 

28.8

 

 

28.8

 

 

29.1

 

29.1

 

29.1

 

575-3-60

28.8

 

 

 

28.8

 

28.8

 

28.8

 

 

28.8

 

 

29.1

 

29.3

 

29.3

 

230-3-50, 400-3-50

23.8

 

 

 

23.8

 

23.8

 

23.8

 

 

23.8

 

 

23.8

 

23.8

 

23.8

 

REFRIGERANT

 

 

 

 

 

 

 

 

R-22

 

 

 

 

 

 

Operating charge (kg)

1.36

 

 

 

1.36

 

0.68/0.68

 

0.90/0.90

 

 

1.13/1.13

 

 

1.59/1.59

 

2.04/2.04

 

2.27/2.27

 

 

 

 

 

 

 

 

 

 

 

(approx per circuit)*

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

DIRECT-EXPANSION COIL

 

 

 

 

 

 

Enhanced Copper Tubes, Aluminum Sine-Wave Fins

 

 

 

 

 

Max Working Pressure (kPag)

 

 

 

 

 

 

 

2999

 

 

 

 

 

 

 

 

Face Area (sq m)

0.62

 

 

 

0.77

 

0.93

 

0.93

 

 

1.64

 

 

1.85

 

2.30

 

2.77

 

 

 

 

 

 

 

 

 

 

 

No. of Splits

1

 

 

 

1

 

2

 

2

 

 

2

 

 

2

 

2

 

2

 

No. of Circuits per Split (3 Row/4 Row)

12/12

 

 

 

15/15

 

9/9

 

9/12

 

 

12/16

 

 

13/18

 

15/20

 

18/24

Split Type...Percentage

 

 

 

 

 

 

 

 

 

Face...50/50

 

 

 

 

 

Fins/m

591

 

 

 

591

 

670

 

591

 

 

591

 

 

670

 

591

 

591

 

 

 

 

 

 

 

 

 

 

 

STEAM COIL

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Max Working Pressure (kPag at 126 C)

 

 

 

 

 

 

 

 

 

138

 

 

 

 

 

 

 

 

Total Face Area (sq m)

0.62

 

 

 

0.62

 

0.62

 

1.24

 

 

1.24

 

 

1.24

 

1.39

 

1.39

 

 

 

 

 

 

 

 

 

 

 

Rows...Fins/m

1...355

 

1...355

 

1...355

 

1...394

 

 

1...394

 

 

1...394

 

1...394

 

1...394

HOT WATER COIL

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Max Working Pressure (kPag)

 

 

 

 

 

 

 

1034

 

 

 

 

 

 

 

 

Total Face Area (sq m)

0.62

 

 

 

0.62

 

0.62

 

1.24

 

 

1.24

 

 

1.24

 

1.39

 

1.39

 

 

 

 

 

 

 

 

 

 

 

Rows...Fins/m

2...335

 

2...335

 

2...335

 

2...335

 

 

2...335

 

 

2...335

 

2...493

 

2...493

Water Volume

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(L)

 

 

 

 

31.4

 

 

 

 

52.6

 

 

 

 

54.1

 

(m3)

 

 

 

 

0.031

 

 

 

 

0.052

 

 

 

 

0.054

 

PIPING CONNECTIONS,

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Quantity...Size (in.)

1...11/

 

 

1...11/

 

2...11/

 

2...11/

 

 

2...11/

 

 

2...11/

 

2...13/

 

2...13/

 

DX Coil — Suction (ODF)

 

 

 

 

 

 

 

 

 

 

8

 

 

 

 

 

 

 

 

8

 

 

 

8

 

8

 

8

 

 

8

 

 

8

 

8

 

 

DX Coil — Liquid Refrigerant (ODF)

 

1...

