Manual 238-44943-00D

Flammable Vapor Ignition Resistant Water Heaters

Table of Contents

 

Page

Service Procedure

Introduction

3

 

- - -

Trouble shooting Chart

4

 

- - -

Inner Door Gasket Removal, Inspection, Replacement and Installation

7

 

RG-I

Thermocouple/Thermopile Testing and Replacement

10

 

RG-II

Pilot Assembly Inspection Cleaning and Replacement

13

 

RG-III

Piezo Igniter, Electrode Testing and Replacement

14

 

RG-IV

White Rodgers/Robertshaw Gas Valve Testing and Replacement

15

 

RG-V

Honeywell Gas Control Testing, Disassembly, and Replacement

20

 

RG-VI

Burner Operation Inspection, Adjustment, Cleaning and Replacement

31

 

RG-VII

Resettable Thermal Switch Testing and Replacement

34

 

RG-VIII

ScreenLok® Flame Arrestor Cleaning

36

 

RG-IV

Dip Tube and Anode Inspection and Replacement

37

 

RG-X

Generic Parts List

39

 

- - -

2

2

INTRODUCTION

The Bradford White DEFENDER Safety System®

The Bradford White DEFENDER Safety System® was designed to resist the ignition of flammable vapors that can occur outside of the water heater. Use and installation are nearly identical to previous versions of atmospherically fired and vented water heaters. A number of exclusive design features are incorporated in the system that will require additional knowledge on the part of the qualified service provider. The following information will instruct service professionals on the function, proper diagnosis and repair of water heaters employing the Bradford White DEFENDER Safety System.

How the Safety System Works

During normal operation, air for combustion is drawn into the water heater through the opening in the jacket. This air travels down and around the combustion chamber and enters through holes in the very bottom of the corrosion-resistantcombustion chamber. The air then travels up through the oriented flame arrestor plate louvers, where the velocity of the air is increased and its direction altered. The air then mixes in a normal manner with the supplied gas and is efficiently combusted, producing very low NOx emissions.

In the case where trace amounts of flammable vapors are present in the air flowing into the combustion chamber, the vapors are harmlessly ignited by the burner / pilot flame. If flammable vapors are in sufficient quantity to prevent normal combustion, the burner/pilot flame is shut down.

Should the flammable vapors continue to the burner, the flame arrestor plate prevents the flames from traveling backwards and igniting vapors outside of the combustion chamber. The calibrated, multipurpose thermal switch recognizes this and shuts down the pilot and main burner. This switch also deactivates the burner and pilot in the unlikely event of restricted airflow caused by severe lint, dust or oil accumulation on the arrestor plate.

3

3

White Rodgers/Robertshaw Gas Valve Troubleshooting Chart

Flammable Vapor Ignition Resistant Water Heaters

SYMPTOM

PROBABLE CAUSE

Pilot Will Not Light

Pilot Will Not stay lit

when button is released

Pilot will light but the main burner will not come on

Pilot goes out periodically (after heating cycles, once a day, once a week etc.)

Not enough hot water

1.No incoming gas or too low gas pressure.

2.Gas control knob set to wrong position.

3.Pilot light button not being fully depressed when attempting to light pilot.

4.Pilot orifice or pilot tube is obstructed or kinked.

5.Pilot electrode not sparking to pilot.

6.Piezo igniter not functioning.

1.Poor thermocouple connection at combination thermostat/gas valve.

2.Thermocouple not fully engaged in pilot assembly bracket.

3.Pilot flame is not fully enveloping the thermocouple “hot” junction.

4.Weak or defective thermocouple.

5.Open ECO on combination thermostat/ gas valve.

6.Defective magnet in combination thermostat/gas valve.

7 Resettable thermal switch has opened.

1.Combination thermostat/gas valve set too low for desired water temperature.

2.Combination thermostat/gas valve temperature is satisfied.

3.Insufficient gas supply or low gas pressure.

4.Combination thermostat/gas valve has wide differential or is out of calibration.

1.Insufficient combustion air supply.

2.Incorrect, clogged vent system/ vent terminal or location.

3.Inconsistent gas supply or gas pressure.

1.Combination thermostat/gas valve set too low for desired water temperature.

2.Cold inlet water temperature is very cold.

3.High demand periods.

4.Incorrectly sized water heater for application.

5.Combination thermostat/gas valve is out of calibration/not functioning.

6.Out of spec dip tube is diluting hot water with cold water.

CORRECTIVE ACTION

1.Turn on gas supply and/or check line pressure.

2.Review lighting instruction. Set combination/thermostat

gas valve to correct position.

3.Review lighting instruction. Fully depress pilot lighting button.

4.Clean, repair or replace.

5.Verify correct electrode position. Replace pilot assembly.

6.Replace Piezo igniter.

1.Check connection at combination thermostat/gas valve. Proper tightness should be finger tight plus ¼ turn.

2.Inspect thermocouple to ensure that it is fully engaged into pilot bracket.

3.Adjust tip of thermocouple to be fully engulfed by pilot flame.

4.Check thermocouple and replace if necessary.

5.Check ECO continuity and replace combination thermostat/gas valve if necessary.

6.Check magnet operation and replace combination thermostat/gas valve if necessary.

7.Determine cause of switch activation. To reset, depress button on resettable thermal switch located on inner door.

1.Adjust temperature dial on combination thermostat/gas valve.

2.Check temperature dial setting on combination thermostat/gas valve.

3.Check gas supply and line pressure.

4.Check combination thermostat/gas valve for proper operation, replace if necessary.

1.Verify adequate combustion air is available to the unit. Check and clear Jacket slot openings of any dirt, dust, restrictions or other obstructions. Inspect flame arrestor plate and clean with stiff bristled brush and/or vacuum to remove any debris accumulation.

2.Check venting for proper sizing and proper operation

3.Check gas supply and line pressure.

1. Check dial on combination thermostat/gas valve.

2.Extremely cold water going into the heater will decrease the amount of hot water produced. It may be necessary to temper incoming water supply.

3.Adjust high demand usage.

4.Contact Plumbing professional.

5.Check combination thermostat/gas valve for proper operation, replace if necessary.

6.Inspect dip tube and replace if necessary.

SERVICE

PROCEDURE

1.See Service Procedure RG-V,Page 12.

4.See Service Procedure RG-III,Page 10.

5.See Service Procedure RG-III,Page 10.

6.See Service Procedure RG-IV,Page 11.

4.See Service Procedure RG-II,Page 8

5.See Service Procedure RG-V,Page 14

6.See Service Procedure RG-V,Page 13

2.See Installation & operation manual.

3.See Service Procedure RG-V,Page 12

4.See Service Procedure RG-V,Page 12

1.See Service Procedure RG-VIII,Page 22

3.See Service Procedure RG-V,Page 12

5.See Service Procedure RG-V,Page 12

6.See Service Procedure RG-IX,Page 23

4

4

Honeywell Gas Control Troubleshooting Chart

Flammable Vapor Ignition Resistant Water Heaters

Observe green LED indicator on Gas Control. Error flash codes are displayed with a three second pause before repeating. Check and repair the system as noted in the troubleshooting table below.

LED Status

Control Status

None (LED not on or flashing

One flash and three second pause

LED on continuously (Solid)

Two flashes and three second pause

Gas Control is operating normally. Pilot flame may not be present. Check for pilot flame through sight glass and light if necessary.

If set point knob is in “PILOT” position then pilot flame is detected. Turn set point knob to desired setting.

Set point knob has been recently turned to the “OFF” position. Wait until LED goes out before attempting to relight

Weak pilot signal detected. System will reset when pilot flame is sufficient.

Green LED Indicator

Probable Cause

1. Gas Control is functioning normally.

2. Gas Control is not powered. Light pilot.

3. Thermopile failure.

Gas Control is powered and waiting for the set point knob to be turned to a water temperature setting.

