Carrier 33ZCSECTRM, 33ZCFANTRM, 33ZCVAVTRM User Manual

4.5 (2)

Single Duct Air Terminal Zone Controller

VAV Fan Terminal Zone Controller

Secondary Terminal Zone Controller

Installation, Start-Up and

Configuration Instructions

Part Numbers 33ZCFANTRM, 33ZCVAVTRM, 33ZCSECTRM

CONTENTS

Page

SAFETY CONSIDERATIONS . . . . . . . . . . . . . . . . . . . . . . 1

GENERAL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2

INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-29

General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2

Zone Controller Hardware . . . . . . . . . . . . . . . . . . . . . . . . 2

Field-Supplied Hardware . . . . . . . . . . . . . . . . . . . . . . . . . 2

SPACE TEMPERATURE SENSOR

PRIMARY AIR TEMPERATURE SENSOR

SUPPLY AIR TEMPERATURE (SAT) SENSOR

RELATIVE HUMIDITY SENSOR

INDOOR AIR QUALITY (CO2) SENSOR

Mount Zone Controller . . . . . . . . . . . . . . . . . . . . . . . . . . . 4

LOCATION

MOUNTING

Connect the Power Transformer. . . . . . . . . . . . . . . . . . 7

Connect Airflow Pickups . . . . . . . . . . . . . . . . . . . . . . . . . 7

Install Sensors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19

SPACE TEMPERATURE SENSOR INSTALLATION

PRIMARY AIR TEMPERATURE SENSOR INSTALLATION

SUPPLY AIR TEMPERATURE (SAT) SENSOR INSTALLATION

INDOOR AIR QUALITY SENSOR INSTALLATION

HUMIDITY SENSOR (WALL-MOUNTED) INSTALLATION

Remote Occupancy Contact. . . . . . . . . . . . . . . . . . . . . 26

Connect the Outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26

Modulating Baseboard Hydronic Heating . . . . . . . . 26

Connect the CCN Communication Bus . . . . . . . . . . 26

COMMUNICATION BUS WIRE SPECIFICATIONS

CONNECTION TO THE COMMUNICATION BUS

START-UP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29-31

Perform System Check-Out . . . . . . . . . . . . . . . . . . . . . 29

Network Addressing. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30

Initial Operation and Test. . . . . . . . . . . . . . . . . . . . . . . . 30

Airflow Check . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30

Fan and Heat Configuration and Test. . . . . . . . . . . . 30

CONFIGURATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31-50

Points Display Screen . . . . . . . . . . . . . . . . . . . . . . . . . . . 31

Modify Controller Configuration. . . . . . . . . . . . . . . . . 32

ALARM LIMIT CONFIGURATION SCREEN

CONTROLLER IDENTIFICATION SCREEN

HOLIDAY CONFIGURATION SCREENS

LINKAGE COORDINATOR CONFIGURATION SCREEN

OCCUPANCY CONFIGURATION SCREEN

SET POINT SCREEN

Service Configuration Selection Screen. . . . . . . . . 37

AIRFLOW SERVICE CONFIGURATION SCREEN

TERMINAL SERVICE CONFIGURATION SCREEN

OPTIONS SERVICE CONFIGURATION SCREEN

SECONDARY DAMPER SERVICE

CONFIGURATION SCREEN

Maintenance Table Menu Screen . . . . . . . . . . . . . . . . 43

LINKAGE MAINTENANCE TABLE

OCCUPANCY MAINTENANCE TABLE

ZONE AIR BALANCE/COMMISSIONING TABLE

ZONE MAINTENANCE TABLE

SAFETY CONSIDERATIONS

SAFETY NOTE

Air-handling equipment will provide safe and reliable service when operated within design specifications. The equipment should be operated and serviced only by authorized personnel who have a thorough knowledge of system operation, safety devices and emergency procedures.

Good judgement should be used in applying any manufacturer’s instructions to avoid injury to personnel or damage to equipment and property.

Disconnect all power to the unit before performing maintenance or service. Unit may automatically start if power is not disconnected. Electrical shock and personal injury could result.

If it is necessary to remove and dispose of mercury contactors in electric heat section, follow all local, state, and federal laws regarding disposal of equipment containing hazardous materials.

Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.

Book

1

4

PC 111

Catalog No. 533-355

Printed in U.S.A.

Form 33ZC-1SI

Pg 1

303

11-99

Replaces: New

Tab

11a

13a

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

GENERAL

The zone controller is a single duct, fan powered, Variable Air Volume (VAV) terminal control with a factory-integrated controller and actuator. The zone controller maintains precise temperature control in the space by operating the terminal fan and regulating the flow of conditioned air into the space. Buildings with diverse loading conditions can be supported by controlling reheat or supplemental heat.

The VAV Fan Terminal Zone Controller (33ZCFANTRM) provides dedicated control functions for series fan or parallel fan powered terminals, single duct terminals with 3 stages of heat, or as a primary controller for dual duct or zone pressure control applications.

The Single Duct Air Terminal Zone Controller (33ZCVAVTRM) provides dedicated control functions for single duct terminals with modulating heat or up to 2 stages of heat.

When the VAV Fan Terminal Zone Controller is used in conjunction with a secondary terminal and the 33ZCSECTRM secondary terminal zone controller, either dual duct or zone pressurization applications can be supported.

Carrier’s Linkage system is an integrated combination of Carrier Comfort Network (CCN) controllers for use with Single Duct air terminals and VAV Fan Powered terminals. The Single Duct air terminal and VAV Fan terminal zone controllers are part of the Carrier ComfortID system.

Devices manufactured by Carrier which have Product Integrated Controls on the same communication bus as the zone controller, air handlers (such as the 39L,T), or large rooftop units do not require an external controller to function as part of a Carrier linkage system. These air handlers or large rooftop units feature factory-installed Product Integrated Control (PIC) controllers that are directly compatible with the system. Consult your local Carrier representative for the complete list of compatible air handlers. The Comfort System AirManager (CSAM) or the CC6400 supports linkage for non-Carrier devices or air handlers. Figure 1 shows an example of a Carrier linkage system.

INSTALLATION

General — The zone controller is a microprocessor-based direct digital control (DDC) controller for variable air volume (VAV) air terminals. It can be retrofitted on units manufactured by Carrier or other manufacturers to provide pressureindependent VAV control.