5/8

 

 

 

 

 

 

 

2...5/8

 

 

 

 

 

 

Steam Coil, In (MPT)

 

1...21/2

 

 

 

 

1...21/2

 

 

 

 

 

Steam Coil, Out (MPT)

 

1...11/2

 

 

 

 

1...11/2

 

 

 

 

 

Hot Water Coil, In (MPT)

 

1...11/

2

 

1...11/

 

 

 

 

 

 

 

1...2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Hot Water Coil, Out (MPT)

 

1...11/

 

2

 

 

 

 

 

 

 

1...2

 

 

 

 

 

 

2

 

1...11/

 

 

 

 

 

 

 

 

 

 

 

 

Condensate (PVC)

 

 

 

 

 

2

 

1...11/

ODM/1 IDF

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4

 

 

 

 

 

 

 

 

 

 

 

FILTERS

 

 

 

 

 

 

Throwaway — Factory Supplied

 

 

 

 

 

Quantity...Size

 

4...406 x 610 x 51

 

4...406 x 508 x 51

 

4...508 x 610 x 51

 

 

 

 

 

 

 

 

4...406 x 610 x 51

 

4...508 x 635 x 51

 

Access Location

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Either Side

 

 

 

 

 

 

LEGEND

DX — Direct Expansion

TXV — Thermostatic Expansion Valve *Units are shipped without refrigerant charge.

6

Table 1E — 40RMQ Physical Data, SI — Heat Pump Units

UNIT 40RMQ

008

 

 

012

 

016

 

024

 

028

 

NOMINAL CAPACITY (kW)

26

 

 

35

 

52

 

70

 

87

 

OPERATING WEIGHT (kg)

 

 

 

 

 

 

 

 

 

 

 

 

 

Base Unit with TXV

175

 

 

194

 

323

 

326

 

477

 

Plenum

80

 

 

80

 

102

 

44

 

44

 

FANS

 

 

 

 

 

 

 

 

 

 

 

 

 

Qty...Diam. (mm)

1...381

 

 

1...381

 

2...381

 

2...381

 

2...457

 

Nominal Airflow (L/s)

1604

 

 

1888

 

2831

 

3775

 

4719

 

Airflow Range (L/s)

1203-2006

 

 

1416-2360

 

2124-3539

 

2831-4719

 

3539-5899

Nominal Motor kW (Standard Motor)

 

 

 

 

 

 

 

 

 

 

 

 

 

208/230-1-60

1.79

 

 

 

 

 

 

208/230-3-60 and 460-3-60

1.79

 

 

1.79

 

2.76

 

3.73

 

5.60

 

575-3-60

1.49

 

 

1.49

 

2.24

 

3.73

 

5.60

 

230-3-50, 400-3-50

1.79

 

 

2.16

 

2.16

 

3.73

 

5.60

 

Motor Speed (r/s)

 

 

 

 

 

 

 

 

 

 

 

 

 

208/230-1-60

28.8

 

 

 

 

 

 

208/230-3-60 and 460-3-60

28.8

 

 

28.8

 

28.8

 

29.1

 

29.1

 

575-3-60

28.8

 

 

28.8

 

28.8

 

29.1

 

29.3

 

230-3-50, 400-3-50

23.8

 

 

23.8

 

23.8

 

23.8

 

23.8

 

REFRIGERANT

 

 

 

 

 

R-22

 

 

 

 

 

 

 

Operating charge (kg)

1.36

 

 

0.91/0.91

 

1.36/1.36

 

1.59/1.59

 

2.04/2.04

 

 

 

 

 

 

 

(approx per circuit)*

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

DIRECT-EXPANSION COIL

 

 

 

Enhanced Copper Tubes, Aluminum Sine-Wave Fins

 

 

 

Max Working Pressure (kPag)

 

 

 

 

2999

 

 

 

 

 

 

 

Face Area (sq m)

0.77

 

 

0.93

 

1.85

 

1.85

 

2.30

 

 

 

 

 

 

No. of Splits

1

 

 

2

 

2

 

2

 

 

2

 

No. of Circuits per Split

15

 

 

9

 

18

 

18

 

24/16

 

Split Type...Percentage

 

 

 

 

Face...50/50

 

 

 

 

 

