Installation & Owner’s Manual

Guide d'Installation et d'Utilisation Manual de Instalación y del Propietario

Questions? Help is just a moment away! Preguntas? La ayuda es justa

un momento lejos!

Vous avez des questions? Vous n'avez pas besoin d'aller loin pour trouver de l'aide!

Call: Transfer Switch Helpline

Llamada: Línea Directa de

Interruptor de Transferencia

Appelez: Ligne Directe de

Commutateur de Transfert

1-800-743-4115M-F 8-5 CT

Web: www.briggspowerproducts.com

Models 01917-0&01918-0Part No. 192636GS Rev. 2 (08/17/05)

Briggs & Stratton Power Products Automatic Transfer Switch

Installation and Owner’s Manual

TABLE OF CONTENTS

TABLE OF CONTENTS . . . . . . . . . . . . . . . . . . . . . . . . . . . 2

SAFETY RULES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3

INTRODUCTION. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4

For the Home Owner: . . . . . . . . . . . . . . . . . . . . . . . . 4

For the Installing Dealer/Contractor: . . . . . . . . . . . . . 4

Owner Orientation . . . . . . . . . . . . . . . . . . . . . . . . . . . 4

Installer Responsibilities . . . . . . . . . . . . . . . . . . . . . . . . 5

Equipment Description. . . . . . . . . . . . . . . . . . . . . . . . . 5

INSTALLATION. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5

Unpacking . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5

Delivery Inspection . . . . . . . . . . . . . . . . . . . . . . . . 5

Shipment Contents . . . . . . . . . . . . . . . . . . . . . . . . 5

ESSENTIAL CIRCUIT ISOLATION . . . . . . . . . . . . . . . . . . 6

Mounting Instructions . . . . . . . . . . . . . . . . . . . . . . . . . 7

Power Wiring Interconnections . . . . . . . . . . . . . . . . 7-8

SYSTEM OPERATION. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9

TESTING THE AUTOMATIC TRANSFER SWITCH . . . . 9

Automatic Sequence. . . . . . . . . . . . . . . . . . . . . . . . . . . 9

Utility Fail. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9

Engine Warm-Up . . . . . . . . . . . . . . . . . . . . . . . . . .9

Transfer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9

Utility Pickup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9

Retransfer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9

Engine Cool Down . . . . . . . . . . . . . . . . . . . . . . . . 9

Specifications. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9

Model 01917 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9

Model 01918 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9

When Calling The Factory . . . . . . . . . . . . . . . . . . . . . . 9

TROUBLESHOOTING . . . . . . . . . . . . . . . . . . . . . . . . . . . 11

DIAGRAMS, EXPLODED VIEWS, PARTS LISTS . . . . . 12-15

NOTES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 & 16

WARRANTY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17

Copyright © 2005 Briggs & Stratton Power Products Group, LLC. All rights reserved. No part of this material may be reproduced or transmitted in any form by any means without the express written permission of Briggs & Stratton Power Products Group, LLC.

2

Briggs & Stratton Power Products Automatic Transfer Switch

Installation and Owner’s Manual

SAVE THESE INSTRUCTIONS

SAFETY RULES

This is the safety alert symbol. It is used to alert you to potential personal injury hazards. Obey all safety messages that follow this symbol to avoid possible injury or death.

The safety alert symbol () is used with a signal word (DANGER, CAUTION,WARNING), a pictorial and/or a safety message to alert you to hazards.DANGER indicates a hazard which, if not avoided,will result in death or serious injury.WARNING indicates a hazard which, if not avoided,could result in death or serious injury.CAUTION indicates a hazard which, if not avoided,might result in minor or moderate injury.CAUTION, when usedwithout the alert symbol, indicates a situation that could result in equipment damage. Follow safety messages to avoid or reduce the risk of injury or death.

The manufacturer cannot possibly anticipate every possible circumstance that might involve a hazard.The warnings in this manual, and the tags and decals affixed to the unit are, therefore, not all-inclusive.If you use a procedure, work method or operating technique that the manufacturer does not specifically recommend, you must satisfy yourself that it is safe for you and others.You must also make sure that the procedure, work method or operating technique that you choose does not render the transfer switch unsafe.

WARNING

Only qualified electricians should attempt installation of this system, which must strictly comply with applicable codes, standards and regulations.

WARNING

Low voltage wire cannot be installed in same conduit as power voltage wiring.

