Briggs & Stratton 01897-0 User Manual 2

0 (0)
Briggs & Stratton 01897-0 User Manual 2

Installation,

Start-Up and

Operator’s Manual

Manual de Instalación,

Arranque y Operario

Manuel d'Installation,

Démarrage et Utilisation

Questions? Help is just a moment away! Preguntas? La ayuda es justa un momento lejos!

Vous avez des questions? Vous n'avez pas besoin d'aller loin pour trouver de l'aide!

Call: Home Standby Generator Helpline

Llamada: Línea Directa de Reserva de Hogar

Appelez: Ligne Directe de Secours À la

Maison - 1-800-743-4115 M-F 8-5 CT

Web: www.briggspowerproducts.com

Home Standby Generator

Models 01897-0 Part No. 194943GS Rev. 4 (11/18/05)

Briggs & Stratton Power Products Home Standby Generator

Installation, Start-Up and Operator’s Manual

TABLE OF CONTENTS

 

TABLE OF CONTENTS . . . . . . . . . . . . . . . . . . . . . . .

. . . . 2

IMPORTANT SAFETY INSTRUCTIONS . . . . . . . . . .

. . 3-4

SAVE THESE INSTRUCTIONS . . . . . . . . . . . . . . . . . . .

. . . 5

INTRODUCTION . . . . . . . . . . . . . . . . . . . . . . . . . . . .

. . . 5

CUSTOMER RESPONSIBILITIES . . . . . . . . . . . . . . . . .

. . . 5

INSTALLER RESPONSIBILITIES . . . . . . . . . . . . . . . . . .

. . 5

INSTALLATION ASSISTANCE . . . . . . . . . . . . . . . . . . . .

. . 5

For the Home Owner: . . . . . . . . . . . . . . . . . . .

. . 5

For the Installing Dealer/Contractor: . . . . . . .

. . 5

KNOW YOUR HOME STANDBY GENERATOR . . . .

. . 6

KNOW YOUR CONTROL PANEL . . . . . . . . . . . . . . . .

. . 7

OWNER ORIENTATION . . . . . . . . . . . . . . . . . . . . . . .

. . 8

Fuel Factors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

. . 8

Power Decrease at High Altitude or High

 

Temperature . . . . . . . . . . . . . . . . . . .

. . 8

INSTALLATION PROCEDURES . . . . . . . . . . . . . . . . . .

. . 8

Unpacking Precautions . . . . . . . . . . . . . . . . . . . . . .

. . 8

Delivery Inspection . . . . . . . . . . . . . . . . . . . . . . . . .

. . 8

Approved Transfer Switches . . . . . . . . . . . . . . . . . .

. . 8

Shipment Contents . . . . . . . . . . . . . . . . . . . . . . . . .

. . 9

Required Specialty Tools/Equipment . . . . . . . . . . . .

. . 9

Lifting the Generator . . . . . . . . . . . . . . . . . . . . . . . .

. . 9

Home Standby Generator Location . . . . . . . . . . . .

. . 9

Generator Clearances . . . . . . . . . . . . . . . . . . .

. . 9

General Location Guidelines . . . . . . . . . . . . . .

. . 9

Essential Circuits . . . . . . . . . . . . . . . . . . . . . . . . . . .

. 10

Essential Circuit Selection . . . . . . . . . . . . . .

10-11

Disconnect Box Mounting Guidelines . . . . . . . . . . .

. 11

Fuel Inlet Dimensions . . . . . . . . . . . . . . . . . . . . . . .

. 11

Removable Roof and Access Door . . . . . . . . . . . .

. 11

To remove roof: . . . . . . . . . . . . . . . . . . . . . . . .

. 11

To remove access door: . . . . . . . . . . . . . . . . . .

. 11

To install access door and roof: . . . . . . . . . . . .

. 11

THE GASEOUS FUEL SYSTEM . . . . . . . . . . . . . . . . .

12-13

Fuel Consumption . . . . . . . . . . . . . . . . . . . . . . . . . .

. 13

Fuel Pipe Sizing . . . . . . . . . . . . . . . . . . . . . . . . . . . .

. 14

Fuel Comparison Chart . . . . . . . . . . . . . . . . . . . . .

. 15

Size of Propane Tank Required at Various Temperatures

When Kept at Least Half Full . . . . . . . . . .

. 15

WIRE CONNECTIONS . . . . . . . . . . . . . . . . . . . . . . . . .

. 16

Recommended Torque Values. . . . . . . . . . . . . . . . . .

. 16

Generator AC Connection System . . . . . . . . . . . .

. 16

Grounding the Generator . . . . . . . . . . . . . . . . . .

. . . 16

Utility Control Circuit Connection . . . . . . . . . . .

. . 16

Remote LED Plate . . . . . . . . . . . . . . . . . . . . . . . . .

. . 16

BEFORE INITIAL START-UP . . . . . . . . . . . . . . . . . . . .

. . 16

Engine Oil . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

. . 16

Oil Considerations . . . . . . . . . . . . . . . . . . . . .

. . 16

Battery Connection . . . . . . . . . . . . . . . . . . . . . . . .

. . 17

Fuel Supply System . . . . . . . . . . . . . . . . . . . . . . . .

. . 17

FUEL SYSTEM SELECTION . . . . . . . . . . . . . . . . . . . . .

. . 18

INITIAL START-UP (NO LOAD) . . . . . . . . . . . . . . . .

. . 18

AUTOMATIC OPERATION SEQUENCE . . . . . . . . . .

. . 18

Utility Voltage Dropout Sensor. . . . . . . . . . . .

. . 18

Utility Voltage Pickup Sensor . . . . . . . . . . . . .

. . 18

Engine Cool-down Timer . . . . . . . . . . . . . . . .

. . 18

SETTING EXERCISE TIMER . . . . . . . . . . . . . . . . . . . .

. . 19

INSTALLATION INSPECTION . . . . . . . . . . . . . . . . . .

. . 19

SPECIFICATIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

. . 20

AUTOMATIC OPERATION . . . . . . . . . . . . . . . . . . . . .

. . 20

Checking Automatic Operation . . . . . . . . . . . . . . .

. . 20

Servicing The Generator . . . . . . . . . . . . . . . . . . . .

. . 20

FAULT DETECTION SYSTEM . . . . . . . . . . . . . . . . . . .

. . 20

Reset Fault Detection System . . . . . . . . . . . .

. . 21

No LED - Discharged Battery . . . . . . . . . . . .

. . 21

Low Oil Pressure . . . . . . . . . . . . . . . . . . . . . .

. . 21

Engine Fails to Start . . . . . . . . . . . . . . . . . . . .

. . 21

Low Frequency . . . . . . . . . . . . . . . . . . . . . . . .

. . 21

Engine Overspeed . . . . . . . . . . . . . . . . . . . . . .

. . 21

GENERATOR MAINTENANCE . . . . . . . . . . . . . . . . .

. . 22

Changing Engine Oil and Filter. . . . . . . . . . . . . . . .

. . 22

Changing Oil . . . . . . . . . . . . . . . . . . . . . . . . . .

. . 22

Changing Oil Filter . . . . . . . . . . . . . . . . . . . . .

. . 22

To Clean the Generator . . . . . . . . . . . . . . . . . . . .

. . 23

When Calling the Factory . . . . . . . . . . . . . . . . . . .

. . 23

STORAGE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

. . 23

TROUBLESHOOTING . . . . . . . . . . . . . . . . . . . . . . . . .

. . 24

NOTES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

. . 25

SCHEMATIC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

. . 26

WIRING DIAGRAM . . . . . . . . . . . . . . . . . . . . . . . . . . .

. . 27

REPLACEMENT PARTS . . . . . . . . . . . . . . . . . . . . . . . .

28-34

WARRANTY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

. . 35

ESPAÑOL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

36-59

FRANÇAIS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

60-84

Copyright © 2005 Briggs & Stratton Power Products Group, LLC. All rights reserved. No part of this material may be reproduced or transmitted in any form by any means without the express written permission of Briggs & Stratton Power Products Group, LLC.

2

Briggs & Stratton Power Products Home Standby Generator

Installation, Start-Up and Operator’s Manual

SAVE THESE INSTRUCTIONS

IMPORTANT SAFETY INSTRUCTIONS

The safety alert symbol () is used with a signal word (DANGER, CAUTION,WARNING), a pictorial and/or a safety message to alert you to hazards. DANGER indicates a hazard which, if not avoided, will result in death or serious injury. WARNING indicates a hazard which, if not avoided, could result in death or serious injury. CAUTION indicates a hazard which, if not avoided, might result in minor or moderate injury. CAUTION, when used without the alert symbol, indicates a situation that could result in equipment damage. Follow safety messages to avoid or reduce the risk of injury or death.

The manufacturer cannot possibly anticipate every possible circumstance that might involve a hazard.The warnings in this manual, and the tags and decals affixed to the unit are, therefore, not all-inclusive. If you use a procedure, work method or operating technique that the manufacturer does not specifically recommend, you must satisfy yourself that it is safe for you and others.You must also make sure that the procedure, work method or operating technique that you choose does not render the generator unsafe.

NOTE: Your generator is equipped with a spark arrester muffler.The spark arrester must be maintained in effective working order by the owner/operator. In the State of California, a spark arrester is required by law (Section 4442 of the California Public Resources Code). Other states may have similar laws. Federal laws apply on federal lands.

WARNING

Only qualified electricians and gaseous fuel technicians should attempt installation of this generator, which must strictly comply with applicable codes, standards and regulations.

DANGER

Storage batteries give off explosive hydrogen gas during recharging.

Slightest spark will ignite hydrogen and cause explosion.

Battery electrolyte fluid contains acid and is extremely caustic.

Contact with battery contents will cause severe chemical burns.

A battery presents a risk of electrical shock and high short circuit current.

DO NOT dispose of battery in a fire.

DO NOT allow any open flame, spark, heat, or lit cigarette during and for several minutes after charging a battery.

DO NOT open or mutilate the battery.

Wear protective goggles, rubber apron, and rubber gloves.

Remove watches, rings, or other metal objects.

Use tools with insulated handles.

WARNING

Running generator gives off carbon monoxide, an odorless, colorless, poison gas.

Breathing carbon monoxide can cause nausea, fainting or death.

Operate generator ONLY outdoors.

Keep exhaust gas from entering a confined area through windows, doors, ventilation intakes or other openings.

WARNING

Running engines produce heat.Temperature of muffler and nearby areas can reach or exceed 150°F (65°C).

Severe burns can occur on contact.

Combustible debris, such as leaves, grass, brush, ect. can catch fire.

DO NOT touch hot surfaces.

Allow equipment to cool before touching.

The generator enclosure must be at least 5 feet from structures having combustible walls and/or other combustible materials.

Keep at least 3 feet of clearance on all sides of generator enclosure for adequate cooling, maintenance and servicing.

3

Briggs & Stratton Power Products Home Standby Generator

Installation, Start-Up and Operator’s Manual

WARNING

Generator produces powerful voltage.

Failure to properly ground generator can result in electrocution.

Failure to isolate generator from power utility can result in death or injury to electric utility workers due to backfeed of electrical energy.

When using generator for backup power, notify utility company.

DO NOT touch bare wires or receptacles.

DO NOT use generator with electrical cords which are worn, frayed, bare or otherwise damaged.

DO NOT handle generator or electrical cords while standing

in water, while barefoot, or while hands or feet are wet.

If you must work around a unit while it is operating, stand on an insulated dry surface to reduce shock hazard.

DO NOT allow unqualified persons or children to operate or service generator.

In case of an accident caused by electrical shock, immediately shut down the source of electrical power and contact the local authorities. Avoid direct contact with the victim.

Before performing any maintenance on the generator, disconnect the battery cable indicated by a NEGATIVE, NEG or (-) first.When finished, reconnect that cable last.

After your Home Standby Generator is installed, the generator may crank and start without warning any time there is a power failure.To prevent possible injury, always set the AUTO/OFF/MANUAL switch to OFF, remove the service disconnect from the disconnect box AND remove the

15 Amp fuse BEFORE working on the equipment.

WARNING

Propane and Natural Gas are extremely flammable and explosive.

Fire or explosion can cause severe burns or death.

Install the fuel supply system according to applicable fuel-gas codes.

Before placing the Home Standby Generator into service, the fuel system lines must be properly purged and leak tested.

After the generator is installed, you should inspect the fuel system periodically.

NO leakage is permitted.

DO NOT operate engine if smell of fuel is present or other explosive conditions exist.

DO NOT smoke around the generator.Wipe up any oil spills immediately. Ensure that no combustible materials are left in the generator compartment. Keep the area near the generator clean and free of debris.

CAUTION

Excessively high operating speeds increase risk of injury and damage to generator.

Excessively low speeds impose a heavy load.

DO NOT tamper with governed speed. Generator supplies correct rated frequency and voltage when running at governed speed.

DO NOT modify generator in any way.

CAUTION

Exceeding generators wattage/amperage capacity can damage generator and/or electrical devices connected to it.

See “Essential Circuits” on page 10.

Start generator and let engine stabilize before connecting electrical loads.

CAUTION

Improper treatment of generator can damage it and shorten its life.

Use generator only for intended uses.

If you have questions about intended use, ask dealer or contact Briggs and Stratton.

Operate generator only on level surfaces.

Adequate, unobstructed flow of cooling and ventilating air is critical to correct generator operation.

The access door and roof must be installed whenever the unit is running.

DO NOT expose generator to excessive moisture, dust, dirt, or corrosive vapors.

Despite the safe design of the Home Standby Generator, operating this equipment imprudently, neglecting its maintenance or being careless can cause possible injury or death.

Remain alert at all times while working on this equipment. Never work on the equipment when you are physically or mentally fatigued.

DO NOT start engine with air cleaner or air cleaner cover removed.

DO NOT insert any objects through cooling slots.

DO NOT use the generator or any of its parts as a step. Stepping on the unit can cause stress and break parts.This may result in dangerous operating conditions from leaking exhaust gases, fuel leakage, oil leakage, ect..

If connected devices overheat, turn them off and disconnect them from generator.

Shut off generator if:

-electrical output is lost;

-equipment sparks, smokes, or emits flames; -unit vibrates excessively.

4

Briggs & Stratton Power Products Home Standby Generator

Installation, Start-Up and Operator’s Manual

SAVE THESE

CUSTOMER

INSTRUCTIONS

RESPONSIBILITIES

This manual contains important instructions that should be followed during installation and maintenance of the generator and battery.

INTRODUCTION

Thank you for your purchase of a Briggs & Stratton Home Standby Generator.This product is intended for use as an optional standby system which provides an alternate source of electric power and to serve loads such as heating, refrigeration systems, and communication systems that, when stopped during any power outage, could cause discomfort, or the like.This product DOES NOT qualify for emergency standby as defined by NFPA 70 (NEC).

This manual is an important document and should be retained by the owner after installation has been completed.

This manual contains installation, startup and adjustment instructions for a Home Standby Generator that supplies 120/240 Volt, single phase, 60Hz devices.The Home Standby Generator may be operated on LP or natural gas fuel.

Every effort has been made to ensure that the information in this manual is both accurate and current. However, the manufacturer reserves the right to change, alter or otherwise improve the generator at any time without prior notice.

Briggs and Stratton has made every effort to provide for a safe, streamlined and cost-effective installation. Because each installation is unique, it is impossible to know of and advise the trade of all conceivable procedures and methods by which installation might be achieved. Neither could we know of possible hazards and/or the results of each method or procedure. For these reasons,

Only current licensed electrical and plumbing contractors should attempt Home Standby Generator installations. Installations must strictly comply with all applicable codes, industry standards

and regulations.

Read and follow the instructions given in this manual, especially the section regarding selecting essential circuits.

Follow a regular schedule in maintaining, caring for and using your Home Standby Generator, as specified in this manual.

