Carrier 39L User Manual

0 (0)
With Product Integrated Controls (PIC)
Installation, Operation, and
Start-Up Instructions
CONTENTS
Page
SAFETY CONSIDERATIONS ...................2
GENERAL ...................................2
INSTALLATION .............................2-64
Service Area Requirements ...................2
• REMOTE CONTROL BOX CONDENSATE PREVENTION
Make Electrical Connections ..................3
Variable Frequency Drives ...................38
Water Valve Assemblies .....................38
• VALVE WIRING
Duct Static Pressure Probe (VAV Units) ......39
Space Temperature Sensor ..................40
Outdoor-Air Temperature Sensor .............42
Mixed-Air Temperature Sensor ...............42
• CONTROL RANGES
Supply-Air Temperature Sensor ..............44
Return-Air Temperature Sensor ..............44
Heat Interlock Relay .........................45
Fan Relay ..................................45
Wall-Mounted Relative Humidity Sensor ......46
Duct-Mounted Relative Humidity Sensor ......47
• LOCATION FOR OUTSIDE AIR RELATIVE HUMIDITY
• LOCATION FOR RETURN AIR RELATIVE HUMIDITY
Airflow Switch ..............................48
Low-Temperature Thermostat ................48
Filter Status Switch .........................49
High-Pressure Switch .......................49
Air Quality Sensors .........................49
Constant Outside Air (OAC) Control ..........50
• PROBE INSTALLATION
• OAC CALIBRATION
• USING OAVP VALUES TO DETERMINE DUCT AIRFLOW
• FIELD-SUPPLIED OR HIGH-VELOCITY PRESSURE TRANSDUCERS
• REMOTE LOCAL INTERFACE DEVICE (HSIO)
• RETURN-AIR TEMPERATURE SENSOR, OUTDOOR-AIR TEMPERATURE SENSOR, ENTHALPY SWITCH, AND MIXED-AIR TEMPERATURE SENSOR
• SPACE TEMPERATURE SENSOR (SPT)
• DAMPER ACTUATORS
• SMOKE CONTROL OPTION
• ANALOG DEVICE FOR ANALOG OUTPUT TEMPERATURE CONTROL
39L,NX
Central Station Air-Handling Units
• DEVICE UNDER DISCRETE OUTPUT TEMPERATURE CONTROL
• DISCRETE OUTPUT DEVICE UNDER TIMECLOCK CONTROL
• HUMIDIFICATION DEVICES
• AIR QUALITY SENSOR
• OUTSIDE AIR VELOCITY PRESSURE (OAVP) SENSOR
• FAN VOLUME CONTROL
• ELECTRIC HEATER
• CARRIER COMFORT NETWORK INTERFACE
• OUTDOOR-AIR THERMOSTAT
CONTROL SYSTEM .......................64-68 Processor (PSIO Master) and Option (PSIO Slave)
Modules .................................65
Relay (DSIO) Module .......................65
Local Interface Device (HSIO) ...............67
CONTROL OPERATION ...................69-91
Accessing Functions and Subfunctions .....69
Display Functions ..........................69
• SUMMARY DISPLAY
• STATUS FUNCTION
• HISTORY FUNCTION
• TEST FUNCTION
Programming Functions ...................81
• SERVICE FUNCTION
• SET POINT FUNCTION
• SCHEDULE FUNCTION
CONTROL OPERATING SEQUENCE .......92-102 Constant Volume and Variable Air
Volume Units ............................92
Constant Volume Units Only ................96
Variable Air Volume Units Only .............99
START-UP ..............................103-108
Initial Check ..............................103
Quick Test ................................103
Electronic Valve Actuator Field Test ........108
CONTROL LOOP CHECKOUT ............108,109
To Check Operation of Analog Outputs .....108
VALVE TROUBLESHOOTING .............109-111
General ...................................109
1
⁄2-in. Through 11⁄4-in. Electric Hot Water/Steam
All
Valve Assemblies .......................109 All 11⁄2-in. Through 3-in. Valve Assemblies ..110
CONTROL MODULE
TROUBLESHOOTING ..................111,112
General ...................................111
Module Replacement (PSIO, DSIO) .........112
UNIT TROUBLESHOOTING ...............113-115
METRIC CONVERSION CHART .............116
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 3 Tab 1b
PC 201 Catalog No. 533-913 Printed in U.S.A. Form 39L,NX-2SI Pg 1 3-96 Replaces: 39L,NX-1SI
IMPORTANT: This equipment generates, uses, and can radiate radio frequency energy and if not installed and used in accordance with these instructions may cause radio interference. It has been tested and found to com­ply with the limits of a Class A computing device as defined by FCC regulations, Subpart J of Part 15, which are designed to provide reasonable protection against such interference when operated in a commercial environment.