Face...60/40

Rows...Fins/m

3...591

 

 

4...591

 

4...591

 

4...591

 

4...591

 

 

 

 

 

 

STEAM COIL

 

 

 

 

 

 

 

 

 

 

 

 

 

Max Working Pressure (kPag at 126 C)

 

 

 

 

138

 

 

 

 

 

 

 

Total Face Area (sq m)

0.62

 

 

0.62

 

1.24

 

1.24

 

1.39

 

 

 

 

 

 

Rows...Fins/m

1...355

 

 

1...355

 

1...394

 

1...394

 

1...394

 

HOT WATER COIL

 

 

 

 

 

 

 

 

 

 

 

 

 

Max Working Pressure (kPag)

 

 

 

 

1034

 

 

 

 

 

 

 

Total Face Area (sq m)

0.62

 

 

0.62

 

1.24

 

1.24

 

1.39

 

 

 

 

 

 

Rows...Fins/m

2...335

 

 

2...335

 

2...335

 

2...335

 

2...493

 

Water Volume

 

 

 

 

 

 

 

 

 

 

 

 

 

(L)

 

31.4

 

 

52.6

 

 

 

(m3)

 

0.031

 

 

0.052

 

 

 

PIPING CONNECTIONS,

 

 

 

 

 

 

 

 

 

 

 

 

 

Quantity...Size (in.)

1...11/

 

 

2...11/

 

2...11/

 

 

 

2...13/

 

DX Coil — Vapor (ODF)

 

 

 

 

 

 

8

 

 

 

 

 

 

8

 

 

8

 

 

8

 

 

 

 

DX Coil — Liquid Refrigerant (ODF)

1...5/

 

 

2...5/

 

 

2...5/

8

 

 

 

 

Steam Coil, In (MPT)

8

 

 

8

 

 

 

 

 

 

 

 

1...21/

 

 

1...21/

 

 

1...21/

2

 

 

 

Steam Coil, Out (MPT)

2

 

 

2

 

 

1...11/

 

 

 

1...11/

 

 

1...11/

 

 

2

 

 

 

Hot Water Coil, In (MPT)

2

 

 

2

 

 

1...2

 

 

 

 

1...11/

 

 

1...11/

 

 

 

 

 

 

 

Hot Water Coil, Out (MPT)

2

 

 

2

 

 

1...2

 

 

 

 

 

1...11/

 

 

1...11/

 

 

 

 

 

 

 

Condensate (Male PVC)

2

 

 

2

 

1...11/ ODM/1 IDF

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4

 

 

 

 

 

 

 

FILTERS

 

 

 

Throwaway — Factory Supplied

 

 

 

 

 

Quantity...Size

4...406 x 610 x 51

 

4...406 x 508 x 51

 

4...406 x 610 x 51

 

4...406 x 610 x 51

 

 

 

 

 

4...406 x 610 x 51

 

4...406 x 508 x 51

 

4...508 x 635 x 51

Access Location

 

 

 

 

 

 

 

 

 

 

Either Side

 

 

 

 

 

Right or

 

Left Side

 

LEGEND

DX — Direct Expansion

TXV — Thermostatic Expansion Valve *Units are shipped without refrigerant charge.

7

Table 1F — 40RMS Physical Data, SI — Chilled Water Units

UNIT 40RMS

008

 

 

010

 

012

 

014

 

 

016

 

024

 

028

 

034

NOMINAL CAPACITY (kW)

26

 

 

29

 

35

 

43

 

 

52

 

70

 

87

 

105

OPERATING WEIGHT (kg)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Base Unit

177

 

 

177

 

177

 

300

 

 

307

 

310

 

469

 

473

Plenum

80

 

 

80

 

80

 

102

 

 

102

 

102

 

148

 

148

FANS

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Qty...Diam. (mm)

1...381

 

1...381

 

1...381

 

2...381

 

 

2...381

 

2...381

 

2...457

 

2...457

Nominal Airflow (L/s)

1416

 

 

1605

 

