Network Management Teleservice Card

(66124)

Installation manual

990-3402231500AC3402231500/AC

INTRODUCTION

The Network Management Teleservice Card (66124)is recommended for central UPSs protecting entire networks or for UPS units backing up critical loads.

With the card installed, the UPS has its own IP address and uses the local computer capabilities to:

supply web pages (http or https (SSL)) with information on status conditions and measurements/settings/alarms,

integrate an SNMP-basedNMS such as HP OpenView, IBM Tivoli Netview and Computer Associates Unicenter,

communicate with shutdown modules installed on the protected servers (Network Shutdown Module),

send e-mailand SMS messages,

control the ON/OFF function of the UPS and the outlets,

monitor the Environment Sensor,

Access the Teleservice solution for remote monitoring and maintenance services of your UPS.

The Network Management Teleservice Cardmust be installed and used in accordance with manufacturer instructions.

OVERVIEW

000623001C07

000623001C07

MAC adress

 

 

UPS

 

 

 

 

 

Data

CD

 

 

 

 

 

ETHERNET

 

 

 

 

SENSOR/RS

 

 

 

 

 

 

 

 

 

485

PHONE

 

ACT

 

 

 

 

 

 

 

 

 

 

RESET

100M

 

 

 

 

 

(

Settings)

 

 

 

 

 

 

 

 

 

66124

PHONE port:

Green LED : Phone communication with the UPS

Orange LED : Modem connection

ETHERNET port:

Green LED : Connection + activity

Orange LED : 10/100 M

Service port (Sensor/RS485):

Green LED : Communication with the UPS

Orange LED :RS232 activity

Catalogue number

UNPACKING AND CHECKS

One Network Management Teleservice Card(66124),

One serial cable for configuration (3402226700),

One phone cable for teleservice (3402226800),

One installation manual (34022315EN),

One Teleservice information form (3402228500),

Settings/Sensor

ETHERNET

 

 

 

 

Settings/Sensor

Settings/Sensor

 

 

 

 

 

 

 

 

100M

10M

 

UPS

data RS232

 

 

 

 

 

 

 

 

 

66108

Settings/Sensor

ETHERNET

 

 

 

 

 

Settings/Sensor

 

 

Settings/Sensor

 

 

 

 

 

 

 

 

 

 

66124

 

 

Network Management Teleservice Card (66124)

Installation manual

3402231500/AC

INDICATIONS

PHONE port

LED

Colour

 

 

Status

 

Description

 

 

 

 

 

 

 

 

UPS Data

Green

 

 

OFF

Card not connected to phone

 

 

 

 

 

 

 

network

 

 

 

 

 

 

ON

Card connected to phone

 

 

 

 

 

 

 

network, but no activity

 

 

 

 

 

 

Flashing

 

Port is sending/receiving

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CD

Orange

 

 

OFF

Modem is not connected

 

 

 

 

 

 

ON

 

Modem is connected

 

 

 

 

 

 

Flashing

 

Modem is connecting

 

 

 

 

 

 

 

 

 

ETHERNET port

 

 

 

 

 

 

 

 

 

 

 

 

 

 

LED

Colour

 

 

Status

 

Description

 

 

 

 

 

 

 

 

ACT

Green

 

 

OFF

Card not connected to network

 

 

 

 

 

 

ON

Card connected to network, but

 

 

 

 

 

 

 

no activity

 

 

 

 

 

 

Flashing

 

Port is sending/receiving

 

 

 

 

 

 

 

 

100M

Orange

 

 

OFF

Port operating at 10 Mbits/s

 

 

 

 

 

 

ON

 

Port operating at 100 Mbits/s

 

 

 

 

 

 

 

Service port (Sensor/RS485)

 

 

 

 

 

 

 

 

 

 

 

LED

 

Colour

 

 

 

Status

 

Description

 

 

 

 

 

 

 

 

Sensor

 

Green

 

 

OFF

 

Card starting

 

 

 

 

 

ON

 

Card ready

 

 

 

 

 

Flashing

Communication with environment

 

 

 

 

 

 

 

Sensor is operational

 

 

 

 

 

 

 

 