SAFETY CONSIDERATIONS
Installation and start-up of air-conditioning equipment can be hazardous due to system pressure and electrical compo­nents. Only trained and qualified service personnel should install, start up, or service air-conditioning equipment.
When working on air-conditioning equipment, observe pre­cautions in the literature, tags and labels attached to the unit, and other safety precautions that may apply.
Follow all safety codes, including ANSI (American National Standards Institute) Z223.1 (latest version). Wear safety glasses and work gloves.
Disconnect all power to the unit before performing main­tenance or service. Unit may automatically start if power is not disconnected. Electrical shock and personal in­jury could result.
Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance.
GENERAL
The Product Integrated Control (PIC) option is available for 39L and 39NX indoor units with a draw-thru configu­ration. The PIC control box can be supplied as part of a dedi­cated PIC section; it is factory-installed and wired and has the same hand (orientation) as the fan section. The control box can also be shipped separately for remote mounting with­out a PIC section. For the remote control box option, all con­nections from the control box to the unit are made to a junc­tion box in the unit’s fan section.
The control box includes electronic modules, fuses, re­lays, transformers, terminal blocks, low-limit air tempera­ture protection (optional), static pressure transducer (VAV
[Variable Air Volume] units only) and high-pressure switch (VAV units). An ON/OFF switch is included to shut off the power to the control box.
PIC environmental limitations are as follows:
Shipping Temperature — −20 to 165 F Shipping Humidity — 10 to 95% Operating Temperature — 32 to 125 F Operating Humidity — 30 to 90%
INSTALLATION
Follow all basic installation instructions for 39L or 39NX units as described in the 39L or 39NX Installation, Start-Up, and Service Instructions shipped with the unit. To verify the PIC and PIC option configurations according to the model numbers, see Fig. 1 and 2.
Leave protective coverings on the unit until it is installed inside and protected from the elements, construction debris, and dirt.
Use one of the keys provided in the 39L or 39NX instal­lation packet (located in fan section) to open the control box door.Visually inspect all components and wiring for any dam­age. Remove the valve assembly packages and the sensor packages from the fan section. For units with PIC sections, remove protective plastic caps from the bulkhead fittings (located on the top edge of the control box) and discard.
Verify that the 10.0 amp ON/OFF switch located on the PIC control box door is in the OFF position. Do not turn the
power supply on at this time.
NOTE: The 39NX and 39L air handlers are designed for in­door applications. Modified units are available for outdoor applications on pier or slab mounts (not curb mounts). Prod-
uct integrated controls are not available for outdoor appli­cations. Consult your Carrier sales representative for further
details.
ServiceArea Requirements — Article 110-16 of the
NEC (National Electrical Code) describes electrical instal­lation.All 39L and 39NX PIC installations must comply with the minimum clearances required for electrical installation as listed in Table 110-16(a) of the code. Make sure to pro­vide the necessary clearance from the PIC unit to any ad­joining wall. Refer to the base unit installation instructions for detailed dimensions for each unit section.