Set point knob was turned to “OFF” position.

1. Thermopile failure

2. Unstable pilot

3. Pilot tube block or restricted.

4. Resettable thermal switch has opened

Service

Procedure

If the pilot will not stay lit replace pilot assembly. If problem persists replace Gas Control.

Normal operation. Adjust thermostat to desired temperature setting.

LED will go out and the control will function normally when the pilot is lit.

1.See service procedure RG-II

2.See service procedure RG-III

3.See service procedure RG-III

4.See service procedure RG-VIII

Three flashes and

three second Insufficient water heating. System

will reset.

pause

Four flashes and

Excessive tank temperature.

three second

System must be reset.

pause

 

1.Temperature sensor out of calibration

1.Temperature sensor out of calibration

2.Faulty Gas Control

1.See service procedure RG-VI

1.See service procedure RG-VI

2.See service procedure RG-VI

5

5

Honeywell Gas Control Troubleshooting Chart

Flammable Vapor Ignition Resistant Water Heaters

Observe green LED indicator on Gas Control. Error flash codes are displayed with a three second pause before repeating. Check and repair the system as noted in the troubleshooting table below.

Green LED Indicator

LED Status

Control Status

Probable Cause

Five flashes and three second pause

Six flashes and three second pause

Seven flashes and three second pause

Eight flashes and three second pause

Thermostat/well sensor fault.

Water leak detected by accessory module.

Gas Control electronic fault detected.

Standing pilot remains on while set point knob is in “OFF” position.

1.Damage to the temperature sensor.

2.Temperature sensor resistance out of range.

Excessive amount of water in drain pan/water dam.

1.Control need to be reset.

2.Control is wet or physically damaged.

Pilot valve stuck in open position.

Service

Procedure

1. See service procedure RG-VI

1.Check T&P valve

2.Check all water fittings.

3.Pressurize and leak test tank.

1.Reset Gas Control

2.Replace Gas Control.

Replace Gas Control.

6

66

White

SERVICE PROCEDURE RG-I

Inner Door/Gasket Removal, Inspection

DEFENDER

Replacement and Reinstallation

®

For Honeywell Control, rotate

Safety System

knob counter-clockwiseto the

 

“OFF” position.

 

Inner Door Removal Procedure

 

 

Step 1. Rotate knob of the combination

 

 

thermostat/gas valve to the “OFF” position.

 

 

Step 2. Remove outer jacket burner access door

For Robertshaw Control,

For White Rodgers Control,

 

Step 3. Inner Door Removal.

depress knob slightly and rotate

rotate knob clockwise to

clockwise to the “OFF” position.

 

the “OFF” position.

 

 

a)Disconnect resettable thermal switch wire leads (leading from Gas Control/gas valve).

b)Remove (2) hex drive screws from right side inner door.

c)Remove (2) hex drive screws from flange section of inner door.

d)Remove (2) hex drive screws from left side inner door.

e)Remove inner door and inspect per step 4.

Resettable Thermal Switch

Wire Connection

Hex Drive Screws

Right and Left Side Inner Door.

Hex Drive Screws at

Flange Area of Inner Door

Step 4. Fully inspect inner door gaskets for the following:

>Tears

>Other imperfections that will inhibit proper seal

>Missing Material

>Gasket adhesion to inner door

>Cracks

>Material left on combustion chamber (around opening)

>Dirt or debris

 

If the gasket is not effected by any of the above, gasket replacement is not required. If replacement is required, proceed to Inner Door Gasket Replacement Procedure.

Inner Door Gasket Replacement Procedure.

WARNING

If the information in these instructions is not followed exactly, a fire or explosion may result causing property damage, personal injury or death.

Step 5. After inspection of inner door as noted in step 4, completely remove gasket and adhesive residue from right and left side inner doors as needed.

Step 6. Use RTV sealant (recommended bead size 1/8") to secure the inner door gasket to the inner door sections (right & left). Refer to illustration on next page for proper application. Note the overlap configuration in the flange area of the inner door. Set the flange section first, this will help to achieve the proper over lap position.

7

7

SERVICE PROCEDURE RG-I

Inner Door/Gasket Removal, Inspection

Replacement and Reinstallation

RECOMMENDED PATTERN

FOR RTV SEALANT

PLACE FLANGE

SECTIONS FIRST

EXPANDED VIEW

Installation of Inner Door With Gasket.

Step 7. Clean any residual gasket residue or other debris from combustion chamber surface before installing the inner door/gasket assembly.

Step 8. Place the left side inner door into position first. Firmly position the radiused channel of the inner door aroundthe feedline. Using the (2) hex drive screws from step 3d, secure left side inner door in place. DO NOT OVER TIGHTEN SCREWS.

Step 9 Position thermocouple, pilot tube and Piezo wire against left side inner door flange gasket.

DO NOT ROUTE THROUGH RADIUSED CHANNEL WITH FEEDLINE.

Radiused Channel for Feedline

8

GASKET

OVERLAP MUST

BE AS SHOWN

ENLARGED

±1/32"

VIEW OF

 

FLANGE AREA

VIEW WITH GASKETS

IN PLACE

WARNING

Stripped fastener connections may allow for seal breach of inner door. A seal breach may result in a fire or explosion causing property damage, personal injury or death. Do not over tighten screws in steps 8, 10 and 11.

If a fastener connection is stripped, contact the manufacturer listed on the water heater rating plate.

Position thermocouple/thermopile, pilot tube and piezo wire.

88

SERVICE PROCEDURE RG-I

Inner Door/Gasket Removal, Inspection

Replacement and Reinstallation

Step 10. Firmly place right side inner door flange against the left side inner door flange and secure with (2) hex drive screws from step 3c. DO NOT OVER TIGHTEN SCREWS.

Step 11. Align right side inner door to combustion chamber and verify the fastener holes of the combustion chamber are aligned with the right side inner door slotted opening. Verify seal integrity around combustion

opening. Secure right side inner door using (2) hex drive screws from step 3b. DO NOT OVER TIGHTEN SCREWS. Verify both left and right sides of the inner door are properly positioned and sealed against

the combustion chamber.

Secure flange with hex drive screws.

Verify threaded hole alignment with slotted openings in inner door.

Step 12. Reconnect lead wires from combination thermostat/gas valve to resettable thermal switch (See photo in step 3). Note, wire terminations are interchangeable with either resettable thermal switch connections.

Step 13. Replace outer jacket burner access door.

Step 14. To resume operation follow the instructions located on the lighting instruction label or the lighting instructions located in the installation and operation manual.

9

9

White

DEFENDER

Safety System®

SERVICE PROCEDURE RG-II

Thermocouple/Thermopile Testing and

Replacement

CLOSED CIRCUIT THERMOCOUPLE TESTING (White Rodgers Control)

Step 1. Closed circuit testing is the preferred method for testing thermocouple. Following the lighting instruction label on the heater, proceed to light the pilot and allow to operate for three minuets. If the pilot will not stay lit, hold the pilot button (located on the combination thermostat/gas valve) down during this test

Step 2. Using a multimeter capable of measuring millivolts, connect one lead

using an alligator clip to the copper sheath of the thermocouple, use the second lead of the multi meter to probe the top terminal located at the back of the combination thermostat/gas valve.

Step 3. If meter reads 10 millivolts or higher, the thermocouple is OK. If reading is below 10 millivolts, replace the thermocouple.

Probe top terminal on back of combination

thermostat/gas valve Alligator clip to copper sheath of thermocouple

CLOSED CIRCUIT THERMOCOUPLE TESTING (Robertshaw Control)

Step 1. Disconnect thermocouple from combination thermostat/gas valve.

Step 2. Connect a thermocouple adaptor

(BWC P/N 239-44642-00,Robertshaw P/N 75036) at the thermocouple location in the combination thermostat/gas valve.

Step 3. Reconnect thermocouple to adaptor. Make certain all connections are tight (finger tight plus ¼ turn)

Step 4 Using a multimeter capable of measuring millivolts, connect one alligator clip to the set screw of the adaptor, and the other alligator clip to copper portion of the thermocouple.

Step 5. Following the lighting instruction label on the heater, proceed to light the pilot and allow to operate for three minuets. If the pilot will not stay lit, hold the red reset button (located on the combination thermostat/gas valve) down during this test

Step 6. If meter reads 13 millivolts or higher, the thermocouple is OK. If reading is below 13 millivolts replace the thermocouple.

10

10

SERVICE PROCEDURE RG-II

Thermocouple/Thermopile Testing and

Replacement

OPEN CIRCUIT THERMOCOUPLE TESTING (White Rodgers/Robertshaw Gas Valve)

Step 1. Disconnect thermocouple from combination thermostat/gas valve.

Step 2. Using a multimeter capable of measuring millivolts, connect one alligator clip to the end ball or contact portion of the thermocouple, and the other alligator clip to copper portion of the thermocouple.

Step 3. Following the lighting instruction label on the heater, proceed to light the pilot and allow to operate for three minutes. It will be necessary to hold the pilot button down continuously throughout this test.

A reading of 20 to 30 millivolts indicates good thermocouple output.

THERMOCOUPLE REPLACEMENT (White Rodgers/Robertshaw Gas Valve)

Step 1. Turn off gas supply to water heater. Rotate knob of combination thermostat/gas valve to “OFF” position.

For White Rodgers Control, depress knob slightly and rotate clockwise to the “OFF” position.

For Robertshaw Control, rotate knob clockwise to the “OFF” position.

Step 2. Remove outer jacket door.

Step 3. Remove right side of inner door per SERVICE PROCEDURE RG-I,steps 3a through 3c.

Step 4 Disconnect thermocouple from combination thermostat/gas valve. Locate other end of thermocouple inside of combustion chamber and remove from pilot bracket. Pull firmly pulling away from the pilot assembly.

Step 5. Install new thermocouple into pilot bracket making certain the thermocouple is fully engaged into the pilot bracket. Position thermocouple against left side inner door flange at its original position. Connect other end of thermocouple to combination thermostat/gas valve (finger tight + ¼ turn).

Step 6. Inspect inner door gasket per

SERVICE PROCEDURE RG-I,Step 4.

Step 7. Install right side inner door per SERVICE PROCEDURE RG-I,Step 10 through Step 13

Thermocouple position

Step 8. To resume operation follow the instructions located on the lighting instruction label or the lighting instructions located in the installation and operation manual.

11

11

SERVICE PROCEDURE RG-II

Thermocouple/Thermopile Testing and

Replacement

OPEN CIRCUIT THERMOPILE TESTING (Honeywell Gas Control)

The following test should be performed while the pilot flame is on. Step 1. Turn knob to pilot position and depress.

Step 2. Continue pressing knob and remove red (+) wire from resettable thermal door switch.

Step 3. Using a multimeter capable of measuring millivolts, connect the positive side of the multimeter to the terminal of the resettable thermal door switch. Connect the negative side of the multimeter to any earth ground location (jacket base, screw, etc.).

Resettable Thermal Door

Switch Terminal (+)

Jacket Base Screw (-)

Normal thermopile operation will be between 350mV - 850mV. If reading is less than 350mV, replacement of pilot assembly is recommended following SERVICE PROCEDURE RG-III.

Step 4. If thermopile reading is between 350mV - 850mV, remove multimeter and reconnect red wire to positive (+) terminal of Gas Control.

Step 5. Release Gas Control knob and turn to desired setting to resume normal operation.

12

12

Removal of thermopile from Honeywell pilot assembly is not recommended, but can be achieved by viewing the pilot assembly from the top and pressing the thermopile towards the right while pulling to remove.
Primary Air
Opening
Pilot Orifice
Feedline Nut

White

Safety System®

PILOT/ELECTRODE ASSEMBLY INSPECTION,

CLEANING AND REPLACEMENT

Step 1. Turn off gas supply to water heater. Rotate knob of gas control/gas valve

to “OFF” position.

Step 2. Remove outer jacket door.

Step 3. Remove right side of inner door per SERVICE PROCEDURE RG-I,steps 3a through 3c.

Step 4 Disconnect thermocouple/thermopile, pilot tube, and feedline from gas control/gas valve.

SERVICE PROCEDURE RG-III

Pilot Assembly Inspection, Cleaning

and Replacement

For Honeywell Control, rotate knob counter-clockwiseto the “OFF” position.

For White Rodgers Control, depress knob slightly and rotate clockwise to the “OFF” position.

For Robertshaw Control, rotate knob clockwise to the “OFF” position.

NOTE: Feedline nut for natural gas control

uses right hand threads, LP control uses left hand thread.

Step 5 Disconnect piezo ignition wire from piezo igniter.

Step 6. Remove burner assembly from combustion chamber. Step 7. Remove pilot/electrode assembly from feedline

Step 8. Inspect pilot for the following:

a) Primary air openings for blockage. Must be free from any debris (dirt, lint, etc).

b) Kinks or cracks in the pilot tube. If found, the pilot must be replaced.

Step 9. Inspect pilot orifice:

a) Remove ½" nut from bottom of pilot assembly.

b) Remove pilot tube and pilot orifice.

c) Inspect pilot orifice for blockage, must be cleaned or replaced. (Honeywell pilot orifice not replaceable, replace pilot assembly)

Step 10. Install pilot/electrode assembly to feedline, secure with screw from step 7.

Step 11. Re-Installburner assembly into combustion chamber, connect feedline, pilot tube and thermocouple/thermopile to gas conrol/gas valve.

Step 12. Install inner door per SERVICE PROCEDURE RG-I,step 4 through 13.

Step 13. To resume operation follow the instructions located on the lighting instruction label or the lighting instructions located in the installation and operation manual.

13

13

White

Safety System®

SERVICE PROCEDURE RG-IV

Piezo Igniter, Electrode Testing

and Replacement

PIEZO IGNITER, ELECTRODE TESTING AND REPLACEMENT

With the pilot not in operation (no pilot flame) you can check the Piezo and electrode circuit by viewing pilot thru the sight glass located on the inner door and observing the spark action.

Step 1. Remove outer jacket door.

Step 2. Repeatedly depress the Piezo igniter while viewing the pilot thru the sight glass. If a spark is present, the circuit is OK. If there is no spark, proceed to step 3.

View spark Action through

Repeatedly Sight glass Depress Piezo

Igniter

Step 3 Remove orange (or white) wire from Piezo igniter and install a jumper wire in its place. Hold the other end of the jumper by the wire insulation or using an insulated tool, next to an unpainted surface such as the feedline or gas valve and depress the Piezo igniter. If there is a spark, the igniter is OK, the pilot is not functioning and must be replaced, see SERVICE PROCEDURE RG-IIIfor pilot replacement. If no spark is present the igniter is not functioning and must be replaced.

Step 4a. For White Rodgers/Robertshaw gas valves: With orange wire disconnected from piezo igniter. Using a common screw driver, place blade of screw driver under piezo bracket and gently pry bracket from front of gas valve and unhook bracket from rear of gas valve.

Common Screw

Driver

Step 4b. For Honeywell gas controls: To replace igniter, see “Gas Control Disassembly/Reassembly” in SERVICE PROCEDURERG-VI.

14

14

White

Safety System®

SERVICE PROCEDURE RG-V

Gas Valve

Testing and Replacement (White Rodgers/Robertshaw)

Gas Valve Testing and Replacement (White Rodgers/Robertshaw)

The gas valve is a non repairable device. If trouble shooting has determined a problem with the gas valve, it must be replaced.

If the burner and/or pilot do not function, service checks for gas pressure, thermocouple output, magnet assembly and ECO are to be performed. If these check OK, the gas valve may be faulty.

