APC PDPM150L6F, 175kW, PDPM175G6H, PDPM150G6F, 150 User Manual

0 (0)
APC PDPM150L6F, 175kW, PDPM175G6H, PDPM150G6F, 150 User Manual

Installation

150/175kW Modular PDU

PDPM150G6F

PDPM150L6F

PDPM175G6H

Contents

Overview ..........................................................................

1

Important Safety Information. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1

Disclaimer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2

Please Note: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2

Additional Safety Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3

Before you begin . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

3

Operation and Adjustments . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

3

About This Manual..........................................................

4

Related Documents. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4

Product Related Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4

User Comments. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4

Installation .......................................................................

5

Electrical Safety . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5

Inrow Installation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5

Perform Equipotential Bonding. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6

Connect and Level Enclosures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6

Install Input Power Cables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7

Top entry installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7

Bottom entry installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8

Install Subfeed Cables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10

Install User Input/Output Contacts . . . . . . . . . . . . . . . . . . . . . . . . . . 11

Install the Communication Cable . . . . . . . . . . . . . . . . . . . . . . . . . . . 13

150/175kW Modular PDU Installation

i

Power Distribution Modules (PDMs). . . . . . . . . . . . . . . . . . . . . . . . . 14

Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14

Remove power distribution modules (PDMs) . . . . . . . . . . . . . . . . . 15

Install filler plates . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15

Options...........................................................................

16

Shielding Troughs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16

Seismic Stability Kit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17

Install rear anchoring brackets . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17

Install front anchoring bracket . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18

Specifications ................................................................

19

Recommended conductor sizes . . . . . . . . . . . . . . . . . . . . . . . . . . .

21

Regulatory Agency Approval .......................................

22

ii

150/175kW Modular PDU Installation

Overview

Important Safety Information

Read the instructions carefully and look at the equipment to become familiar with the device before trying to install, operate, service or maintain it. The following special messages may appear throughout this manual or on the equipment to warn of potential hazards or to call attention to information that clarifies or simplifies a procedure.

The addition of this symbol to a Danger or Warning safety label indicates that an electrical hazard exists which will result in personal injury if the instructions are not followed.

This is the safety alert symbol. It is used to alert you to potential personal injury hazards. Obey all safety messages that follow this symbol to avoid possible injury or death.

DANGER

DANGER indicates an imminently hazardous situation which, if not avoided, will result in death or serious injury.

WARNING

WARNING indicates a potentially hazardous situation which, if not avoided, can result in death or serious injury.

CAUTION

CAUTION indicates a potentially hazardous situation which, if not avoided, can result in minor or moderate injury.

CAUTION

CAUTION, used without the safety alert symbol, indicates a potentially hazardous situation which, if not avoided, can result in equipment damage.

NOTICE

NOTICE addresses practices not related to physical injury including certain environmental hazards, potential damage or loss of data.

150/175kw Modular PDU Installation

1

Disclaimer

The information presented in this manual is not warranted by Schneider Electric to be authoritative, error free, or complete. This publication is not meant to be a substitute for a detailed operational and site specific development plan. Therefore, Schneider Electric assumes no liability for damages, violations of codes, improper installation, or any other problems that could arise based on the use of this publication.

The information contained in this publication is provided as is and has been prepared solely for the purpose of evaluating data center design and construction. This publication has been compiled in good faith by Schneider Electric. However, no representation is made or warranty given, either express or implied, as to the completeness or accuracy of the information this publication contains.