Remote Control Box Option — This option allows
the PIC control box to be mounted away from the unit; the remote control box (Fig. 3) must be wired to the supply fan section. Mount the remote control box assembly to the mechanical room wall near the unit using field-supplied Unistrutt metal framing or equivalent supports. The control box has 4 mounting holes in the back of the enclosure for this purpose.
2
Mount the remote control box as follows:
1. Loosen and remove the 4 nuts securing the control panel in the control box.
2. Remove the control panel from the box; set the panel and nuts aside for reassembly later.
3. Mount the control box to the Unistrutt support using field­supplied fasteners.
4. Locate, mark, and drill pilot holes on the top of the box for each of the following:
• Motor starter wiring
• Actuator and sensor wires to fan section junction box
• Supply power wires (ac)
• Valve wiring or tubing (water valves, field-supplied
sensors, or other devices)
5. Expand the pilot holes as required. Recommended sizes are as follows:
• Motor starter wiring —3⁄4in. (5 wires)
• Actuator and sensor wires to fan section junction
box —
3
⁄4in. to 1 in. (number of wires and hole di-
ameter determined by application)
1
• Supply power wires (ac) —
⁄2in. or3⁄4in.
• Valve wiring or tubing — size as required
Fan section panels are provided with pilot holes that can be drilled or punched to accomodate an electrical conduit for the remote control box wiring. Where possible, install the conduit in a panel that will not be removed, such as the discharge panel. See Fig. 4.
REMOTE CONTROL BOX CONDENSATE PREVEN­TION — When the remote control box is installed, precau­tions must be taken to prevent condensation from forming inside the junction box mounted in the unit’s supply fan sec­tion. Standard installation practice is to mount the remote control box adjacent to the air handling unit and then to en­close the Class II wiring in flexible conduit between the con­trol box and the junction box in the fan section.
The sheet metal housing of the control box is not airtight, therefore warm, moist air can migrate through the flexible conduit to the junction box in the fan section. Condensate can form inside the junction box and possibly on the termi­nal lugs.
To prevent moist air from migrating through the conduit, seal the control wires inside the conduit at the remote con­trol box enclosure. See Fig. 4. Use a nonconductive, non­hardening sealant. Permagum (manufactured by Schnee Morehead) or sealing compound, thumb grade (manufac­tured by Calgon), are acceptable materials.
MakeElectrical Connections — 39L and 39NX units
have internal control wiring for the operation of the PIC sec­tion and its control devices. The control system requires a dedicated 120 vac or 230 vac (50 or 60 Hz) power circuit capable of providing a minimum of 10 amps (but not greater than 20 amps) to the control box. The actual number of con­trols on one power source depends on the installation and power circuit requirements. Do not run PIC power wiring in the same conduit as sensor wiring or control wiring of field­installed devices.
IMPORTANT: To ease installation, control wiring is located on the service side of the unit with electrical connectors provided at all unit separation points. If a unit is separated into pieces for installation, rejoin all connectors in their original alpha-numeric sequence upon reassembly. Connectors for vertical fan sections that are shipped out of the normal operating position must also be joined at final assembly.
For units with an integral PIC section, all unit factory con­trol wiring is internal. Only a small number of wires must be field-installed. All internal wiring consists of plenum wires which enter the rear of the control box through sealed fit­tings. Control wiring is 18 to 20 gage, 2-conductor twisted pair.
The electrical power disconnect and fan motor starter are field-supplied and installed. Connections are provided in the control box to wire a field-supplied HOA (HANDS/OFF/ AUTOMATIC) switch. If an HOA switch is used, it must be field-installed in the supply and return fan motor starter cir­cuit. The factory-wired high-pressure switch (variable air vol­ume only) and low-temperature thermostat options are en­ergized when the supply fan circuit is powered.
See Fig. 5-7 for control box component arrangements and Fig. 8 for fan motor wiring. PIC input and output points are listed in Table 1. Consult the wiring diagram located in the control box or Fig. 9-12 for further details.
Power is present in the PIC control box in the motor starter circuit even when the dedicated power to the PIC control box is off.