Failure to follow above warning could cause personal injury, damage and/or malfunction of equipment.

WARNING

Failure to properly ground transfer switch can result in electrocution.

DO NOT touch bare wires or receptacles.

DO NOT use transfer switch with worn, frayed, bare or otherwise damaged wiring.

DO NOT handle electrical cords while standing in water, while barefoot, or while hands or feet are wet.

If you must work around a unit while it is operating, stand on an insulated dry surface to reduce shock hazard.

DO NOT allow unqualified persons or children to operate or service transfer switch.

In case of an accident caused by electrical shock, immediately shut down the source of electrical power and contact local authorities. Avoid direct contact with the victim.

WARNING

Transfer Switch contains high voltage that can cause personal injury or death.

Despite the safe design of the transfer switch, operating this equipment imprudently, neglecting its maintenance or being careless can cause possible injury or death.

CAUTION

Improper treatment of transfer switch can damage it and shorten its life.

Use transfer switch only for intended uses.

If you have questions about intended use, ask dealer or contact Briggs and Stratton Power Products.

DO NOT expose transfer switch to excessive moisture, dust, dirt, or corrosive vapors.

Remain alert at all times while working on this equipment. NEVER work on the equipment when you are physically or mentally fatigued.

If connected devices overheat, turn them off and turn off their circuit breaker/fuse.

3

Briggs & Stratton Power Products Automatic Transfer Switch

Installation and Owner’s Manual

INTRODUCTION

Thank you for your purchase of this Briggs & Stratton Power Products Automatic Transfer Switch.This product is intended for use with Briggs & Stratton Home Standby Generator sets ONLY.This is an optional home standby system which provides an alternate source of electric power and to serve loads such as a gas furnace, refrigeration and communication systems that, when stopped during any power outage, could cause discomfort, or the like.This product DOES NOT qualify for emergency standby as defined by NFPA 70 (NEC).

Briggs and Stratton Power Products (BSPP) has made every effort to provide for a safe, streamlined and cost-effectiveinstallation. Each installation is unique, it is impossible to know of and advise of all conceivable procedures and methods by which installation might be achieved.We do not know all possible hazards and/or the results of each method or procedure. For these reasons,

Only licensed electrical contractors should install transfer switches.

Installations must strictly comply with all applicable federal, state and local codes, standards and regulations.

Your BSPP Transfer Switch is supplied with this combined “Installation and Owner’s Manual”.This is an important document and should be retained by the owner after the installation has been completed.

Every effort has been expended to make sure that the information in this manual is both accurate and current. However, the manufacturer reserves the right to change, alter or otherwise improve the system at any time without prior notice.

For the Home Owner

To help you make informed choices and communicate effectively with your installation contractor(s),

Read and understand the

Owner Orientation Section of this manual BEFORE contracting or starting your transfer switch installation.

To arrange for proper installation, contact the store at which you purchased your BSPP Transfer Switch, your dealer, or your utility power provider.

The Transfer Switch Warranty is VOID unless the system is installed by a licensed electrical professional.

For the Installing Dealer/Contractor

Check federal, state and local codes for questions on installation.

If you need more information about the transfer switch, call 1-800-743-4115,between 8:00 AM and 5:00 PM CT.

Owner Orientation

The illustrations are for typical circumstances and are meant to familiarize you with the installation options available with your transfer switch.

Local codes, appearance, and distances are the factors that must be considered when negotiating with an installation professional. As the distance from the existing electrical service increases, compensation in wiring materials must be allowed for.This is necessary to comply with local codes and overcome electrical voltage drops.

The factors mentioned above will have a direct effect on the overall price of your transfer switch installation.

NOTE: Your installer must check local codes AND obtain permits before installing the system.

Read and follow the instructions given in this manual.

Follow a regular schedule in caring for and using your transfer switch, as specified in the manual.

4

Briggs & Stratton Power Products Automatic Transfer Switch

Installation and Owner’s Manual

Installer Responsibilities

Read and observe the safety rules.

Read and follow the instructions given in this manual.

Check federal, state and local codes.

Ensure generator is not overloaded with selected loads.

Equipment Description

These new generation transfer switches are intended to operate compatible electrical loads of normal residential installations.The load is connected either to utility power (normal) or home standby power (generator).The transfer switch monitors utility and generator voltages and will automatically connect to the appropriate source of power.

Major components of the transfer switch are 2 pole contactor switches, control circuit board, fused utility terminals and interconnecting wiring.

The transfer switch is coil-operatedfrom utility or generator inputs and contains suitable electrical interlock switches to eliminate the possibility of connecting the utility service to the generator output. It has ratings capable of switching generator power into the residence.

The control module circuit board has active circuits sensing utility and generator voltages. It creates a signal for the generator start-up,switch transfer, retransfer when utility is restored and generator cool down periods.The control board also contains red and green lights indicating the power sources available.

INSTALLATION

Unpacking

Delivery Inspection

After removing the carton, carefully inspect the transfer switch components for any damage that may have occurred during shipment.

IMPORTANT: If loss or damage is noted at time of delivery, have the person(s) making delivery note all damage on the freight bill and affix his signature under the consignor's memo of loss or damage. If loss or damage is noted after delivery, contact the carrier for claim procedures. Freight damaged parts are not warranted.

Shipment Contents

Automatic Power Transfer Switch

Installation and Owner’s Manual

5

Briggs & Stratton Power Products Automatic Transfer Switch

Installation and Owner’s Manual

ESSENTIAL CIRCUIT

Ensure that the total of the selected load circuits fed by this transfer switch are within the generator's rated capacity.

ISOLATION

Essential electrical loads are loads that will be powered by the Home Generator System. Essential loads are grouped together and wired into the transfer switch.

TO THE INSTALLER: Consult with Home Generator System owner(s) to discuss their “Selection of Essential Circuits”, described in the owner’s manual.

Figure 1 — Typical System Diagram with Essential Circuits

The following requirements apply to this type of isolation system:

The Automatic Transfer Switch is installed after the main distribution panel.

The Automatic Transfer Switch has a load rating of

50 Amps.This is the maximum load rating of the essential loads.

All wiring must conform to national, state and local codes.

The illustration in Figure 1 depicts the Home Generator System and assumes the utility is supplying 120/240 Volt, single-phaseelectrical service.

 

To Utility Power

 

 

Watt Meter

 

 

Main Distribution Panel

To Range

 

 

240V

 

 

To Water Heater

To Air Conditioner (240V)

 

To Other Circuits (120V)

 

Automatic Transfer Switch

 

(in normal position)

To Briggs & Stratton

 

 

Home Generator Unit

 

 

120V To Microwave

 

 

120 V To Bathroom

120V To Freezer

 

 

 

240V To Well Pump

To Refrigerator

 

 

 

120V To Sump Pump

To Lights

120V

 

To Furnace Blower

 

 

Neutral

 

 

6

 

Briggs & Stratton Power Products Automatic Transfer Switch

Installation and Owner’s Manual

Mounting Guidelines

The Model 01917 Automatic Transfer Switch is enclosed in a NEMA Type 1 enclosure suitable for indoor use only.

The Model 01918 Automatic Transfer Switch is enclosed in a NEMA Type 3R enclosure suitable for indoor/outdoor use.

Guidelines for mounting the Automatic Transfer Switch include:

Model 01918 Automatic Transfer Switch must be installed with minimum NEMA 3R hardware for conduit connections.

Install the switch on a firm, sturdy supporting structure.

To prevent switch contact distortion, level and plumb the enclosure.This can be done by placing washers between the switch enclosure and the mounting surface.

NEVER install the switch where any corrosive substance might drip onto the enclosure.

Protect the switch at all times against excessive moisture, dust, dirt, lint, construction grit and corrosive vapors.

The typical installation of the Automatic Power Transfer Switch is depicted in Figure 2. Discuss layout suggestions/changes with the owner before beginning the system installation process.

Figure 2 — Typical Switch Mounting

Main

 

Distribution

Automatic

Panel

 

Transfer Switch

Power Wiring Interconnections

All wiring must be the proper size, properly supported, of approved insulation qualities, and protected by NEC approved conduit.

Complete the following connections between the generator, transfer switch and main distribution panel (Figure 3, on next page).

CAUTION

Per NEC code, low voltage wire cannot be installed in same conduit as power voltage wiring.

Failure to follow above warning could cause damage and/or malfunction of equipment.

1.Connect utility power supply leads from a two pole breaker installed in the main distribution panel to transfer switch terminals marked “UTILITY CONNECTION”. Use a 50 Amp circuit breaker. Ensure breaker is turned OFF.

2.Connect main distribution panel ground to the transfer switch “GND” bus.