INSTALLER RESPONSIBILITIES

Read and observe the safety rules.

Read and follow the instructions given in this manual.

IMPORTANT: If operating the generator below 10°F, a battery warmer MUST be installed. Both items are available at your local servicing dealer.

INSTALLATION

ASSISTANCE

For the Home Owner:

To help you make informed choices and communicate effectively with your installation contractor(s),

Read and understand the

Owner Orientation Section of this manual BEFORE contracting or starting

your Home Standby Generator installation.

To arrange for proper installation, contact the store at which you purchased your Briggs & Stratton Standby Generator, your dealer, a licensed electrician or your utility power provider.

The Home Standby Generator Warranty is VOID unless the generator is installed by licensed electrical and plumbing professionals.

For the Installing Dealer/Contractor:

For most applications, this manual contains all the information required to properly install and start the Home Standby Generator.This manual also describes essential circuit selection, routine operation and owner maintenance procedures.

If you need more information, call 1-800-743-4115, between 8:00 AM and 5:00 PM CT.

The Emission Control System for this generator is warranted for standards set by the U.S. Environmental Protection Agency and by the California Air Resources Board (CARB).

5

Briggs & Stratton Power Products Home Standby Generator

Installation, Start-Up and Operator’s Manual

KNOW YOUR HOME STANDBY GENERATOR

Read this operator’s manual and safety rules before operating your generator.

Compare the illustrations with your generator to familiarize yourself with the locations of various controls and adjustments. Save this manual for future reference.

Air Cleaner

Engine Label

Oil Fill

 

 

Cap/DipStick

Oil

Filter

Exhaust

Port

Lifting Pocket

Fuel Inlet

Battery

 

 

Generator is shown with roof, plastic access door and control panel door removed for clarity

Control Panel

(see page 7)

Oil Drain Hose

Unit Data

Decal

Disconnect Box

Air Cleaner — Uses a dry type filter element and foam precleaner to protect engine by filtering dust and debris out of intake air..

Battery — 12 Volt DC, 33 Amp-Hour sealed battery provides power to start the engine. Battery receives trickle charge whenever generator is not running.

Control Panel — Used for various test, operation and maintenance functions. See “KNOW YOUR CONTROL PANEL” on the next page.

Disconnect Box — Convenient junction box for ease of installation. Allows you to connect to generator output and disconnect utility input.

Engine Label (stamped on top of valve cover)

Identifies engine model and type.

Exhaust Port — High-performance muffler lowers engine noise to comply with most residential codes.

Fuel Inlet — Attach appropriate fuel supply to generator here.

Lifting Pocket — Provided at each corner for lifting generator.

Oil Fill Cap/Dipstick — Check and fill engine with recommended oil here.

Oil Drain Hose — Provided to facilitate oil changing.

Oil Filter — Filters engine oil to prolong generator life.

Unit Data Decal — Identifies unit by serial number.

6

Briggs & Stratton Power Products Home Standby Generator

Installation, Start-Up and Operator’s Manual

KNOW YOUR CONTROL PANEL

Compare this Control Panel illustration with your generator to familiarize yourself with the location of these important controls:

15 Amp Fuse

Set Exercise Switch

Set

Exercise

 

Auto/Off/Manual

Breaker

Circuit

15Amp Fuse

Circuit Breaker

AUTO/OFF/MANUAL

Switch

15 Amp Fuse — Protects the Home Standby Generator DC control circuits. If the fuse has melted open or was removed, the engine cannot crank or start. Replace the fuse using only an identical BUSS AGC 15A fuse.

AUTO/OFF/MANUAL Switch — This three-position switch is used as follows:

AUTO” position is the normal operating mode. If a utility power outage is sensed, the generator will start automatically.When utility power is restored, the generator will shut down, and is ready for the next utility power outage.

OFF” position turns off generator, prevents generator from starting and resets any faults.

MANUAL” position starts the generator. It is used for maintenance or diagnostic functions.

Circuit Breaker — Protects the system from overcurrent conditions and must be in the “On” position to supply power to the Transfer Switch.

Set Exercise Switch — Used to set the exercise cycle start time and day-of-the-week. Exercise cycle only occurs in AUTO mode.

7

Briggs & Stratton Power Products Home Standby Generator

Installation, Start-Up and Operator’s Manual

OWNER ORIENTATION

This section provides the Home Standby Generator owner with the information necessary to achieve the most satisfactory and cost effective installation possible.

The illustrations are for typical circumstances and are meant to familiarize you with the installation options available with the Home Standby Generator. A thorough understanding of these options will provide fundamental control over the cost of installation, as well as ensure final satisfaction and security.

Federal and local codes, appearance, noise levels, fuel types, and distances are the factors that must be considered when negotiating with an installation professional. As the distance from the existing electrical service and gaseous fuel supply increases, so must the piping and wiring materials.This is necessary to comply with local codes, overcome electrical voltage drops and gaseous fuel pressure drops.

The factors mentioned above will have a direct affect on the overall price of your Home Standby Generator installation.

NOTE: In some areas you may need to acquire electrical permits for installing the Home Standby Generator, building permits for installing gas lines, and permits for noise allowances.Your installer should check your local codes AND obtain the permits before installing the generator.

Fuel Factors

An important consideration affecting the entire installation is the type of fuel used by your Home Standby Generator. The generator was factory tested and adjusted using natural gas as a fuel. Liquid propane (LP) may also be used as fuel by installing the included conversion kit.

For proper generator performance, the following fuel guidelines are recommended:

In engines set up to run on propane (LP) gas, commercial grade HD5 propane with a minimum fuel energy of 2500 BTUs/ft3 with maximum propylene content of

5% and butane and heavier gas content of 2.5% and minimum propane content of 90%.

WARNING

Propane and Natural Gas are extremely flammable and explosive.

Fire or explosion can cause severe burns or death.

The Home Standby Generator is equipped with an automatic safety gas “fuel shut-off” valve.

DO NOT operate the equipment if the “fuel shut-off” valve is missing or inoperative.

Power Decrease at High Altitude or High Temperature

Air density is less at high altitudes, resulting in less available engine power. Specifically, engine power will decrease 3.5% for each 1,000 feet (300 meters) above sea level and 1% for each 10° F (5.6°C) above 77°F (25°C). Make sure you and your installer consider these factors when determining total generator load.

INSTALLATION

PROCEDURES

Unpacking Precautions

The unit is shipped bolted to its mounting pad, ready for installation. Avoid damage from dropping, bumping, collision, etc. Store and unpack carton with the proper side up, as noted on the shipping carton.

Delivery Inspection

After removing the carton, carefully inspect the Home Standby Generator for any damage that may have occurred during shipment.

IMPORTANT: If loss or damage is noted at time of delivery, have the person(s) making delivery note all damage on the freight bill and affix his signature under the consignor's memo of loss or damage. If loss or damage is noted after delivery, separate the damaged materials and contact the carrier for claim procedures. Missing or damaged parts are not warranted.

Approved Transfer Switches

The Home Standby Generator should be used ONLY with Briggs & Stratton Power Products UL approved Transfer Switches. Connection to any other transfer switch will void your generator warranty.

8

Briggs & Stratton Power Products Home Standby Generator

Installation, Start-Up and Operator’s Manual

Shipment Contents

The Home Standby Generator is supplied with:

Home Standby Generator w/disconnect box

Pre-attached mounting pad

One 24” flexible hook-up hose

Installation, start-up and operator’s manual

Installation checklist

Remote diagnostic LED plate

Oil drain tray

Touch-up paint

One spare 15A fuse

LP conversion kit

Roof hardware bag

Lifting the Generator

CAUTION! The generator weighs more than 280 pounds. Proper tools, equipment and qualified personnel should be used in all phases of handling and moving generator.

CAUTION! DO NOT lift unit by roof as damage to generator will occur.

Lifting pockets are provided at each corner between the base of the generator and its mounting pad. Retouch any chipped paint with supplied touch-up paint.