The supply and return fan starter circuits are independent from each other. Either circuit and its related control box interface can have 24 vac, 120 vac, or 240 vac power.
All options that require a factory-installed transformer are fused with 3.2 amp fuses on the secondary of each transformer.
When the control box is shipped separately for remote mount­ing, all unit wiring terminates in a junction box located in the fan section. Refer to Fig. 12 for the applicable wiring diagram and Table 2 for junction box connections.
If the unit is provided with a factory-installed smoke con­trol option, refer to the section titled Field-Wiring Connec­tions, Smoke Control Option, page 54.
All PIC electrical components are UL (Underwriters’Labo­ratories) listed. The electronic modules are approved under UL HVACEquipment Standard 873. PIC units are listed and labeled by ETL (Engineering Testing Laboratory) to comply with UL Standard 1995 for heating and cooling units, and comply with NFPA (National Fire Protection Association) Standard 90A.
3
LEGEND
ABX — Air Blender AF Airfoil CV Constant Volume IGV — Inlet Guide Vanes FC Forward-Curved FMB — Filter Mixing Box MXB — Mixing Box PIC — Product Integrated Controls VAV — Variable Air Volume
*The cv capacity rating is the flow (gpm) through a valve at 1 psi pres-
sure drop.
Fig. 1 — Basic PIC Order Number
4
LEGEND
AF Airfoil CV Constant Volume DX Direct Expansion FC Forward-Curved FMB — Filter Mixing Box MXB — Mixing Box N.C. — Normally Closed N.O. — Normally Open PIC — Product Integrated Controls VAV — Variable Air Volume
*The cv capacity rating is the flow (gpm) through a
valve at 1 psi pressure drop.
Fig. 2 — PIC Option Order Number
5
NOTE: Dimensions in [ ] are in millimeters.
Fig. 3 — Control Box for Remote Mounting
Fig. 4 — Sealing Control Wiring in Flexible Conduit
6
LEGEND (Fig. 5-12, Table 2)
AFS Airflow Switch AO Analog Output AOTC — Analog Output Temperature Control AQ AQ C—Contactor CCW Counterclockwise CH Channel CR Control Relay CUST — Condensing Unit Status CV Constant Volume CW Clockwise CWV Chilled Water Valve DHH Duct High Humidity DO Discrete Output DOTC — Discrete Output Temperature Control DSIO Control Module, Electric Heat and/or DX DTCC — Discrete Time Clock Control DX Direct Expansion DXS DX Cooling Stage DXSD — Direct Expansion Cooling Shutdown EHS Electric Heaters ELEC — Electric ENT Enthalpy Switch EQUIP — Equipment EVAC — Smoke Evacuation Input EXD ExhaustAir Damper Actuator FLTS Filter Status Switch FSD Fire Shutdown Device FU Fuse GND Ground HIR Heat Interlock Relay HOA Hand-Off-Auto. Switch HPS High-Pressure Switch HSIO Keyboard and Display Module HT Heat HUM Humidifier HWV Hot Water Valve IGV Inlet Guide Vane Actuator LTT Low Temperature Thermostat MAD Mixed-Air Damper Actuator MAT Mixed-Air Temperature MPSIO — Master Processor Module
OAD Outdoor-Air Damper Actuator OARH — Outdoor-Air Relative Humidity OAT Outdoor-Air Temperature OAVP — Outdoor-Air Velocity Pressure
Air Quality Sensor, No. 1
1
Air Quality Sensor, No. 2
2
(Processor Module)
OT Outside-Air Thermostat PH Preheat PL Plug Assembly PRESS — Smoke Pressurization Input PSIO Processor Module PURG — Smoke Purge Input RAD Return-Air Damper Actuator RAT Return-Air Temperature RFAN Return Fan RFR Return Fan Relay RFVC Return Fan Volume Control RH Relative Humidity RVP Return Velocity Pressure SAT Supply-Air Temperature SF Fan Status Relay SFAN Supply Fan SFR Supply Fan Relay SMK Smoke SNB Snubber SP Static Pressure Transducer SPSIO — Slave Processor Module
SPT Space Temperature SVP Supply Velocity Pressure SW Switch TB Terminal Block Terminal TEMP Temperature TRAN Transformer VAV Variable Air Volume W/ With WO/ Without
(Option Module)
Marked Wire or Cable Terminal (Marked) Terminal (Unmarked)
Terminal Block Splice (Factory)
Splice (Field) Wiring Factory Wiring Field Control Wiring Field Power Option or Accessory Common Potential
NOTES:
