Contents

Introduction. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1

About this UPS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1

Unpack . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1

Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2

Installation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2

Rack-mount configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

2

Rack-mount to tower conversion procedure . . . . . . . . . . . . . . . . . . . . . .

4

Input hardwire 230 V models only . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

5

Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

5

Connect batteries . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

6

Configure bezel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

6

Connect display cable and install bezel . . . . . . . . . . . . . . . . . . . . . . . . .

7

Start-up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8

Connect Equipment and Power to the UPS . . . . . . . . . . . . . . . . . . . . . . .

8

Communication Ports . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

9

Emergency Power Off . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

9

Operation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10

Display Panels . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10

Display Panel Indicators and Function Buttons . . . . . . . . . . . . . . . . . . .10

Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12

UPS settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12

Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14

Maintenance, Transport, and Service. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17

Replace battery modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .17

Service . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .18

Two-YearWarranty. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19

Regulatory Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20

Smart-UPS5000 VA 208/230 VacTower/Rack-Mount5U User Manual

i

For further information contact UPS Direct Ltd:

Tel: 08456 445 002 - Fax: 08456 445 003 - Email: info@upsdirect.com - Website: www.upsdirect.com

For further information contact UPS Direct Ltd:

Tel: 08456 445 002 - Fax: 08456 445 003 - Email: info@upsdirect.com - Website: www.upsdirect.com

Introduction

About this UPS

The American Power Conversion (APC®) Uninterruptible Power Supply (UPS) provides protection for electronic equipment from utility power blackouts, brownouts, sags and surges. The UPS filters small utility line fluctuations and isolates electronic equipment from large disturbances by internally disconnecting from utility line power. The UPS provides continuous power from the internal battery until utility power returns to safe levels or the battery is fully discharged.

Unpack

Read the Safety Guide before installing the UPS.

Inspect the UPS upon receipt. Notify the carrier and dealer if there is damage. The packaging is recyclable; save it for reuse or dispose of it properly.

The UPS and the battery modules are heavy. Remove the battery modules to lighten the UPS during installation. Refer to battery removal instructions on the packaging.

Check the package contents:

UPS

Front bezel

Display bezel

Top covers (2) and one screw (tower configuration)

EPO connector

Serial cable

Eight ornamental screws for securing the unit in the rack

Four cage nuts

Two rack-mountbrackets (used as stabilizers in tower configuration)

Eight pan-headlocking screws

Two rail cleats

Eight pan-headscrews

Literature kit containing:

Product documentation

Smart-UPS®User Manuals CD

PowerChute® Business EditionCD

Safety information

Warranty information

Additional contents for 230 V models:

IEC power connector

IEC jumper cables

Hardware

8

8

1

8

4

2

pan head screws for securing rail cleats to UPS

pan head locking screws for securing rack-mountbrackets/ stabilizer brackets to the UPS

pan head locking screw (black) for securing top covers to UPS

ornamental screws for securing UPS to rack

cage nuts for rack installation

rack-mountbrackets forrack-mountconfiguration stabilizer brackets for tower configuration

2

rail cleats

 

Smart-UPS5000 VA 208/230 VacTower/Rack-Mount5U User Manual

1

For further information contact UPS Direct Ltd:

Tel: 08456 445 002 - Fax: 08456 445 003 - Email: info@upsdirect.com - Website: www.upsdirect.com

Specifications

Temperature

32° to 104° F (0° to 40° C)

This unit is intended for indoor use

Operating

only. Select a location sturdy enough

Storage

5° to 86° F(-15° to 30° C) charge the UPS battery every six months

to handle the weight.

 

86° to 113° F (30° to 45° C) charge the UPS battery every three months

Do not operate the UPS where there

 

is excessive dust or the temperature

Maximum

 

or humidity are outside the specified

 

limits.

Elevation

 

 

Environmental factors impact battery

Operating

6562 ft (2,000 m)

life. High temperatures, poor utility

Storage

50,000 ft (15,240 m)

power, and frequent, short duration

 

 

discharges will shorten battery life.

 

 

 

Humidity

0 to 95% relative humidity, non-condensing

 

 

 

 

Weight

215 lbs (98 kg) with battery module

215 lbs (98 kg)

 

107 lbs (49 kg) without battery module

 

 

27 lbs (12 kg) each battery module

 

 

 

 

NOTE: The model and serial numbers are located on a small, rear panel label. For some models, an additional label is located on the chassis under the front bezel.

Installation

Rack-mountconfiguration

This unit is intended for mounting in a four post rack. To order a two post rack-mountkit contact your dealer or refer to the APC Web site, www.apc.com.

The UPS and the battery modules are heavy. Remove the battery modules to lighten the UPS during installation. Refer to the battery removal instructions on the packaging.