1888

 

2360

 

 

2831

 

3775

 

4719

 

5663

Airflow Range (L/s)

1062-1770

1204-2006

 

1416-2360

 

1770-2949

 

 

2124-3539

 

2831-4719

 

3539-5899

 

4247-7079

Nominal Motor kW

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(Standard Motor)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

208/230-1-60

1.79

 

 

1.79

 

 

 

 

 

 

 

208/230-3-60, 460-3-60

1.79

 

 

1.79

 

1.79

 

1.79

 

 

2.76

 

3.73

 

5.60

 

7.46

575-3-60

1.49

 

 

1.49

 

1.49

 

1.49

 

 

2.24

 

3.73

 

5.60

 

7.46

230-3-50, 400-3-50

1.79

 

 

1.79

 

2.16

 

2.16

 

 

2.16

 

3.73

 

5.60

 

7.46

Motor Speed (r/s)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

208/230-1-60

28.8

 

 

28.8

 

 

 

 

 

 

 

208/230-3-60, 460-3-60

28.8

 

 

28.8

 

28.8

 

28.8

 

 

28.8

 

29.1

 

29.1

 

29.1

575-3-60

28.8

 

 

28.8

 

28.8

 

28.8

 

 

28.8

 

29.1

 

29.3

 

29.3

230-3-50, 400-3-50

23.8

 

 

23.8

 

23.8

 

23.8

 

 

23.8

 

23.8

 

23.8

 

23.8

CHILLED WATER COIL

 

 

 

 

 

Enhanced Copper Tubes, Aluminum Sine-Waves

 

 

 

 

Max Working Pressure (kPag)

 

 

 

 

 

 

2999

 

 

 

 

 

 

Face Area (sq m) — Upper

0.77

 

 

0.84

 

0.91

 

0.77

 

 

0.77

 

1.02

 

1.15

 

1.44

 

 

 

 

 

 

 

 

Face Area (sq m) — Lower

 

 

 

 

0.51

 

 

0.77

 

0.77

 

1.15

 

1.15

Rows...Fins/m

3...591

 

3...591

 

3...591

 

3...591

 

 

3...591

 

3...591

 

3...591

 

3...591

STEAM COIL

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Max Working Pressure

 

 

 

 

 

 

 

 

138

 

 

 

 

 

 

(kPag at 126 C)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Total Face Area (sq m)

0.62

 

 

0.62

 

0.62

 

1.24

 

 

1.24

 

1.24

 

1.39

 

1.39

 

 

 

 

 

 

 

 

Rows...Fins/m

1...355

 

1...355

 

1...355

 

1...355

 

 

1...394

 

1...394

 

1...394

 

1...394

HOT WATER COIL

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Max Working Pressure (kPag)

 

 

 

 

 

 

1034

 

 

 

 

 

 

Total Face Area (sq m)

0.62

 

 

0.62

 

0.62

 

1.24

 

 

1.24

 

1.24

 

1.39

 

1.39

 

 

 

 

 

 

 

 

Rows...Fins/m

2...335

 

2...335

 

2...335

 

2...335

 

 

2...335

 

2...335

 

2...493

 

2...493

Water Volume

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(L)

 

 

 

31.4

 

 

 

 

52.6

 

 

 

54.1

(m3)

 

 

 

0.031

 

 

 

 

0.052

 

 

 

0.054

PIPING CONNECTIONS,

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Quantity...Size (in.)

1...13/

 

1...13/

 

2...13/

 

 

 

 

 

 

 

 

 

 

 

Chilled Water — In

 

 

 

2...13/ ODM

 

 

2...13/ ODM

 

2...13/ ODM

 

2...21/ ODM

 

2...21/ ODM

8

 

 

8

 

8

 

 

 

 

 

 

 

ODF

 

 

ODF

 

ODF

 

8

 

 

8

 

8

 

8

 

8

Chilled Water — Out

1...13/

 

1...13/

 

2...13/

 

2...13/ ODM

 

 

2...13/ ODM

 

2...13/ ODM

 

2...21/ ODM

 

2...21/ ODM

8

 

 

8

 

8

 

 

 

 

 

 

 

ODF

1...21/

ODF

 

ODF

 

8

 

 

8

 

8

 

8

 

8

Steam Coil, In (MPT)

 

2

 

 

 

 

 

 

1...