1. Use copper conductors only.
2. Wire is in accordance with National Electrical Code (NEC).Forlocalcodes, replace original wires with 90 C wire or its equivalent.
3. Replace wires fromIGV, FLTS,MAT,SAT,OAD,RAD,andELEC HTwith 125 C plenum cable conductor as required.
4. Input channel numbers and points for configuration of the optional analog output temperature control (AOTC) follow:
CHANNEL SENSOR DESCRIPTION
1 SAT Supply-Air Temperature 2 OAT Outdoor-Air Temperature 3 MAT Mixed-Air Temperature 6 SPT Space-Air Temperature 7 RAT Return-Air Temperature
34 TEMP Preheat or Optional Carrier Sensor
5. Reference for wire markers, where ‘X’ represents a numeral:
X — Item number on wiring harness BX — Box wire CX — Cable KX — Accessory kit wire
7
ARRANGEMENT FOR SIZES 03 AND 06
ARRANGEMENT FOR SIZES 08 THROUGH 35
Fig. 5 — PIC Section Control Box Component Arrangements, 39L
8
Fig. 6 — PIC Section Control Box Component Arrangement, 39NX Sizes 07-21
9
Fig. 7 — PIC Section Control Box Component Arrangement, 39NX Sizes 26-92
10
Fig. 8 — Fan Motor Starter Circuit and PIC Control Wiring Interface — PIC Power for
Control Circuit From Dedicated Source
11
MODULE,
DEFAULT ADDRESS
PSIO (Processor) ADDRESS 1
PSIO (Option) ADDRESS 31
DSIO (Electric Heat) ADDRESS 19
DSIO (DX without Electric Heat) ADDRESS 19
DSIO (DX with Electric Heat) ADDRESS 49
Table 1 — Input and Output Points
INPUT
SAT AI 1 IGV* AO 13 OAT AI 2 MIXD AO, DO† 14 MAT AI 3 HWC AO 15 RH AI 4 CWC AO 16 LTT DI 5 SF DO 17 SPT AI 6 HIR* DO 18 RAT AI 7 — SP* AI 8 — AFS DI 9 — FLTS DI 10 — OARH AI 11 — ENT DI 12 — SVP* AI 31 RFVC* AO 43 RVP* AI 32 HUM1 AO, DO 44 DHH DI 33 HUM2 DO 45 TEMP AI 34 AOTC AO 46 PRES DI 35 DOTC DO 47 EVAC DI 36 DTCC DO 48 PURG DI 37 — FSD DI 38 — AQ1 AI 39 — AQ2 AI 40 — OAVP* AI 41 — METER DI 42 — — EHS1 DO 23 — EHS2 DO 24 — EHS3 DO 25 — EHS4 DO 26 — EHS5 DO 27 — EHS6 DO 28 — EHS7 DO 29 — EHS8 DO 30 CUST DI 19 DXS1 DO 23 DXSD DI 20 DXS2 DO 24 — DXS3 DO 25 — DXS4 DO 26 — DXS5 DO 27 — DXS6 DO 28 — DXS7 DO 29 — DXS8 DO 30 CUST DI 49 DXS1 DO 53 DXSD DI 50 DXS2 DO 54 — DXS3 DO 55 — DXS4 DO 56 — DXS5 DO 57 — DXS6 DO 58 — DXS7 DO 59 — DXS8 DO 60
INPUT
TYPE
CHANNEL
NUMBER
OUTPUT
OUTPUT
TYPE
CHANNEL
NUMBER
AFS Airflow Switch (Supply Fan AI Analog Input
AO Analog Output AOTC — Analog Output Temperature
AQ1, 2 — Air Quality Sensors 1, 2 CUST — Condensing Unit Status
CWC Chilled Water Coil DI Discrete Input DHH Duct High Humidity DO Discrete Output DOTC — Discrete Output Temperature
DTCC — Discrete Output Timeclock
*Available on VAV only. †Discrete output with two-position damper control.