Each zone controller has the ability to function as a linkage coordinator for systems with up to 128 zones. As a linkage coordinator, a zone controller will retrieve and provide system information to the air handling equipment and other zone controllers. A zone controller can function as a stand alone device by installing a primary supply air sensor.

The zone controller monitors differential pressure from an airflow pickup (or a pair of pickups) mounted on the terminal box. It compares the resulting signal to an airflow set point in order to provide pressure-independent control of the air passing through the terminal.

The zone controller is connected to a wall-mounted, fieldsupplied, space temperature sensor (SPT) in order to monitor zone temperature changes and satisfy zone demand.

On stand-alone applications or applications with heat, the zone controller must be connected to a field-supplied supply air temperature (SAT) sensor to monitor the temperature of the air delivered by the air terminal.

Carrier’s Network Service Tool can be connected to the system at the SPT sensor if CCN communication wiring is run to

the SPT sensor. The Network Service Tool can be used to adjust set points, set operating parameters, and fully configure the zone controller or any device on the system.

Zone Controller Hardware — The zone controller consists of the following hardware:

terminal control module

torque-limiting damper actuator

airflow transducer (velocity sensor)

plastic enclosure

one no. 8 x 1/2-in. sheet metal screw (to prevent zone controller rotation)

NOTE: A filter is not provided for the airflow transducer. For installations on systems with a high degree of impurities, an air filter can be purchased and installed on the transducer high pressure pickup.

Figure 2 shows the zone controller physical details. Figures 3-5 show the 3 different types of zone controllers.

Field-Supplied Hardware — Each zone controller requires the following field-supplied components to complete its installation:

air terminal unit

space temperature sensor

transformer — 24 vac, 40 va

two no. 10 x 1/2-in. sheet metal screws (to secure SAT sensor to duct, if required)

two no. 6-32 x 5/8-in. screws (to mount SPT sensor base to electrical box)

contactors (if required for fan or electric heat)

supply air temperature sensor (required for terminal with ducted heat)

indoor air quality sensor (if required)

relative humidity sensor (if required)

one SPST (for each stage of electric heat, not required for Carrier fan terminals)

valve and actuator for hot water heat (if required)

delta pressure airflow pickup

NOTE: When selecting an airflow pickup, it is the designer's responsibility to select a sensor that provides the desired output at the design airflow.

wire

polyethylene tubing (for pressure pickup)

bushings (required when mounting SAT sensor in a duct 6-in. or less in diameter)

primary air temperature sensor (if required)

SPACE TEMPERATURE SENSOR — Each zone controller requires a field-supplied Carrier space temperature sensor. There are two sensors available for this application:

33ZCT55SPT, Space Temperature Sensor with Override Button

33ZCT56SPT, Space Temperature Sensor with Override Button and Set Point Adjustment

PRIMARY AIR TEMPERATURE SENSOR — A fieldsupplied, primary air temperature (PAT) sensor (part number 33ZCSENPAT) is used on a zone controller which is functioning as a Linkage Coordinator for a non CCN/Linkage compatible air source.

SUPPLY AIR TEMPERATURE (SAT) SENSOR — On stand-alone applications or applications with ducted heat, the zone controller must be connected to a field-supplied supply air temperature (SAT) sensor (part number 33ZCSENSAT) to monitor the temperature of the air delivered by the air terminal. The zone controller will maintain the air temperature below the maximum air temperature in ducted heating applications.

2

CCN

SYSTEM

CCN PRIMARY BUS (BUS 0) MONITORING

SOFTWARE

FULLY

CC6400 OR CSAM

EQUIPPED

COMPATIBLE

NON-CCN

AIR HANDLER

AIR HANDLER

 

BRIDGE (RECOMMENDED)

COMFORTID

EQUIPPED

AIR TERMINAL

SECONDARY BUS (1 OF UP TO 128)

ADDRESSED

SEQUENTIALLY

DATA

COLLECTION

OPTION

LEGEND

CCN — Carrier Comfort Network

CSAM — Comfort System AirManager

Fig. 1 — Typical Carrier Linkage System

3

DAMPER

ACTUATOR

 

LOW PRESSURE

SHAFT

CLAMP

 

TUBING ROUTING

 

ASSEMBLY

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

LOW

 

 

 

 

 

15

 

+24V

16

 

 

 

 

 

 

 

C

 

US

 

 

 

RH/IAQ

SPT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

GND

 

 

MECHANICAL

 

 

 

 

 

 

 

 

1

J6

 

FAN AC

 

GND

 

 

 

 

 

 

 

 

 

 

 

SECFLOW

 

 

 

 

 

 

 

 

 

 

 

 

 

 

STOP

 

 

 

 

 

 

 

 

1 2

 

FAN

SAT

 

 

 

 

 

 

 

 

 

 

 

 

 

24VAC

J4

+10V

T56

 

GROMMET

 

 

 

 

 

 

 

 

 

 

J7

 

DMPPOS

 

 

0

 

 

 

 

 

1

 

 

 

N/A

GND

 

 

 

 

 

 

 

 

 

 

HEAT3

 

GND

 

 

 

 

 

 

 

 

3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

PAT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

TEST

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

REMOTE

 

 

 

 

 

 

 

 

 

®

 

 

 

 

GND

 

HF23BJ042

 

 

 

 

ZONE Controller

 

 

 

 

 

 

 

 

 

1

 

 

 

2

 

Made in Switzerland

 

 

 

®

 

1

 

 

by Belimo Automation

 

35 in-lb (4 Nm)

 

 

1

 

SECDMP

 

1

 

 

 

 

 

 

 

 

 

 

3

J8

 

CCNJ2A

G-

3

 

G-

 

 

 

 

80...110s

 

 

 

 

 

 

COM

 

 

LEN

 

+

 

 

 

 

 

 

 

 

 

 

CW

 

 

 

 

 

 

LR 92800

 

 

 

 

 

3art Number: 33ZCFANTRM

 

 

COW

 

+

J2B

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

S/N:

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NEMA 2

 

 

 

 

 

Bus#:

 

 

 

 

 

 

 

 

 

 

 

LISTED

 

 

 

 

 

Element#:

 

 

 

 

 

3

 

 

 

 

 

94D5

 

 

 

 

 

 

 

 

 

 

 

J3

SRVC

 

ANTI-

 

TENP IND &

 

 

 

 

 

Unit#:

 

 

 

 

 

 

 

 

REG. EQUIP.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Class 2 Supply

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ROTATION

 

 

 

 

24VAC/DC

 

 

 

J6

 

 

 

 

 

 

 

TAB

 

 

 

 

50/60 Hz

 

HIGH

 

CCW COM CW HEAT1

24VAC

HEAT2

 

3 J1

24VAC

G

 

 

5K

 

3VA 2W

 

 

 

 

 

 

 

1

 

 

+

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

-

 

 

 

 

COM

 

 

 

1

 

 

 

6

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ACTUATOR

 

WIP

 

1

2

3

 

 

 

 

 

 

 

 

 

 

 

yel

 

 

 

 

 

 

 

 

 

 

 

 

 

RELEASE

blu

ora

blk

red

wht

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

BUTTON

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

HIGH PRESSURE TUBING ROUTING

NOTE: Actuator clamp accepts dampers shafts with the following characteristics: Round — 1/4-in. to 5/8-in.

(6 to 16 mm) Square — 1/4-in. to 7/16-in.

(6 to 11 mm)

Damper shaft must be a minimum of 1.5-in. (38 mm) long.

Fig. 2 — Zone Controller Physical Details (33ZCFANTRM Shown)

R E L A T I V E H U M I D I T Y S E N S O R — The 33AMSENRHS000 relative humidity sensor is required for zone humidity control (dehumidification).

NOTE: The relative humidity sensor and CO2 sensor cannot be used on the same zone controller.

INDOOR AIR QUALITY (CO2) SENSOR — An indoor air quality sensor is required for optional demand control ventilation. The CGCDXSEN002A00 CO2 Sensor is an indoor, wall mounted sensor with an LED display. The CGCDXSEN003A00 CO2 Sensor is an indoor, wall mounted sensor without display.

NOTE: The relative humidity sensor and CO2 sensor cannot be used on the same zone controller.

Mount Zone Controller

LOCATION — The zone controller must be mounted on the air terminal’s damper actuator shaft. For service access, there should be at least 12 in. of clearance between the front of the zone controller and adjacent surfaces. Refer to Fig. 6.

MOUNTING — Perform the following steps to mount the zone controller:

1.Visually inspect the damper and determine the direction in which the damper shaft moves to open the damper — clockwise (CW) or counterclockwise (CCW). Refer to Fig. 7.

If the damper rotates CCW to open, it does not require any configuration changes.

If the damper rotates CW to open, then the damper actuator logic must be reversed. This is done in the software when performing system start-up and damper calibration test. Do not attempt to change damper rotation by changing wiring. This will upset the damper position feedback potentiometer readings.

2.Rotate the damper shaft to the fully closed position. Note direction of rotation.

3.Press the release button on the actuator and rotate the clamp in the same direction that was required to close the damper in Step 2.

4.Press the release button on the actuator and rotate the actuator back one position graduation. Release the button and lock the actuator in this position.

5.Mount the zone controller to the terminal by sliding the damper shaft through the actuator clamp assembly. Secure the zone controller to the duct by installing the screw provided through the grommet in the antirotation tab. Be sure the floating grommet is in the center of the slot. Failure to center the grommet may cause the actuator to stick or bind.

6.Tighten the actuator clamp assembly to the damper shaft. Secure by tightening the two 10-mm nuts.

7.If the damper has less than 90 degrees of travel between the fully open and fully closed positions, then a mechanical stop must be set on the actuator. The mechanical stop prevents the damper from opening past the maximum damper position. To set the mechanical stop, perform the following procedure:

a.Press the actuator release button and rotate the damper to the fully open position.

b.Using a Phillips screwdriver, loosen the appropriate stop clamp screw.

c.Move the stop clamp screw so that it contacts the edge of the cam on the actuator. Secure the stop clamp screw in this position by tightening the screw.

8.Verify that the damper opens and closes. Press the actuator release button and rotate the damper. Verify that the damper does not rotate past the fully open position. Release the button and lock the damper in the fully open position.

801

4

Carrier 33ZCSECTRM, 33ZCFANTRM, 33ZCVAVTRM User Manual

 

 

 

 

LOW

 

 

 

 

 

15

 

 

16

 

 

 

 

C

 

US

 

 

 

RH/IAQ

+24V

 

 

 

 

 

 

 

 

SPT

 

 

 

 

 

 

 

 

 

 

GND

 

 

 

 

 

 

 

1

J6

 

FAN AC

 

GND

 

 

 

 

 

 

 

 

SECFLOW

 

 

 

 

 

 

1 2

 

FAN

SAT

 

 

 

 

 

 

 

 

 

24VAC

J4

+10V

T56

 

 

 

 

 

 

 

 

J7

 

DMPPOS

 

0

 

 

1

 

 

 

 

N/A

GND

 

 

 

 

 

 

 

HEAT3

 

GND

 

 

 

 

3

 

 

 

 

 

 

 

 

 

 

 

 

 

PAT

 

 

 

 

 

 

 

 

 

 

 

TEST

 

 

 

 

 

 

 

 

 

 

 

REMOTE

 

 

 

 

 

 

®

 

 

 

 

GND

HF23BJ042

 

 

 

ZONE Controller

 

 

 

 

 

 

1

 

 

2

Made in Switzerland

 

 

®

 

1

by Belimo Automation

35 in-lb (4 Nm)

 

 

3

J8

DMPSEC

 

CCNJ2A

G-

3

G-

 

 

 

1

 

 

CW

1

 

LEN

 

 

80...110s

 

 

 

 

 

 

 

 

+

 

 

 

 

 

 

 

 

 

COM

 

+

 

LR 92800

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Part Number: 33ZCFANTRM

 

 

COW

 

 

J2B

 

 

 

 

 

 

 

 

 

 

 

 

 

 

S/N:

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NEMA 2

 

 

 

Bus#:

 

 

 

 

 

 

 

 

 

LISTED

 

 

 

Element#:

 

 

 

 

 

3

 

 

 

94D5

 

 

 

 

 

 

 

 

 

J3

SRVC

 

TENP IND &

 

 

 

Unit#:

 

 

 

 

 

 

 

REG. EQUIP.