 

21/

 

 

 

 

Steam Coil, Out (MPT)

 

1...11/

 

 

 

 

 

 

 

2

 

 

 

 

 

2

 

 

 

 

1...11/

 

 

 

 

Hot Water Coil, In (MPT)

 

1...11/

 

1...11/

 

 

 

 

 

2

 

 

 

 

 

2

 

 

 

 

 

 

1...2

 

 

 

 

Hot Water Coil, Out (MPT)

 

1...11/

 

2

 

 

 

 

 

1...2

 

 

 

 

 

2

 

1...11/

 

 

 

 

 

 

 

 

 

Condensate (PVC)

 

 

 

 

2

 

1...11/4 ODM/1 IDF

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FILTERS

 

 

 

 

 

 

Throwaway — Factory Supplied

 

 

 

 

Quantity...Size (mm)

 

4...406 x 610 x 51

 

4...406 x 508 x 51

 

4...508 x 610 x 51

 

 

 

 

 

 

4...406 x 610 x 51

 

4...508 x 635 x 51

Access Location

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Either Side

 

 

 

 

 

 

8

LEGEND

TXV — Thermostatic Expansion Valve

NOTES:

1.

Dimensions in [ ] are in millimeters.

2.

 

 

Direction of airflow.

 

 

 

 

3.

Recommended clearance:

 

• Rear: 3 in. (76 mm)

 

• Front: 2 ft, 6 in. (762 mm)

 

• Right Side: 2 ft, 6 in. (762 mm)

 

• Left Side: 2 ft, 6 in. (762 mm)

 

• Local codes or jurisdiction may prevail.

4.

Liquid piping not supplied by Carrier.

5.

Duct flange is factory supplied and field

 

installed.

6.

40RMS units may require alternate or addi-

 

tional field-fabricated piping access holes.

UNIT

UNIT WEIGHT

lb (kg)

 

40RM007

381 (173)

40RM008

385 (175)

40RM012

405 (184)

40RMQ008

385 (175)

40RMQ012

427 (194)

40RMS008

390 (177)

40RMS010

391 (177)

40RMS012

391 (177)

Fig. 1A — Dimensions — Sizes 007-012

9

LEGEND

TXV — Thermostatic Expansion Valve

NOTES:

1.

Dimensions in [ ] are in millimeters.

2.

 

 

Direction of airflow.

 

 

 

 

3. Recommended clearance:

• Rear: 3 in. (76 mm)

• Front: 2 ft, 6 in. (762 mm)

• Right Side: 2 ft, 6 in. (762 mm)

• Left Side: 2 ft, 6 in. (762 mm)

• Local codes or jurisdiction may prevail.

4. Liquid piping not supplied by Carrier.

5. Duct flange is factory-supplied and field-installed.

6. 40RMQ016,024 and 40RMS units may require alternate or additional fieldfabricated piping access holes.

UNIT

UNIT WEIGHT

lb (kg)

 

40RM014

670 (304)

40RM016

685 (311)

40RM024

690 (313)

40RMQ016

713 (323)

40RMQ024

720 (326)

40RMS014

661 (300)

40RMS016

677 (307)

40RMS024

683 (310)

Fig. 1B — Dimensions — Sizes 014-024

10

Carrier 40RMS008-034, 40RMQ008-028, 40RM007-034 User Manual

LEGEND

TXV — Thermostatic Expansion Valve

NOTES:

 

 

 

 

 

1.

Dimensions in [

] are in millimeters.

2.

 

 

 

Direction of airflow.

 

 

 

 

 

 

 

 

 

 

 

 

3.