Status Switch)
Control
(Outdoor Air Thermostat)
Control Control
LEGEND
DXS1-8 — Direct Expansion Cooling DXSD Direct Expansion Cooling EHS1-8 — Electric Heater Stages 1-8
ENT Enthalpy Switch EVAC Evacuation FLTS Filter Status Switch FSD Fire Shutdown HIR Heat Interlock Relay HWC Hot Water Coil HUM1, 2 — Humidity Stages 1, 2 IGV Inlet Guide Vanes LTT Low Temperature Thermostat
MAT Mixed-Air Temperature METER — Meter (Pulsed Dry-Contact
Stages 1-8 Shutdown
(also labelled FRZ)
Input)
12
MIXD — Mixed-Air Dampers OARH — Outdoor-Air Relative Humidity OAT Outdoor-Air Temperature OAVP — Outdoor-Air Velocity Pressure PRES — Pressurization PURG — Purge RAT Return-Air Temperature RFVC — Return Fan Volume Control RH Relative Humidity RVP Return Velocity Pressure SAT Supply-Air Temperature SF Supply Fan Relay SP Static Pressure SPT Space Temperature SVP Supply Velocity Pressure TEMP — Optional Temperature Input
13
Fig. 9 — Unit Wiring Schematic, 39L Sizes 03-35 (115 v, Typical)
14
Fig. 9 — Unit Wiring Schematic, 39L Sizes 03-35 (115 v, Typical) (cont)
15
Fig. 9 — Unit Wiring Schematic, 39L Sizes 03-35 (115 v, Typical) (cont)
Fig. 9 — Unit Wiring Schematic, 39L Sizes 03-35 (115 v, Typical) (cont)
16
Fig. 9 — Unit Wiring Schematic, 39L Sizes 03-35 (115 v, Typical) (cont)
17
Fig. 9 — Unit Wiring Schematic, 39L Sizes 03-35 (115 v, Typical) (cont)
18
19
Fig. 10 — Unit Wiring Schematic, 39NX Sizes 07-21 (115 v, Typical)
20
Fig. 10 — Unit Wiring Schematic, 39NX Sizes 07-21 (115 v, Typical) (cont)
21
Fig. 10 — Unit Wiring Schematic, 39NX Sizes 07-21 (115 v, Typical) (cont)
Fig. 10 — Unit Wiring Schematic, 39NX Sizes 07-21 (115 v, Typical) (cont)
22
Fig. 10 — Unit Wiring Schematic, 39NX Sizes 07-21 (115 v, Typical) (cont)
23
Fig. 10 — Unit Wiring Schematic, 39NX Sizes 07-21 (115 v, Typical) (cont)
24
25
Fig. 11 — Unit Wiring Schematic, 39NX Sizes 26-92 (115 v, Typical)
26
Fig. 11 — Unit Wiring Schematic, 39NX Sizes 26-92 (115 v, Typical) (cont)
27
Fig. 11 — Unit Wiring Schematic, 39NX Sizes 26-92 (115 v, Typical) (cont)
Fig. 11 — Unit Wiring Schematic, 39NX Sizes 26-92 (115 v, Typical) (cont)
28
Fig. 11 — Unit Wiring Schematic, 39NX Sizes 26-92 (115 v, Typical) (cont)
29
Fig. 11 — Unit Wiring Schematic, 39NX Sizes 26-92 (115 v, Typical) (cont)
30
Loading...
+ 86 hidden pages