Carrier 38AN User Manual

0 (0)
Carrier 38AN User Manual

38AN,BK with 40QN009,012 Cooling Only/Heat Pump Systems

Installation, Start-Up an

Service Instructions

(For Use in High Wall Applications)

CONTENTS

 

Page

SAFETY CONSIDERATIONS....

.. I

GENERAL......................................

. 1,2

INSTALLATION.............................................

.2-13

Step 1 - Complete Pre-Installation Checks ...

 

 

• UNPACK UNIT

 

 

• INSPECT SHIPMENT

 

.2

Step 2 - Select Location.......................................

 

Step 3 - Mount Mounting Bracket on Wall ...

 

.3

Step 4 - Mount Outdoor Section..........................

 

.9

Step 5 - Connect Refrigerant Piping ..................

 

10

• RIGHT REAR AND BOTTOM PIPING

 

 

CONNECTIONS

 

 

• RIGHT SIDE PIPING CONNECTIONS

 

 

• LEFT SIDE PIPING CONNECTIONS

 

 

• ALL TYPES PIPING CONNECTIONS

 

 

Step 6 - Make Piping Connections......................

 

10

Step 7 - Connect Condensate Drain Line_____

11

Step 8 - Make Electrical Connections ................

 

11

• INDOOR SECTION WIRING

 

 

• OUTDOOR SECTION WIRING

 

 

Step 9 - Install Fan Coil Unit Onto

 

 

Mounting Bracket..............................................

 

13

START-UP ...................................................

14-17

40QN Control System ...............................

..

14

Wireless Remote Controllers ...................

..

14

After Extended Shutdowns ......................

..

14

Seasonal Changeovers.............................

..

14

To Turn the Unit On and Off .....................

..

14

Adjusting Airflow .......................................

..

14

Operating Mode Memory ..........................

..

14

Automatic Operation (Auto) Mode...........

,.

14

Operating Fault Diagnosis........................

..

15

Microprocessor Control Operation..........

.. 15

CLEANING AND MAINTENANCE......................

18-19

Lubrication ............................................................

 

18

To install or Replace Remote Controller

 

18

Batteries .............................................................

 

To Set the Current Time.......................................

 

18

To Remove and Clean or Replace Air Filters ..

18

• TO REMOVE AIR FILTERS

 

 

• TO CLEAN OR REPLACE FILTERS

 

 

To Clean Indoor Unit Front Panel .......................

 

19

To Clean Indoor Coil .............................................

 

19

To Clean Outdoor Coil (Outdoor Unit) ................

 

19

To Clean Condensate Drains...............................

 

19

SERVICE ........................................................

 

.20

Diagnostic Codes..........................................

 

.20

System Tests..................................................

 

.20

THERMISTOR TESTS

COMPRESSOR FAILURE

REVERSING VALVE FAILURE (38BK Only)

 

Page

System Safeties and Interlocks

...........................20

INDOOR FAN FAILURE

COMPRESSOR SHORT-CYCLING PROTECTION

INDOOR COIL FREEZE PROTECTION

INDOOR COIL HIGH-TEMPERATURE PROTECTION

TROUBLESHOOTING ..

.......... 20-27

START-UP CHECKLIST

.CL-1, CL-2

SAFETY CONSIDERATIONS

Installing and servicing air-conditioning equipment ean be hazardous due to system pressure and electrical compo­ nents. Only trained and qualified service personnel should install or service air-conditioning equipment.

Untrained personnel can perform basic maintenance func­ tions such as cleaning coils and filters and replacing filters. All other operations should be performed by trained service personnel.

When working on air conditioning equipment, observe pre­ cautions in the literature and on tags and labels attached to unit. Follow all safety codes. Wear safety glasses and work gloves. Use quenching cloth for brazing operations. Have fire extinguisher available. Before installation, read these in­ structions thoroughly. Consult local building codes and Na­ tional Electrical Code (NEC) for special installation requirements.

A WARNING

Electrical shock can cause personal injuiy or death. Be­ fore installing or servicing system, be sure to turn off main power to system. There may be more than one dis­ connect switch. Turn olf indoor fan coil power as applicable.

GENERAL

The Carrier 40QNH012 heat pump high wall fan coil unit (Fig, 1) comes with supplemental electric heat (40QNE009 heat pmnp fan coil unit does not have electric heat). If your application requires heating, heat pump units must be used both outdoors and indoors. See Table 1 for recommended system combinations.