Install rack-mountbrackets and rail cleats

Four screws must be used to secure each rail bracket and rail cleat to the UPS. One rack-mountbracket and one rail cleat must be secured to the both sides of the UPS.

Rack-mountbracket

four post rack-mountposition

Rail cleat

4x 4x

2

Smart-UPS5000 VA 208/230 VacTower/Rack-Mount5U User Manual

For further information contact UPS Direct Ltd:

Tel: 08456 445 002 - Fax: 08456 445 003 - Email: info@upsdirect.com - Website: www.upsdirect.com

Install unit in rack

Ensure rack stability prior to installing devices in the rack. The UPS should be installed at or near the bottom of the rack.

When installing rails in the rack, install two cage nuts above each rail, (see diagram).

Secure the UPS in the rack using the four cage nuts and eight ornamental screws included in the package.

Second cage nut: count three holes up from first cage nut

First cage nut: count four holes up from top edge of rail

3 holes

3 holes

4 holes

4 holes

Install batteries

Connect only the first two batteries in the string of three batteries. Be sure that the battery connectors are fully engages.

Do not connect the single battery or the last battery installed in the string of three batteries.

Close and secure battery doors

Foam spacers

4x

Smart-UPS5000 VA 208/230 VacTower/Rack-Mount5U User Manual

3

For further information contact UPS Direct Ltd:

Tel: 08456 445 002 - Fax: 08456 445 003 - Email: info@upsdirect.com - Website: www.upsdirect.com

Rack-mountto tower conversion procedure

The UPS and the battery modules are heavy. Remove the battery modules to lighten the UPS during installation. Refer to the battery removal instructions on the packaging.

Install stabilizer brackets

Stand the UPS on the side with the embossed marks.

Secure a stabilizer bracket (supplied), to both sides of the UPS.

Secure each bracket with two pan head locking screws (supplied).

4x

Install two top covers

Install the large top cover by placing it in the slots on the UPS and sliding the cover forward.

Install the small top cover by placing it in the slots on the UPS and sliding the cover forward.

Secure the top covers with a #8 black screw (supplied).

Install batteries

Connect only the first two batteries in the string of three batteries. Be sure that the battery connectors are fully engages.

Do not connect the single battery or the last battery installed in the string of three batteries.

Close and secure the battery doors

Foam spacers

2x

2x

4

Smart-UPS5000 VA 208/230 VacTower/Rack-Mount5U User Manual

For further information contact UPS Direct Ltd:

Tel: 08456 445 002 - Fax: 08456 445 003 - Email: info@upsdirect.com - Website: www.upsdirect.com

Input hardwire 230 V models only

Hardwiring must be performed by a qualified electrician. Adhere to all national and local regulations.

1.Use a dedicated branch circuit with a maximum of 32 A of over-currentprotection, (either a circuit breaker of fuses).

A lower rated branch may be used depending on the requirements of the UPS load. Allow an additional 600 W for the UPS during the battery replacement procedure.

2.Switch the circuit breaker OFF prior to connecting equipment and power to the UPS.

3.Remove the access panels located on the rear panel of the UPS.

4.Remove the knockout from the input access panel.

5.Use # 10 AWG (5 mm²).

Strip approximately six inches (152.4 mm) of the outer jacket from the input cable exposing the wires. Strip .5 inch (12.7 mm) of the individual wire coverings.

6.Route the input cable through the hole in the input access panel. Apply an appropriate strain relief.

7.Connect the ground wire prior to connecting the line wires.

8.Replace the access panels and secure each panel with three screws.

 

input

access panel

access panel

Access panel screws

Terminal block

L1 L2/N

Accessories

Install accessories prior to connecting power to the UPS.

Refer to the APC Web site, www.apc.com for available accessories.

Input/output hardwire kit

Two post rack option

Smart-UPS5000 VA 208/230 VacTower/Rack-Mount5U User Manual

5

For further information contact UPS Direct Ltd:

Tel: 08456 445 002 - Fax: 08456 445 003 - Email: info@upsdirect.com - Website: www.upsdirect.com

Connect batteries

Rack-mountconfiguration Tower configuration

Battery disconnect cord Battery disconnect cord

After all of the batteries have been connected, tuck the battery cables and the battery disconnect cord in the space provided in the battery doors. This will ensure a secure fit of the bezel to the unit.

Configure bezel

Snap the display out of the bezel. Rotate the bezel and reinstall the display for a tower configuration.

Display

6

Smart-UPS5000 VA 208/230 VacTower/Rack-Mount5U User Manual

For further information contact UPS Direct Ltd:

Tel: 08456 445 002 - Fax: 08456 445 003 - Email: info@upsdirect.com - Website: www.upsdirect.com