APC 750 VA User Manual
Size:
333.23 Kb
Download

Operation Manual

Smart-UPS®

Uninterruptible Power Supply

750/1000/1500/2200/3000 VA Tower 100/120/230 Vac

500 VA Tower

100 Vac

Overview

Product Description

The APC® by Schneider ElectricSmart-UPS® 500 VA to 3000 VA Tower is a high performance uninterruptible power supply (UPS). It provides protection for electronic equipment from utility power blackouts, brownouts, sags, and surges, small utility fluctuations and large disturbances. The UPS also provides battery backup power for connected equipment until utility power returns to safe levels or the batteries are fully discharged.

Safety and General Information

Read the Safety Guide included in the package before installing the UPS.

This unit is intended for indoor use only.

Do not operate this unit in direct sunlight, in contact with fluids, or where there is excessive dust or humidity. Be sure the air vents on the UPS are not blocked. Allow adequate space for proper ventilation.

The battery typically lasts for two to five years. Environmental factors impact battery life. Elevated ambient temperatures, poor quality utility power, and frequent short duration discharges will shorten battery life.

Connect the Smart-UPSpower cable directly to a wall outlet. Do not use surge protectors or extension cords. The batteries are heavy. Remove the batteries prior to installing the UPS in a rack.

Specifications

For additional specifications, refer to the APC Web site at www.apc.com.

Environmental

 

Operating

0° to 40° C (32° to 104° F)

Temperature

 

 

Storage

-15°to 45° C (5° to 113° F)

 

 

charge UPS battery every six months

 

 

 

Maximum

Operating

3,000 m (10,000 ft)

Elevation

 

 

Storage

15,000 m (50,000 ft)

 

 

 

Humidity

0% to 95% relative

humidity, non-condensing

 

 

 

Smart-UPS750/1000/1500/2200/3000 VA 100/120/230 Vac 500 VA 100 Vac Tower

1

Product Overview

Front panel features

Display interface

500/750/1000/1500 VA

2200/3000 VA

Bezel

 

 

Battery

 

 

Internal battery connector

 

 

 

su0453a

su0452a

Rear panel features 500 VA to 1500 VA models

USB portSerial port

Ground screwSmart slot

Circuit breakerUPS input

Outlets

Internal or external battery connector

500/750 VA 100 Vac

750 VA 230 Vac

750 VA 120 Vac

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

su0326b

su0327b

1000/1500 VA 100 Vac

 

 

1000/1500 VA 230 Vac

1000/1500 VA 120 Vac

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1 PU OR G

su0325c

su0328c

 

2

Smart-UPS750/1000/1500/2200/3000 VA 100/120/230 Vac 500 VA 100 Vac Tower

Rear panel features 2200 VA and 3000 VA models

2200 VA 120 Vac

USB Port

Serial portGround screwSmartSlot

Circuit breakerUPS input

OutletsEPO connector

su0351b

2200/3000 VA 100 Vac

 

 

 

 

 

 

 

2200/3000 VA 230 Vac

 

 

 

3000 VA 120 Vac

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

P U O R G

 

1

su0330a

su0329b

Installation

For UPS installation information, refer to the Smart-UPSInstallation Guide 750/1000/1500/2200/3000 VA 100/120/230 Vac, 500 VA 100 Vac Tower, that is included with the UPS. The Installation guide is also available on the documentation CD included with the UPS and on the APC Web site, www.apc.com.

Smart-UPS750/1000/1500/2200/3000 VA 100/120/230 Vac 500 VA 100 Vac Tower

3

Operation

Connect Equipment

Note: The UPS will charge to 90% capacity in the first four and a half hours of normal operationfor the 2200/3000 VA 100 Vac model or the first three hours of normal operationfor all other models.Do not expect full battery runtime capability during this initial charge period.

1.Connect equipment to the UPS.

2.Connect the UPS to the building utility power. Connect the UPS to a two-pole, three-wire, grounded source only.

3.To use the UPS as a MASTER ON/OFF switch, turn on equipment that is connected to the UPS.

See “Main Outlet Group and Switched Outlet Group” on page 9 for information on how to configure the outlet groups.

su0441a

Rear Panel Features

Serial port: Connect to a computer to use power management software.

USB port: Connect to a computer to use power management software.

Ground Screw: Connect the ground leads on transient voltage devices to the chassis ground screw(s), located on the rear panel of the UPS.

