USER’S MANUAL

A03-HP1001 /A03-HP1501 /A03-HP2001 /A03-HP3001

IMPORTANT SAFETY INSTRUCTIONS

SAVE THESE INSTRUCTIONS

This manual contains important safety instructions. Please follow all instructions carefully during installation. Read this manual thoroughly before attempting to unpack, install or operate.

CAUTION: To prevent the risk of fire or electric shock, install in a temperature and humidity controlled indoor area,

free of conductive contaminants.

CAUTION: Risk of electric shock, do not remove the cover. No user

serviceable parts. Refer servicing to qualified service personnel. CAUTION: Risk of electric shock, hazardous live parts inside this UPS can be

energized from the battery supply even when the input AC power is disconnected.

CAUTION: Risk of electric shock, Battery Circuit is not isolated from AC input; hazardous voltage may exist between battery terminals and

ground. Test before touching. WARNING:This is a ClassA-UPSProduct. In a domestic environment, this

product may cause radio interference, in which case, the user may be required to take additional measures.

NOTICE: The UPS is designed to be for use with computer loads only.NOTICE: To prevent injury, do not carry with the handle of front cover when

moving the UPS.

SETUP

1

Inspection

3 Connect the loads

4 Connect Computer

Inspect the UPS upon receipt. Notify the carrier

First, connect the UPS with Utility, then plug the

 

 

Interface Port

and dealer if there is damage. The package is

loads into the outlets on the rear of the UPS. To

 

 

recyclable; save it for reuse or dispose of it

use the UPS as a master “On/Off” switch, make

Connect the supplied interface cable (RS-232or

properly.

sure that all of the loads are switch “On”.

USB) to the interface port on the rear of the UPS

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

These UPS outlets provide battery power and

and the computer interface port. See software

2

Place the UPS properly

surge protection to the equipment when utility

installation guide in the CD-ROM(Optional) for

voltage is outside acceptable limits.

installation purpose.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Caution: Do not connect a laser printer to the

 

UPS outlets.

5 Connect Network

6 UPS Start Up

Surge protection

1. Connect the UPS to the wall receptacle.

2. Push the “On” Switch on the front panel of the UPS until 4 LEDs (LCD) are lit then extinguished

Connect a 10 base-T /100base-Tnetwork cable

and release the “On” Switch.

into the RJ-45network surge protection “IN” jack

3. The Backup mode LED (Amber) lights up and the UPS is under self-testmode now. If Utility is

on the rear of the UPS. Connect from the “OUT”

normal, the UPS will run under Utility mode (Green LED) after its self-testis complete. On the

jack with network cabling to network equipment.

contrary, the UPS will run under Backup mode and the buzzer alarms every 2 seconds in case of

 

blackout or over/under voltage.

 

Caution:

 

1. The UPS “On” will not be executed if the above procedure is not done completely, which means

IN O U T

the button is released before all 4 LEDs (LCD) are extinguished.

 

 

2. The UPS will remain at “NO” output, if the start-upoperation is not proceeded properly even

 

though the Input Power Cord is connected to the wall receptacle.

 

IMPORTANT NOTICE: Plug the UPS into the wall receptacle to charge the UPS for over 10

 

hours after initial installation.

Operation Test

Turn Off the UPS

Push the “Off” Switch for at least 3 seconds to turn off the UPS. If you press the “Off” Switch less than 3 seconds, the UPS will not execute shutdown command due to insufficient pressing time.

In some occasions, the UPS will shut itself down in case of overload, output short-circuitedor battery cutoff point reached in the Backup mode. The UPS will automatically shut off the output and beep for 5 seconds then completely shut itself down.

Plug-inCharge

If the Input Power Cord is connected to the wall receptacle properly and the utility is normal, the UPS will start to charge automatically without processing “Turn On” procedure. You have to charge for at least 8 hours every 3 months to avoid from battery self over-dischargenaturally, if the UPS is in an idle condition.