3.Connect main distribution panel neutral lead to transfer switch “NEUTRAL” terminal.

4.Connect generator power supply leads from the generator’s control panel to transfer switch terminals marked “GENERATOR CONNECTION”.

5.Connect generator Neutral from the control panel to the transfer switch “NEUTRAL” terminal.

6.Connect generator “GND” from the control panel to the transfer switch “GND” terminal.

7.Connect generator utility 240V terminals to transfer switch utility 240V terminals.

8.Tighten all wire connections/fasteners to proper torque.

7

Briggs & Stratton Power Products Automatic Transfer Switch

Installation and Owner’s Manual

Figure 3 — Typical Installation Diagram for Transfer Switch

Main

 

Automatic Power Transfer Switch

Home Standby

Rear of

 

 

Distribution

 

 

Neutral

System

Control

Panel

 

 

Generator

Panel

 

 

Bus

 

 

 

 

 

Neutral

Ground

 

Generator

 

 

 

Neutral is

 

 

Bus

Bus

 

 

 

 

White wire

 

 

 

 

 

 

 

 

 

 

Generator

 

 

 

 

 

Connection

 

 

 

Utility

 

 

 

 

 

Connection

 

Wire

 

 

 

 

 

Nut

 

 

 

 

GND lug

 

 

 

Two Pole

 

 

 

 

 

Breaker

Utility 240V AC

 

 

 

 

 

 

8

Briggs & Stratton Power Products Automatic Transfer Switch

Installation and Owner’s Manual

SYSTEM OPERATION

To select automatic transfer operation, do the following:

1.Set circuit breaker that sends utility power to transfer switch to “On” position.

2.Set generator’s main circuit breaker to its “On” position.

3.Install 15 Amp fuse in control panel on generator.

4.Set AUTO/OFF/MANUAL switch on generator to “AUTO” position.

The system will now be in automatic operation mode.

TESTING THE AUTOMATIC TRANSFER SWITCH

Turn the circuit breaker feeding the transfer switch, to the “Off” position.The automatic sequence will follow.To go back to utility power, turn the circuit breaker to the “On” position.

Automatic Sequence

Utility Fail

Utility voltage sensor senses when utility voltage is below 70 percent of nominal. Engine start sequence is initiated after 6 second time delay.

Engine Warm-Up

Time delay to allow for engine warm-upbefore transfer fixed at 20 seconds or 50 seconds with optional cold weather package.

Transfer

Transfers from utility to standby supply occurs after standby voltage is above set levels. Minimum engine run time is 4 minutes after transfer.

Utility Pickup

Voltage pickup level is 80 percent of nominal voltage.

Retransfer

Retransfer from standby to utility supply 10 seconds after utility voltage supply is above pickup level.

Engine Cool Down

Engine will run for 60 seconds after retransfer.

Specifications

UL® 1008 Listed Transfer Switch

Model 01917

Enclosure . . . . . . . . . . . . . . . . . . . NEMA 1

Maximum Load/Circuit:

from Load Center . . . . . . . . . . 50 Amps Rated AC Voltage. . . . . . . . . . . . . 250 Volts Poles . . . . . . . . . . . . . . . . . . . . . . 2 Frequency . . . . . . . . . . . . . . . . . . 50/60 Hz

Fault Current Rating . . . . . . . . . . 5,000 RMS Symmetrical

Amperes

Weight . . . . . . . . . . . . . . . . . . . . . 27 lbs.

Model 01918

Enclosure . . . . . . . . . . . . . . . . . . . NEMA 3R

Maximum Load/Circuit:

from Load Center . . . . . . . . . . 50 Amps Rated AC Voltage. . . . . . . . . . . . . 250 Volts Poles . . . . . . . . . . . . . . . . . . . . . . 2 Frequency . . . . . . . . . . . . . . . . . . 50/60 Hz

Fault Current Rating . . . . . . . . . . 5,000 RMS Symmetrical

Amperes

Weight . . . . . . . . . . . . . . . . . . . . . 34 lbs.

When Calling the Factory

Before contacting Briggs and Stratton Power Products regarding service or repair of this transfer switch, obtain the Model Number and Serial Number from the unit data decal located on or inside the case.

To contact Briggs and Stratton Power Products call 1-800-743-4115,between 8:00 AM and 5:00 PM CT.

9

Briggs & Stratton Power Products Automatic Transfer Switch

Installation and Owner’s Manual

NOTES