Home Standby Generator Location

Before installing generator, consult with homeowner and convey the following guidelines which may affect the desired location.

Generator Clearances

WARNING

Exhaust heat/gases can ignite combustibles, structures or damage fuel tank causing a fire.

Keep at least 5 ft. (152 cm) clearance on all sides of generator including overhead.

Place generator in a well ventilated area which will allow for removal of deadly exhaust gas. DO NOT install generator where exhaust gas could accumulate and enter inside or be drawn into a potentially occupied building. Ensure exhaust gas is kept away from any windows, doors, ventilation intakes or other openings that can allow exhaust gas to collect in a confined area (Figure 1). Prevailing winds and air currents should be taken into consideration when positioning generator.

General Location Guidelines

WARNING

Running generator gives off carbon monoxide, an odorless, colorless, poison gas.

Breathing carbon monoxide can cause nausea, fainting or death.

Operate generator ONLY outdoors.

Keep exhaust gas from entering a confined area through windows, doors, ventilation intakes or other openings.

Install the unit outdoors ONLY.

Place the unit in a prepared location that is flat and has provisions for water drainage.

Install the unit where air inlet and outlet openings will not become obstructed by leaves, grass, snow, etc. If prevailing winds will cause blowing or drifting, you may need to construct a windbreak to protect the unit.

Install the generator as close as possible to the Transfer Switch to reduce the length of wiring and conduit.

Install the generator as close as possible to the fuel supply to reduce length of pipes.

IMPORTANT: Laws or local codes may regulate the distance to the fuel supply.

Figure 1 — Home Standby Generator Clearances

Exhaust

Port

The Home Standby Generator is shipped already attached to its mounting pad. Unless mandated by local code, a concrete slab is not required.

If mandated by local code, construct a concrete slab at least 3 inches thick and 6 inches longer and wider than the unit. Attach unit to slab with 1/4” diameter (minimum) masonry anchor bolts long enough to retain the unit.

9

Briggs & Stratton Power Products Home Standby Generator

Installation, Start-Up and Operator’s Manual

Essential Circuits

Consult with owner to clearly identify the circuits in building that are "essential".

It is important that you understand which circuits the owner wants to include as "Essential Circuits". Depending on the power consumed by these circuits, most or all of them can be switched to the Home Standby Generator for the duration of normal power interruption.

The wattage reference guide shown in Figure 2 will assist the owner with their decision-making process. It provides the wattage used by many ordinary household devices. Use it as a guide when selecting essential circuits. Review this information with the owner and convey any technical considerations that might affect the cost of installation.

Essential Circuit Selection

When selecting the essential circuits that will be switched to “Standby Power,” it is important that the sum of the combined circuit loads does not exceed the wattage/amperage capacity of the generator.To help you with your selection of essential circuits, please consider the following:

Add up the total wattage of all electrical devices to be connected at one time.This total should NOT be greater than the generator’s wattage capacity.

The rated wattage of lights can be taken from light bulbs.The rated wattage of tools, appliances and motors can usually be found on a data plate or decal affixed to the device.

If the appliance, tool or motor does not give wattage, multiply volts times the ampere rating to determine watts (Volts x Amps = Watts).

Some electric motors (induction types) require about three times more watts of power for starting than for running.This surge lasts for only a few seconds. Be sure you allow for this high starting wattage when selecting electrical devices that will be energized by the Home Standby Generator:

Figure the watts required to start the largest motor.

Add that to the total running watts of all other connected loads.

This Briggs & Stratton Home Standby Generator complies with the following “stationary standby power rating”:

The standby power rating is applicable for supplying power for the duration of normal power interruption. NO sustained overload capability is available for this rating.

Figure 2 — Wattage Reference Guide

 

Device

Running

 

Watts

 

 

 

Air Conditioner (12,000 Btu)*

1700

 

Air Conditioner (24,000 Btu)*

3800

 

Air Conditioner (40,000 Btu)*

6000

 

Battery Charger (20 Amp)

500

 

Circular Saw (6-1/2")

800 to 1000

 

Clothes Dryer (Electric)*

5750

 

Clothes Dryer (Gas)*

700

 

Clothes Washer*

1150

 

Coffee Maker

1750

 

Compressor (1 HP)*

2000

 

Compressor (1/2 HP)*

1400

 

Compressor (3/4 HP)*

1800

 

Curling Iron

700

 

Dehumidifier*

650

 

Electric Blanket

400

 

Electric Range (per element)

1500

 

Electric Skillet

1250

 

Freezer*

700

 

Furnace Fan (3/5 HP)*

875

 

Garage Door Opener*

500 to 750

 

Hair Dryer

1200

 

Hand Drill

250 to 1100

 

Iron

1200

 

Jet Pump*

800

 

Light Bulb

100

 

Microwave Oven

700 to 1000

 

Milk Cooler*

1100

 

Oil Burner on Furnace

300

 

Oil Fired Space Heater (140,000 Btu)

400

 

Oil Fired Space Heater (30,000 Btu)

150

 

Oil Fired Space Heater (85,000 Btu)

225

 

Radio

50 to 200

 

Refrigerator

700

 

Slow Cooker

200

 

Submersible Pump (1 HP)*

2000

 

Submersible Pump (1/2 HP)*

1500

 

Submersible Pump (1-1/2 HP)*

2800

 

Sump Pump*

800 to 1050

 

Table Saw (10")*

1750 to 2000

 

Television

200 to 500

 

Toaster

1000 to 1650

*Allow three (3) times listed watts for starting device

10

Briggs & Stratton Power Products Home Standby Generator

Installation, Start-Up and Operator’s Manual

This rating is applicable to installations served by a reliable normal utility source.This rating is only applicable to variable loads with an average load factor of 80% of the standby rating.The standby rating is only applicable for optional standby power where the generator set serves as the backup to the normal utility source.

Use the “Wattage Reference Guide” provided and mark those circuits you consider “critical” or “essential”. Make sure you and your installer consider the generator’s altitude above sea level and the ambient temperature range when determining total generator load.

Disconnect Box Mounting Guidelines

The disconnect box is a NEMA Type 3R enclosure suitable for outdoor use.

Guidelines for mounting the disconnect box include:

The disconnect box must be installed with appropriate hardware for conduit connections.

Install disconnect box on a firm, sturdy supporting structure, making sure it is level and plumb.

NEVER install disconnect box where any corrosive substance might drip onto enclosure.

Protect disconnect box at all times against excessive moisture, dust, dirt, lint, construction grit and corrosive vapors.

The typical installation of the disconnect box is depicted in Figure 3. Discuss layout suggestions/changes with owner before beginning installation process.

Figure 3 — Typical Disconnect Box Mounting

Fuel Inlet Dimensions

Figure 4, below, depicts the location of the fuel piping connector.

Figure 4 — Generator Fuel Attachment Location

Fuel Piping

Connector

4.5”

3/4” NPT

13.5”

Removable Roof and Access Door

The Home Standby Generator is equipped with an enclosure that has a removable roof and an access door for the control panel.

To Remove Roof:

Remove the four screws and lift off.

To Remove Access Door:

1.Remove roof as described above.

2.Remove screw at top of access door.

3.Pull access door outward (away) from unit while pulling door upward and out of base. Door will come free of generator enclosure.

To Install Access Door and Roof:

1.Guide bottom of access door into base.

2.Push access door until it is flush with sides.

3.Replace door screw.

4.Replace roof and screws.

11

Briggs & Stratton Power Products Home Standby Generator

Installation, Start-Up and Operator’s Manual

THE GASEOUS FUEL SYSTEM

WARNING

Propane and Natural Gas are extremely flammable and explosive.

Fire or explosion can cause severe burns or death.

LP gas is heavier than air and will settle in low areas.

Natural gas is lighter than air and will collect in high areas.

The slightest spark can ignite these fuels and cause an explosion.

The information provided below is to assist gaseous fuel system technicians in planning installations. In no way should this information be interpreted to conflict with applicable fuel gas codes. Consult with your local fuel supplier or Fire Marshall if questions or problems arise.