 

 

 

 

 

 

 

 

 

 

 

 

Class 2 Supply

 

 

 

 

 

 

 

 

 

 

 

 

 

 

24VAC/DC

 

 

 

J6

 

 

 

 

 

 

 

 

50/60 Hz

 

HIGH

 

CCW COM CW HEAT1

24VAC

HEAT2

 

3 J1

24VAC

G

5K

3VA 2W

 

 

 

 

 

 

 

1

 

 

+

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

-

 

COM

 

 

 

1

 

 

 

6

 

 

 

 

 

 

 

 

 

 

 

 

 

 

WIP

1

2

3

 

 

 

 

 

 

 

 

 

 

yel blu ora

blk red wht

Fig. 3 — VAV Fan Terminal Zone Controller

LOW

US

C

0

 

 

 

1

 

 

 

 

 

 

 

 

®

HF23BJ042

 

 

 

ZONE Controller

Made in Switzerland

 

 

®

by Belimo Automation

35 in-lb (4 Nm)

 

 

 

 

 

 

 

 

80...110s

 

 

 

 

LR 92800

 

 

 

Part Number: 33ZCVAVTRM

 

 

 

 

 

 

 

 

 

 

S/N:

 

 

NEMA 2

 

 

 

Bus#:

 

 

LISTED

 

 

 

Element#:

 

 

94D5

 

 

 

 

 

TENP IND &

 

 

 

Unit#:

 

 

REG. EQUIP.

 

 

 

 

 

Class 2 Supply

 

 

 

 

 

 

 

24VAC/DC

 

 

 

J6

 

50/60 Hz

 

HIGH

1

CCW COM CW HEAT1 24VAC HEAT2

5K

3VA 2W

 

 

 

 

 

 

 

 

 

 

 

 

COM

 

 

 

 

 

WIP

1

2

3

 

 

 

yel blu ora

blk

red

wht

 

 

 

6

15

 

 

16

RH/IAQ

+24V

SPT

 

 

GND

 

 

GND

SECFLOW

SAT

 

J4

+10V

 

T56

 

DMPPOS

 

GND

 

GND

 

PAT

 

TEST

 

 

GND REMOTE

1

 

1

2

1

 

 

 

LEN

 

CCNJ2A

 

+

G-

3

G-

 

+

J2B

 

 

 

 

3

 

 

 

 

J3

SRVC

 

1

 

24VAC

+

3

J1

G

 

 

 

-

Fig. 4 — Single Duct Air Terminal Zone Controller

5

801

LOW

®

 

 

 

C

 

US

6

 

 

 

 

 

 

J1

0

 

 

1

 

 

 

 

 

 

 

 

®

1

 

 

 

 

 

 

H F 2 3 B J 0 4 2

 

 

ZONE Controller

M a d e i n S w i t z e r l a n d

 

 

 

 

 

 

b y B e l i m o A u t o m a t i o n

35 in-lb (4 Nm)

 

 

 

 

 

 

 

 

80...110s

 

 

 

 

L R 9 2 8 0 0

 

 

Part Number: 33ZCSECTRM

 

 

 

 

 

 

 

 

S/N:

 

 

 

NEMA2

 

 

 

 

 

 

LISTED

 

 

 

 

 

 

94D5

 

 

 

 

 

 

TEMP. IND. & UL

 

 

 

 

 

 

REG. EQUIP.

 

 

Unit#:

 

 

 

Class 2 Supply

24VAC/DC

 

 

 

 

 

 

 

 

 

50/60Hz

 

 

J2

 

5K

3VA

2W

HIGH

 

CCW COM CW N/A N/A N/A

 

 

 

 

 

 

COM

 

 

 

 

 

WIP

1

2

3

1

 

6

yel blu ora

blk

red

wht

 

 

 

GND

D

OUT

TPUT

 

FLOW

+10V

OV

CW

 

COM

MMON

 

CCW

CW

 

 

J1

Fig. 5 — Secondary Terminal Zone Controller

ALLOW 12” CLEARANCE FOR SERVICE

ACCESS TO CONTROL BOX

3” REF.

ZONE

CONTROLLER

END VIEW INLET

Fig. 6 — Service Clearance for Zone Controller Mounting

6

AIR

FLOW

CW TO OPEN, CCW TO CLOSE

AIR

FLOW

CCW TO OPEN, CW TO CLOSE

Fig. 7 — Damper Configuration

Connect the Power Transformer — An individual, field-supplied, 24 vac power transformer is recommended for each zone controller. If multiple zone controllers are powered from one power transformer (100 va maximum for UL [Underwriters’ Laboratories] Class 2 conformance), maintain polarity on the power input terminals. All transformer secondaries are required to be grounded. Use only stranded copper conductors for all wiring to the zone controller. Wiring connections must be made in accordance with NEC (National Electrical Code) and local codes. Ground the transformer at the transformer location. Provide an 18-gage, green, chassis ground wire at the terminal.

The power supply is 24 vac ± 10% at 40 va (50/60 Hz).

For 33ZCVAVTRM zone controllers, the power requirement sizing allows for accessory water valves and for electric heat contactor(s). Water valves are limited to 15 va on both two-position and modulating hot water. The electric heat contactor(s) are limited to 10 va (holding) each.

For 33ZCFANTRM zone controllers, the power requirement sizing allows for accessory water valves and for the fan contactor. Water valves are limited to 8 va on both two-position and modulating hot water. The fan contactor is limited to 11 va (holding).

NOTE: If a water valve or electric heat contactor exceeds these limits, or external contactors are required for electric heat, then it is recommended a 60 va transformer be used. The maximum rating for any output is 20 va.

NOTE: Do not run sensor or communication wiring in the same conduit with line-voltage wiring.

NOTE: An accessory conduit box (part no. 33ZCCONBOX) is available for conduit wiring connections to the zone controller.

Perform the following steps to connect the power transformer:

1.Install the field-supplied transformer in an electrical enclosure that conforms to NEC and local codes.

2.Connect 24 vac from the transformer as shown in the applicable wiring diagram (Fig. 8A-J).

Connect Airflow Pickups — The zone controller determines velocity pressure by obtaining the difference between high and low duct pressure from two airflow pickups. The pickups are connected to barb fittings on the zone controller with 1/4-in. polyethylene tubing. All piping for this purpose must conform to local codes.

Figure 9 indicates the positions of the two barb fittings.

Perform the following steps to install and connect the airflow pickups:

1.Select a location on the air handler’s supply air duct where the airflow pickups will be installed. The location should be one where there are at least three duct diameters of straight duct upstream of the pickups. If this requirement is not met, stable airflow measurements may not be possible.