Recommended clearance:

 

 

 

 

• Rear: 3 in. (76 mm)

 

 

 

 

 

• Front: 2 ft, 6 in. (762 mm)

 

 

 

 

• Right Side: 2 ft, 6 in. (762 mm)

 

 

 

• Left Side: 2 ft, 6 in. (762 mm)

 

 

 

• Local codes or jurisdiction may prevail.

4.

Liquid piping not supplied by Carrier.

5.

Duct flange is

factory-supplied and

 

field-installed.

 

 

 

 

 

6.

40RMQ028 and 40RMS may require

 

alternate or additional field fabricated pip-

 

ing access holes.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

UNIT

UNIT WEIGHT

 

 

 

 

 

lb (kg)

 

 

 

 

 

 

 

 

 

 

 

40RM028

 

1020

(463)

 

 

 

 

 

40RM034

 

1030

(467)

 

 

 

 

 

40RMQ028

 

1050

(477)

 

 

 

 

 

40RMS028

 

1035

(469)

 

 

 

 

 

40RMS034

 

1042

(473)

 

Fig. 1C — Dimensions — Sizes 028,034

11

40RM – 016 – – B 5 0 1 GC

40RM – Commercial Packaged

Air Handler

Cooling Coil

– – Direct Expansion

Q – Direct Expansion for Heat Pump Duty S – Chilled Water

Nominal Capacity – Tons (kW)

007

6 (21)

016

15

(52)

008

7-1/2 (26)

024

20

(70)

010

8-1/2 (29)

028

25

(87)

012

10 (35)

034

30

(105)

014

12-1/2 (43)

 

 

 

Not Used

Expansion Device

– – None (40RMS)

B – Thermostatic Expansion Valves (40RM, 40RMQ) H – TXV with High Capacity, 4 Row Coil

Voltage Designation (V-Ph-Hz)

 

 

1

575-3-60

8 –

230-3-50

3

208/230-1-60

9 –

400-3-50

 

(007-010 sizes only)

 

 

5

208/230-3-60

 

 

6208/230/460-3-60 (all sizes 007-014; size 016 except YC and WD options)

460-3-60 (sizes 016 with YC or WD options and all size 024-034 units)

LEGEND

TXV — Thermostat Expansion Valve

*YC and WD option codes for all 034 size units and 008, 010 size units with 208/230-1-60 power designate standard motor and high-static drive.

NOTE: See the following table for the sizes available for each unit.

UNIT

007

008

010

012

014

016

024

028

034

40RM

X

X

 

X

X

X

X

X

X

40RMQ

 

X

 

X

 

X

X

X

 

40RMS

 

X

X

X

X

X

X

X

X

Factory-Installed Options

GC – Unpainted, Standard Motor,

and Standard Drive

HC – Unpainted, Standard Motor, and Medium-Static Drive

(Not available for 60 Hz 028 size or 50 Hz 016-028 sizes)

TC – Unpainted, Alternate Motor, and Medium-Static Drive (60 Hz 028 size and

50 Hz 016-028 sizes)

YC – Unpainted, Alternate Motor, and High-Static Drive*

ED – Painted, Standard Motor, and Standard Drive

FD – Painted, Standard Motor, and

Medium-Static Drive

(Not available for 60 Hz 028 size or 50 Hz 016-028 sizes)

RD – Painted, Alternate Motor, and

Medium-Static Drive (60 Hz 028 size and 50 Hz 016-028 sizes)

WD – Painted, Alternate Motor, and High-Static Drive*

Packaging

1 – Standard Domestic

3 – Standard Export

Revision Number

0 – Original

Fig. 2 — Model Number Nomenclature

LEGEND

TXV — Thermostatic Expansion Valve

Fig. 3 — Foam Block Location

12

Unit Positioning — The unit can be mounted on the floor for vertical application with return air entering the face of the unit and supply air discharging vertically through the top of the unit. The unit can also be applied in a horizontal arrangement with return air entering horizontally and the supply air discharging horizontally. When applying the unit in a horizontal arrangement, ensure the condensate drain pan is located at the bottom center of the unit for adequate condensate disposal. See Fig. 4 for condensate connections for each unit position.