Piping must be of the correct size to maintain the required supply pressures and volume flow under varying generator load conditions with all gas appliances connected to the fuel system turned on and operating.

Use an approved pipe sealant or joint compound on all threaded fittings to reduce the possibility of leakage.

Installed piping must be properly purged and leak tested, in accordance with applicable codes and standards.

WARNING

Propane and Natural Gas are extremely flammable and explosive.

Fire or explosion can cause severe burns or death.

Before placing the Home Standby Generator into service, the fuel system lines must be properly purged and leak tested.

NO leakage is permitted.

Consider the following factors when planning to

Consult with the Home Standby Generator owner(s) and convey any technical considerations that might affect their installation plans before applying these general guidelines.

The following general rules apply to gaseous fuel system piping:

The piping should be of a material that conforms to federal and local codes, rigidly mounted and protected against vibration.

Piping should be protected from physical damage where it passes through flower beds, shrub beds, and other cultivated areas where damage could occur.

Install the flexible, gaseous hose (supplied) between the Home Standby Generator Fuel Inlet port and rigid piping to prevent thermal expansion or contraction from causing excessive stress on the piping material.

NOTE: Where local conditions include earthquake, tornado, unstable ground, or flood hazards, special consideration shall be given to increase strength and flexibility of piping supports and connections.

CAUTION

The supplied flexible gaseous pipe is not to be installed underground or in contact with the ground.

The entire flexible gaseous pipe must be visible for periodic inspection and must not be concealed within, contact, or run through any wall, floor, or partition.

install the fuel supply system:

The Home Standby Generator engine is fitted with a fuel mixer system that meets the specifications of the California Air Resources Board for “tamper-proof” dual fuel systems. The unit will run on natural gas or liquefied propane.

A minimum of one accessible, approved manual shutoff valve shall be installed in the fuel supply line within 6 ft (1.8 m) of the Home Standby Generator. A union or flanged connection shall be provided downstream from this valve to permit removal of controls.

Natural gas fuel supply pressure at the generator's fuel inlet port should be between 5 to 7 inches of water (in. W.C.) at full load. LP fuel supply pressure should be 11 to 14 inches of water (in.W.C.) at full load.

The Home Standby Generator unit has been factory set to run on natural gas. If you need to change from natural gas to LP gas, the unit will need to be reconfigured, as described on page 18.

It is recommended that the fuel connection incorporate the following components:

A manual fuel shut-off valve located in the interior of the building.

A manual fuel shut-off valve located outside the building, just before the generator unit.

12

Briggs & Stratton Power Products Home Standby Generator

Installation, Start-Up and Operator’s Manual

Where the formation of hydrates or ice is known to occur, piping should be protected against freezing.The termination of hard piping should include a sediment trap where condensate is not likely to freeze.

When the initial test runs are completed, the manometer is removed and the port is plugged. A typical final fuel connection assembly is shown in Figure 6.

Figure 6 — Completed Fuel Connections

• A manometer port should be provided.

The manometer port permits temporary installation of a manometer (Figure 5), to ensure that the engine receives the correct fuel pressure to operate efficiently throughout its operating range.

Figure 5 — Temporary Manometer Installed

From Fuel

Supply Line

To Home Standby

Generator

Fuel Consumption

See Figure 7 for fuel supply requirements at half and full load for both natural gas and LP vapor.

Figure 7 — Fuel Supply Requirements

Natural Gas*

LP Vapor**

 

 

 

 

1/2 Load

Full Load

1/2 Load

Full Load

 

 

 

 

80

137

33

56

 

 

 

 

*= Natural Gas is in cubic feet per hour

**= LP Vapor is in cubic feet per hour

NOTE: A digital manometer, P/N 19495, is available at your local Briggs and Stratton Power Products service center.

13

Briggs & Stratton Power Products Home Standby Generator

Installation, Start-Up and Operator’s Manual

Fuel Pipe Sizing

Figures 8 and 9 provide the maximum capacity of pipe in cubic feet of gas per hour for gas pressures of 0.5 psi or less and a pressure drop of 0.3 in. water column. Specific gravity of gas is shown.

Listed values compensate for a nominal amount of restriction from bends, fittings, etc. If an unusual number of fittings, bends, or other restrictions are used, please refer to federal and local codes.

Figure 8 — NATURAL GAS (NG) Pipe Size - Gas Flow Chart, in cubic feet per hour

NPT

10ft

15ft

20ft

30ft

40ft

50ft

60ft

70ft

80ft

90ft

100ft

 

 

 

 

 

 

 

 

 

 

 

 

1/2”

168

146

115

93

79

70

63

59

55

51

48

 

 

 

 

 

 

 

 

 

 

 

 

3/4”

346

293

240

192

163

145

132

120

113

106

99

 

 

 

 

 

 

 

 

 

 

 

 

1”

653

549

446

360

307

274

250

230

211

197

187

 

 

 

 

 

 

 

 

 

 

 

 

Natural Gas (sg=0.65)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Figure 9 — LIQUID PROPANE (LP) GAS Pipe Size - Gas Flow Chart, in cubic feet per hour

 

 

 

NPT

10ft

15ft

20ft

30ft

40ft

50ft

60ft

70ft

80ft

90ft

100ft

 

 

 

 

 

 

 

 

 

 

 

 

1/2”

110

96

76

61

52

46

42

38

36

33

32

 

 

 

 

 

 

 

 

 

 

 

 

3/4”

277

192

158

126

107

95

87

79

74

69

65

 

 

 

 

 

 

 

 

 

 

 

 

1”

428

360

293

236

202

180

164

151

139

129

123

 

 

 

 

 

 

 

 

 

 

 

 

Liquid Propane (LP) (sg=1.50)

14

Briggs & Stratton Power Products Home Standby Generator

Installation, Start-Up and Operator’s Manual

Fuel Comparison Chart

Fuel Comparison Chart

 

 

 

 

 

 

Physical Properties

Propane

Natural Gas

 

 

Normal Atmospheric State

Gas

Gas

 

 

Boiling Point (in °F):

 

 

 

 

Initial

-44

-259

 

 

End

-44

-259

 

 

Heating Value:

 

 

 

 

BTU per gallon (Net LHV*)

83,340

63,310

 

 

BTU per Gallon (Gross**)

91,547

 

 

 

Cubic Feet (Gas)

2,516

1,000

 

 

Density***

36.39

57.75

 

 

Weight†

4.24

2.65

 

 

Octane Number:

 

 

 

 

Research

110+

110+

 

 

Motor

97

 

 

 

 

 

 

 

*LHV (Low Heat Value) is the more realistic rating.

**Gross Heat Value does not consider heat lost in the form of water during combustion.

***Density is given in "Cubic Feet of Gas per Gallon of Liquid".

Weight is given in "Pounds per Gallon of Liquid".

Size of Propane Tank Required at Various Temperatures When Kept at Least Half Full

Given the gas withdrawal rate and the lowest average winter temperature, an installer can specify the required LP storage tank size:

Required Propane Tank Size (Lowest Average Winter Temperature), in Gallons

 

 

 

 

 

 

 

 

 

 

 

Withdrawal Rate

32°F

20°F

10°F

0°F

-10°F

-30°F

-40°F

 

 

50 CFH

115

115

115

250

250

400

600

 

 

100 CFH

250

250

250

400

500

1000

1500

 

 

150 CFH

300

400

500

500

1000

1500

2500

 

 

200 CFH

400

500

750

1000

1200

2000

2500

 

 

300 CFH

750

1000

1500

2000

2500

4000

5000

 

 

 

 

 

 

 

 

 

 

 

15

Briggs & Stratton Power Products Home Standby Generator

Installation, Start-Up and Operator’s Manual

WIRE CONNECTIONS

Recommended Torque Values

Torque all wire connections/fasteners to values recommended in Figure 10. Suitable for copper wire of 60°/75°C rating.

Figure 10 — Recommended Torque Values

CONNECTIONS:

Torque Value

 

 

In Main Distribution Panel:

 

Refer to panel manufacturer specs

 

 

 

In Disconnect Box:

 

 

 

240V AC Utility

5 in-lb

 

 

Engine Start

5 in-lb

 

 

Remote Status

5 in-lb

 

 

Generator

17 in-lb

 

 

Ground

40 in-lb

 

 

Circuit Breakers:

Refer to circuit breaker manufacturer specs

Generator AC Connection System

A single-phase, three-wire AC connection system is used in the Home Standby Generator.The stator assembly consists of a pair of stationary windings with two leads brought out of each winding.The junction of leads 22 and 33 forms the neutral lead.A complete schematic and wiring diagram can be found on pages 26-27.

NOTE: Neutral is not bonded to ground at generator.

Remote Diagnostic LED Plate

The light on the remote LED plate is referred to as the Diagnostic LED.The LED will stay lit indicating the generator is in ready mode and will turn on and off in a series of blinks if certain faults are detected in the Home Standby Generator.A mounting plate is supplied so that it can be installed at a convenient indoor location.The owner will use it to observe the status of the Home Standby Generator. Consult with the owner for a convenient location.

To install the remote diagnostic LED plate:

Mount installer-supplied electrical box to wall.

Using installer-supplied wire, connect the remote LED leads to the “Remote Status Light” in disconnect box.

NOTE: LED leads are polarity sensitive.

• Attach mounting plate to electrical box.

Refer to the section “Fault Detection System” on page 20 for operation.

BEFORE INITIAL START-UP

Engine Oil

This engine is shipped from the factory filled with the recommended oil. Before starting the engine, check oil level and ensure that engine is serviced as described in the engine operator’s manual.

Grounding the Generator

Installer-supplied stranded copper wire is connected to the disconnect box GND lug and routed through conduit to the Transfer Switch GND. Continue the wire through conduit to the main distribution panel ground bus.

Generator Control Circuit

Connection

Control circuit interconnections consist of "240V AC Utility" leads.These two leads must be routed in conduit. Control lead functions are briefly described as follows:

Leads deliver utility power to the generator’s circuit board, optional battery warmer and oil heater and charge the battery.

Using installer-supplied minimum 300V, 16 AWG stranded copper wire, connect control circuit terminals in the disconnect box to the Transfer Switch.

CAUTION

Any attempt to crank or start the engine before it has been properly serviced with the recommended oil will result in equipment failure.

Refer to engine manual for oil fill information.

Damage to equipment resulting from failure to follow this instruction will void warranty.

Oil Considerations

Your Home Standby Generator is equipped with an engine that has been pre-run at the factory and does not require the traditional “break-in” procedure.

The generator is filled with synthetic oil (API SJ/CF 5W30W).This allows for generator operation in the widest range of temperature and climate conditions.

NOTE: The use of synthetic oil DOES NOT alter the required oil change intervals described in the engine operator’s manual.

16

Briggs & Stratton Power Products Home Standby Generator

Installation, Start-Up and Operator’s Manual

Battery Connection

The Home Standby Generator is supplied with a 12 Volt DC,AGM type, 33 Amp-Hour, valve regulated battery. It is a sealed, lead-acid rechargeable battery. It is installed in the unit and the battery cables are connected at the factory.The unit’s 15 Amp fuse, which isolates the battery and prevents the unit from starting, has been removed for shipping.The battery will lose some charge charge prior to installation of the generator. If battery voltage is below 12 Volts, charge the battery.

IMPORTANT: If battery voltage is below 5 Volts, it may not take a charge and you will need a new battery.

Charging the Battery

If it is necessary to charge the battery, proceed as follows:

1.Set the generator's “AUTO/OFF/MANUAL” switch to

OFF.

2.Remove the 15 Amp fuse from the control panel.

3.Disconnect the negative battery cable to the negative battery terminal (indicated by NEGATIVE, NEG, or (-).

CAUTION

Failure to disconnect negative battery cable will result in equipment failure.

DO NOT attempt to jump start the battery.

Damage to equipment resulting from failure to follow this instruction will void warranty.

4.Charge battery with battery charger at 2 Amps until battery holds 12 Volts.

DANGER

Storage batteries give off explosive hydrogen gas during recharging.

Slightest spark will ignite hydrogen and cause explosion.

Battery electrolyte fluid contains acid and is extremely caustic.

Contact with battery contents will cause severe chemical burns.

A battery presents a risk of electrical shock and high short circuit current.

DO NOT dispose of battery in a fire.

DO NOT allow any open flame, spark, heat, or lit cigarette during and for several minutes after charging a battery.

DO NOT open or mutilate the battery.

Wear protective goggles, rubber apron, and rubber gloves.

Remove watches, rings, or other metal objects.

Use tools with insulated handles.

NOTE: With the battery installed and utility power available to the Automatic Transfer Switch, the battery receives a trickle charge whenever the engine is not running.This process may take up to 72 hours to fully charge a battery from 5 Volts.The trickle charge cannot be used to recharge a battery that is completely discharged.

5.Connect the negative battery cable to the negative battery terminal (indicated by NEGATIVE, NEG, or (-).

6.Ensure hardware on both positive and negative battery terminals is secure.

7.Reinstall the 15 Amp fuse in the control panel.

CAUTION

Installing the 15A fuse could cause the engine to start.

DO NOT install the 15 Amp fuse until all plumbing and wiring has been completed and inspected.

8.Set the generator's “AUTO/OFF/MANUAL” switch to

AUTO.

Servicing the Battery

If it is necessary to service the battery, proceed as follows:

1.Set the generator's “AUTO/OFF/MANUAL” switch to

OFF.

2.Remove the 15 Amp fuse from the control panel.

3.Service or replace battery as required.

4.Connect the red battery cable to the battery positive terminal (indicated by POSITIVE, POS, or (+)).

5.Connect the negative battery cable to the negative battery terminal (indicated by NEGATIVE, NEG, or (-).

6.Ensure hardware on both positive and negative battery terminals is secure.

7.Reinstall the 15 Amp fuse in the control panel.

8.Set the generator's “AUTO/OFF/MANUAL” switch to

AUTO.

Fuel Supply System

Ensure that all fuel pipe connections are tight, secure and without leaks.

Ensure that all gas line shutoff valves are OPEN and that adequate fuel pressure is available whenever automatic operation is desired.

17

Briggs & Stratton Power Products Home Standby Generator

Installation, Start-Up and Operator’s Manual

FUEL SYSTEM SELECTION

The engine of your Home Standby Generator is factory calibrated to run on natural gas (NG). It may also be operated on liquid propane (LP).

To configure the fuel system for LP use:

1.LP fuel inlet pressure must be between 11 and 14 inches water column.

2.Set AUTO/OFF/MANUAL switch to OFF.

3.Pull service disconnect from disconnect box.

4.Remove 15 Amp fuse.

5.Change main jet in fuel mixer following instruction sheet provided in LP conversion kit.

6.Reinstall 15 Amp fuse.

9.Connect an RMS AC voltmeter and a frequency meter to check generator output at load side of circuit breaker.Voltage should be 230-240 Volts, frequency should be 62.0 - 62.5 Hz.

10.Check generator output between one generator connection lug and neutral lug, then between other generator connection lug and neutral lug. In both cases, voltage reading should be between 115-120 Volts.

11.Set AUTO/OFF/MANUAL switch to OFF. Engine will shut down.

AUTOMATIC OPERATION SEQUENCE

7.Reinstall service disconnect in disconnect box.

8.Set AUTO/OFF/MANUAL switch to AUTO.

9.Reset exercise timer following instructions “Setting Exercise Timer” on page 19.

The generator is now ready to operate automatically using LP fuel.With a fixed main jet for LP gas, there is no need to perform any engine adjustments for LP operation.

INITIAL START-UP (NO LOAD)

Begin testing the generator without any electrical loads connected, as follows:

1.Set AUTO/OFF/MANUAL switch to OFF.

2.Set generator’s main circuit breaker to OFF (open) position.

3.Install 15 Amp fuse in control panel.

4.Set AUTO/OFF/MANUAL switch to MANUAL.

NOTE: When the Home Standby Generator is started for the very first time, it will require that air in the gaseous fuel lines be purged.This may take a few minutes.

5.DO NOT crank engine for more than 15 seconds, then pause for 15 seconds to reduce heat in starter.

6.Repeat process until engine starts.

7.Listen for unusual noises, vibration or other indications of abnormal operation. Check for oil leaks while the engine runs.

8.Let engine warm up for about five minutes to allow internal temperatures to stabilize.Then, set generators main circuit breaker to ON (or closed) position.

The generator’s control panel houses a logic control circuit board.This control board constantly monitors utility power source voltage. Should that voltage drop below a preset level, control board action will signal the engine to crank and start.

When utility source voltage is restored above a preset voltage level, the engine is signaled to shut down.

The actual system operation is not adjustable and is sequenced by sensors and timers on the control board, as follows:

Utility Voltage Dropout Sensor

This sensor monitors utility source voltage.

If utility source voltage drops below 70 percent of the nominal supply voltage, the sensor energizes a six second timer.

Once the timer has expired, the generator will start.

Utility Voltage Pickup Sensor

This sensor monitors utility power supply voltage.When that voltage is restored above 70 percent of the nominal source voltage, a time delay starts timing and the generator will go to engine cool-down.

Engine Cool-down Timer

When the load is transferred back to the utility power source, the engine cool-down timer starts timing.

The timer will run for about one minute, then the generator will stop.

Minimum generator run time is five minutes.

18

Briggs & Stratton Power Products Home Standby Generator

Installation, Start-Up and Operator’s Manual

SETTING EXERCISE TIMER

The Home Standby Generator is equipped with an exercise timer that will start and exercise the generator once every seven days. During this exercise period, the unit runs for approximately 20 minutes and then shuts down. Electrical load transfer DOES NOT occur during the exercise cycle (unless an utility power outage occurs).

A switch on the control panel is labeled “Set Exercise” (see page 7). On the specific day and time the switch is pressed, the control board is programmed.This date and time is then used to automatically initiate the generator exercise cycle.

To perform the Set Exercise procedure:

1.Choose day and time you want Home Standby Generator to exercise.

2.On that day and time, set AUTO/OFF/MANUAL switch to OFF position.

3.Press and hold down “Set Exercise” switch for two seconds.

4.Set AUTO/OFF/MANUAL switch to AUTO. “Set Exercise” is complete.

For example, if you press the “Set Exercise” switch on Sunday morning at 10:00 AM, the unit will run an exercise cycle the following Sunday at 10:00 AM (+/- 1 hour).

NOTE: “Set Exercise” will only work if the unit is in the Automatic mode and this exact procedure is followed.

If you want to change the day and time the unit exercises, simply perform the “Set Exercise” procedure at the day and time you want it to take place.

INSTALLATION

INSPECTION

Before placing the Home Standby Generator into service, inspect the entire installation carefully. Ensure that any scratches or broken paint on the inside or outside of the enclosure are touched up with the supplied paint.

Complete the ”Installation Checklist” as you make the inspection. Ensure all items have been filled-in and all signatures have been obtained. Instruct the owner to mail the white copy to:

Briggs & Stratton Power Products

Warranty Registration

P. O. Box 1144

Milwaukee,WI 53201-1144

19

Briggs & Stratton Power Products Home Standby Generator

Installation, Start-Up and Operator’s Manual

SPECIFICATIONS

Rated Maximum Power (LP*) . . . . . . . .

. . . . . . . . . .7.0 kW

Rated Maximum Load Current:

 

at 240 Volts . . . . . . . . . . . . . . . . . . . .

. . . . . . . .29.1 Amps

at 120 Volts . . . . . . . . . . . . . . . . . . . . .

. . . . . . .58.2 Amps

Rated AC Voltage . . . . . . . . . . . . . . . . . .

. . . . .120/240 Volts

Rated Frequency . . . . . . . . . . . . . . . . . .

60 Hz at 3600 rpm

Phase . . . . . . . . . . . . . . . . . . . . . . . . . . .

. . . . . .Single Phase

Power Factor . . . . . . . . . . . . . . . . . . . . .

. . . . . . . . . . . . .1.0

NG Fuel Supply Pressure . . . . . . . . . . . .

. . . . . .5-7 in W.C.

LP Fuel Supply Pressure . . . . . . . . . . . . .

. . . .11-14 in W.C.

Normal Operating Range -20°F (-28.8°C) to 104°F (40°C)

Output Sound Level . . .

81 dB(A) at 23 ft. (7 m) at full load

Shipping Weight . . . . . .

. . . . . . . . . . . . . . . . . . . . . .280 lbs.

*Natural gas rating will depend on specific fuel but typical derating of generator is between 10 to 20% off the LP gas rating.

AUTOMATIC OPERATION

To select automatic operation, do the following:

2.With generator output supplying load, turn ON service disconnect or main distribution panel circuit breaker that supplies utility power to automatic transfer switch.

3.Automatic transfer switch will transfer loads back to utility power after five minute minimum run time and utility is restored.

4.Generator will run for approximately an additional minute for engine cool down, then shut down.

5.Install control panel access door and roof following instructions in “Removable Roof and Access Door” on page 11.

NOTE: If generator does not shut down after approximately 10 minutes, put AUTO/OFF/MANUAL switch to OFF and contact your local service center.

This completes the test procedures for automatic operation.The Home Standby Generator will now start automatically when utility power is lost and will supply power to the transfer switch.

Servicing the System

To service system:

1.Remove roof by removing four screws and lifting off.

2.Remove screw at top of control panel access door.

1.Set service disconnect or main distribution panel circuit breaker that sends utility voltage to transfer switch to ON.

2.Set generator’s main circuit breaker to ON position.

3.Set AUTO/OFF/MANUAL switch to AUTO.

Checking Automatic Operation

To check the system for proper automatic operation, proceed as follows:

1.Turn OFF service disconnect or main distribution panel circuit breaker sending power to automatic transfer switch.

The generator will crank and start once the utility voltage drops out and the sensor has timed out. Let the system go through its entire automatic operation sequence.

3.Pull access door outward (away) from unit while pulling door upward and out of base. Door will come free of generator enclosure.

4.Set AUTO/OFF/MANUAL switch to OFF.

5.Set generator’s main circuit breaker to OFF position.

6.Pull service disconnect from disconnect box.

7.Remove 15A fuse from control panel.

FAULT DETECTION SYSTEM

The generator may have to run for long periods of time with no operator present. For that reason, the system is equipped with sensors that automatically shut down the generator in the event of potentially damaging conditions, such as low oil pressure, over speed, and other conditions.

A light on the remote LED plate is called the Diagnostic LED.The LED will turn on and off in a series of blinks if certain problems are detected in your Home Standby Generator.The blink pattern is repeated with a brief pause

20

Briggs & Stratton Power Products Home Standby Generator

Installation, Start-Up and Operator’s Manual

between each series.The number of blinks in the series indicates the detected fault, as listed on the mounting plate and as follows:

Number of LED Flashes

Fault Description

2

Low oil pressure

4

Engine failed to start

5

Low frequency

6

Engine overspeed

Engine Fail To Start

This fault is indicated by four blinks.This feature prevents the generator from damage by continually attempting to start. Each time the system is directed to start, the generator will crank for 15 seconds, pause for 15 seconds, crank for 15 seconds, pause for 15 seconds, and repeat. If the generator does not begin producing electricity after approximately 90 seconds, the generator will stop cranking and the LED will blink.

Reset Fault Detection System

The operator must reset the fault detection system each time it activates.To do so, place the AUTO/OFF/MANUAL switch in the OFF position for 30 seconds or more. Return the Home Standby Generator to service after correcting the problem by placing the AUTO/OFF/MANUAL switch in the AUTO position.

The most likely cause of this problem is no fuel supply. Check the inside and outside fuel shut off valves to ensure they are fully open. Other causes could be failed spark plug, failed engine ignition, or the engine air filter is clogged.You may need to contact your local service center for assistance if you can’t remedy these problems.