LINE PRESSURE

The gas valve is designed for a maximum line pressure of 14.0" w.c. and a minimum line pressure of 1.0"w.c. over the water heater rated manifold pressure (check rating plate). Line pressure must be checked with burner on and burner off to assure proper readings.

MANIFOLD PRESSURE TESTING (this procedure assumes a maximum line pressure of 14.0" w.c.)

Step 1. Set gas valve to “OFF” position.

Step 2. Remove pressure tap plug and install pressure tap.

Step 3. Connect manometer to pressure tap.

Step 4 Follow lighting instructions and proceed to light main burner and observe manometer reading.

Pressure Tap

Shown Installed

Step 5 Proper operating range for natural gas is 4.0 ±0.3" W.C.

Proper operating range for L.P. gas is 10.0 ±0.5" W.C.

Step 6 If pressure is OK, set gas valve to “OFF”

remove manometer and pressure tap and replace pressure tap plug. Check for gas leaks before placing water heater back in operation. If pressure is out of the specification noted in step 5, proceed to step 7 or 8 for proper service procedure.

Step 7 For White Rodgers control, the manifold pressure is not adjustable. If manifold pressure is outside the range in step 5, the control must be replaced.

Step 8 For Robertshaw control, the manifold pressure is adjustable, proceed to step 9 for adjustment procedure

Step 9 While burner is in operation, remove regulator access cap to expose the regulator adjusting screw. With small screw driver, rotate adjusting screw clockwise to increase pressure and counter clockwise to decrease pressure.

Step 10 Replace regulator access cap, set gas valve to “OFF”. Remove manometer and

pressure tap and replace pressure tap plug. Check for gas leaks before placing water heater back in operation.

15

15

SERVICE PROCEDURE RG-V

Gas Valve

Testing and Replacement (White Rodgers/Robertshaw)

THERMOCOUPLE TESTING

See SERVICE PROCEDURE RG-II

MAGNET ASSEMBLY TESTING (White Rodgers Control)

Step 1. Following the lighting instruction label on the heater, proceed to light the pilot and allow to operate for

three minuets. If the pilot will not stay lit, hold the pilot button (located on the gas valve) down during this test.

Step 2. Using a multimeter capable of measuring millivolts, connect one lead

using an alligator clip to the copper sheath of the thermocouple, use the second lead of the multi meter to probe the top terminal located at the back of the gas valve.

Probe top terminal on back of combination

thermostat/gas valve Alligator clip to copper sheath of thermocouple

Step 6. With a meter reading of 13 millivolts or greater, rotate knob of combination thermostat/gas valve to the “OFF” position.

Step 7. The magnet should remain closed for a drop of at least 6 millivolts. You will here a “snap” or “click” sound when the magnet opens, if you hear this sound prior to a drop of 6 millivolts, the magnet is out of specification and the gas valve should be replaced.

MAGNET ASSEMBLY TESTING (Robertshaw Control)

Step 1. Disconnect thermocouple from gas valve.

Step 2. Connect a thermocouple adaptor

(BWC P/N 239-44642-00,Robertshaw P/N 75036) at the thermocouple location in the gas valve.

Step 3. Reconnect thermocouple to adaptor. Make certain all connections are tight (finger tight plus ¼ turn).

Step 4 Using a multimeter capable of measuring millivolts, connect one alligator clip to the set screw of the adaptor and the other alligator clip to copper portion of the thermocouple.

Step 5. Following the lighting instruction label on the heater, proceed to light the pilot and allow to operate for three minuets.

Step 6. With a meter reading of 13 millivolts or greater, rotate knob of gas valve to the “OFF” position.

Step 7. The magnet should remain closed for a drop of at least 6 millivolts. You will here a “snap” or “click” sound when the magnet opens, if you hear this sound prior to a drop of 6 millivolts, the magnet is out of specification and the gas valve should be replaced.

16

16

SERVICE PROCEDURE RG-V

Gas Valve

Testing and Replacement (White Rodgers/Robertshaw)

ECO (Energy Cut Off) TESTING

Step 1. Disconnect thermocouple from gas valve.

Step 2. Using a multimeter capable of measuring Ohms (or continuity), attach one lead (alligator clip) to the pilot tube. Insert the other lead (probe) fully into the magnet opening, Be sure the probe makes contact only at the top center of the magnet opening. Do not allow the probe to make contact with the threaded sides of the opening.

Step 3. If continuity is indicated, the ECO is OK. If continuity is not indicated, the ECO has opened and the gas valve must be replaced.

COMBINATION THERMOSTAT/GAS VALVE REPLACEMENT

Step 1. Rotate knob of the gas valve to the “OFF” position. Step 2. Turn off gas supply to water heater.

Step 3. Disconnect gas supply line from gas valve.

Step 4. Turn off water supply and drain water heater completely. Step 5. Remove outer jacket burner access door.

Step 6. Right side inner door removal.

For White Rodgers Control, depress knob slightly and rotate clockwise to the “OFF” position.

For Robertshaw Control, rotate knob clockwise to the “OFF” position.

a)Disconnect resettable thermal switch wire leads (leading from gas valve) and remove wire tie from feedline.

b)Remove (2) hex drive screws from right side inner door.

c)Remove (2) hex drive screws from flange section of inner door.

d)Remove right side inner door and set aside. Be careful not to damage gasket material on inner door.

Remove

Wire Tie

Resettable Thermal Switch

Wire Connection

Hex Drive Screws shown on Right Side Inner Door.

Hex Drive Screws at

Flange section of Inner Door

17

17

SERVICE PROCEDURE RG-V

Gas Valve

Testing and Replacement (White Rodgers/Robertshaw)

Step 7. Removal of gas valve.

a)Disconnect main burner feedline, pilot tube and thermocouple from gas valve & remove burner from combustion chamber.

NOTE: Feed line nut for natural gas control uses right hand threads,

LP control uses left hand thread.

b) Remove piezo bracket with piezo igniter (refer to SERVICE PROCEDURE RG-IV)from gas valve.

c) Remove gas valve from water heater,

 

Wrench Boss

rotating counter clockwise using a control body wrench or a

 

 

 

length of ½" NPT pipe threaded into inlet of control.

 

 

To remove or install control, insert only ½" NPT threaded pipe into inlet and use to loosen or tighten control.

Step 8. Installation of gas valve.

a)Install new gas valve using a control body wrench or a length of ½" NPT

pipe threaded into inlet of control. DO NOT OVER TIGHTEN. Use caution not to damage cast aluminum body of gas valve. Be certain not to damage the bundled wire leads.

Note: Gas valve must be installed in proper upright position to assure the feedline will align properly at the inner door flange.

DO NOT OVER TIGHTEN. If control is turned past proper alignment, do not reverse direction to align.

b)Reattach Piezo bracket with Piezo igniter to gas valve.

c)Reattach main burner feedline, pilot tube and thermocouple to gas valve.

NOTE: Feedline nut for natural gas control uses right hand threads,

LP control uses left hand thread.

d)Gather wire leads of gas valve and Piezo igniter and secure along side of feedline using new wire tie provided.

e)Connect gas supply piping to inlet of control. Use back up wrench on wrench boss of control, never use back up wrench on body of control.

Step 9. Reinstallation of inner door assembly.

a) Prior to reinstallation of inner door, fully inspect inner door gasket for the following:

> Tears

> Gasket Adhesion to inner door

> Missing Material

> Other imperfections that will inhibit proper seal

> Cracks

> Material left on combustion chamber

> Dirt or debris

 

If the gasket is not effected by any of the above, gasket replacement will not be required. If replacement is required, replace using new gasket kit following the instructions provided with kit.

18

18

Secure flange with ¼" drive screws.