2.Mount the field-supplied airflow pickup(s) in the duct, following the manufacturer's directions. Two individual pickups may be used, one for high pressure airflow and one for low pressure airflow. A dual pickup, which combines the two functions, may also be used. When using individual pickups, make sure that the one for high pressure airflow faces upstream, in the direction the air is coming from, and the one for low pressure airflow faces downstream, in the direction the air is going to.

3.Use field-supplied 1/4-in. tubing (rated for the application) to connect the high pressure airflow pickup to barb fitting P1 on the pressure transducer. At the zone controller, the P1 fitting is on the side with the filter installed. Be careful to avoid sharp bends in the tubing, because malfunctions may occur if the tubing is bent too sharply. Use at least 2 ft of tubing for reading stability.

4.Use field-supplied 1/4-in. tubing (rated for the application) to connect the low pressure airflow pickup to barb fitting P2 on the pressure transducer. Be careful to avoid sharp bends in the tubing, because malfunctions may occur if the tubing is bent too sharply. Use at least 2 feet of tubing for stability.

7

303

 

 

 

 

 

 

 

 

+24V

 

 

 

 

 

 

 

 

 

 

RH/IAQ

SPT

SPT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

GND

 

 

 

 

 

 

 

 

 

 

 

 

GND

SAT

 

 

 

 

 

 

 

 

 

SECFLOW

SAT

 

 

 

 

 

 

Low

 

 

Y

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

+10V

 

 

 

 

 

 

 

 

 

 

 

 

T56

 

 

 

 

 

 

 

 

 

 

DMPPOS

 

 

 

 

 

 

 

 

 

 

 

Bl

GND

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

GND

 

 

 

 

 

 

 

 

 

 

 

Or

PAT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0

1

 

 

 

N/A

 

 

 

 

 

 

 

 

 

REMOTE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

GND

 

 

 

HF23BJ042

 

 

 

 

 

 

 

 

 

Made in Switzerland

 

 

 

 

 

 

 

 

 

 

By Belimo Automation

 

35 in-lb(4Nm)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

80...110s

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(+)

R

 

 

 

 

 

 

 

 

 

 

(GND)

W

 

 

 

 

 

 

 

 

 

 

(-)

B

Not used

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

24VAC/DC

 

 

 

 

 

 

 

 

 

 

50/60Hz

Hi

 

 

 

 

CCN comunications

8

 

 

3VA 2W

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CCN comunications

 

 

 

com

 

 

 

 

 

 

 

 

 

 

 

 

 

W

B

R

HEAT1 24VAC HEAT2

 

24 VAC

Line Voltage

Yel

Blu

Ora

Blk

Red

Wht

 

 

 

 

TRAN

 

 

 

 

 

 

 

 

 

 

 

TRANSFORMER

 

 

 

 

 

 

 

 

 

 

 

GROUND

 

 

 

 

 

 

 

 

 

 

 

TERMINAL

 

 

 

 

 

 

 

 

 

 

 

GROUND

 

 

LEGEND

 

 

 

 

 

 

 

 

 

CCN

Carrier Comfort Network

SAT

Supply-Air Temperature Sensor

SPT

Space Temperature Sensor

TRAN

Transformer

 

Field Wiring

 

Factory Wiring

Fig. 8A — Zone Controller Wiring — Single Duct Air Terminal, Cooling Only

 

LEGEND

 

CCN

Carrier Comfort Network

 

HWV

Hot Water Valve

 

SAT

Supply-Air Temperature Sensor

 

SPT

Space Temperature Sensor

 

TRAN

Transformer

 

 

Field Wiring

HWV

 

Factory Wiring

 

*Normally open or normally closed valve may be used.

 

 

 

 

 

 

 

 

 

 

+24V

 

 

 

 

 

 

 

 

 

 

RH/IAQ

 

SPT

 

 

 

 

 

 

 

 

 

 

SPT

 

 

 

 

 

 

 

 

 

GND

 

 

 

 

 

 

 

 

 

 

 

 

GND

SAT

 

 

 

 

 

 

 

 

 

SECFLOW

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Low

 

 

 

SAT

 

 

 

 

 

 

 

 

 

+10V

 

 

 

 

 

 

 

 

 

 

 

Y

T56

 

 

 

 

 

 

 

 

 

 

DMPPOS

 

 

 

 

 

 

 

 

 

 

 

Bl

GND

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

GND

 

 

 

 

 

 

 

 

 

 

 

Or

PAT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0

1

 

 

 

N/A

 

 

 

 

 

 

 

 

 

REMOTE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

GND

 

 

9

HF23BJ042

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Made in Switzerland

 

 

 

 

 

 

 

 

 

 

By Belimo Automation

 

35 in-lb(4Nm)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

80...110s

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(+)

R

 

 

 

 

 

 

 

 

 

 

(GND)

W

 

 

 

 

 

 

 

 

 

 

(-)

B

 

 

 

 

 

 

 

 

 

 

 

Not used

 

 

 

 

 

24VAC/DC

 

 

 

 

 

 

 

 

 

 

50/60Hz

Hi

 

 

 

CCN comunications

 

 

 

 

3VA 2W

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CCN comunications

 

 

 

 

com

 

 

 

 

 

 

 

 

 

 

 

 

 

W

B

R

HEAT1 24VAC HEAT2

24 VAC

Line Voltage

 

 

 

 

 

 

 

 

Yel

Blu

Ora

Blk

Red

Wht

 

 

 

TRAN

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

TRANSFORMER

 

 

 

 

 

 

 

 

 

 

GROUND

 

 

 

 

 

 

 

 

 

 

TERMINAL

 

 

 

 

 

 

 

 

 

 

 

GROUND

 

303

Fig. 8B — Zone Controller Wiring — Single Duct Air Terminal, Two-Position Hot Water Heat

303

10

 

LEGEND

 

 

 

CCN

Carrier Comfort Network

 

 

 

HWV

Hot Water Valve

 

 

 

SAT

Supply-Air Temperature Sensor

 

 

 

SPT

Space Temperature Sensor

 

 

 

TRAN

Transformer

 

 

 

 

Field Wiring

COM

CL

OP

 

Factory Wiring

 

 

 

HWV

*Required for some spring return modulating valves.

 

 

 

 

 

 

 

 

 

+24V

 

 

 

 

 

 

 

 

 

 

RH/IAQ

SPT

SPT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

GND

 

 

 

 

 

 

 

 

 

 

 

 

GND

 

 

 

 

 

 

 

Low

 

 

SECFLOW

SAT

SAT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

+10V

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Y

T56

 

 

 

 

 

 

 

 

 

 

DMPPOS

 

 

 

 

 

 

 

 

 

 

 

Bl

GND

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

GND

 

 

 

 

 

 

 

 

 

 

 

Or

PAT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0

1

 

 

 

 

N/A

 

 

 

 

 

 

 

 

 

 

REMOTE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

GND

 

 

 

HF23BJ042

 

 

 

 

 

 

 

 

 

Made in Switzerland

 

 

 

 

 

 

 

 

 

 

By Belimo Automation

35 in-lb(4Nm)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

80...110s

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(+)

R

 

 

 

 

 

 

 

 

 

 

(GND)

W

 

 

 

 

 

 

 

 

 

 

(-)

B

Not used

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

24VAC/DC

 

 

 

 

 

 

 

 

 

 

50/60Hz

Hi

 

 

 

 

CCN comunications

 

 

 

3VA

2W

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CCN comunications

 

 

 

com

 

 

 

 

 

 

 

 

 

 

 

 

 

W

B

R

HEAT1 24VAC HEAT2

 

24 VAC

Line Voltage

 

 

 

 

 

 

 

 

 

 

Yel

Blu

Ora

Blk

Red

Wht

 

 

 

 

TRAN

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

TRANSFORMER

 

 

 

 

 

 

 

 

 

 

GROUND

 

 

 

 

 

 

 

 

 

 

 

TERMINAL

 

 

 

 

 

 

 

 

 

 

 

GROUND

 

Fig. 8C — Zone Controller Wiring — Single Duct Air Terminal, Modulating Hot Water Heat

 

LEGEND

 

 

 

 

 

 

 

 

 

 

 

CCN

Carrier Comfort Network

 

 

 

 

 

 

 

 

 

 

 

H

Heater Relay

 

 

 

 

 

 

 

 

 

 

 

HWV

Hot Water Valve

 

 

 

 

 

 

 

 

 

 

 

SAT

Supply-Air Temperature Sensor

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SPT

Space Temperature Sensor

 

 

 

H2

 

 

 

 

H1

 

 

 

 

 

TRAN

Transformer

 

 

 

 

 

 

 

 

 

 

 

 

Field Wiring

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Factory Wiring

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

+24V

 

 

 

 

 

 

 

 

 

 

 

RH/IAQ

 

 

SPT

 

 

 

 

 

 

 

 

 

 

SPT

 

 

 

 

 

 

 

 

 

 

GND

 

 

 

 

 

 

 

 

 

 

 

 

 

GND

 

SAT

 

 

 

 

 

 

Low

 

 

SECFLOW

SAT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Y+10V

 

 

 

 

 

 

 

 

 

 

 

 

T56

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

DMPPOS

 

 

 

 

 

 

 

 

 

 

 

 

Bl

GND

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

GND

 

 

 

 

 

 

 

 

 

 

 

 

Or

PAT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0

 

1

 

 

 

 

N/A

 

 

 

 

 

 

 

 

 

 

 

REMOTE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

GND

 

 

 

11

HF23BJ042

 

 

 

 

 

 

 

 

 

 

 

Made in

 

35 in-lb(4Nm)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Switzerland

 

 

 

 

 

 

 

 

 

 

 

80...110s

 

 

 

 

 

 

 

 

 

By Belimo

 

 

 

 

 

 

 

 

 

 

Automation

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(+)

R

 

 

 

 

 

 

 

 

 

 

 

(GND)

W

 

 

 

 

 

 

 

 

 

 

 

(–)

B

Not Used

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

24VAC/DC

 

 

 

 

 

 

 

 

 

 

 

50/60Hz

Hi

 

 

 

 

CCN

 

 

 

 

 

3VA

2W

 

 

 

 

comunications

 

 

 

 

 

 

 

 

 

 

 

CCN

 

 

 

 

 

com

 

 

 

 

 

 

comunications

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

W

B

R

HEAT1 24VAC HEAT2

 

24 VAC

Line

 

 

 

 

 

 

 

Voltage

 

Yel

Blu

Ora

Blk

Red

Wht

 

 

 

 

 

 

 

 

 

 

TRAN

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

TRANSFORMER

 

 

 

 

 

 

 

 

 

 

 

GROUND

 

 

 

 

 

 

 

 

 

 

 

 

TERMINAL

 

 

 

 

 

 

 

 

 

 

 

 

GROUND

 

Fig. 8D — Zone Controller Wiring — Single Duct Air Terminal, Staged Electric Heat (2 Stages)

801

303

12

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

LEGEND

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CCN

Carrier Comfort Network

 

 

 

 

 

 

 

 

 

 

 

 

 

 

H

Heater Relay

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SAT

Supply-Air Temperature Sensor

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SPT

Space Temperature Sensor

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

H3

 

 

 

 

H2

 

 

 

 

H1

TRAN

Transformer

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Field Wiring

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Factory Wiring

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NOTE: The VAV fan terminal zone controller is used on single duct air

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

terminals with 3 stages of electric heat.

 

 

 

 

 

 

 

 

 

 

 

+24V

 

 

 

 

 

 

 

 

 

 

 

 

RH/IAQ

 

SPT

 

 

 

 

 

 

 

 

 

 

 

 

SPT

 

 

 

 

 

 

 

 

 

 

 

GND

GND

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SECFLOW

 

SAT

 

 

 

 

 

 

 

 

 

 

 

 

SAT

 

 

 

 

 

 

Low

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

+10V

 

 

 

 

 

 

 

 

 

 

 

 

FAN AC

Y

T56

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

DMPPOS

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Bl

GND

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FAN

GND

 

 

 

 

 

 

 

 

 

 

 

 

 

Or

PAT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0

1

 

 

 

 

24 VAC

N/A

 

 

 

 

 

 

 

 

 

 

REMOTE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

GND

 

 

 

HF23BJ042

 

 

 

 

 

 

Not Used

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Made in Switzerland

 

 

 

 

 

 

 

Heat3

 

 

 

 

By Belimo Automation

 

35 in-lb(4Nm)

 

 

 

 

 

 

 

 

 

 

 

 

80...110s

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

R

R

 

 

 

 

 

 

 

 

 

 

 

CW

W

W

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Second

COM

B

B

 

 

 

 

 

 

 

 

 

 

 

Not used

 

 

 

 

 

 

 

 

 

Damper

 

 

 

 

 

 

 

24VAC/DC

 

 

 

 

CCW

 

 

 

 

 

 

 

50/60Hz

Hi

 

 

 

 

 

 

CCN comunications

 

 

 

3VA 2W

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CCN comunications

 

 

 

com

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

W

B

R

HEAT1 24VAC HEAT2

 

 

 

24 VAC

Line Voltage

 

 

 

 

 

 

 

 

 

 

 

 

Yel

Blu

Ora

Blk

Red

Wht

 

 

 

 

 

 

TRAN

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

TRANSFORMER

 

 

 

 

 

 

 

 

 

 

 

 

 

GROUND

 

 

 

 

 

 

 

 

 

 

 

 

 

TERMINAL

 

 

 

 

 

 

 

 

 

 

 

 

 

GROUND

 

Fig. 8E — Zone Controller Wiring — Single Duct Air Terminals, Staged Electric Heat (3-Stage)

LEGEND

CCN —

Carrier Comfort Network

 

Fan

 

 

 

 

SPT —

Space Temperature Sensor

 

 

 

 

Contactor

 

 

 

 

TRAN — Transformer

 

 

 

 

 

 

 

 

M

 

 

 

Field Wiring

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Factory Wiring

 

 

 

 

Fan Motor

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Line

Voltage

 

 

 

 

 

 

 

 

 

 

 

 

+24V

 

 

 

 

 

 

 

 

 

 

 

 

 

RH/IAQ

 

 

SPT

 

 

 

 

 

 

 

 

 

 

 

 

SPT

 

 

 

 

 

 

 

 

 

 

 

 

GND

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

GND

 

 

 

 

 

 

 

 

Low

 

 

 

 

SECFLOW

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SAT

 

 

 

 

 

 

 

 

 

 

 

 

Y+10V

 

 

 

 

 

 

 

 

 

 

 

 

 

 

T56

 

 

 

 

 

 

 

 

 

 

 

 

FAN

 

 

 

 

 

 

 

 

 

 

 

 

 

DMPPOS

 

 

 

 

 

 

 

 

 

 

 

 

 

AC

 

 

 

 

 

 

 

 

 

 

 

 

 

Bl

GND

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FAN

GND

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Or

PAT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0

 

1

 

 

 

 

 

24 VAC

N/A

 

 

 

 

 

 

 

 

 

 

 

 

REMOTE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

13

 

 

 

 

 

 

 

 

 

 

GND

 

 

 

HF23BJ042

 

 

 

 

 

 

Not

 

 

 

 

 

 

 

 

 

 

 

Used

 

 

 

 

 

Made in Switzerland

 

35 in-lb(4Nm)

 

 

 

 

Heat3

 

 

 

 

 

By Belimo Automation

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

80...110s

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(+)

R

 

 

 

 

 

 

 

 

 

 

 

 

CW

 

W

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

COM

(GND)

 

 

 

 

 

 

 

 

 

 

 

 

Second

 

B

 

 

 

 

 

 

 

 

 

 

 

 

(–)

Not Used

 

 

 

 

 

 

 

 

 

 

Damper

 

 

 

 

 

 

 

24VAC/DC

 

 

 

 

CCW

 

 

CCN

 

 

 

 

 

50/60Hz

Hi

 

 

 

 

 

 

 

 

 

 

 

3VA

2W

 

 

 

 

 

 

comunications

 

 

 

 

 

 

 

 

 

 

 

 

 

CCN

 

 

 

 

 

com

 

 

 

 

 

 

 

 

comunications

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

W

B

R

HEAT1 24VAC HEAT2

 

 

 

24 VAC

Line

 

Yel

Blu

Ora

Blk

Red

Wht

 

 

 

 

 

 

 

Voltage

 

 

 

 

 

 

 

TRAN

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

TRANSFORMER

 

 

 

 

 

 

 

 

 

 

 

 

 

GROUND

 

TERMINAL

GROUND

Fig. 8F — Zone Controller Wiring — Fan Powered Terminals, Cooling Only

801

801

14

 

LEGEND

 

CCN

Carrier Comfort Network

 

HWV

Hot Water Valve

Fan Contactor

SAT

Supply-Air Temperature Sensor

SPT

Space Temperature Sensor

M

TRAN

Transformer

 

Field Wiring

 

 

Factory Wiring

Fan Motor

 

 

 

 

 

 

 

HWV

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Line

 

 

 

 

 

 

 

 

 

 

 

 

 

Voltage

 

 

 

 

 

 

 

 

 

 

 

+24V

 

 

 

 

 

 

 

 

 

 

 

 

RH/IAQ

 

 

SPT

 

 

 

 

 

 

 

 

 

 

 

SPT

 

 

 

 

 

 

 

 

 

 

 

GND

 

 

 

 

 

 

 

 

 

 

 

 

 

 

GND

 

 

 

 

 

 

 

 

 

 

 

 

SECFLOW

SAT

 

SAT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Low

 

 

 

 

+10V

 

 

 

 

 

 

 

 

 

 

 

FAN AC

Y

T56

 

 

 

 

 

 

 

 

 

 

 

 

DMPPOS

 

 

 

 

 

 

 

 

 

 

 

 

 

Bl

GND

 

 

 

 

 

 

 

 

 

 

 

FAN

GND

 

 

 

 

 

 

 

 

 

 

 

 

 

Or

PAT

 

 

 

0

 

1

 

 

 

 

 

24 VAC

N/A

 

 

 

 

 

 

 

 

 

 

 

REMOTE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

GND

 

 

 

HF23BJ042

 

 

 

 

 

 

 

Not Used

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Made in Switzerland

 

35 in-lb(4Nm)

 

 

 

 

Heat3

 

 

 

 

By Belimo Automation

 

 

 

 

 

 

 

 

 

 

 

80...110s

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(+)

R

 

 

 

 

 

 

 

 

 

 

 

CW

(GND)

W

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Second

COM

(-)

B

 

 

 

 

 

 

 

 

 

 

 

Not Used

 

 

 

 

 

 

 

 

 

Damper

 

 

 

 

 

 

 

24VAC/DC

 

 

 

 

CCW

 

 

CCN

 

 

 

 

50/60Hz

Hi

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

comunications

 

 

 

3VA

2W

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CCN

 