4

Smart-UPS750/1000/1500/2200/3000 VA 100/120/230 Vac 500 VA 100 Vac Tower

Display Panel

Online LED

On Battery LED

UPS Output ON/OFF key

Fault LED

Replace Battery LED

Display screen

UP and DOWNkeys

 

 

 

 

 

 

 

 

APC By Schneider

 

 

ENTER key

 

 

 

 

 

 

 

 

 

 

 

Electric

 

 

ESCAPE key

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

su0343e

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Using the display interface

Use the UP andDOWN keys to scroll through the main menu options. PressENTER to view thesub-menusunder each main menu option. PressESCAPE to exit asub-menuand return to a main menu.

Standard menus

The Standard menus are the most commonly used menus.

Menu

General Functions

 

 

 

 

Status

View UPS information:

 

 

• Operating Mode

• Battery Temp

 

• Efficiency

• Input

 

• Load Power

• Output

 

• Load VA

• Last Transfer

 

• Battery Charge state

• Last UPS Self Test

 

• Estimated Runtime

 

 

 

 

Configuration

Configure UPS settings:

 

 

• Language

• Display (Auto Dim, Auto Off, Always On)

 

• Local Power Quality: Good, Fair, Poor

• Battery Install Date

 

• Menu Type: Standard or Advanced

• Reset to Factory Default

 

• Audible Alarm

 

 

 

 

Test & Diags

Perform UPS tests and diagnostic functions:

 

 

• UPS Self Test

 

 

• UPS Alarms Test

 

 

• Calibration Test

 

 

 

 

About

View UPS information:

 

 

• UPS Model

• Battery Part No.

 

• UPS Part No.

• Battery Install Date

 

• UPS Serial No.

• Replace Battery by

 

• UPS Manufacture Date

• UPS Firmware 1

 

 

 

Smart-UPS750/1000/1500/2200/3000 VA 100/120/230 Vac 500 VA 100 Vac Tower

5

Advanced menus

The Advanced menus provide additional options for the UPS and are available only if the display interface is configured to use the Advanced menus.

Menu

General Functions

 

 

 

 

Status

View detailed UPS information:

 

 

• Operating Mode

• Battery Temp

 

• Efficiency

• Input

 

• Load Power

• Output

 

• Load VA

• Last Transfer

 

• Load Amps

• Last UPS Self Test

 

• Load Energy

• Outlet Group 1 (if Switched Outlet is available)

 

• Battery Charge state

• NMC IP Address (if NMC is available)

 

• Estimated Runtime

 

 

• Battery Voltage

 

 

 

 

Configuration

Configure advanced UPS settings:

 

 

• Language

• Battery Install Date

 

• Local Power Quality

• Reset Energy Meter

 

• Menu Type

• Enter Setup Wizard

 

• Audible Alarm

• Firmware Update (standby mode)

 

• Display (Auto Dim, Auto Off, Always On)

• Reset to Factory Default

 

• Sensitivity

• Config Main Group Outlets

 

• Low Transfer

• Config Group 1 Outlets (if Switched Outlet is

 

• High Transfer

available)

 

• Low Battery Warning

• Config NMC (if NMC is available)

 

• Auto Self Test

 

 

 

Control

Control the Main and Switched Outlet Group to turn on, turn off, shutdown, or reboot.

 

 

 

Test & Diags

Perform UPS test and diagnostic functions:

 

 

• UPS Self Test

 

 

• UPS Alarms Test

 

 

• Calibration Test

 

 

 

Log

View the event and error logs for information about UPS events and faults that have occurred.

 

 

 

About

View UPS information:

 

 

• UPS Model

• NMC Model No.*

 

• UPS Part No.

• NMC Serial No.*

 

• UPS Serial No.

• NMC Hardware Version*

 

• UPS Manufacture Date

• NMC Manufacture Date*

 

• Battery Part No.

• NMC MAC Address*

 

• Battery Install Date

• SmartSlot FW 1*

 

• Replace Battery by

• SmartSlot FW 2*

 

• UPS Firmware 1

• SmartSlot FW 3*

 

• UPS Firmware 2

 

 

• UPS Firmware 3

*If NMC is available

 

• UPS Firmware 4

 

 

 

 

6

Smart-UPS750/1000/1500/2200/3000 VA 100/120/230 Vac 500 VA 100 Vac Tower

Configuration

UPS Settings

Start-upSettings

Configure these settings at initial start-up,using the display interface. As an alternative, configuration can be performed using APC PowerChute® software.

