APC AP9218 User Manual
Size:
672.92 Kb
Download

Menu Items

MasterSwitch

 

 

Configure Device

 

 

Settings

Item

Definition

 

 

 

 

 

Unit Name

The name of the MasterSwitch PDU.

 

Maximum: 23 characters.

 

 

 

 

 

 

Coldstart Delay

The time that the MasterSwitch PDU waits before applying

 

power to outlets after AC power is applied to the unit.

 

 

 

 

 

 

 

The longest reboot duration of any outlet in the group of

 

 

accessible outlets. You can change this value only by

 

Reboot Duration

modifying the Reboot Duration of individual accessible

 

 

outlets. Sequenced Rebootand Delayed Sequenced Reboot

 

 

use this value.

Outlet

 

 

 

 

Configuration

Item

Definition

 

 

 

 

 

Outlet Name

The name that identifies the outlet.

 

Maximum: 23 characters.

 

 

 

 

 

 

 

The time that the outlet waits before turning on after the

 

Power On Delay

command is issued. Delayed On,Sequenced Reboot, and

 

 

Delayed Sequenced Reboot use this value.

 

 

 

 

 

The time that the outlet waits before turning off after the

 

Power Off Delay

command is issued. Delayed Off,Delayed Reboot, and

 

 

Delayed Sequenced Reboot use this value.

 

 

 

 

Reboot Duration

The time that the outlet will remain off during a reboot.

 

Immediate Reboot and Delayed Rebootuse this value.

 

 

 

 

 

 

URL Links

Defines HTTP links to relevant Web pages.

 

 

 

MasterSwitch Power Distribution Unit User’s Guide

12