Auto-Restart

The UPS will automatically restart to provide energy to the output if the utility recovers in 24 hours after battery cut. The “Backup LED” will flash every 5 seconds under the waiting situation. On the contrary, the UPS will not auto-restartif the Utility doesn’t recover within 24 hours. You are required to start up the UPS manually. If you don’t need UPSauto-restart,you can turn off the UPS by proceeding the “Turn Off” procedure.

Alarm Silence

The Alarm might be turned off by pushing the “On” Switch for approximately 1 second in the “Backup” mode. Unless any other warning or fault condition occurs, the alarm remains at Silence condition once the “Alarm Silence” is turned off.

Test

Under Utility Normal condition, push the “On” Switch for 3 seconds to execute the Battery Self-testfunction. In case the battery is normal, it will enter into Battery Backup Mode for 10 seconds then return back to Utility Mode. If the battery voltage is detected lower than set limit, the Battery Replacement LED will blink for 5 seconds then extinguish to stopself-testprocedure. And if battery is detected weak or dead, the Battery Replacement LED will steadily illuminate.

 

 

FRONT PANEL EXPLANATIONS

REAR PANEL EXPLANATIONS

1.

Utility LED

1.

RJ45 Port

2.

Fault LED

2.

DIP Switch

3.

On Switch

3.

USB Communication Port

4.

Off Switch

4.

RS232 Communication Port

5.

Battery Replacement LED

5.

Internal CPU Reset Button

6.

Battery Backup LED

6.

(press to shutdown)

7.

Screw for Easy Swappable Battery

Output Breaker

 

Cover

7.

Outlet

8.

Battery Low

8.

Rating Label

9.

Bypass

9.

Input Fuse

10.

Utility Low, UPS Boost

10.Input Power Cord(Inlet)

11.

Utility High, UPS Buck

 

 

12.

UPS Output Indicator

 

 

13.

Polarity Error or Ground Fault

 

 

14.

Over load

 

 

15.

Load/Battery Level(%)

 

 

16.

Load/Battery Level Indication

 

 

 

 

Control Button

 

 

REPLACING THE BATTERY

Note: Once the battery is disconnected, the loads are not protected from power outages.

When the Battery Replacement LED(Red) lights up, you may leave the UPS to be re-chargedfor at least 8~10 hours to see whether the Red LED will be extinguished after theSelf-testFunction is executed again. In case the Red LED remains unchanged, you may unscrew the Easy Swappable Battery cover, replace a new battery than push the “On” Switch to disable the RED LED. Please follow the steps1-7to replace the new battery

STEP3

STEP 7

STEP 2

STEP 6

STEP 1

STEP 4

STEP 5

DIP SWITCH SETTING

 

INDICATORS & ALARMS

The voltage & frequency of the UPS might be re-setby the DIP

 

 

 

 

Switch on the rear panel of the UPS. The following charts may

Indicator

Color

Description

Alarm

bring you clear pictures about how the settings are done by the

Utility Mode

Green

Steady:

None

DIP Switch.

 

 

Output Load is supplied by Utility.

 

 

 

 

 

 

 

 

Blinking:

 

 

 

 

Polarity error or Ground Fault

 

 

Backup

Amber

Steady (with alarm):

Every 2 seconds

 

Mode

 

Output Load is supplied by Battery

before battery Low

 

 

 

Blinking every 5 seconds(no

and every 1 second

 

 

 

alarm):Stand by for Utility

before battery Cutoff.

 

Fault

 

recovery to re-startup

 

 

Red

When Overload, short circuit, or

Buzzer beeps

 

 

 

Output Voltage Abnormal occurs

continuously.

 

Battery

Red

Blinking: Battery is weak and

None

 

Replacement

 

needs to be recharged.

 

 

 

 

Steady: Battery is dead.

 

SUPPORT

If you have any problems with the UPS, please consult this manual.

If you continue to have problems you should contact the dealer where you bought this device. If you have any other questions you can contact the Atlantis Land company directly at the following address: