Seismic Stability Kit

Install rear anchoring brackets

1 Secure the floor anchoring bracket to the floor using floor anchoring bolts (not supplied). Use M12 strength class 8.8 or 1/2 inch, grade 5 steel bolts.

1

2Secure the back of the other half of the bracket assembly to the back of the unit.

2

3Push the unit back to slide the bracket on the unit under the bracket bolted to the floor.

3

150/175kw Modular PDU Installation

17

Install front anchoring bracket

1Secure the front anchoring bracket to the enclosure.

1

2Secure the front anchoring bracket to the floor using floor anchoring bolts (not supplied). Use M12 strength class 8.8 or 1/2 inch, grade 5 steel bolts.

2

18

150/175kw Modular PDU Installation

Specifications

AC Input

Model

PDPM150G6F

PDPM150L6F

PDPM175G6H

 

 

 

 

Nominal voltage

480V, 3W +G

600V, 3W +G

480V, 3W + G

 

 

 

 

Frequency

60 Hz

60 Hz

60 Hz

 

 

 

 

Maximum

180 A

150 A

214 A

continuous

 

 

 

current

 

 

 

 

 

 

 

Nominal current

178 A

141 A

214 A

 

 

 

 

Recommended current rating of input circuit breakers

 

 

 

 

 

Mains Input1 (A)

225

200

300

Inrush currents

 

 

 

 

 

 

 

Inrush Current2

2000

1500

2100

 

 

 

 

1 Standard circuit breakers are rated to carry 80% of their current rating continuously.

2 The supply overcurrent protective device must be able to handle the listed transformer inrush currents.

AC Output

Model

PDPM150G6F

PDPM150L6F

PDPM175G6H

 

 

 

 

Nominal voltage

208Y/120V,

208Y/120V,

415Y/240V,

 

3W + N + G

3W + N + G

3W + N + G

 

 

 

 

Maximum continuous current

400 A

400 A

243 A

 

 

 

 

Full load rating

144 kW @ 208V 3

144 kW @ 208V 3

175kW @ 415V 3 PH

 

PH

PH

 

 

 

 

 

Power distribution module

208/120V, 3-pole

208/120V, 3-pole

415/240V, 3-pole

(PDM)

modules

modules

modules

 

 

 

 

Power distribution poles

72

72

72

available

 

 

 

 

 

 

 

Maximum number of PDMs

24

24

24

 

 

 

 

150/175kw Modular PDU Installation

19

Distribution Transformer

 

Model

 

PDPM150G6F

PDPM150L6F

PDPM175G6H

 

 

 

 

 

 

 

 

Size

 

150 kVA

150 kVA

175 kVA

 

 

 

 

 

 

 

 

Type

 

Delta/Wye

Delta/Wye

Delta/Wye

 

 

 

 

 

 

 

 

 

Input voltage

 

 

480V

600V

480V

 

 

 

 

 

 

 

 

 

Input current

 

 

180 A

150 A

214 A

 

 

 

 

 

 

 

 

Output voltage

 

208Y/120V

208Y/120V

415Y/240V

 

 

 

 

 

 

 

 

Output current

 

399.72 A

399.72 A

243.47

 

 

 

 

 

 

 

 

 

 

Thermal sensing

 

 

180 NC

180 NC

180 NC

 

 

 

 

 

 

 

 

Weight

 

455 kg (1003 lb)

500 kg (1102 lb)

560 kg (1235 lb)

 

 

 

 

 

 

 

 

Efficiency

 

98.2% min.

98.2% min.

98.5% min.

 

 

 

 

 

 

 

 

 

Frequency

 

 

60 Hz

60 Hz

60 Hz

 

 

 

 

 

 

 

 

Noise

 

< 55 db @ 1 m

< 55 db @ 1 m

< 55 db @ 1 m

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Environment and Compliance

 

 

 

 

 

 

 

 

 

Temperature

 

 

Operating: -5to +40°C (23 to 104°F)

 

 

 

 

 

 

Storage: -25to +65°C(-13to 149°F)

 

 

 

 

 

 

 

 

Humidity

 

 

Operating: 0 to 95%, non-condensing

 

 

 

 

 

 

Storage: 0 to 95%, non-condensing

 

 

 

 

 

 

 

 

 

Elevation

 

 

3000 m (9,842.5 ft)

 

 

 

 

 

 

 

 

 

 

Certification

 

 

UL and cUL

 

 

 

 

 

 

 

 

 

 

Conditional Short-Circuit

 

10 kA*

 

 

 

 

Current Rating (ICC)

 

 

 

 

 

 

 

* The Conditional Short-CircuitCurrent Rating was not evaluated by

 

 

Underwriters Laboratories.

 

 

 

 

 

 

 

 

 

 

 

 

Note: Circuit breakers and conductor ampacity are derated in accordance with the National Electrical Code.

20

150/175kw Modular PDU Installation

Recommended conductor sizes

Note: All wiring must comply with all applicable national and or local electrical codes.

Conductor sizing in this manual is based on Table 310-16of the 2011 National Electrical Code (NEC) with the following assertions:

90°C conductors (THHN) for 75°C termination

3 Current Carrying Conductors for Unit Input Circuit Breaker and 4 Current Carrying Conductors for Subfeed Circuit Breaker

An ambient temperature of 30°C

Two conduits for each subfeed

One Equipment Grounding Conductor for each conduit

If the ambient room temperature is greater than 30°C, larger conductors are to be selected in accordance with the correction factors of the NEC.

Equipment Grounding Conductors (EGC) are sized in accordance with NEC Article 250-122and Table250-122.