RS485

 

Orange

 

 

OFF

 

Settings mode activated

 

 

 

 

 

Flashing

 

Port is sending/receiving

 

 

 

 

 

Flashing

 

Communication fault or

 

 

 

 

every seconds

configuration errors

 

 

 

 

 

 

 

 

 

SWITCHES SETTING

Default settings, sensor configuration :

SA2

SA1

1

1

3

3

8

8

OFF ON

OFF ON

menu):

INSTALLATION

The Network Management Teleservice Card(66124) can be hotplugged on MGETM GalaxyTM 7000 UPSs. It is not necessary to shutdown the UPS, disconnect the load or restart the UPS.

A. Remove the plastic cover of the Minislot.

B. Note the MAC address of the card before inserting it.

C. Connect the PHONE cable.

D. Connect the ETHERNET cable (network already connected).

E. Insert and secure the card with the screws.

A

 

E

 

 

 

 

 

UPS

 

 

UPSData CD

ETHERNET

 

 

 

SENSOR/RS485

000623001C07

000623001C07

 

 

 

 

66124

 

 

C

D

B

Check the ETHERNET port indications.

Wait until the UPS Data LED flashes regularly (approx. two minutes), indicating that card start-uphas terminated correctly.

IP SETTINGS

Once the card has started, proceed as indicated below.

Connect one end of the serial cable to the Service port.

Connect the other end of the cable to the COM (IOIOI) port of a PC.

Run a terminal emulator such as HyperTerminalTM with these settings

Bits per second

Data bits

Stop bits

Flow control

38400

8

1

none

 

 

 

 

"Echo typed characters locally" option: disabled

Press the key.

press the 1 key (Network configuration menu)

Type MGEUPS (or mgeups), then press the key. The main configuration menu is displayed

:

APC by Schneider Electric

NETWORK MANAGEMENT CARD

1 : Reset

2 : Network configuration

3 : Set Login Password to Default

4 : Return to Default Configuration

0 : Exit

Your network is equipped with a BOOTP/DHCP server (default)

The card is configured by default with this service enabled. No manual configuration is required.The IP parameters are automatically collected by the card.

To view the network configuration(from the main configuration

Press the 2 key (Network configuration), then press the key.Press the 1 key(Read Network settings)., then press the key. The settings supplied by the server are displayed:

Network configuration :

MAC address : 00:06:23:00:1C:07

Mode : DHCP

IP address : 172.17.23.18

Subnet mask : 255.255.248.0

Gateway : 172.17.17

Note the IP address.

Press the key

Press the 0 key (Exit), then press the key.

Press the 0 key (Exit), then press the key.

Your network is not equipped with a BOOTP/DHCP server

Manual configuration is required.

To set the network configuration(from the main configuration menu):

Press the 2 key (Network configuration), then press the key.

Press the 2 key (Modify Network settings), then press the key.

Follow the instructions and enter the IP parameters:

1 : Read Network settings

2 : Modify Network settings

3 : Set ethernet speed

0 : Exit

For each of the following questions, you can press "Return" to select the value shown in braces, or you can enter a new value

Should this target obtain IP settings from the network?[N] N Static IP address [172.17.16.16]?172.16.1.82

Subnet mask IP address [255.255.0.0]? 255.255.255.0 Gateway address IP address[0.0.0.0]? 172.17.17.1 Done

Wait until "Done" is displayed, indicating that the IP parameters have been saved.

Press the 0 key (Exit), then press the key.

Press the 1 key (Reset), then press the key.

The card restarts with the new IP settings (after approx. two minutes).

ACCESS TO SUPERVISION

To check whether the Network Management Teleservice Cardis operational after installation and IP settings, proceed as follows.

Run a browser

Enter in the address bar:

http://IP address/ (e.g. http://172.16.1.82/)The home page is displayed:

Set the time by clicking the Time command.

Continue configuration via the sections in the Settings menu.

Teleservice procedure

Install the Network Management Teleservice Cardkit using the present manual.

Fill in the information form (3402228500).

Send the form to your Teleservice centre (by Fax or Internet).

Your centre will activate this service.

You receive an acknowledgement of receipt.

