Carrier 40MVC, 38MVQ, 40MVQ, 38MVC User Manual

0 (0)

38MVC/40MVC

38MVQ/40MVQ

Comfortt Series High---Wall Duct---Free Split System

Sizes 009 --- 024

Service Manual

TABLE OF CONTENTS

PAGE SAFETY CONSIDERATIONS . . . . . . . . . . . . . . . . . . . . . . . . . 1 STANDARD FEATURES AND ACCESSORIES . . . . . . . . . . . 2 SPECIFICATIONS - COOLING ONLY . . . . . . . . . . . . . . . . . . 3 SPECIFICATIONS - HEAT PUMP UNITS . . . . . . . . . . . . . . . 4 DIMENSIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 SERVICE VALVE LOCATIONS . . . . . . . . . . . . . . . . . . . . . . . . 5 CLEARANCES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 SYSTEM OPERATING ENVELOPE . . . . . . . . . . . . . . . . . . . . 7 ELECTRICAL DATA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 WIRING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 CONNECTION DIAGRAMS . . . . . . . . . . . . . . . . . . . . . . . . . . 9 WIRING DIAGRAMS . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 - 16 REFRIGERATION CYCLE DIAGRAM . . . . . . . . . . . . . . . . . 17 REFRIGERANT LINES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18 SYSTEM EVACUATION AND CHARGING . . . . . . . . . . . . . 19 CONTROL SYSTEM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20 SYSTEM SAFETIES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20 3 MINUTE TIME DELAY . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20 COMPRESSOR OVERCURRENT PROTECTION . . . . 20 - 21 SEQUENCE OF OPERATION . . . . . . . . . . . . . . . . . . . . . . . . 21 MODES OF OPERATION . . . . . . . . . . . . . . . . . . . . . . . . 22 - 24 TROUBLESHOOTING . . . . . . . . . . . . . . . . . . . . . . . . . . 25 - 37 APPENDIX . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38 - 43

SAFETY CONSIDERATIONS

Improper installation, adjustment, alteration, service, maintenance, or use can cause explosion, fire, electrical shock, or other conditions which may cause death, personal injury, or property damage. Consult a qualified installer, service agency, or your distributor or branch for information or assistance. The qualified installer or agency must use factory-authorized kits or accessories when modifying this product. Refer to the individual instructions packaged with the kits or accessories when installing.

Follow all safety codes. Wear safety glasses, protective clothing, and work gloves. Use quenching cloth for brazing operations. Have fire extinguisher available. Read these instructions thoroughly and follow all warnings or cautions included in literature and attached to the unit. Consult local building codes and National Electrical Code (NEC) for special requirements.

Recognize safety information. This is the safety-alert symbol !! When you see this symbol on the unit and in instructions or manuals, be alert to the potential for personal injury.

Understand these signal words: DANGER, WARNING, and CAUTION. These words are used with the safety-alert symbol. DANGER identifies the most serious hazards which will result in severe personal injury or death. WARNING signifies hazards which could result in personal injury or death. CAUTION is used to identify unsafe practices which may result in minor personal injury or product and property damage. NOTE is used to highlight suggestions which will result in enhanced installation, reliability, or operation.

!WARNING

ELECTRICAL SHOCK HAZARD

Failure to follow this warning could result in personal injury or death.

Before installing, modifying, or servicing system, main electrical disconnect switch must be in the OFF position. There may be more than 1 disconnect switch. Lock out and tag switch with a suitable warning label.

INTRODUCTION

Section 1 of this Service Manual provides the necessary information to service, repair, and maintain the EEZ family of Puron air conditioners and heat pumps. Section 2 of this manual is an appendix with data required to perform troubleshooting. Use the Table of Contents to locate a desired topic.

38/40MVC, MVQ

MODEL NUMBER NOMENCLATURE

INDOOR UNIT

40

MVC

018

---

 

 

 

Fan Coil Unit

 

 

Nominal Capacity

 

 

009 ---

3/4 Ton

Unit Type

012 ---

1 Ton

MVC ---

Cooling Only

018 ---

1---1/2 Ton

MVQ ---

Heat Pump

024 ---

2 Tons

OUTDOOR UNIT

38

MVC

018

---

Air---Cooled Condenser

 

Nominal Capacity

Unit Type

009

--- 3/4 Ton

012

--- 1

Ton

MVC --- Cooling Only

018

--- 1---1/2 Ton

MVQ --- Heat Pump

024

--- 2

Tons

3---

01

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Voltage

 

 

 

 

 

---

--- 30VDC

 

 

 

 

1

--- 115---

1---

60

 

 

 

3 ---

208/230---

1---

60

3---

01

 

 

 

 

 

 

 

 

Voltage

 

 

 

 

1---

115---

1---

60

 

 

3---

208/230---

1---

60

SERIAL NUMBER NOMENCLATURE

 

01

 

06

 

V

 

00001

 

Week of Manufacture

 

 

 

 

 

 

 

 

Serial Number

 

 

 

 

 

 

 

 

 

 

 

Year of Manufacture

Manufacturing Site

 

 

2

STANDARD FEATURES AND ACCESSORIES

Ease Of Installation

 

Mounting Brackets

S

Low Voltage Controls

S

Comfort Features

 

Microprocessor Controls

S

Wireless Remote Control

S

Automatic Air Sweep

S

Air Direction Control

S

Auto Restart Function

S

Cold Blow Protection On Heat Pumps

S

Turbo Mode On Sizes 9K and 12 K

S

Auto Changeover On Heat Pumps

S

Energy Saving Features

 

Sleep Mode

S

Stop/Start Timer

S

Safety And Reliability

 

3 Minute Time Delay For Compressor

S

Over Current Protection For Compressor

S

Indoor Coil Freeze Protection

S

Indoor Coil High Temperature Protection On Heat Pumps

S

Condenser High Temperature Protection On heat Pumps{

S

Accumulator On Heat Pumps

S

Ease Of Service And Maintenance

 

Cleanable Filters

S

Diagnostics

S

Liquid Line Pressure Taps

S

Suction And Discharge Pressure Taps (Sizes 18 and 24K)

S

Application Flexibility

 

Low Ambient Controls (---20˚F)

A

Condensate Pumps

A

Crankcase Heater

A

Wind Baffles

F

Warranty

 

5 ---Year Compressor Warranty

S

1 --- Parts Warranty

S

Compressor Extended Warranty Years 6 Thru 10

O

All Parts And Labor Years 2 Thru 5

O

All Parts And Labor Years 2 Thru 5, Compressor Years 6

O

Thru 10

 

{ Sizes 18k & 24k

 

Legend

 

S Standard

 

A Accessory

 

O Optional

 

F Field Fabricated

 

INDOOR UNITS

A07892

Fig. 1 – Condensate Pump

On high wall fan coils, the condensate pump has a lift capability of 18 ft (5.5 m) or the discharge side with the pump mounted in the fan coil or 6 ft (1.8 m) on the suction side if the pump must be remote mounted. The pump mounts inside the unit with quick plug-in connections, and is recommended when adequate drain line pitch cannot be provided, or when the condensate must move up to exit.

NOTE: An external 115v power source will be required to run the pump on unit sizes 9k and 12k.

OUTDOOR UNITS

LOW AMBIENT KIT

The kit controls condenser fan cycling using a pressure switch. It is specifically designed to control fan-motor cycles in response to saturated condensing pressure. This device maintains a constant saturated condensing temperature of 100 _F ± 10 _F (37.78_C ± -12.22 _C) at outdoor-air temperatures between 55 _F and -20 _F (12.78_C ± -12.22_C), and can be used on all outdoor units without changing the outdoor fan motor.

CRANKCASE HEATER

Available for units with rotary compressors. Heater clamps around compressor oil sump. Recommended for low-ambient applications on sizes 9, 12 , 18, 24 and long line applications.

38/40MVC, MVQ

3

SPECIFICATIONS - COOLING ONLY UNITS

 

 

 

System Model Number

53MVC009--- --- ---1

53MVC012--- --- ---1

 

53MVC012--- --- ---3

53MVC018--- --- ---3

 

 

System

System Voltage

115 V

115 V

 

208/230

208/230

 

 

Capacity (Btuh)

9000

12000

 

12000

18000

 

 

 

Control Voltage

0 --- 12 Pulse DC

0 --- 12 Pulse DC

 

0 --- 12 Pulse DC

Pulse DC

 

 

 

 

 

 

 

 

 

 

 

 

SEER

13.0

13.0

 

13.0

13.0

 

 

Refrigerant

Refrigerant Type

 

R---410A

 

 

 

Charge (lb)

2.3

2.9

 

3.0

4.4

 

 

 

Design Pressure (PSIG)

550

550

 

550

550

 

 

 

Metering Device

 

Capillary Tube in Outdoor Unit

 

 

 

 

 

 

 

 

 

 

 

Compressor

Type

 

Rotary

 

 

 

Model

EA82X1C---1FZDU1

EA108X1C---1FZDU1

 

PA108X1C---3FZDU

PA150X2CS---3KUU

 

 

 

 

 

 

 

Oil Charge (POE ---oz)

11.8

11.8

 

11.8

25.4

 

 

 

Capacitor

45µF/250VAC

45µF/250VAC

 

35µF/370VAC

40µF/370VAC

 

 

 

Rated Current (RLA)

7.5

9.9

 

5.2

7.3

MVQ

 

 

Locked Rotor Amp (LRA)

40

47

 

21

32.6

 

Outdoor Motor

Rpm/CFM

900/1060

900/1090

 

900/1120

840/1470

 

Diameter (in) .. No. of Blades

15.8 … 3

15.8 … 3

 

15.8 … 3

18.1 … 3

38/40MVC,

 

 

 

 

 

Motor (hp)

0.102

0.102

 

0.102

0.224

 

OutdoorCoil

Circuits

4

4

 

4

4

 

 

 

Capacitor

6.5µF/260VAC

6.5µF/260VAC

 

2.5µF/450VAC

3µF/450VAC

 

 

 

Face Area (sq. ft)

4.05

3.94

 

3.94

5.51

 

 

 

No. Rows

2

2

 

2

4

 

 

 

Fins per inch

17

17

 

17

18

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Motor

Motor Watts/HP

20/.034

20/.034

 

20/.034

25/.044

 

 

Rpm/Cfm (High)

1250/325

1270/425

 

1270/425

1070/630

 

 

 

 

 

 

Indoor

Rpm/Cfm (Medium)

1000/260

1100/365

 

1100/365

1000/570

 

 

Rpm/Cfm (Low)

800/190

1000/340

 

1000/340

960/500

 

 

 

 

 

 

 

Blower Diameter … Length (in)

3.84 … 25.87

4.17 … 25.2

 

4.17 … 25.2

4.21 … 37.6

 

 

Indoor

Face Area (sq. ft)

2.15

2.54

 

2.54

4.36

 

 

No. Rows

2

2

 

2

2

 

 

Coil

 

 

 

Fins per inch

19.5

19.5

 

19.5

19.5

 

 

 

 

 

 

 

Circuits

2

3

 

3

6

 

 

 

Connection Type

 

Flare

 

 

 

 

Refrigerant Lines

Liquid (Mix Phase) (in) OD

1/4”

1/4”

 

1/4”

1/4”

 

 

Vapor Line (in) OD

3/8”

1/2”

 

1/2”

1/2”

 

 

 

 

 

 

 

Condensate Drain (in)

.65 (OD) .53 (ID)

.65 (OD) .53 (ID)

 

.65 (OD) .53 (ID)

.65 (OD) .53 (ID)

 

 

 

Maximum Length (ft)

65

65

 

65

100

 

 

 

Max Lift (Fan Coil Above) (ft)

35

35

 

35

50

 

 

 

Max Drop (Fan Coil Below) (ft)

35

35

 

35

50

4

SPECIFICATIONS - HEAT PUMP UNITS

 

