Bard HAC181-AD040 User Manual

Size:
402.72 Kb
Download

Manual

2100-346

Page

19

TABLE 13

PRESSURE TABLE

HAC181-A

Indoor

Return Air

 

 

 

Air Temperature Entering Outdoor Coil

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

65

70

75

80

85

90

95

100

 

105

110

115

Section

Temp.

Pressure

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

75 DB

Low Side

68

70

72

74

76

78

80

82

 

84

85

87

 

62 WB

High Side

150

170

187

203

226

244

254

258

 

255

246

320

AS30AS-A

 

 

 

 

 

 

 

 

 

 

 

 

 

 

80 DB

Low Side

70

73

76

79

81

84

86

88

 

90

92

93

S24AS-A

67 WB

High Side

169

183

198

213

228

244

260

276

 

293

310

328

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

85 DB

Low Side

76

79

82

85

87

90

92

94

 

96

98

99

 

72 WB

High Side

177

191

206

221

236

252

269

286

 

304

322

340

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

75 DB

Low Side

55

62

68

73

78

81

84

86

 

87

87

87

 

62 WB

High Side

162

178

193

209

224

240

256

272

 

288

304

320

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

BC24B

80 DB

Low Side

77

78

78

80

81

82

84

86

 

88

90

93

67 WB

High Side

164

180

198

213

230

246

263

280

 

296

313

329

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

85 DB

Low Side

76

79

82

85

87

90

92

94

 

96

98

99

 

72 WB

High Side

177

191

206

221

236

252

269

286

 

304

322

340

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Low side pressure ± 2 PSIG (suction line 8 inches from compressor)

High side pressure ± 5 PSIG (discharge line 8 inches from compressor, liquid at base valve approximately -20PSIG from values listed)

Tests are based upon rated CFM (airflow) across the evaporator coil. If there is any doubt as to correct operating change being in the system. The charge should be removed, system evacuated and recharged to serial plate instructions.

TABLE 14

PRESSURE TABLE

HAC241-A

Indoor

Return Air

 

 

 

Air Temperature Entering Outdoor Coil

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

65

70

75

80

85

90

95

100

 

105

110

115

Section

Temp.

Pressure

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

75 DB

Low Side

60

64

68

71

74

76

78

80

 

81

82

82

 

62 WB

High Side

172

190

207

224

241

258

275

292

 

308

325

341

AS30AS-A

 

 

 

 

 

 

 

 

 

 

 

 

 

 

80 DB

Low Side

66

70

73

76

79

81

83

85

 

86

87

88

S24AS-A

67 WB

High Side

177

195

213

230

247

265

282

299

 

316

333

350

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

85 DB

Low Side

73

76

79

82

85

87

89

91

 

92

94

95

 

72 WB

High Side

185

203

220

238

257

273

291

309

 

326

344

362

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

75 DB

Low Side

65

69

73

77

80

82

83

84

 

85

86

87

 

62 WB

High Side

179

194

209

225

241

257

273

290

 

306

324

341

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

BC24B

80 DB

Low Side

70

73

75

77

79

81

83

85

 

86

88

89

67 WB

High Side

104

152

192

225

251

269

280

284

 

281

270

252

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

85 DB

Low Side

73

76

79

82

85

87

89

91

 

92

94

95

 

72 WB

High Side

185

203

220

238

256

273

291

309

 

326

344

362

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Low side pressure ± 2 PSIG (suction line 8 inches from compressor)

High side pressure ± 5 PSIG (discharge line 8 inches from compressor, liquid at base valve approximately -20PSIG from values listed)

Tests are based upon rated CFM (airflow) across the evaporator coil. If there is any doubt as to correct operating change being in the system. The charge should be removed, system evacuated and recharged to serial plate instructions.

Manual 2100-346

Page 20

TABLE 15

PRESSURE TABLE

HAC301-A

Indoor

Return Air

 

 

 

Air Temperature Entering Outdoor Coil

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

65

70

75

80

85

90

95

100

 

105

110

115

Section

Temp.

Pressure

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

75 DB

Low Side

62

65

67

69

71

73

75

77

 

78

80

81

 

62 WB

High Side

162

183

204

224

244

262

280

297

 

313

329

344

A36AS-A

 

 

 

 

 

 

 

 

 

 

 

 

 

 

80 DB

Low Side

68

70

72

74

76

78

80

82

 

84

85

87

 

67 WB

High Side

167

188

210

230

250

269

287

305

 

321

338

353

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

85 DB

Low Side

75

77

78

80

82

84

86

88

 

90

92

94

 

72 WB

High Side

171

194

216

238

258

278

297

315

 

333

349

365

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

75 DB

Low Side

61

65

69

72

75

77

79

81

 

82

83

84

 

62 WB

High Side

185

201

217

234

250

266

282

298

 

314

331

347

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

BC36B

80 DB

Low Side

67

71

74

77

80

82

84

86

 

87

88

89

67 WB

High Side

190

207

223

239

256

272

289

306

 

322

339

356

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

85 DB

Low Side

74

77

80

83

86

88

90

92

 

93

95

96

 

72 WB

High Side

198

215

232

248

265

282

299

316

 

333

351

368

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Low side pressure ± 2 PSIG (suction line 8 inches from compressor)

High side pressure ± 5 PSIG (discharge line 8 inches from compressor, liquid at base valve approximately -20PSIG from values listed)

Tests are based upon rated CFM (airflow) across the evaporator coil. If there is any doubt as to correct operating change being in the system. The charge should be removed, system evacuated and recharged to serial plate instructions.

TABLE 16

PRESSURE TABLE

HAC361-A

Indoor

Return Air

 

 

 

Air Temperature Entering Outdoor Coil

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

65

70

75

80

85

90

95

100

 

105

110

115

Section

Temp.

Pressure

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

75 DB

Low Side

66

68

70

72

74

76

78

80

 

82

84

86

 

62 WB

High Side

181

197

213

230

246

262

278

294

 

310

326

343

A37AS-A

 

 

 

 

 

 

 

 

 

 

 

 

 

 

80 DB

Low Side

71

73

75

77

79

81

83

85

 

87

89

91

 

67 WB

High Side

186

202

219

235

252

268

285

302

 

318

335

351

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

85 DB

Low Side

77

79

81

83

85

87

89

91

 

93

95

97

 

72 WB

High Side

191

208

226

243

260

278

295

312

 

330

347

364

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

75 DB

Low Side

63

66

68

70

72

74

76

78

 

79

81

82

 

62 WB

High Side

178

195

212

228

245

262

279

296

 

313

331

348

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

BC36B

80 DB

Low Side

66

69

72

75

78

80

82

84

 

85

87

88

67 WB

High Side

184

200

217

234

251

269

286

304

 

321

339

357

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

85 DB

Low Side

72

75

78

81

83

86

88

90

 

92

94

95

 

72 WB

High Side

188

206

224

242

260

278

296

314

 

332

351

369

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Low side pressure ± 2 PSIG (suction line 8 inches from compressor)

High side pressure ± 5 PSIG (discharge line 8 inches from compressor, liquid at base valve approximately -20PSIG from values listed)

Tests are based upon rated CFM (airflow) across the evaporator coil. If there is any doubt as to correct operating change being in the system. The charge should be removed, system evacuated and recharged to serial plate instructions.

Manual 2100-346

Page 21

TABLE 17

PRESSURE TABLE

HAC 421-A

Indoor

Return Air

 

 

 

Air Temperature Entering Outdoor Coil

 

 

 

 

 

 

 

 

 

 

 

 

 

75

80

85

90

95

100

105

110

115

Section

Temp.

Pressure

 

 

 

 

 

 

 

 

 

 

 

 

 

75 DB

Low Side

64

67

70

72

74

76

77

78

79

 

62 WB

High Side

203

218

233

250

266

283

300

318

336

A42AS-A

 

 

 

 

 

 

 

 

 

 

 

80 DB

Low Side

69

72

75

77

79

82

82

84

85

BC36B

67 WB

High Side

208

224

240

256

273

290

308

326

345

 

 

 

 

 

 

 

 

 

 

 

 

 

 

85 DB

Low Side

73

77

80

83

85

87

89

90

91

 

72 WB

High Side

216

232

248

265

282

300

318

337

359

 

 

 

 

 

 

 

 

 

 

 

 

 

75 DB

Low Side

73

74

76

77

79

81

82

84

86

 

62 WB

High Side

212

228

244

260

277

294

312

330

349

A48AS-A

 

 

 

 

 

 

 

 

 

 

 

80 DB

Low Side

77

79

81

83

85

87

89

90

92

BC60B

67 WB

High Side

218

234

250

267

284

302

320

339

358

 

 

 

 

 

 

 

 

 

 

 

 

 

85 DB

Low Side

83

85

87

89

91

93

95

97

99

 

72 WB

High Side

224

241

258

276

294

294

331

350

370

 

 

 

 

 

 

 

 

 

 

 

 

Low side pressure ± 2 PSIG (suction line 8 inches from compressor)

High side pressure ± 5 PSIG (discharge line 8 inches from compressor, liquid at base valve approximately -20PSIG from values listed)

Tests are based upon rated CFM (airflow) across the evaporator coil. If there is any doubt as to correct operating change being in the system. The charge should be removed, system evacuated and recharged to serial plate instructions.

 

 

 

 

TABLE 18

 

 

 

 

 

 

 

 

 

PRESSURE TABLE

 

 

 

 

 

 

 

 

HAC481-A,

HAC481-B

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Indoor

Return Air

 

 

 

Air Temperature Entering Outdoor Coil

 

 

 

 

 

 

 

 

 

 

 

 

 

75

80

85

90

95

100

105

110

115

Section

Temp.

Pressure

 

 

 

 

 

 

 

 

 

 

 

 

 

75 DB

Low Side

74

75

77

78

80

82

83

85

87

 

62 WB

High Side

208

223

238

254

271

288

306

324

343

 

 

 

 

 

 

 

 

 

 

 

 

A61AS-B

80 DB

Low Side

78

80

82

84

86

88

90

91

93

67 WB

High Side

214

229

245

261

278

296

314

333

352

 

 

 

 

 

 

 

 

 

 

 

 

 

 

85 DB

Low Side

84

86

88

90

92

94

96

97

99

 

72 WB

High Side

220

236

253

270

288

306

325

344

364

 

 

 

 

 

 

 

 

 

 

 

 

 

75 DB

Low Side

68

70

72

74

76

78

79

80

81

 

62 WB

High Side

242

250

260

272

285

300

317

336

356

 

 

 

 

 

 

 

 

 

 

 

 

BC60B

80 DB

Low Side

76

77

78

80

81

82

84

85

87

67 WB

High Side

248

256

266

278

292

308

325

344

365

 

 

 

 

 

 

 

 

 

 

 

 

 

 

85 DB

Low Side

82

83

84

86

87

88

90

91

93

 

72 WB

High Side

257

265

276

288

302

318

336

356

378

 

 

 

 

 

 

 

 

 

 

 

 

Low side pressure ± 2 PSIG (suction line 8 inches from compressor)

High side pressure ± 5 PSIG (discharge line 8 inches from compressor, liquid at base valve approximately -20PSIG from values listed)

Tests are based upon rated CFM (airflow) across the evaporator coil. If there is any doubt as to correct operating change being in the system. The charge should be removed, system evacuated and recharged to serial plate instructions.

Manual 2100-346

Page 22

 

 

 

 

TABLE 19

 

 

 

 

 

 

 

 

 

PRESSURE TABLE

 

 

 

 

 

 

 

 

 

HAC601-A,

HAC601-B

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Indoor

Return Air

 

 

 

Air Temperature Entering Outdoor Coil

 

 

 

 

 

 

 

 

 

 

 

 

 

 

75

80

85

 

90

95

100

105

110

115

Section

Temp.

Pressure

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

75 DB

Low Side

67

69

71

 

73

75

76

78

79

79

 

62 WB

High Side

227

243

260

 

276

293

310

326

343

359

 

 

 

 

 

 

 

 

 

 

 

 

 

A61AS-B

80 DB

Low Side

72

74

76

 

78

80

82

84

86

88

67 WB

High Side

232

249

266

 

284

301

318

336

353

370

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

85 DB

Low Side

78

80

82

 

84

86

88

90

92

94

 

72 WB

High Side

240

258

276

 

293

311

329

346

364

382

 

 

 

 

 

 

 

 

 

 

 

 

 

 

75 DB

Low Side

64

67

70

 

72

74

76

77

78

78

 

62 WB

High Side

223

239

257

 

275

295

316

339

363

388

 

 

 

 

 

 

 

 

 

 

 

 

 

BC60B

80 DB

Low Side

69

72

75

 

77

79

81

82

83

84

67 WB

High Side

230

246

264

 

283

303

325

348

372

398

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

85 DB

Low Side

76

78

80

 

82

85

85

87

89

90

 

72 WB

High Side

237

255

273

 

293

314

336

360

385

411

 

 

 

 

 

 

 

 

 

 

 

 

 

Low side pressure ± 2 PSIG (suction line 8 inches from compressor)

High side pressure ± 5 PSIG (discharge line 8 inches from compressor, liquid at base valve approximately -20PSIG from values listed)

Tests are based upon rated CFM (airflow) across the evaporator coil. If there is any doubt as to correct operating change being in the system. The charge should be removed, system evacuated and recharged to serial plate instructions.

Manual 2100-346

Page 23