The information form must be sent back in order to trigger remote monitoring of your equipment.

USER MANUAL

The manual (34003991EN) provides all the information required to use, install and configure the Network Management Teleservice Card.

For more information on the supervision, control and configuration functions offered by the Network Management Teleservice Card, see the user manual on thewww.apc.com web site.

3402231500/AC

SENSOR CONNECTION (option)

The Environment sensor is a Network Management Teleservice Card option.

The sensor remotely monitors the UPS environment by regularly measuring the temperature and humidity, and checking the states of two external contacts. It can also send alarms (e-mail,SNMP trap) tripped bypre-setthresholds.

Connection is made via the Service port (Settings/Sensor) on the

Network Management Teleservice Card. The sensor is detected automatically. Configuration and supervision use a menu that may be accessed directly from the home page. For more information, see the user manual of the Network Teleservice Management Card.

Setings

 

 

 

 

 

 

/Sensor

ETHERNET

 

 

 

 

 

 

 

 

UPS data

 

 

 

Settings/Sensor

 

 

RS232

 

 

 

 

Setings

 

 

100M

 

 

 

 

 

 

On = Li

10M

UPS data

 

/Sensor

ETHERNET

 

 

Blink =nk

 

RS232

 

PHONE

 

Act

 

 

 

Settings/Sensor

 

 

 

 

66102

 

 

 

 

 

 

 

 

100M

 

 

 

 

 

 

 

10M

ETHERNET

UPS

TECHNICAL CHARACTERISTICS

Physical characteristics

Dimensions (W x D x H)

132 x 66 x 42 mm

 

 

Weight

85 g

 

 

RoHS

100% compatible

 

 

Storage

 

 

 

Storage temperature

-10°Cto 70°C

range

 

 

 

Ambient conditions

 

 

 

Operating temperature

0°C to 40°C

range

 

 

 

Relative humidity

90% RH max. without condensation

 

 

Card performance

 

 

 

Supply voltage

5V ±5%

 

 

Supply current (all LEDs

500 mA max.

ON and Environment

 

Sensor connected)

 

 

 

Functions

 

 

 

Web supervision

5 browsers max. (http),

 

3 browsers max. (https)

 

 

Languages

English

 

 

Alarms

E-mail,SNMP TRAP, Web page

 

 

Log

400 measurements or events

 

 

Server protection

Up to 35 servers protected

 

 

Network

Fast ETHERNET, 10/100 Mbits, auto-negotiation

 

HTTP 1.1, SNMP V1, NTP, TFTP, SMTP,

 

BOOTP/DHCP

 

 

Identification

User name and password

 

 

Security

SSL 3.0, TLS 1.0

 

 

Browsers

Microsoft Internet Explorer 6.x or higher

 

 

NMS

Enterprise Power Manager (EPM)

 

Management-Pac2

 

 

MIB

MIB II standard - MGE V1.7 MIB

 

 

Settings (default values)

 

 

IP network

BOOTP/DHCP enabled

 

IP address: 172.17.16.16

 

Subnet mask: 255.255.0.0

 

Gateway: 0.0.0.0

 

NTP server: pool.ntp.org

 

 

Web-pageaccess control

User name: MGEUPS

 

Password: MGEUPS

 

 

Service-portmenu access

Password: MGEUPS or mgeups

control

(not modifiable)

 

 

Date and time

Synchronise with an NTP server (GMT)

 

 

Service port

38400 bits/s, 8 bits, 1 bit stop, no parity

 

 

Standards

 

 

 

ITE (Information

IEC/EN 60950-1(2005)

Technology Equipment)

 

safety

 

 

 

R&TTE

99/05/EEC

 

 

EMC

EN 61000-6-2(2005), EN61000-6-3(2006)

 

2004/108/EEC

 

 

Low voltage

2006/95/EEC

 

 

FCC (Federal

This equipment has been tested and found to

Communication

comply with the limits for a Class B digital device,

Commission )

pursuant to part 15 of the FCC rules. These limits

 

are designed to provide reasonable protection

 

against harmful interference when the equipment

 

is operated in a commercial environment.

 

 

3402231500/AC