Note: Duringstart-up,use the display interface to configure these settings. If nothing is selected, the unit will use the default settings.

Function

Factory Default

Options

Description

 

 

 

 

Language

English

• English

The language for the display interface.

 

 

• French*

 

 

 

• German*

*Language options will vary by model.

 

 

• Spanish*

 

 

• Italian*

 

 

 

• Portuguese*

 

 

 

• Japanese*

 

 

 

 

 

Local Power

Good

• Good

Select the quality of input utility power.

Quality

 

• Fair

• If Good is selected, the unit will go on battery power

 

 

• Poor

more often to provide the cleanest power supply to the

 

 

 

connected equipment.

 

 

 

• If Poor is selected, the UPS will tolerate more

 

 

 

fluctuations in power and will go on battery power less

 

 

 

often.

 

 

 

If unsure of the local power quality, select Good.

 

 

 

 

Menu Type

Standard

Standard or

The Standard menus display a limited set of menus

 

 

Advanced

and options. The advanced menus include all

 

 

 

parameters.

 

 

 

 

General Settings

Configure these settings at any time. Use the display interface or APC PowerChute® software.

Function

Factory Default

Options

Description

 

 

 

 

 

High Transfer Point

100

Vac:

108 Vac - 114 Vac

To avoid unnecessary battery usage, set the transfer

 

108

Vac

 

point higher if the utility voltage is chronically high and

 

 

 

 

the connected equipment is known to work under this

 

120

Vac:

127 Vac - 136 Vac

 

condition. The Power Quality setting will

 

127 Vac

 

 

 

automatically change this setting.

 

 

 

 

 

 

 

 

Note: Use the Advanced Menus to configure this

 

230

Vac:

253 Vac - 265 Vac

 

setting.

 

253 Vac

 

 

 

 

 

 

 

 

 

Smart-UPS750/1000/1500/2200/3000 VA 100/120/230 Vac 500 VA 100 Vac Tower

7

Function

Factory Default

Options

Description

 

 

 

 

Low Transfer Point

100 Vac:

86 Vac - 92 Vac

Set the transfer point lower if the utility voltage is

 

92 Vac

 

chronically low and the connected equipment can

 

 

 

tolerate this condition.This setting may also be adjusted

 

120 Vac:

97 Vac - 106 Vac

 

using the power quality setting.

 

106 Vac

 

 

 

 

 

 

 

Note: Use the Advanced Menus to configure this

 

230 Vac:

196 Vac -208Vac

 

setting.

 

208 Vac

 

 

 

 

 

 

 

 

Nominal Output

100 Vac

N/A

230 Vac models only: Set the nominal output voltage of

Voltage

 

 

the UPS to standby mode.

120 Vac

N/A

 

 

 

 

 

 

 

230 Vac

• 220 Vac

 

 

 

• 230 Vac

 

 

 

• 240 Vac

 

 

 

 

 

Transfer Sensitivity

Normal

Normal, Reduced, Low

Select the level of sensitivity to power events that the

 

 

 

UPS will tolerate.

 

 

 

Normal: The UPS will go on battery power more

 

 

 

often to provide the cleanest power supply to the

 

 

 

connected equipment.

 

 

 

Low: The UPS will tolerate more fluctuations in

 

 

 

power and will go on battery power less often.

 

 

 

If the connected load is sensitive to power disturbances,

 

 

 

set the sensitivity to Normal.

 

 

 

 

Low Battery Warning

120 sec

Set the value in seconds

The UPS will emit an audible alarm when the remaining

 

 

 

runtime has reached this level.

 

 

 

 

Date of Last Battery

Date set at factory

Reset this date when the battery module is replaced.

Replacement

 

 

 

 

 

 

 

Audible Alarm

On

On/Off

The UPS will mute all audible alarms if this is set to Off

 

 

 

or when the display keys are pressed.

 

 

 

 

Battery

On start-upand every

• Never

The interval at which the UPS will execute a

Self-TestInterval

14 days since the last

Start-uponly

self-test.

Setting

test

• Frequency of test

 

 

 

(every 7 to 14 days)

 

 

 

 

 

Reset to Factory

No

Yes/No

Restore the UPS factory default settings.

Default

 

 

 

 

 

 

 

8

Smart-UPS750/1000/1500/2200/3000 VA 100/120/230 Vac 500 VA 100 Vac Tower