The matched cooling and heat pump systems consist of an outdoor section (condensing unit or heat pump) and an in­ door section (fan coil). The outdoor section (38AN or 38BK) is installed alongside the building structure. It can also be installed on a flat roof, deck, or on an apartment building balcony. The indoor section (40QNB009,012 or 40QNE009, 40QNH012) is mounted high on an interior wall that is con­ venient for piping connection to the outdoor section. Two sizes are available: 9,000 and 12,000 Btuh cooling capaci­ ties. See Fig. 1 for system components. Table 1 for system

Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obiigations.

Book|1 |4

PC 111 Catalog No. 533-848 Printed In U.S.A. Form 38A.B/40Q-1SI Pg 1

5-99 Replaces; 53AN,BK-1 SI

Tab 3e 2f

 

 

combinations, and Table 2 for application range. Refer to this manual for proper installation of the complete system. Refer to Table 1 to make sure the correct indoor unit is in­ stalled with the correct outdoor unit. Be sure the unit will be operated within the application guidelines shown in Table 2. When installing the 38AN or 38BK unit, it is important to note that for cooling operation when the outdoor air tem­ perature is below 55 F, it is necessary to equip the outdoor unit with the low-ambient accessory.

To install this unit you will need:

1 — 40QNB or 40QNE/H Fan Coil unit with standard wire­ less remote controller and indoor unit wire

1 — 38AN or 38BK. Outdoor Unit

1 — Low-Ambient Kit (if required for your application)

NOTE: Field-supplied wire, drain pipe, refrigerant tubing, etc., are also required to install unit.

The installation materials provided are for use on instal­ lations where the indoor section is mounted to gypsum wall board with wall studs. Other types of applications require field-supplied mounting hardware. Be sure to follow all in­ stallation instructions in this manual carefully in order to achieve proper unit operation, and be sure that you have all of the required parts before beginning installation.

Note that the cooling only and heat pump systems utilize a microprocessor control system to deliver optimum levels of comfort and efficiency. Refer to Microprocessor Control Operation section on page 15 for details.

Table 1 — System Combinations for Indoor and Outdoor Units

SYSTEM

INDOOR

OUTDOOR

UNIT

UNIT

 

High Wall Cooling Only

40QNB009

38AN009

40QNB012

38AN012

 

High Wall Heat Pump

40QNE009

38BK009

40QNH012

38BK012

 

NOTE: A cooling only outdoor unit may not be matched with a heat pump indoor unit, a heat pump outdoor unit may not be matched with a cooiing only indoor unit. Do not mismatch systems.

Table 2 — Application Range

 

 

COOLING

 

 

 

Maximum

 

Minimum

Indoor

 

Outdoor

Indoor

 

Outdoor

95 F DB

 

115 F DB

67 F DB

 

55 F DB*

71 F WB

 

 

57 F WB

 

 

 

 

HEATING

 

 

 

Maximum

 

Minimum

Indoor

 

Outdoor

Indoor

 

Outdoor

80 F DB

 

75 F DB

55FDB

 

0° F DB

71 F WB

 

65 F WB

 

 

 

LEGEND

DB — Dry Bulb

WB — Wet Bulb

'Unit may be equipped with a low-ambient control that will allow op­ eration down to —20 F.

INSTALLATION

Step 1 — Complete Pre-Installation Checks

UNPACK UNIT(S) — Store unit{s) in original packaging until moved to the final site for installation. When removing unit from carton, lift by its 4 comers. Note that there is a plastic bag containing mounting screws taped to the mount­ ing bracket.

INSPECT SHIPMENT — Upon receipt of shipment, in­ spect unit (Fig. 1) for damage. Forward claim papers di­ rectly to the transportation company. Manufacturer is not re­ sponsible for damage incurred in transit.

Check all items (see Table 3), and if any item is missing, notify your Carrier distributor. To prevent loss or damage, leave all parts in the original packages until installation.

NOTE: The expansion device is located in outdoor unit.

Step 2 — Select Location — Consult local building codes and NEC for special installation requirements.

NOTE: There are several ways the unit may be installed in different types of wall construction. These instructions do not cover all installation methods. As a typical installation, these instructions focus primarily on mounting the unit to wall studs in new construction.

Plan your installation carefully before you begin. Listed below are some guidelines to follow when determining a lo­ cation for the unit;

1.Center unit (horizontally) on the wall selected.

2.Allow sufficient space for airflow clearance, wiring, re­ frigerant piping, and servicing the unit. See Fig. 2-4.

3.Place the unit so it faces normal location of room occupants.

TYPICAL FAN COL UNIT

TYPICAL OUTDOOR UNIT

Fig. 1 — Typical Cooling Only/

Heat Pump System

*A clearance of 31^" is the absolute minimum, A clearance of 10” is recommended.

NOTE: Remove unit front cover for controi box access.

Fig. 2 — Minimum Required Fan Coil Unit

Clearances

4, Select walls that are;

a.Strong enough to support the weight of the unit (see Tables 4A-4D for unit operating weight).

b.Accessible to convenient condensate drainage.

c.Free of obstacles that may block air circulation to the fan coil.

d.Outside walls (if possible) to make piping easier,

5.Place top of fan coil unit as high on wall as possible, mak­ ing sure that unit is at least 3 ’/i in. down from ceiling to permit proper airflow (the recommended clearance is 10 inches). Also, make sure that the unit is not placed directly over anything that would prevent filter removal or block airflow.

6, Make sure units are easily accessible to electric power.

7.Reirigerant piping can enter the unit through the prepunched holes. Refrigerant piping can run down along the wall, to the right or left along the wall, straight through the wall, or into the wall (recommended location: right rear). See Fig, 5, Once the piping is through the wall, it can run inside walls, in ceilings, between floors, or straight to the outside. See Fig. 6 for maximum line lengths. See Table 5 for System Piston Guide and Refrigerant Charging.

NOTE: Run refrigerant piping as directly as possible, and avoid any unnecessary turns or bends.

8. Condensate piping can be directed through the inside wall to an approved drain or directed straight outside,

NOTE: The piping hole for condensate line must be made at a downward slope to ensure proper drainage. See Mount Mounting Bracket on Wall section below for details.

Step 3 — Mount Mounting Bracket on Wall

1.Decide how refrigerant will be piped. If necessary, knock out the appropriate pre-punched holes (Fig. 5) on unit for piping and electrical connections.

2.Remove bracket from fan coil unit by pulling it down from fan coil unit bottom as shown in Fig, 7.

3.Using a carpenter’s level, fasten mounting brackets into the studs in the wall at least 10 in. away from the ceiling

with all the screws provided. Always be sure to insert screws into the top 2 holes indicated in Fig, 7. Make sure the attached bracket will support a 200 Tbvertical load. For

a masonry wall, anchor shields can be used to attach bracket to the wall.

4.Temporarily hang unit on bracket to check location and level.

A CAUTION

If mounting bracket is not mounted level, the indoor sec­ tion will be mounted unevenly, and condensate drain­ age water may drip onto the floor. Also, a gap between the bracket and the wall may result in vibration and noise from the indoor section.

5.Mark and cut condensate and piping holes.

a.For piping through the wall, mark the wall below the condensate connection and cut a 2'/i-in. hole into the wall at either point “A” or point “B” in Fig. 8.

NOTE: The 2’/2-in hole must be made at a downward slope to ensure proper condensate drainage. See Fig. 9. Slope condensate line at a minimum pitch of

'A in, per foot of line. The condensate line cannot be run up for upper piping connections — only refriger­ ant lines may be run up.

b.Push the wall sleeve (factory supplied with the xmit) through the 2‘/2-in. wall opening.

Table 3 — High Wall Unit Package Contents

ITEM

QUANTITY

Unit Mounting Template

1

Unit Mounting Bracket

1

1-in. Lag Screws for Unit Mounting

8

Hollow Wall Anchor Bolts for Unit Mounting

5

Wall Sleeve with Wall Cap

1

Infrared Wireless Remote Control

1

AAA Batteries (for Remote Control)

2

Remote Control Mounting Bracket

1

ya-in. Lag Screws for Remote Mounting Bracket

2

35 ft High Voltage Power Wiring

 

40QNB009 (3-Wire with Ground)

1

40QNEQ09 (2-Wire with Ground)

1

40QNB012 (2-Wire with Ground)

1

40QNH012 (2-Wire with Ground)

1

35 ft High Voltage Control Power Wiring (3-Wire)

1

35 ft Low Voltage Thermistor Wiring

1

Owner’s Manual

1

Installation Instructions

1

Warranty Registration Card

1

Table 4A — Physical Data, 38AN Cooling Only Condensing Units*

UNIT 3SAN

009

 

012

NOMINAL CAPACITY (Tons)

%

 

1

OPERATING WEIGHT (lb)

55

 

62

REFRIGERANT TYPE

 

R-22

Control (Cooling)

 

Capillary Tube

Factory Charge (lb)

1.5

1.8

COMPRESSOR TYPE

EAA090111A

Carrier Hernietic Rotary

Model

 

E8B120111A

Oil (Recharge) (oz)

10.1

10.1

Crankcase Heater

 

None

Accumulator

 

Yes

OUTDOOR FAN

 

Propeller, Direct Drive

Rpm

850

 

850

Diameter (in.)...No. of Blades

12y4...4

 

12У4...4

Motor Watts

87

 

87

Nominal Air Cfm

750

 

750

OUTDOOR COIL

Copper Tube, Aluminum Fin

Face Area (sq ft)...No. of Rows

3.5...1

 

3.5...2

FIns/in.

18

 

17

CONTROLS

 

 

 

Fusible Plug (F)

210

 

210

Control Voltage

115

 

230

REFRIGERANT LINES

 

 

 

Connection Type

 

Male

Flare

Liquid Line OD (in.)

У4

 

'/4

Vapor Line OD (in.t

 

 

 

Maximum Length (ft)

35

 

35

Maximum Lift Fan Coil (Above Outdoor) (ft)

16

 

16

Maximum Lift Fan Coil (Below Outdoor) (ft)

30

 

30

‘These units may only be used with 40QNB009,012 fan coil units.

Table 4B — Physical Data, 40QNB Cooling Only High Wall Units

UNIT 40QNB

009*

012*

NOMINAL CAPACITY (Tons)

n

1

NOMINAL SIZE (Btuh)

9000

12,000

OPERATING WEIGHT (lb)

18.7

24.2

MOISTURE REMOVAL RATE (Pints/Hr)

2.4

3.4

FINISH

White

REFRIGERANT

R-22

Control (Cooling)

Capillary Tube in Outdoor Unit

Factory or System Charge (ib)t

1.5

1.8

INDOOR FAN

Direct Drive

Centrifugal

Rpm...Cfm High

1200...240

1040...260

Rpm...Cfm Medium

1100...210

940...240

Rpm...Cfm Low

1000...180

850...210

Motor Watts

34

35

Biowers — No. ...Size (in.)

1...3.54 X27.75

1...3.94X 27.75

INDOOR COIL

Copper Tube, Aluminum Fin

Face Area (sq ft)

1.45

1.6

No. of Rows

2

2

Finsfin.

18

17

Circuits

2

3

FILTERS

Cieanable

(Quantity) Size (in.)

(2) 9x 12

(2) 914 X 13W

AIRSWEEP

 

 

Horizontai

Manual

Vertical

Automatic

CONTROLS

integrated Microprocessor

Remote Controller

Wireless

Freeze Protection

Yes

Auto. Restart

Yes

Diagnostics

Yes

Timer Mode

24-Hour Startup/Shutdown Type

Test Mode

Yes

Dehumidification Mode

Yes

Fan Mode

Hig h/Medium/Low/Auto.

Control Voltage

115 V

230 V

REFRIGERANT LINES

 

 

Connection Type

Male Flare

Liquid Line OD (in.)

W

14

Vapor Line OD (In.)

14

'4

Maximum Len^h (ft)

35

35

Maximum Lift Fan Coil (Above Outdoorl (ft)

16

16

Maximum Lift Fan Coll (Below Outdoor) (ft)

30

30

CONDENSATE DRAIN CONNECTION (in.)

OD, VieID

•Units may only be matched with 38AN outdoor units.

tFull factory charge shipped in outdoor unit. Charge is determined based on 25 ft of line.

Table 4C — Physical Data, 38BK009.012 Outdoor Heat Pump Units*

UNIT 38BK

009

 

012

NOMINAL CAPACITY (Tons)

V*

 

1

OPERATING WEIGHT (lb)

60.7

 

66.5

REFRIGERANT TYPE

 

R-22

Control (Cootingt

AccuRater® Piston at Outdoor Unit

Control (Heating)

AccuRater Piston at Outdoor Unit

Factory Charge (lb)

1.5

2.0

COMPRESSOR TYPE

 

Carrier Hermetic Rotary

Model

EBA095111H

 

EBC130111H

Oil (Recharge) (oz)

10.1

10.1

CRANKCASE HEATER (Watts)

 

40

OUTDOOR FAN

 

Propeller, Direct Drive

Rpm

850

 

850

Diameter (in.)...No. of Blades

12'^...4

 

12'/4...4

Motor Watts

87

 

87

Nominal Air Cfm

756

 

756

OUTDOOR COIL

 

Copper Tube, Aluminum Fin

Face Area (sq ft)...No. of Rows

3.5...1

 

3.5...2

Fins/ln.

18

 

17

CONTROLS

 

 

 

Fusible Plug

210 F

 

210 F

Accumulator

Yes

 

Yes

Defrost Method

Demand

 

Demand

Control Voltage

115 V

 

230 V

REFRIGERANT LINES

 

 

 

Connection TVpe

 

Male

Flare

Liquid Line OD (in.)

V4

 

V4

Vapor Line OD (in.)

 

 

W

Maximum Length (ft)

35

 

35

Maximum Lift (Fan Coll Above) (ft)

16

 

16

Maximum Lift (Fan Coll Below) (ft)

30

 

30

•These units may only be used with 40QNE/H fan coil units.

Table 4D — Physical Data, 40QNE/H Heat Pump High Wall Units

UNIT

40QNE009*

 

40QNH012*

NOMINAL CAPACITY (Tons)

%

 

1

NOMINAL SIZE (Btuh)

9000

 

12,000

OPERATING WEIGHT (lb)

18.7

 

24,2

MOISTURE REMOVAL RATE (PInts/hr)

2.4

 

3.4

REFRIGERANT

R-22

 

Control (Cooling)

Accu Rater® Piston at Outdoor Unit

Control Seating)

AccuRater Piston at Outdoor Unit

Factory Charge (lb)t

_...... ............... _..15.................. ...............

 

2.0

INDOOR FAN

Direct Drive Centrifugal

 

RpmyCfm High

1200/240

 

1040/260

RpnrVCfm Medium

1100/210

 

940/240

Rpm/Cfm Low

1000/180

 

850/210

Motor Watts

34

 

35

Blowers Quantity...Size (in.)

1...3.54 * 27.75

 

1...3.94 X 27.75

INDOOR COIL

Copper Tube, Aluminum Fin

Face Area

1.45

 

1.6

No. of Rows

2

 

2

Fins/in.

18

 

17

Circuits

2

 

3

FILTERS

Cieanabie

 

Quantity...Size (in.)

2...9X 12

2...91/4X 13V4

AIRSWEEP

 

 

 

Horizontal

Manual

 

Vertical

Automatic

 

CONTROLS

Integrated Microprocessor

 

Remote Controller Options

Wireless

 

Diagnostics

Yes

 

Defrost Method

Demand Defrost

 

Timer Mode

Yes

 

Warm Start Feature

Yes

 

Test Mode

Yes

 

Freeze Protection

Yes

 

Dehumidification Mode

Yes

 

Fan Mode

High/Medium/Low/Auto

 

Auto Changeover

Yes

 

Auto Restart

Yes

230 V

Control Voltage

115 V

REFRIGERANT LINES

 

 

 

Connection Type

Male Flare

 

Liquid Line OD (in.)

 

 

W

Vapor Line OD (in.)

 

 

Vi

Maximum Length (m

35

 

35

Maximum Lift (Fan Coil Above) (ft)

16

 

16

Maximum Lift (Fan Coil Below) (ft)

30

 

30

CONDENSATE DRAIN SIZE (in.)

% OD, Vie ID

 

 

 

 

 

'These units may oniy be matched with 38BK outdoor units. The 40QNH unit available in size 012 only. tFuil factory charge is shipped in the outdoor unit. The charge is determined based on 25 ft of line.

r o p Vltw

\_P'-eiM^J

 

*

[235]

^

 

 

> i e n T t i » i v n *

 

¡»«OUT Vltw

 

 

 

 

NOTES;

 

 

 

 

 

 

 

 

UNIT

 

WEIGHT

1. Dimensions in ( ] are in miliimelers.

 

 

 

2.

Direction of airflow.

 

 

38

Lb

 

Kg

 

 

AN009

55.0

 

25.0

 

 

 

 

 

 

Center of Gravity.

 

 

AN012

62,0

 

28.1

4.

Minimum dearances: 4 in. on coil sides, 24 in. on fan side, and

BKD09

60.7

 

27.5

BK012

66.5

 

30.2

 

30 in. service side.

 

 

 

Fig. 3 — 38AN/BK Dimensional Drawing

HiNIHUM CLEARANCE FOR SERVICE

[NL£T AIR

EVAPORATOR

COIL

¿-KWCICOUT FOR LEFT SIDE REFRIGERANT, DRAIN, POUER AND SIGNAL LINES

2.36 OIA 160]

IRISHT SIDE VIEW I

INFRARED

REMOTE OVERRIDE SWITCH

CBEHIND ACCESS COVER)

 

KNOCKOUT FOR RIGHT SIDE -

 

REFRIGERANT, DRAIN, POWER

 

AND SIGNAL LINES

 

‘INDOOR FAN MOTOR

I BOTTOM VIETI

KNOCKOUT FOR BOTTOM

INDOOR AIR BLOWER WHEEL

REFRIGERANT. DRAIN, POWER

 

AND SIGNAL UNES

NOTES:

1.Dimensions are in inches. Dimensions in [ ] are in miliimeters.

2.Direction of airflow.

3.Refrigerant, drain, and power connections may be made rear, left side or right side.

4.Refrigerant ts metered by capillary tubes in the outdoor unit. Insulate both refrigerant lines.

5.Clearances of ZW on top of and to the left of the fan coil unit are absolute minimums, Clearances of 10" are recommended.

6.Do not insert a trap in condensate drain line. Drain is internally trapped.

UNIT

WEIGHT

A

 

 

B

 

c

40QN

Lb

Kg

in.

mm

in.

 

mm

in.

 

mm

009

18.7

8.5

33.46

850

11.02

 

280

6.29

 

160

012

24.2

11.0

36.61

930

11.81

 

300

7.28

 

185

 

 

 

 

 

 

 

 

 

 

 

Fig. 4 — 40QN Dimensional Drawing

8

Table 5 — System Piston Guide and

Refrigerant Charges

UNIT

INDOOR

OUTDOOR

REQUIRED

SYSTEM

 

 

PISTON

PISTON

Indoor

Outdoor

SIZE

SIZE

CHARGE

(lb)*

40QNB009

38AN009

Capillary Tube

Capillary Tube

1.50

40QNB012

38AN012

Capillary Tube

Capillary Tube

1.80

40QNE009

38BK009

32t

30t

1.50

40QNH012

38BK012

42t

42t

2.00

'Charge is based on 25 ft of interconnecting tubing. Charge may need to be added for longer tubing runs or when used with certain fan coiis. Check unit namepiate for required charge. This is a totai sys­ tem charge.

tNon-serviceabie Aeroquip piston.

POSSiBLE PIPiNG DIRECTIONS

PREPUNCHED HOLES

BOTTOM/REAR

PIPING

Fig. 5 — Fan Coil Unit Refrigerant Piping

as" MAX (FOR COOLING ONLY AND HEAT PUMP SYSTEMS)

UNIT

ROOFTOP

GROUND-LEVEL

INSTALLATION

INSTALLATION

Fig. 6 — Maximum System Line Lengths

Step 4 — Mount Outdoor Section

1.If outdoor section is to be installed at ground level, mount on a solid, level support pad one in. longer and one in. wider than the outdoor section dimensions.

2.Provide sufficient clearance for airflow, wiring, refriger­ ant piping, service and maintenance. Provide a minimum clearance of 2 ft from obstructions in front of outdoor section, 2 ft on outdoor coil side, and 2’/2 ft on electrical and piping side. If more than one outdoor section is in­ stalled, provide a minimum clearance of 2 ft between sec­ tions. Position outdoor section so that water or ice from roof cannot fall directly on unit.

NOTE: The outdoor section can be installed higher than, lower than, or level with the elevation of the indoor section. If outdoor section is mounted higher than the in­ door section, the vertical distance between the 2 units should not exceed 30 ft. If the outdoor section is installed lower than indoor section, the vertical distance between the units should not exceed 16 ft. See table below:

MAXIMUM DISTANCE BETWEEN OUTDOOR UNITS

Outdoor Section Higher

30 Ft Maximum

Than Indoor Section

(Vertical)

Outdoor Section Lower

16 Ft Maximum

Than Indoor Section

(Vertical)

NOTE: Maximum system piping length between indoor and outdoor units is 35 ft.

Fig. 7 — Fan Coil Unit Bracket Mounting (Size 009 Shown)

Loading...
+ 21 hidden pages