Grounding Electrode Conductors (GEC) are sized in accordance with NEC Article 250-66and Table250-66.

The conductor sizes are recommendations for maximum configurations. Even if the load is less than the maximum rating, it is wise to plan for future load increases. If the system is operated at a lower load than its rating and it is desired to supply the system with a lower rated breaker and smaller conductors, conductor ampacities are to be selected in accordance with the NEC. The transformer inrush must be taken into account when sizing conductors.

Table for 40°C

PDPM150G6F

PDPM150L6F

PDPM175G6H

ambient/4CCC

480:208

600:208

480:415

 

 

 

 

Mains Input Φ

Cu only: 250kcmil

Cu only: 3/0 AWG

Cu: 350kcmil

 

Al: 500kcmil

 

75°C conductor minimum

90°C conductor minimum

 

75°C conductor minimum

 

 

 

 

 

 

 

Equipment

Cu: 4 AWG

Cu: 6 AWG

Cu: 4 AWG

Grounding

 

 

Al: 2 AWG

Conductor (EGC)

 

 

 

 

 

 

 

Grounding

Cu: 2 AWG

Cu: 2 AWG

Cu: 2 AWG

Electrode

 

 

Al: 1/0 AWG

Conductor (GEC)

 

 

 

Output

Supplied with Power Distribution Modules

 

 

 

 

 

Subfeed Output

Cu only: (2) 300kcmil Φand

Cu only: (2) 300kcmil Φand

Cu: (2) 2/0 AWG Φ and N, 4

 

N, 3 AWG EGC, GEC not

N, 3 AWG EGC, GEC not

AWG EGC, GEC not

 

required.

required.

required.

 

90°C conductor minimum

90°C conductor minimum

Al: (2) 4/0 AWG Φ and N, 2

 

 

 

AWG EGC, GEC not

 

 

 

required.

 

 

 

75°C conductor minimum

 

 

 

 

150/175kw Modular PDU Installation

21

Table for 30°C

PDPM150G6F

PDPM150L6F

PDPM175G6H

ambient/4CCC

480:208

600:208

480:415

 

 

 

 

Mains Input Φ

Cu: 4/0 AWG

Cu only: 3/0 AWG

Cu: 300kcmil

 

A1: 300kcmil

Al: 400kcmil

 

90°C conductor minimum

 

75°C conductor minimum

75°C conductor minimum

 

 

 

 

 

 

Equipment

Cu: 4 AWG

Cu: 6 AWG

Cu: 4 AWG

Grounding Conductor

A1: 2 AWG

 

Al: 2 AWG

(EGC)

 

 

 

 

 

 

 

Grounding Electrode

Cu: 2 AWG

Cu: 2 AWG

Cu: 2 AWG

Conductor (GEC)

A1: 1/0 AWG

 

Al: 1/0 AWG

 

 

 

 

Output

Supplied with Power Distribution Modules

 

 

 

 

 

Subfeed Output

Cu: (2) 250kcmil Φand N,

Cu: (2) 250kcmil Φ and N,

Cu: (2) 2/0 AWG Φ and N,

 

3 AWG EGC, GEC not

3 AWG EGC, GEC not

4 AWG EGC, GEC not

 

required.

required.

required.

 

Al: (2) 350 kcmil Φand N,

Al: (2) 350 kcmil Φand N,

Al: (2) 3/0 AWG Φ and N,

 

1 AWG EGC, GEC not

1 AWG EGC, GEC not

2 AWG EGC, GEC not

 

required.

required.

required.

 

90°C conductor minimum

90°C conductor minimum

75°C conductor minimum

 

 

 

 

Φ = phase, N = neutral

(2) = two conductors per phase and neutral (when neutral is required)

Subfeed is required to have two conductors per phase & N for full output due to limited wire bend space Cu= Copper conductors, Al= Aluminum conductors

CCC = Current Carrying Conductor

Regulatory Agency Approval

This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to Part 15 of the FCC and ICES-003Rules. These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the Installation Guide, may cause harmful interference to radio communications. Operation of this equipment in a residential area is likely to cause harmful interference, in which case the user will be required to correct the interference at his own expense.

22

150/175kw Modular PDU Installation

Radio Frequency Interference

Note: Changes or modifications to this unit not expressly approved by the party responsible for compliance could void the user’s authority to operate this equipment.

USA—FCC

This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with this user manual, may cause harmful interference to radio communications. Operation of this equipment in a residential area is likely to cause harmful interference. The user will bear sole responsibility for correcting such interference.

Canada—ICES

This Class A digital apparatus complies with Canadian ICES-003.

Cet appareil numérique de la classe A est conforme à la norme NMB-003du Canada.

APC Worldwide Customer Support

Customer support for this or any other APC product is available at no charge in any of the following ways:

Visit the APC Web site to access documents in the APC Knowledge Base and to submit customer support requests.

www.apc.com (Corporate Headquarters)

Connect to localized APC Web sites for specific countries, each of which provides customer support information.

www.apc.com/support/

Global support searching APC Knowledge Base and using e-support.

Contact the APC Customer Support Center by telephone ore-mail.

Local, country-specificcenters: go towww.apc.com/support/contact for contact information.

For information on how to obtain local customer support, contact the APC representative or other distributors from whom you purchased your APC product.

© 2012 APC by Schneider Electric. APC, and the APC logo are owned by Schneider Electric Industries S.A.S., American Power Conversion Corporation, or their affiliated companies. All other trademarks are property of their respective owners.

990-4384

5/2012