SERVICE PROCEDURE RG-V

Gas Valve

Testing and Replacement (White Rodgers/Robertshaw)

Step 9. Reinstallation of inner door assembly. (cont.)

b)Clean any gasket residue or other debris from combustion chamber surface before installing the inner door/gasket assembly.

c)Position thermocouple, pilot tube and Piezo wire against left side inner door flange gasket. DO NOT ROUTE THROUGH RADIUSED CHANNEL WITH FEEDLINE. Be sure that thermocouple and pilot tube are not in position to interfere with outer jacket burner access door when reinstalled.

WARNING

A seal breach may result in a fire or explosion causing property damage, personal injury or death.

Position thermocouple, pilot tube and Piezo wire.

d) Firmly place right side inner door flange against the left side inner door flange and secure with (2) hex drive screws from step 6c. DO NOT OVER TIGHTEN SCREWS.

e) Align right side inner door to combustion chamber and verify the fastener holes of the combustion chamber are aligned with the right side inner door slotted openings. Verify seal integrity around combustion

opening. Secure right side inner door using (2) hex drive screws from step 6b. DO NOT OVER TIGHTEN SCREWS. Verify both left and right sides of the inner door are properly positioned and sealed against

the combustion chamber.

Verify threaded hole alignment with slotted openings in inner door.

Step 10. Reconnect wire leads from gas valve to resettable thermal switch (See photo in step 6). Note: wire terminations are interchangeable with either resettable thermal switch connection.

Step 11. Replace outer jacket burner access door. Step 12. Reconnect gas supply to gas valve.

Step 13. Resume water supply to water heater. Be sure tank is full of water.

Step 14. To resume operation follow the instructions located on the lighting instruction label or the lighting instructions located in the installation and operation manual.

19

19

White

Safety System®

SERVICE PROCEDURE RG-VI

Gas Control

Testing, Disassembly & Replacement (Honeywell)

Honeywell Gas Control Testing, Disassembly, and Replacement

The Gas Control is made up of (5) major components; the control cover, the piezo igniter, the valve body, the temperature sensor, and the back plate. The Gas Control is designed so that any of these components may be replaced without replacing the entire Gas Control.

Gas Control

Valve Body

Backplate

Cover

 

 

Gas Control

Cover Screw

Piezo Igniter

 

Temperature

 

Sensor

 

Valve Body

Insertion Stick

 

Screw

 

 

LINE PRESSURE

The Gas Control is designed for a maximum line pressure of 14.0" w.c. and a minimum line pressure of 1.0" w.c. over the water heater’s rated manifold pressure (check rating plate). Line pressure must be checked with the main burner on and off to assure proper readings.

20

20

White

Safety System®

SERVICE PROCEDURE RG-VI

Gas Control

Testing, Disassembly & Replacement (Honeywell)

MANIFOLD PRESSURE TESTING (this procedure presumes a maximum line pressure of 14.0" w.c.)

Step 1. Set the Gas Control to the “OFF” position.

Step 2. Remove pressure tap plug and install 1/8" NPT pipe, coupling, & pressure tap.

Gas Control shown in the “OFF” position

Step 3. Connect manometer to pressure tap.

Step 4. Follow instructions located on the lighting instructions label and proceed to light the main burner and observe manometer reading.

Step 5. Proper operating range for natural gas is: 4.0" ±0.5" w.c. Proper operating range for LP gas is: 10.0" ±0.5" w.c.

Step 6. If pressure is within the range specified in the previous step, set Gas Control knob to the “OFF” position, remove manometer and pressure tap, and replace pressure tap plug. Check for gas leaks prior to placing water heater back into operation by following the instructions located on the lighting instruction label or the lighting instructions located in the installation and operation manual.

Step 7. If gas pressure is outside the specification noted above, refer to “Honeywell Gas Control Testing, Disassembly, and Replacement” to replace Gas Control or valve body.

THERMOPILE TESTING

See SERVICE PROCEDURE RG-II

Pressure Tap

Shown Installed

ECO (Energy Cut Off) TESTING

The Honeywell Gas Control is designed with an ECO device that will reset.

To reset the Gas Control after an error code (4), turn the Gas Control knob to the “OFF” position and wait a minimum of (5) minutes before relighting following the instructions located on the lighting instruction label or the lighting instructions located in the installation and operation manual.

21

21

White

Safety System®

TEMPERATURE SENSOR TESTING

If Control has gone into lockout due to excessive tank temperature (four flash, three second pause) reset control by rotating gas control knob to “OFF” position and wait a minimum of (5) minutes. Then follow lighting instructions and return gas control

knob to desired setpoint.

SERVICE PROCEDURE RG-VI

Gas Control

Testing, Disassembly & Replacement (Honeywell)

CAUTION

DO NOT use standard multimeter probes for this test. Doing so will damage connector. Use special pin type electronic probes or small diameter wire pins inserted into connector.

Observe Green LED indicator.

N

Does error code 4 (four flash, three

 

 

second pause) continue?

 

 

Y

 

Temperature Sensor Testing

 

 

Following “Gas Control

 

 

 

Disassembly/Reassembly”

 

instructions, disassemble Gas

 

Control to access temperature

 

 

sensor.

 

With the temperature sensor still

 

in the back plate, use a multi-

 

meter set to the Ohms setting,

 

 

determine the resistance of

 

 

temperature sensor

 

(see caution and photos above)

 

Using a multi-meterset to the ohms setting, insert one meter probe (see caution) into center wire position of thermal well connector, insert the second probe (see caution) into either of the outside wire positions (see photo on left).

Alternate the probe on the outside position to the opposite outside wire position (see photo on right).

Resume normal operation.

Once the temperature sensor resistance values are known, the

 

 

water temperature must also be known to determine if the

N

 

resistance values are correct. See next page to obtain water

Replace temperature

temperature.

 

sensor

Are temperature sensor resistance values correct?

 

 

 

Y

 

 

 

 

 

 

 

 

 

Replace Gas Control

 

 

22

22

White

Safety System®

SERVICE PROCEDURE RG-VI

Gas Control

Testing, Disassembly & Replacement (Honeywell)

WARNING

Stored water may be HOT when performing the following steps in this procedure. Take necessary precaution to prevent personal injury.

DETERMINE WATER TEMPERATURE INSIDE TANK

Note: It is important to understand once the resistance for the temperature sensor is determined from the previous page, water flow through the water heater should not occur. Prior to drawing water from drain valve, turn off the cold water supply to the water heater. This will prevent cold water flow into the tank affecting the resistance value of the temperature sensor.

Step 1. Set the Gas Control knob to the “OFF” position. Step 2. Turn off inlet water supply to water heater.

Step 3. Draw approximately 4 gallons of water from drain valve into a container, or suitable drain, and discard. Draw an additional gallon and immediately measure water temperature using an accurate thermometer. It may be necessary to open a hot water faucet to allow water heater to drain.

Step 4. Using the chart below, determine correct resistance value for the water temperature from step 3.

Example:

If temperature of water is 84°F, then the resistance through the sensor would be

 

 

8449 (see shaded area). NOTE: Sensor resistance increases as the temperature

 

 

 

decreases.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Sensor Resistance at Various Temperatures

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

In Degrees F

 

 

 

 

 

 

 

°F

0

1

 

2

3

 

4

5

6

7

 

8

 

9

 

40

26109

25400

24712

24045

 

23399

22771

22163

21573

21000

 

20445

 

50

19906

19383

18876

18383

 

17905

17440

16990

16553

16128

 

15715

 

60

15314

14925

14548

14180

 

13823

13477

13140

12812

12494

 

12185

 

70

11884

11592

11308

11032

 

10763

10502

10248

10000

9760

 

9526

 

80

9299

9078

8862

8653

 

8449

8250

8057

7869

7685

 

7507

 

90

7333

7165

7000

6839

 

6683

6531

6383

6238

6098

 

5961

 

100

5827

5697

5570

5446

 

5326

5208

5094

4982

4873

 

4767

 

110

4663

4562

4464

4368

 

4274

4183

4094

4006

3922

 

3839

 

120

3758

3679

3602

3527

 

3453

3382

3312

3244

3177

 

3112

 

130

3048

2986

2925

2866

 

2808

2752

2697

2643

2590

 

2538

 

140

2488

2439

2391

2344

 

2298

2253

2209

2166

2124

 

2083

 

150

2043

2004

1966

1928

 

1891

1856

1820

1786

1753

 

1720

 

160

1688

1656

1625

1595

 

1566

1537

1509

1481

1454

 

1427

 

170

1402

1376

1351

1327

 

1303

1280

1257

1235

1213

 

1191

 

180

1170

1150

1129

1110

 

1090

1071

1953

1035

1017

 

999

 

190

982

965

 

949

933

 

917

901

886

871

857

 

842

 

200

828

814

 

801

788

 

775

762

749

737

725

 

713

23

23

Rotate knob counter-clockwise to the “OFF” posistion.

White

Safety System®

SERVICE PROCEDURE RG-VI

Gas Control

Testing, Disassembly & Replacement (Honeywell)

GAS CONTROL DISASSEMBLY/REASSEMBLY

Step 1. Rotate knob of the Gas Control to the “OFF” position. Step 2. Turn off gas supply to water heater.

Step 3. Disconnect gas supply line from Gas Control. Step 4. Disconnect piezo igniter wire.

Step 5. Remove inner door assembly following SERVICE PROCEDURE RG-I,steps 1 through 3c. Step 6. Remove Gas Control cover screw.

Gas Control cover screw

Step 7. Depress both tabs on the top of the Gas Control cover and pull to remove.

CAUTION

Use caution not to bend or damage valve body pins when removing or installing Gas Control cover.

Valve body pins

24

24

White

Safety System®

SERVICE PROCEDURE RG-VI

Gas Control

Testing, Disassembly & Replacement (Honeywell)

GAS CONTROL DISASSEMBLY/REASSEMBLY

Step 8. Disconnect temperature sensor from control board and remove wire from the temperature sensor wire routing clip.

Temperature sensor wire routing clip

Disconnect temperature sensor

Step 9. Remove the piezo igniter from the control cover by releasing the lock tab on the control cover.

Release lock tab

25

25

White

Safety System®

SERVICE PROCEDURE RG-VI

Gas Control

Testing, Disassembly & Replacement (Honeywell)

GAS CONTROL DISASSEMBLY/REASSEMBLY

Step 10. Remove the valve body by removing screw located at the lower left corner then unclipping the lower right side from the backplate first followed by the lower left side using a flat head screwdriver.

CAUTION

Use caution not to bend or damage valve body pins.

Unclip lower right side first

Unclip lower left side second

Valve body screw

Step 11. Remove temperature sensor and insertion stick from backplate by first removing wire from the temperature sensor wire routing clips located on the backplate. Note the orientation of insertion stick, insertion stick can only be installed in one way.

Temperature sensor

wire routing clips

Insertion stick fully inserted into backplate

CAUTION

When reinstalling temperature sensor and insertion stick, make sure the assembly is inserted FULLY into the backplate and the wires are routed through the wire routing clips. Failure to do so will not allow valve body to be reinstalled properly and may damage temperature sensor wires.

26

26

White

Safety System®

SERVICE PROCEDURE RG-VI

Gas Control

Testing, Disassembly & Replacement (Honeywell)

GAS CONTROL DISASSEMBLY/REASSEMBLY

Step 12. Remove temperature sensor from insertion stick by pulling apart as illustrated below.

Pull in this direction

Temperature sensor

Insertion stick

Pull in this direction

Step 13. To reassemble Gas Control, follow the previous steps in reverse order. Once Gas Control is reassembled, burner assembly is reinstalled, and the gas supply line is reconnected, resume water supply to water heater. Be sure tank is full of water before relighting.

Step 14. To resume operation, follow the instructions located on the lighting instruction label or the lighting instructions located in the installation and operation manual.

27

27

White

Safety System®

SERVICE PROCEDURE RG-VI

Gas Control

Testing, Disassembly & Replacement (Honeywell)

GAS CONTROL REPLACEMENT

Rotate knob counter-clockwiseto the “OFF” position.

Step 1. Rotate knob of the Gas Control to the “OFF” position. Step 2. Turn off gas supply to water heater.

Step 3. Disconnect gas supply line from Gas Control.

Step 4. Turn off water supply and drain water heater completely. Step 5. Remove outer jacket burner access door.

Step 6. Right side inner door removal.

a)Disconnect red wire leads from resettable thermal switch.

b)Remove (2) hex drive screws from RIGHT side inner door.

c)Remove (2) hex drive screws from FLANGE SECTION of inner door.

d)Remove right side inner door and set aside. Be careful not to damage gasket material on inner door.

Resettable Thermal Switch

Remove Wire Connection

Wire Tie

Hex Drive Screws

Right and Left Side Inner Door.

Hex Drive Screws at

Flange Area of Inner Door

Step 7. Removal of Gas Control.

a)Disconnect main burner feedline, pilot tube, piezo igniter wire, inner door wire (red) and thermopile wire (white) from Gas Control.

b)Remove Gas Control from water heater by rotating counter clockwise. DO NOT use a wrench on the Gas Control body, damage to the Gas Control may occur. If necessary, use a length of ½" NPT pipe threaded into gas inlet of Gas Control.

Step 8. Install new Gas Control into water heater.

a)Install new Gas Control into water heater by rotating clockwise. DO NOT use a wrench on the Gas Control body, damage to the Gas Control may occur. If necessary, use a length of ½" NPT pipe threaded into gas inlet of Gas Control.

28

28

White

Safety System®

SERVICE PROCEDURE RG-VI

Gas Control

Testing, Disassembly & Replacement (Honeywell)

GAS CONTROL REPLACEMENT

Step 8. Install new Gas Control into water heater (contintued).

b) Reattach main burner feedline, pilot tube, piezo igniter wire, inner door wire (red) and thermopile wire (white) to Gas Control. Attach inner door wire (red) to the positive (+) terminal and the thermopile wire (white) to the negative (-)terminal.

Positive (+) Terminal

(red wire) Negative(-)Terminal (white wire)

c)Gather piezo igniter wire, thermopile wire (white), inner door wire (red), and pilot tube and secure along side of feedline using new wire tie provided.

d)Reconnect gas supply piping to inlet of Gas Control. CAUTIONUse back up wrench on wrench boss

Step 9. Reinstallation of inner door assembly.

of Gas Control, never use back up

wrench on body of Gas Control.

 

 

a) Prior to reinstallation of inner door, fully inspect inner door gasket for the following:

> Tears

> Gasket Adhesion to inner door

 

> Missing Material

> Other imperfections that will inhibit proper seal

> Cracks

> Material left on combustion chamber

> Dirt or debris

 

 

If the gasket is not effected by any of the above, gasket replacement will not be required. If replacement is required, replace using new gasket kit following the instructions provided with kit.

b)Clean any gasket residue or other debris from combustion chamber surface before installing the inner door/gasket assembly.

c)Position thermopile wire, pilot tube and Piezo wire against left side inner door flange gasket. DO NOT ROUTE THROUGH RADIUSED CHANNEL WITH FEEDLINE. Be sure that thermopile and pilot tube are not

in position to interfere with outer jacket burner access door when reinstalled.

WARNING

A seal breach may result in a fire or explosion causing property damage, personal injury or death.

Position thermopile, pilot tube and Piezo wire.

29

29

CAUTION
Use back up wrench on wrench boss of Gas Control, never use back up wrench on body of Gas Control.
Secure flange with hex drive screws.