A description of each fault and suggested remedies are as follows:

No LED - Discharged Battery

This condition is caused by a completely discharged battery.To remedy the problem, remove the 15 Amp fuse and disconnect the battery from the generator.Take the battery to a local battery store for analysis.

Install the battery after it has been fully recharged or replaced, connecting the NEGATIVE cable last. Install the 15 Amp fuse.

Low Oil Pressure

This fault is indicated by two blinks.The generator is equipped with an oil pressure switch (Figure 11). Should oil pressure drop, switch contacts close and the engine is shut down.

Figure 11 — Low Oil Pressure

Oil Pressure Switch

To remedy the low oil pressure condition, add the recommended oil to the FULL mark on the dipstick.

If low oil pressure condition still exists, generator will start, then shut down after approximately 10 seconds and diagnostic LED will flash. In this case, contact your local service center.

Low Frequency

This fault is indicated by five blinks.This feature protects devices connected to the transfer switch by shutting the generator down if the engine runs slower than the preset limit.

This condition may be potentially caused by a failed engine governor.To remedy the problem, you should contact your local service center for assistance.

This condition may also be potentially caused by excessive loads on the generator.Turn off devices one at a time and check the frequency.To remedy the problem, you may need to contact your local service center for assistance.

Engine Overspeed

This fault is indicated by six blinks.This feature protects devices connected to the transfer switch by shutting the generator down if the engine happens to run faster than the preset limit.The overspeed fault is detected as follows:

If the generator output frequency runs at 72 Hz for five seconds, the generator will shut down.

If the generator output frequency reaches 75 Hz, the generator will shut down immediately.

This condition is potentially caused by a failed engine governor.To remedy the problem, you should contact your local service center for assistance.

21

Briggs & Stratton Power Products Home Standby Generator

Installation, Start-Up and Operator’s Manual

GENERATOR

MAINTENANCE

The generator warranty does not cover items that have been subjected to operator abuse or neglect.To receive full value from the warranty, the operator must maintain the engine as instructed in the engine operator’s manual.

IMPORTANT: Before performing any maintenance on the generator, be sure you follow all steps in “Servicing the System” on page 20.

Generator maintenance consists of keeping the unit clean. Operate the unit in an environment where it will not be exposed to excessive dust, dirt, moisture or any corrosive vapors. Cooling air louvers on the enclosure must not become clogged with snow, leaves, or any other foreign material.

Check the cleanliness of the unit frequently and clean when dust, dirt, oil, moisture or other foreign substances are visible on its exterior/interior surface.

NOTE: DO NOT use direct spray from a garden hose to clean generator.Water can enter the engine and generator and cause problems.

Changing Engine Oil and Filter

Remove the two screws from each plastic access cover and remove both access covers from the two sides of the generator enclosure.

Changing Oil

1.Place oil drain tube into approved container.

2.Push in and rotate oil drain fitting 1/4 turn counterclockwise. Slowly pull outward until oil starts draining (Figure 12). DO NOT pull oil drain fitting off engine.

Figure 12 — Oil Drain Fitting

3.When oil has drained, push oil drain fitting in and rotate 1/4 turn clockwise until it locks in place.

4.Slide oil drain tube up into clamp on generator.

Changing Oil Filter

1.Place oil drain tray over tubing and slide it under oil filter (Figure 13).

Figure 13 — Changing Oil Filter with Oil Drain Tray

oil drain tray

2.Follow instructions given in engine operator’s manual for changing oil filter.

3.Remove oil drain tray from under oil filter and clean up any spilled oil.

CAUTION

Avoid prolonged or repeated skin contact with used motor oil.

Used motor oil has been shown to cause skin cancer in certain laboratory animals.

Thoroughly wash exposed areas with soap and water.

KEEP OUT OF REACH OF CHILDREN. DON'T POLLUTE. CONSERVE RESOURCES. RETURN USED OIL TO COLLECTION CENTERS.

To fill your engine with oil:

Follow synthetic oil grade recommendation given in “Engine Oil” on page 16 and oil fill instructions given in engine operator’s manual.

CAUTION

Any attempt to crank or start the engine before it has been properly filled with the recommended oil will result in equipment failure.

Refer to engine manual for oil fill information.

Damage to equipment resulting from failure to follow this instruction will void warranty.

22

Briggs & Stratton Power Products Home Standby Generator

Installation, Start-Up and Operator’s Manual

To Clean the Generator

• Use a damp cloth to wipe exterior surfaces clean.

CAUTION

Improper treatment of generator can damage it and shorten its life.

DO NOT expose generator to excessive moisture, dust, dirt, or corrosive vapors.

DO NOT insert any objects through cooling slots.

• Use a soft, bristle brush to loosen caked on dirt, oil, etc.

Use a vacuum cleaner to pick up loose dirt and debris.

Use low pressure air (not to exceed 25 psi) to blow away dirt. Inspect cooling air slots and openings on the generator.These openings must be kept clean and unobstructed.

When Calling the Factory

You must have the following information at hand if it is necessary to contact a local service center regarding service or repair of this unit:

1.Obtain unit Model Number and Serial Number from unit data decal. See “Know Your Home Standby Generator” diagram for location.

2.Obtain engine Model/Type/Code numbers from engine label. See “Know Your Home Standby Generator” diagram for location. Please note that model number may vary slightly from that presented herein.

STORAGE

The Briggs & Stratton Home Standby Generator is designed for continuous backup operational duty.As such, there is no need to take any storage precautions. However, if it becomes necessary to take the system out of service for an extended period, call Briggs & Stratton Technical Services at 1-800-743-4115, between 8:00 AM and 5:00 PM CT for specific recommendations.

23

Briggs & Stratton Power Products Home Standby Generator

Installation, Start-Up and Operator’s Manual

TROUBLESHOOTING

Problem

Cause

Correction

 

 

 

 

 

 

1.

Circuit breaker open or defective.

1.

Reset or replace circuit breaker.

Engine is running, but no AC

2.

Fault in generator.

2.

Contact local service facility.

output is available.

3.

Poor wiring connections or

3.

Check and repair.

 

 

 

defective transfer switch.

 

 

 

 

 

 

 

 

1.

Short circuit in a connected load.

1.

Disconnect shorted electrical load.

Engine runs good at no-load but

2.

Generator is overloaded.

2.

See "Essential Circuits".

3.

Shorted generator circuit.

3.

Contact local service facility.

"bogs down" when loads are

4.

Fuel Pressure is incorrect.

4.

See "The Gaseous Fuel System".

connected.

 

5.

Natural gas fuel mixture is

5.

See "The Gaseous Fuel System".

 

 

incorrect.

 

 

 

 

 

 

 

 

1.

15 Amp fuse missing or blown.

1.

Install (new) 15 Amp fuse. See

 

 

 

 

“Know Your Control Panel”.

 

2.

Out of fuel.

2.

Open fuel valve(s); check propane

Engine will not start; or starts and

 

 

 

tank.

runs rough.

3.

Battery doesn’t have enough

3.

Install battery warmer, contact

 

 

power to crank over generator in

 

local service facility.

 

 

cold temperatures.

 

 

 

4.

Failed battery.

4.

Replace battery.

 

 

 

 

 

Engine shuts down during

1.

Out of fuel.

1.

Check fuel valves, fill propane tank.

2.

Fault indicator blinking.

2.

Count blinks and refer to "Fault

operation.

 

 

 

Detection System".

 

 

 

 

 

 

 

 

 

Loss of power on essential

1.

Generator circuit breaker is open.

1.

Reset circuit breaker.

circuits.

2.

Transfer switch problems.

2.

See transfer switch manual.

 

 

 

 

 

24

Briggs & Stratton Power Products Home Standby Generator

Installation, Start-Up and Operator’s Manual

NOTES

25

Briggs & Stratton Power Products Home Standby Generator

Installation, Start-Up and Operator’s Manual

SCHEMATIC

26

Loading...
+ 58 hidden pages