System Model Number

53MVQ009--- --- ---1

53MVQ012--- --- ---1

 

53MVQ012--- --- ---3

53MVQ018--- --- ---3

 

 

System

System Voltage

115 V

115 V

 

208/230

208/230

 

 

 

Control Voltage

0 --- 12 Pulse DC

0 --- 12 Pulse DC

 

0 --- 12 Pulse DC

Pulse DC

 

 

 

Capacity (Btuh)

9000

12000

 

12000

18000

 

 

 

SEER

13.0

13.0

 

13.0

13.0

 

 

 

HSPF

7.7

7.7

 

7.7

7.7

 

 

Refrigerant

Refrigerant Type

 

R---410A

 

 

 

 

 

 

 

 

 

 

 

Charge (lb)

2.35

3.0

 

3.0

550

 

 

 

Design Pressure (PSIG)

550

550

 

550

 

 

 

Metering Device

 

Capillary Tubes in Outdoor Unit

 

 

 

 

 

 

 

 

 

 

 

Compressor

Type

 

Rotary

 

 

 

 

Model

EA82X1C---1FZDU1

EA108X1C---1FZDU1

 

PA108X1C---3FZDU

PA150X2CS---3KUU

 

 

 

Oil Charge (POE ---oz)

11.8

11.8

 

11.8

25.4

 

 

 

Capacitor

45µF/250VAC

45µF/250VAC

 

35µF/370VAC

40µF/370VAC

 

 

 

Rated Current (RLA)

7.5

9.9

 

5.2

7.3

 

 

 

 

 

 

 

Locked Rotor Amp (LRA)

40

47

 

21

32.6

 

MVQ38/40MVC,

MotorOutdoorCoil

Rpm/CFM

900/1060

900/1090

 

900/1120

840/1470

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Diameter (in) .. No. of Blades

15.8 … 3

15.8 … 3

 

15.8 … 3

18.1 … 3

 

 

 

Motor (hp)

0.102

0.102

 

0.102

0.224

 

 

 

 

 

 

 

 

 

 

 

 

Capacitor

6.5µF/260VAC

6.5µF/260VAC

 

2.5µF/450VAC

3µF/450VAC

 

 

 

 

 

 

 

 

 

 

 

 

Face Area (sq. ft)

4.05

3.94

 

3.94

5.51

 

 

 

 

 

 

 

 

 

 

 

Outdoor

No. Rows

2

2

 

2

4

 

 

 

 

 

 

 

 

 

 

 

Fins per inch

17

17

 

17

18

 

 

 

 

 

 

 

 

 

 

 

 

Circuits

4

4

 

4

4

 

 

 

 

 

 

 

 

 

 

 

 

Motor Watts/HP

20/.034

20/.034

 

20/.034

25/.044

 

 

Indoor Motor

Rpm/Cfm (High)

1250/325

1270/425

 

1270/425

1070/630

 

 

Rpm/Cfm (Medium)

1000/260

1100/365

 

1100/365

1000/570

 

 

Rpm/Cfm (Low)

800/190

1000/340

 

1000/340

960/500

 

 

 

Blower Diameter … Length (in)

3.84 … 25.87

4.17 … 25.2

 

4.17 … 25.2

4.21 … 37.6

 

 

Indoor

Face Area (sq. ft)

2.15

2.54

 

2.54

4.36

 

 

Coil

No. Rows

2

2

 

2

2

 

 

Fins per inch

19.5

19.5

 

19.5

19.5

 

 

 

 

 

 

 

Circuits

2

3

 

3

6

 

 

 

Connection Type

 

Flare

 

 

 

 

Refrigerant

Liquid (Mix Phase) (in) OD

1/4”

1/4”

 

1/4”

1/4”

 

 

Lines

Vapor Line (in) OD

3/8”

1/2”

 

1/2”

1/2”

 

 

Maximum Length (ft)

65

65

 

65

100

 

 

 

Condensate Drain (in)

.65 (OD) .53 (ID)

.65 (OD) .53 (ID)