White

Safety System®

SERVICE PROCEDURE RG-VI

Gas Control

Testing, Disassembly & Replacement (Honeywell)

GAS CONTROL REPLACEMENT

Step 9. Reinstallation of inner door assembly (continued).

d) Firmly place right side inner door flange against the left side inner door flange and secure with (2) hex drive screws from step 6c. DO NOT OVER TIGHTEN SCREWS.

e) Align right side inner door to combustion chamber and verify the fastener holes of the combustion chamber are aligned with the right side inner door slotted openings. Verify seal integrity around combustion

opening. Secure right side inner door using (2) hex drive screws from step 6b. DO NOT OVER TIGHTEN SCREWS. Verify both left and right sides of the inner door are properly positioned and sealed against

the combustion chamber.

Verify threaded hole alignment with slotted openings in inner door.

Step 10. Reconnect (2) red wire leads from pilot assembly and Gas Control to resettable thermal switch. Note: wire terminations are interchangeable with either resettable thermal switch connection.

Step 11. Replace outer jacket burner access door. Step 12. Reconnect gas supply to Gas Control.

Step 13. Resume water supply to water heater. Be sure tank is full of water before resuming operation.

Step 14. To resume operation follow the instructions located on the lighting instruction label or the lighting instructions located in the installation and operation manual.

30

30

White

DEFENDER

Safety System®

SERVICE PROCEDURE RG-VII

Burner Operation Inspection, Adjustment

Cleaning and Replacement

MAIN BURNER: Inspection, Adjustment,

Cleaning and Replacement

At periodic intervals (not more then 6 months) a visual inspection should be made of the main burner for proper operation and to insure no debris accumulating.

Main burner should light smoothly from pilot and burn with a blue flame with a minimum of yellow tips.

Steel burner models have a self adjusting air mixture and do not have an adjustable air shutter. Cast iron burner can have the gas and air mixture properly proportioned by adjusting the air shutter on the mixer face of the main burner (see step 2 below).

Main burner must be free from any debris accumulation that may effect burner operation (see burner cleaning procedure on page 17).

CAST IRON BURNER ADJUSTMENT

DANGER

Under no circumstances shall flammable materials be used or stored in the vicinity of the water heater. With the inner door removed the Bradford White Defender Safety System will be inactivated. If flammable vapors are present, a fire or explosion may result causing property damage, personal injury or death.

Upon completion of the cast iron burner adjustment procedure, the inner door must be replaced per SERVICE PROCEDURE RG-1,steps 4 through 14 to reactivate Bradford White Defender Safety System.

WARNING

Inner door and burner components may be HOT when performing this operation. Take necessary precaution to prevent personal injury.

Step 1. With main burner in operation, remove right side inner door per SERVICE PROCEDURE I, steps 3b & 3c. Be sure to maintain wire connection to resettable thermal switch for this adjustment procedure.

Step 2. To adjust for proper burning, loosen the air shutter nut, rotate the shutter to close the opening in the burner, then slowly rotate the shutter until the yellow tips disappear and the flame becomes blue. Tighten the air shutter nut. Too much air will cause the flame to lift off the burner ports and create noisy burner operation. Too little air (yellow tips) will result in soot formation.

Place right side inner door into proper position to confirm proper burner flame pattern and correct air shutter adjustment. It may be necessary to allow the burner to operate for several minutes for burner flame to stabilize.

Air Shutter Nut

31

31

SERVICE PROCEDURE RG-VII

Burner Operation Inspection, Adjustment

Cleaning and Replacement

MAIN BURNER: Inspection, Adjustment,

Cleaning and Replacement (cont.)

Step 3. Fully inspect inner gasket per SERVICE PROCEDURE RG-I,step 4. Replace gasket if required following SERVICE PROCEDURE I, steps 5 & 6.

Step 4. Be certain that thermocouple, pilot tube and piezo wire are

routed by inner door flange as shown and Reinstall inner door per SERVICE PROCEDURE RG-I,step 10 and 11.

Position thermocouple/thermopile,

pilot tube and Piezo wire.

Step 5. Observe burner operation through sight glass of inner door. Burner should operate as adjusted in step 2, if not, repeat procedure compensating air shutter position for proper burner operation with inner door in place.

Step 6. It may be necessary to clean main burner or main burner orifice to achieve proper burner operation. If cleaning is required proceed to burner cleaning section in this procedure.

BURNER CLEANING (Steel & Cast Iron)

Step 1.

Step 2.

Step 3.

Step 4.

Remove inner door assembly per SERVICE PROCEDURE RG-I,steps 1 through 3c.

Disconnect main burner feed line, pilot tube and thermocouple/thermopile

from combination thermostat gas valve and remove burner assembly from combustion chamber.

NOTE: Feedline nut for natural gas control uses right hand threads,

LP control uses left hand thread.

Thoroughly inspect burner surface area and burner ports and remove any loose debris accumulation.

On cast iron burners, inspect for any debris build up inside burner venturi. If found, disconnect feedline from burner and remove debris build up.

Burner Surface Area

Burner Port Area

Burner Venturi

Opening

Feedline

32

32

SERVICE PROCEDURE RG-VII

Burner Operation Inspection, Adjustment

Cleaning and Replacement

BURNER CLEANING (Cont.)

Step 5. Disconnect (unscrew) Main burner (steel) from main

burner orifice or on cast iron burners (“C” burner), loosen air shutter & disconnect (unscrew) feedline from burner.

Step 6. Remove main burner orifice from feed line. Inspect and clean if necessary.

Step 7. Remove pilot assembly, refer to SERVICE PROCEDURE RG-IIIfor cleaning and inspection. Step 8. Reassemble burner.

Step 9. Inspect combustion chamber area of heater prior to reinstallation of burner assembly. If cleaning is required, refer to SERVICE PROCEDURE RG-VIII.

Step 10. Reinstall burner assembly into combustion chamber, reconnect feedline, thermocouple and pilot tube to the combination thermostat/gas valve.

Step 11. Reinstall inner door per SERVICE PROCEDURE RG-I,steps 4 through 13.

Step 12. To resume operation, follow the instructions located on the lighting instruction label or the lighting instructions located in the installation and operation manual.

33

33

White

DEFENDER

Safety System®

SERVICE PROCEDURE RG-VIII

Resettable Thermal Switch

Testing and Replacement

RESETTABLE THERMAL SWITCH CONTINUITY TESTING

Step 1. Remove outer jacket door.

Step 2. Disconnect wire leads from resettable thermal switch.

Step 3. Using a multimeter capable of measuring continuity (Ohms), place one probe of meter on one of the brass connection tabs of the resettable thermal switch, and the remaining probe on the other connection tab.

Step 4. If continuity is indicated, the switch is closed, allowing millivolt current to pass.

Step 5. If continuity is not indicated, the switch is open, possibly due to an over heating condition. The switch is designed to open at predetermined temperatures depending on model. An open switch can be reset by depressing the red colored button located at the center of the switch. The overheating condition must be determined prior to putting the heater back in service.

PROBABLE CAUSE FOR RESETTABLE THERMAL SWITCH ACTIVATION

 

 

PROBABLE CAUSE

 

 

 

CORRECTIVE ACTION

 

 

 

 

 

 

1.

Verify adequate combustion air supply is

 

 

 

 

 

 

 

 

 

 

 

available.

 

 

Insufficient combustion air

2.

Clear jacket slot openings of any dirt, dust,

 

 

 

restrictions or other obstructions.

 

 

 

 

 

 

 

 

 

 

 

3. inspect flame arrestor plate and clean with

 

 

 

 

 

 

stiff brush and/or vacuum to remove scale

 

 

 

 

 

 

deposits and debris.

 

 

1. Weak switch or switch

1. Replace resettable thermal switch

 

 

out of calibration.

2.

Verify switch color code and approximate

 

 

 

 

 

 

 

2. Incorrect switch.

 

temperature.

 

 

 

 

 

 

Flammable vapor incident

1. Replace water heater.

 

 

 

 

 

 

 

 

 

 

Resettable thermal switch color code reference.