 

 

 

com

 

 

 

 

 

 

 

 

comunications

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

W

B

R

HEAT1 24VAC HEAT2

 

 

 

24 VAC

Line

 

 

 

 

 

 

 

 

Voltage

Yel

Blu

Ora

Blk

Red

Wht

 

 

 

 

 

 

 

 

 

 

 

 

 

TRAN

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

TRANSFORMER

 

 

 

 

 

 

 

 

 

 

 

 

 

GROUND

 

 

 

 

 

 

 

 

 

 

 

 

 

TERMINAL

 

 

 

 

 

 

 

 

 

 

 

 

 

GROUND

 

Fig. 8G — Zone Controller Wiring — Fan Powered Terminals, Two-Position Hot Water Heat

LEGEND

CCN — Carrier Comfort Network

HWV — Hot Water Valve

PAT — Primary Air Temperature Sensor

SAT — Supply-Air Temperature Sensor

SPT — Space Temperature Sensor

TRAN — Transformer

Field Wiring

Factory Wiring

Fan Contactor

M

Fan Motor

COM

CL

OP

24V*

HWV

Line

Voltage

*Required only on Linkage master if on a non-compatible air source.

 

 

 

 

 

 

 

 

 

 

 

+24V

 

 

 

 

 

 

 

 

 

 

 

 

RH/IAQ

 

 

SPT

 

 

 

 

 

 

 

 

 

 

 

SPT

 

 

 

 

 

 

 

 

 

 

 

GND

 

 

 

 

 

 

 

 

 

 

 

 

 

 

GND

 

SAT

 

 

 

 

 

Low

 

 

 

 

SECFLOW

SAT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Y+10V

 

 

 

 

 

 

 

 

 

 

 

 

 

T56

 

 

 

 

 

 

 

 

 

 

 

FAN AC

 

 

 

 

 

 

 

 

 

 

 

 

DMPPOS

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Bl

GND

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FAN

GND

 

 

PAT*

 

 

 

 

 

 

 

 

 

 

Or

PAT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0

 

1

 

 

 

 

 

24 VAC

N/A

 

 

 

 

 

 

 

 

 

 

 

REMOTE

 

 

15

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

GND

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

HF23BJ042

 

 

 

 

 

 

 

Not

 

 

 

 

 

 

 

 

 

 

 

Used

 

 

 

 

Made in Switzerland

 

35 in-lb(4Nm)

 

 

 

 

Heat3

 

 

 

 

By Belimo Automation

 

 

 

 

 

 

 

 

 

 

 

80...110s

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(+)

R

 

 

 

 

 

 

 

 

 

 

 

CW

(GND)

W

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Second

COM

(-)

B

 

 

 

 

 

 

 

 

 

 

 

Not Used

 

 

 

 

 

 

 

 

 

Damper

 

 

 

 

 

 

 

24VAC/DC

 

 

 

 

CCW

 

 

CCN

 

 

 

 

50/60Hz

Hi

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

comunications

 

 

 

3VA

2W

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CCN

 

 

 

 

com

 

 

 

 

 

 

 

 

comunications

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

W

B

R

HEAT1 24VAC HEAT2

 

 

 

24 VAC

Line

 

 

 

 

 

 

 

 

Voltage

Yel

Blu

Ora

Blk

Red

Wht

 

 

 

 

 

 

 

 

 

 

 

 

 

TRAN

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

TRANSFORMER

 

 

 

 

 

 

 

 

 

 

 

 

 

GROUND

 

 

 

 

 

 

 

 

 

 

 

 

 

TERMINAL

 

 

 

 

 

 

 

 

 

 

 

 

 

GROUND

 

801

Fig. 8H — Zone Controller Wiring — Fan Powered Terminals, Modulating Hot Water Heat

801

Fan Contactor

M

H3

H2

H1

Fan Motor

Line

Voltage

 

 

 

 

 

 

 

 

 

 

 

 

+24V

 

 

 

 

 

 

 

 

 

 

 

 

RH/IAQ

SPT

SPT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

GND

GND

 

 

 

 

 

 

 

 

 

 

 

 

 

SAT

 

 

 

 

 

 

Low

 

 

 

 

SECFLOW

SAT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Y+10V

 

 

 

 

 

 

 

 

 

 

 

 

FAN AC

T56

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

DMPPOS

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Bl

GND

 

 

 

 

 

 

 

 

 

 

 

FAN

GND

 

PAT*

 

 

 

 

 

 

 

 

 

 

 

Or

PAT

 

 

0

 

1

 

 

 

 

 

24 VAC

N/A

 

 

 

 

 

 

 

 

 

 

 

REMOTE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

GND

 

 

 

HF23BJ042

 

 

 

 

 

 

 

Not Used

 

 

 

16

 

 

 

 

 

 

 

 

 

 

 

Made in Switzerland

 

35 in-lb(4Nm)

 

 

 

 

Heat3

 

 

 

 

 

 

 

 

 

 

 

 

 

By Belimo Automation

 

 

 

 

 

 

 

 

 

 

 

 

 

80...110s

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(+)

R

 

 

 

 

 

 

 

 

 

 

 

CW

(GND)

W

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Second

COM

(-)

B

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Damper

 

Not Used

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

24VAC/DC

 

 

 

 

CCW

 

CCN

 

 

 

 

 

50/60Hz

Hi

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

comunications

 

 

 

 

3VA

2W

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CCN

 

 

 

 

 

com

 

 

 

 

 

 

 

comunications

 

 

 

 

 

 

W

B

R

HEAT1 24VAC HEAT2

 

 

24 VAC

Line

 

Yel

Blu

Ora

Blk

Red

Wht

 

 

 

 

 

 

Voltage

 

 

 

 

 

 

TRAN

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

TRANSFORMER

 

 

 

 

 

 

 

 

 

 

 

 

 

GROUND

LEGEND

 

 

 

 

 

 

 

 

 

 

 

 

 

TERMINAL

GROUND

*Required only on Linkage master if on a non-compatible air source.

Fig. 8I — Zone Controller Wiring — Fan Powered Terminals, Staged Electric Heat

CCN — Carrier Comfort Network

H — Heater Relay

PAT — Primary Air Temperature Sensor

SAT — Supply-Air Temperature Sensor

SPT — Space Temperature Sensor

TRAN — Transformer

Field Wiring

Factory Wiring

Loading...
+ 36 hidden pages