Typical positioning and alternate return air locations are shown in Fig. 4. Alternate return air locations can be used by moving the unit panel from the alternate return air location to the standard return air location. Refer to overhead suspension accessory drawing (Fig. 5) for preferred suspension technique. The unit needs support underneath to prevent sagging.

IMPORTANT: Do NOT attempt to install unit with return air entering top panel of unit. Condensate will not drain from unit.

Unit Isolation — Where extremely quiet operation is essential, install isolators between floor and base of unit, or between ceiling and top section of unit.

Be sure that unit is level and adequately supported. Use channels at front and sides of unit for reference points when leveling.

Refrigerant and Chilled Water Piping Access — The 40RM Series units come with standard knockouts for refrigerant and chilled water piping. These knockouts are located on both sides of the unit for installation flexibility. The standard knockouts provide sufficient access to the unit’s coils for all 40RM and some 40RMQ units, however, for 40RMQ016,028 and 40RMS units, additional holes must be field-fabricated to accommodate the piping. See Fig. 6 for the positions and dimensions of the additional access holes required for these units, including hole diameters and drilling dimensions. Recommended access hole use is also listed for all units. Note that Fig. 6 shows the access holes on the controlbox side of the unit; this is the side of the unit with the coil headers, so it is used most often for piping access.

IMPORTANT: Do not bury refrigerant piping underground.

Refrigerant Piping — See Tables 1A, 1B, 1D, 1E for refrigerant pipe connection sizes. For ease in brazing, it is recommended that all internal solder joints be made before unit is placed in final position.

The 40RM and 40RMQ direct-expansion units have internal factory-installed thermostatic expansion valves (TXVs), distributors, and nozzles for use with R-22. See Table 2 for part numbers. Knockouts are provided in the unit corner posts for 40RM and 40RMQ008 and 012 refrigerant piping. The 40RMQ016,024 and 028 units requires additional fieldfabricated piping access holes. See Fig. 6, which also lists recommended knockouts and access holes to use for each 40RM and 40RMQ unit size. Recommended fittings are listed in Table 3.

The sensor bulb capillary tubes must be routed from the TXVs inside the unit through one of the piping access holes. Clamp the TXV sensor bulb on a vertical portion of the suction line, outside the unit. See Fig. 7.

NOTE: Be sure to remove the styrofoam shipping pad from the TXV. Verify that it has been removed. See Fig. 3.

IMPORTANT: Never attach the sensor to the suction manifold. Do NOT mount the sensor on a trapped portion of the suction line.

LEGEND

Accessory Line

Alternate Air Intake and Discharge

Air Intake and Discharge

Fig. 4 — Typical Unit Positioning

The 40RM Series evaporator coils have a face-split design. Ensure that lower circuit of coil is first on/last off when connected to the condensing unit and/or system controls. See Fig. 8.

External TXV equalizer connections are provided and factory-brazed into the coil suction manifolds.

If suction line must be horizontal, clamp bulb to suction line at least 45 degrees above bottom, at approximately the 4 o’clock or 8 o’clock position. See Fig. 9.

NOTE: The 40RMQ units are supplied with factory-installed thermostatic expansion valves and check valve bypasses. No extra piping connections or kits are required to install the 40RMQ with a 38AQ, 38ARQ, or 38AQS condensing unit in a heat pump system, however, some field-supplied components may be required. See the following two sections.

HEAT PUMP SYSTEM PIPING — Addition of a liquid solenoid valve (LLSV) is recommended. The LLSV must be a bi-flow type suited for use in heat pump systems. Refer to the 38AQ, ARQ, AQS literature for recommended component part numbers. Wire the solenoid valve in parallel with the compressor contactor coil.

The LLSV must be installed at the outdoor unit with the flow arrow pointed toward the outdoor unit (in-flow direction for the heating mode.)