Approximate switch Color Code activation temperature

(open)

Blue

240°

Yellow

270°

Red

290°

34

34

SERVICE PROCEDURE RG-VIII

Resettable Thermal Switch

Testing and Replacement

RESETTABLE THERMAL SWITCH REPLACEMENT

Step 1. Rotate knob of combination thermostat gas valve to the off position.

For Honeywell Control, rotate knob counter-clockwiseto the “OFF” position.

For White Rodgers Control, depress knob slightly and rotate clockwise to the “OFF” position.

For Robertshaw Control, rotate knob clockwise to the “OFF” position.

Step 2. Remove outer jacket door.

Step 3. Disconnect wire leads from resettable thermal switch.

Step 4. Remove resettable thermal switch from inner door (Phillips screw driver)

Step 5. Place new resettable thermal switch in place. Be sure contact surface of resettable thermal switch and inner door are free of any debris. Secure resettable thermal switch into place using screws from step 4. DO NOT

OVER TIGHTEN SCREWS.

Step 6. Reconnect wire leads from combination thermostat/gas valve to resettable thermal switch.

Note: Wire termination are interchangeable with either resettable thermal switch connection. Step 7. Replace outer jacket door

Step 8. To resume operation follow the instructions located on the lighting instruction label or the lighting instruction located in the installation and operation manual.

35

35

White

Safety System®

SERVICE PROCEDURE RG-IX

ScreenLok® Flame Arrestor Cleaning

ScreenLok® Flame Arrestor Cleaning

Step 1. Rotate knob of combination thermostat gas valve to the off position.

For Honeywell Control, rotate knob counter-clockwiseto the “OFF” position.

For White Rodgers Control, depress knob slightly and rotate clockwise to the “OFF” position.

For Robertshaw Control, rotate knob clockwise to the “OFF” position.

Step 2. Remove outer jacket door.

Step 3. Remove inner door per SERVICE PROCEDURE RG-I,step 3a through 3e.

Step 4. Disconnect main burner feed line, pilot tube and thermocouple/thermopile from combination thermostat gas valve and remove burner assembly from combustion chamber.

NOTE: Feedline nut for natural gas control uses right hand threads, LP control uses left hand thread.

Feedline

Nut

Step 5. Clean ScreenLok® Flame Arrestor using stiff brush, compressed air and/or shop vacuum to remove any scale or other debris accumulation. Using a soft brush, clear jacket openings of any dirt, dust, restrictions or other obstructions.

Step 6. Remove any debris from burner assembly per SERVICE PROCEDURE RG-Vand reinstall burner assembly into combustion chamber.

Step 7. Reconnect feedline, thermocouple and pilot tube to the combination thermostat/gas valve. Step 8 Reinstall inner door per SERVICE PROCEDURE RG-I,steps 4 through 13.

Step 9. To resume operation follow the instructions located on the lighting instruction label or the lighting instruction located in the installation and operation manual.

36

36

White

Safety System®

SERVICE PROCEDURE RG-X

Dip Tube and Anode

Inspection and Replacement

DIP TUBE INSPECTION AND REPLACEMENT

WARNING

Heater components and stored water may be HOT when performing the following steps in this procedure. Take necessary precaution to prevent personal injury.

Step 1. Rotate knob of combination thermostat/gas valve to “OFF” position.

For Honeywell Control, rotate knob counter-clockwiseto the “OFF” position.

For White Rodgers Control, depress knob slightly and rotate clockwise to the “OFF” position.

For Robertshaw Control, rotate knob clockwise to the “OFF” position.

Step 2. Turn off cold water supply to heater. Connect hose to drain spigot of water heater and route to an open drain. Open a nearby hot water faucet to vent heater for draining. Open drain spigot of hot water heater and allow heater to drain to a point below the inlet connection nipple.

Step 3. Disconnect inlet nipple from plumbing system.

Step 4 With an appropriate wrench, remove inlet nipple/dip tube from the water heater. Use caution not to damage pipe threads.

Step 5. Visually Inspect inlet nipple/dip tube. Inlet nipple/dip tube should be free of cracks and any blockage. Hydro-jetslocated near the bottom of the dip tube should be open and free of any blockage.Anti-siphonhole located approximately 6" from the bottom of nipple, should be free of any blockage.

Any damage such as cracks, restriction due to deformation or unintentional holes are not field repairable and the inlet nipple/dip tube must be replaced.

Step 6. Upon completion of inspection or subsequent replacement, reinstall inlet nipple/dip tube into heater. Connect nipple to plumbing system, resume water supply and refill heater with water.

Step 7. To resume operation follow the instructions located on the lighting instruction label or the lighting instructions located in the installation and operation manual.

37

37

SERVICE PROCEDURE RG-X

Dip Tube and Anode

Inspection and Replacement

ANODE INSPECTION AND REPLACEMENT

WARNING

Heater components and stored water may be HOT when performing the following steps in this procedure. Take necessary precaution to prevent personal injury.

Step 1. Turn off water supply to water heater. Rotate knob of combination thermostat/gas valve to “OFF” position.

For Honeywell Control, rotate knob counter-clockwiseto the “OFF” position.

For White Rodgers Control, depress knob slightly and rotate clockwise to the “OFF” position.

For Robertshaw Control, rotate knob clockwise to the “OFF” position.

Step 2. Turn off cold water supply to heater. Connect hose to drain spigot of water heater and route to an open drain. Open a nearby hot water faucet to vent heater for draining. Open drain spigot of hot water heater and allow heater to drain to a point below the outlet connection nipple.

Step 3. Disconnect outlet nipple from plumbing system.

Step 4 With an appropriate wrench, remove outlet nipple/anode from the water heater. Use caution not to damage pipe threads.

Step 5. Visually Inspect outlet nipple/anode. Outlet nipple/anode should show signs of depletion, this is normal.

If depletion is ½ of the original anode diameter (approximately 5/8” diameter), replacement is recommended. If any of thesteel core of the anode is exposed, replacement is recommended.

Step 6. Upon completion of inspection or subsequent replacement, reinstall outlet nipple/anode into heater. Connect nipple to plumbing system, resume water supply and refill heater with water.

Step 7. To resume operation, follow the instructions located on the lighting instruction label or the lighting instructions located in the installation and operation manual.

38

38

White

Generic Parts List

Safety System®

16

1

34 32

33

 

2

17

3

 

4

 

 

18

 

21

 

19

5

20

28

6A

6B

6C

 

 

30

7

23

 

 

8

24

27 25

11

26

1

Draft Hood

16

Complete BN Burner Assembly (Natural)

2

Hot Water Outlet/Anode

17

BN Burner Only

3

Cold Water Inlet Tube

18

Main Burner Orifice

4

Flue Baffle

19

Pilot Assembly

5

T&P Relief Valve

20

Pilot Orifice

6A

Gas Control (Honeywell)

21

Thermocouple/Thermopile

6B

Gas Valve (Robertshaw)

22

Complete SX Burner Assembly (LP)

6C

Gas Valve (White Rodgers)

23

SX Burner Only

7

Piezo Igniter (White Rodgers/Robertshaw)

24

Main Burner Orifice

8

Brass Drain Valve

25

Pilot Assembly

9

Screw-#8-18x 3/4 Hex Washer Head

26

Pilot Orifice

10

Screw-#10-12x 3/4 Hex Washer Head

27

Thermocouple/Thermopile

11

Left Side Inner Door with Gasket

28

ASSE Approved Mixing Valve (Optional)

12

Complete Right Side Inner Door

29

¾ NPT Tank Plug (XR Models)

14

Resettable Thermal Switch

30

Inner Door Gasket Kit

15

Outer Door

31

Wire Tie

 

 

32

Heat Trap (Outlet)

 

 

33

Heat Trap (Inlet)

 

 

34

Heat Trap Kit

 

39

 

 

39