 

.65 (OD) .53 (ID)

.65 (OD) .53 (ID)

 

 

 

 

 

 

 

 

 

 

 

 

Max Lift (Fan Coil Above) (ft)

35

35

 

35

50

 

 

 

Max Drop (Fan Coil Below) (ft)

35

35

 

35

50

 

 

5

DIMENSIONS - INDOOR

38/40MVC, MVQ

 

 

 

 

 

A07336

 

 

 

 

 

 

Model Size

W

H

D

Weight lb (kg)

in. (mm)

in. (mm)

in. (mm)

 

 

 

9K

32.09 (815)

11.02 (280)

7.68 (195)

24.2

(11)

12K

35.67 (906)

11.26 (286)

9.25 (235)

33.0

(15)

18K

49.21 (1250)

12.80 (325)

9.06 (230)

55.0

(25)

24K

49.21 (1250)

12.80 (325)

9.06 (230)

55.0

(25)

DIMENSIONS - OUTDOOR

Air Flow

H

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

L1

W

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

L2

L3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

35

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A07337

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Model Size

W

H

 

 

 

 

 

L1

 

 

 

 

L2

 

 

L3

Weight lb (kg)

Weight lb (kg)

in. (mm)

in. (mm)

 

 

 

 

in. (mm)

 

 

in. (mm)

 

in. (mm)

 

Cooling Only

Heat Pumps

 

 

 

 

 

 

 

 

 

9K

30.71 (780)

21.26 (540)

21.61 (549)

11.81 (300)

 

10.87 (276)

77.0 (35)

79.2 (36)

12K

29.92 (760)

23.23 (590)

20.87 (530)

12.40 (315)

 

11.42 (290)

85.8 (39)

90.2 (41)

18K

33.07 (840)

27.36 (695)

22.05 (560)

14.17 (360)

 

13.19 (335)

125.4 (57)

125.4 (57)

24K

31.16 (893)

33.86 (860)

23.11 (588)

13.98 (355)

 

13.11 (333)

159.5 (72)

160.6 (73)

SERVICE VALVE LOCATIONS

9K

 

12K

18K

 

 

 

K

J

K

J

J

 

24K

K

K

 

J

 

 

 

 

A07376a

 

 

 

 

 

Service Valve Locations

9K

12K

18K

24K

in. (mm)

in. (mm)

in. (mm)

in. (mm)

 

J

3.46 (88)

3.19 (81)

3.46 (88)

4.02 (102)

K

3.46 (88)

5.63 (143)

3.62 (92)

6.57 (167)

6

CLEARANCES - INDOOR

6" (0.15m) min.

5"

5"

(0.13m)

(0.13m)

min.

min.

6'

(1.8m)

A07891

Fig. 2 – Indoor unit clearance

CLEARANCES - OUTDOOR

A

Air-inlet

E

D

B

C

 

 

 

Air-outlet

 

 

A07894

UNIT

9k and 12k in. (mm)

18k and 24k in. (mm)

A

24 (610)

24 (610)

B

24 (610)

36 (914)

C

24 (610)

24 (610)

D

4 (102)

12 (305)

E

12 (305)

12 (305)

Fig. 3 – Outdoor Unit Clearance

38/40MVC, MVQ

7

SYSTEM OPERATING ENVELOPE

38/40MVC, MVQ

53MVC/MVQ System Operating Envelope Chart

Indoor Temperature (ºF)

-40 -35 -30 -25 -20

120

110

100

90

80 80ºF

70

60

50 5ºF

40

-10

0

10

20

Outdoor Temperature (ºC)

-15 -10

-5

0

5

10

15

20

25

30

35

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Cooling

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Continuous

 

Heating

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Operation

 

Continuous

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Operation

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

55ºF

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

55º

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

75ºF

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

30

40

50

60

70

80

90

100

 

 

 

 

 

Outdoor Temperature (ºF)

 

 

 

 

40 45 50 55 60

 

 

60

 

 

 

 

 

 

 

55

 

 

 

 

 

 

 

 

50

 

 

 

 

 

 

 

45

 

 

 

 

40

(ºC)

 

 

 

35

Temperature

85º

 

 

 

 

 

 

 

 

 

 

 

 

30

 

 

 

 

 

 

 

25

Indoor

 

 

 

 

 

 

 

 

 

20

 

 

 

62ºF

 

 

 

 

 

 

15

 

125º 10

5

0 110 120 130 140

Use low ambient control if the unit will operate in cooling at ambient conditions below 55_F (12.78_C).