38ARQ DUPLEX/40RMQ024 HEAT PUMP SYSTEM PIPING — Two 38ARQ012 heat pump condensing units may be connected in a duplex arrangement with the 40RMQ024. See Fig. 10. Ensure that the lower circuit of the 40RMQ coil is the first on/last off by connecting to the “A” condensing unit and by configuring the controls so that the “A” condensing unit is the first on/last off.

38ARQ012/38AQS016 DUPLEX/40RMQ028 HEAT PUMP SYSTEM PIPING — One 38ARQ012 and one 38AQS016 heat pump condensing unit may be connected in a duplex arrangement with the 40RMQ028. See Fig. 10. The 40RMQ028 has a 60/40 face split coil. Ensure that the larger coil section (connection “B”, Fig. 8) is connected to the 38QAS016 and the smaller coil section is connected to the 38AQS012. In addition, ensure that the lower circuit of the 40RMQ coil is the first on/last off by connecting to the “A” condensing unit and by configuring (see 38ARQ,AQS installation instructions for more information) the controls so that the “A” condensing unit is the first on/last off.

FILTER DRIER REQUIREMENTS FOR HEAT PUMP SYSTEMS — The 38ARQ and 38AQS units do not include filter driers. Filter driers must be field-supplied and fieldinstalled. The filter driers used with these systems must be bi-flow types suited for use in heat pump applications. Refer to the 38AQ,ARQ,AQS literature for recommended component part numbers. See Fig. 11 for filter drier quantity and location information.

13

OVERHEAD SUSPENSION ACCESSORY

UNIT SIZES 007-012

UNIT SIZES 014-024

UNIT SIZES 028,034

NOTE: Dimensions in [ ] are millimeters.

Fig. 5 — Preferred Suspension Technique

14

 

USE HOLE

 

FIELD-FABRICATED HOLE DIAMETERS,

 

FIELD-FABRICATED HOLE POSITION

UNIT

 

 

 

 

 

in. (mm)

 

 

 

 

DIMENSIONS, in. (mm)

 

NUMBERS

 

 

 

 

 

 

 

 

 

 

 

No. 5

No. 6

No. 7

No. 8

 

A

B

C

D

 

 

 

40RM007,008

1, 3

 

 

 

 

 

 

 

40RMQ008

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

40RM012-034

1, 2, 3, 4

 

 

 

 

 

 

 

40RMQ012

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

40RMS008-012

4, 5

13/

4

(44.5)

 

 

 

 

6.25 (158.8)

40RMS014-024

4, 5, 6, 7

13/

4

(44.5)

13/

4

(44.5)

13/

4

(44.5)

3.0

(76.2)

6.0 (152.4)

10.5 (266.7)

40RMQ016,024,028

3*, 5, 6, 7

11/

8

(28.6)

11/

8

(28.6)

13/

4

(44.5)

3.25

(82.6)

6.125 (155.6)

10.38 (263.7)

40RMS028,034

5, 6, 7, 8

21/

2

(63.5)

21/

2

(63.5)

21/

2

(63.5)

21/ (63.5)

6.0

(152.4)

9.625 (244.5)

13.38 (339.9)

17.0 (431.8)

 

 

 

 

 

 

 

 

2

 

 

 

 

 

*Must be enlarged from 11/8 in. to 13/4 inches.

NOTE: Access hole knockouts 1-4 are factory-supplied.

Fig. 6 — Refrigerant and Chilled Water Piping Access Holes

LEGEND

TXV — Thermostatic Expansion Valve

NOTE: Component location arrangement shown for field installation of sight glasses, solenoid valves, filter driers, and TXV sensing bulbs. The TXVs and equalizer lines are factory installed.

Fig. 7 — Face-Split Coil Suction and

Liquid Line Piping (Typical)

FIRST ON/LAST OFF = B

VERTICAL INSTALLATION

FIRST ON/LAST OFF = A

HORIZONTAL INSTALLATION

Fig. 8 — Typical Evaporator Coil Connections

(40RM, 40RMQ)

15