A08180

Fig. 4 – System Operating Enevelope

ELECTRICAL DATA

UNIT

 

OPERATING

 

COMPRESSOR

 

OUTDOOR FAN

 

INDOOR FAN

 

 

 

MAX

 

VOLTAGE*

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MCA

FUSE/CB

SIZE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MAX/MIN

 

VOLTS---PH---HZ

RLA

LRA

FLA

HP

W

VOLTS

 

FLA

 

HP

W

 

AMP

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

009

 

127/104

 

115---1---60

7.5

40

0.60

0.102

23

35 DC

 

1.1

 

0.034

20

12

20

 

 

 

 

 

 

 

 

 

 

 

 

012

 

 

9.9

47

 

1.18

 

0.044

25

15

25

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

012

 

 

 

 

5.2

21

0.38

0.116

36

35 DC

 

1.18

 

0.044

25

9

15

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

018

 

253/187

 

208/230---1---60

7.3

32.6

0.78

0.224

53

208/230---1---60

0.26

 

0.075

31

11

20

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

024

 

 

 

 

9.7

34.8

0.62

0.218

100

0.39

 

0.112

50

14

25

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

*Permissible limits of the voltage range at which the unit will operate satisfactorily

 

 

 

 

 

 

 

 

 

LEGEND

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FLA---

Full Load Amps

 

 

 

 

 

 

 

 

 

 

 

 

 

 

LRA ---

Locked Rotor Amps

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MCA ---

Minimum Circuit Amps

 

 

 

 

 

 

 

 

 

 

 

 

 

RLA ---

Rated Load Amps

 

 

 

 

 

 

 

 

 

 

 

 

 

 

8

WIRING

The main power is supplied to the outdoor unit. The field supplied connecting cable from the outdoor unit to indoor unit consists of four wires and provides the power for the indoor unit as well as the communication signal between the outdoor unit and indoor unit.

Voltage drop on the connecting cable should be kept to a minimum. Use cable size and max length below:

18 AWG

50 ft. (16 m)

16 AWG

100 ft. (33 m)

CONNECTION DIAGRAMS

CONNECTING CABLE

CONTROL

CONTROL

38/40MVC, MVQ

CONNECTING CABLE

CONNECTING CABLE

Notes:

1.Do not use thermostat wire for any connection between indoor and outdoor units.

2.All connections between indoor and outdoor units must be as shown. The connections are sensitive to polarity.

3.On the 18k and 24k units, the “S” terminal “CONTROL” output is pulse DC with a potential AC voltage shock hazard.

A07654

Fig. 5 – Connection Diagrams

9

38/40MVC, MVQ

WIRING DIAGRAMS

10

Fig. 6 – Wiring Diagram 38MVC009----1 W/ 40MVC009----1

WIRING DIAGRAMS (CONT.)

11

Fig. 7 – Wiring Diagram 38MVC012----1 W/ 40MVC012----1

38/40MVC, MVQ

38/40MVC, MVQ

WIRING DIAGRAMS (CONT.)

12

Fig. 8 – Wiring Diagram 38MVC012----3 W/ 40MVC012----3

WIRING DIAGRAMS (CONT.)

13

Fig. 9 – Wiring Diagram 38MVC018----3 W/ 40MVC018----3

38/40MVC, MVQ

Carrier 40MVC, 38MVQ, 40MVQ, 38MVC User Manual

38/40MVC, MVQ

WIRING DIAGRAMS (CONT.)

14

Fig. 10 – Wiring Diagram 38MVQ009----1 W/ 40MVQ009----1