IN NO EVENT SHALL SCHNEIDER ELECTRIC, OR ANY AFFILIATE OR SUBSIDIARY COMPANY OF SCHNEIDER ELECTRIC OR THEIR RESPECTIVE OFFICERS, DIRECTORS, OR EMPLOYEES BE LIABLE FOR ANY DIRECT, INDIRECT, CONSEQUENTIAL, PUNITIVE, SPECIAL, OR INCIDENTAL DAMAGES (INCLUDING, WITHOUT LIMITATION, DAMAGES FOR LOSS OF BUSINESS, CONTRACT, REVENUE, DATA, INFORMATION, OR BUSINESS INTERRUPTION) RESULTING FROM, ARISING OUT OF, OR IN CONNECTION WITH THE USE OF, OR INABILITY TO USE THIS PUBLICATION OR THE CONTENT, EVEN IF SCHNEIDER ELECTRIC HAS BEEN EXPRESSLY ADVISED OF THE POSSIBILITY OF SUCH DAMAGES. SCHNEIDER ELECTRIC RESERVES THE RIGHT TO MAKE CHANGES OR UPDATES WITH RESPECT TO OR IN THE CONTENT OF THE PUBLICATION OR THE FORMAT THEREOF AT ANY TIME WITHOUT NOTICE.

Copyright, intellectual, and all other proprietary rights in the content (including but not limited to software, audio, video, text, and photographs) rests with Schneider Electric or its licensors. All rights in the content not expressly granted herein are reserved. No rights of any kind are licensed or assigned or shall otherwise pass to persons accessing this information.

This publication shall not be for resale in whole or in part.

Please Note:

Electrical equipment should be installed, operated, serviced, and maintained only by qualified personnel. No responsibility is assumed by Schneider Electric for any consequences arising from the use of this material.

A qualified person is one who has skills and knowledge related to the construction, installation, and operation of electrical equipment and has received safety training to recognize and avoid the hazards involved.

2

150/175kw Modular PDU Installation

Additional Safety Information

Before you begin

Verify that the system is free from all short circuits and grounds, except those grounds installed according to local regulations (according to the National Electrical Code in the U.S.A., for instance). If high-potential voltage testing is necessary, follow recommendations in equipment documentation to prevent accidental equipment damage.

Before energizing equipment:

Remove tools, meters, and debris from equipment.

Close the equipment enclosure door.

Remove ground from incoming power lines.

Perform all start-up tests recommended by the manufacturer.

Operation and Adjustments

The following precautions are from the NEMA Standards Publication ICS 7.1-195 (English version prevails):

Regardless of the care exercised in the design and manufacture of equipment or in the selection and ratings of components, there are hazards that can be encountered if such equipment is improperly operated.

It is sometimes possible to misadjust the equipment and thus produce unsatisfactory or unsafe operation. Always use the manufacturer’s instructions as a guide for functional adjustments. Personnel who have access to these adjustments should be familiar with the equipment manufacturer's instructions and the machinery used with the electrical equipment.

Only those operational adjustments actually required by the operator should be accessible to the operator. Access to other controls should be restricted to prevent unauthorized changes in operating characteristics.

WARNING

UNGUARDED MACHINERY HAZARD

Do not use this product with equipment which does not have point-of-operation protection.

Do not reach into equipment during operation.

Failure to follow these instructions can result in death, serious injury, or equipment damage.

150/175kw Modular PDU Installation

3

About This Manual

This manual is intended for users of the specified APC equipment. It contains important safety warnings and instructions, gives an introduction to the display interface and provides detailed information for proper use of the equipment.

Related Documents

Download technical publications and other technical information or look for updates to your manual at our website at www.apc.com.

Product Related Information

DANGER

HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH

Turn off all power supplying this equipment before working on the equipment.

Failure to follow these instructions will result in death or serious injury.

User Comments

We welcome your comments about this document. Contact www.apc.com/support.

4

150/175kw Modular PDU Installation

Installation

Electrical Safety

SAVE THESE INSTRUCTIONS!

This document contains important instructions that should be followed during installation of the 150/ 175kW Modular Power Distribution Unit (PDU).

DANGER

HAZARD OF ELECTRIC SHOCK

Only certified electricians are authorized to connect power to the PDU.

The PDU must be installed in accordance with the National Electrical Code or the Canadian Electrical Code and all applicable local codes.

To prevent arcing when removing a Power Distribution Module (PDM) from the panel, set all circuit breakers on that module to OFF (open).

Failure to follow these instructions can result in death or serious injury.

CAUTION

UNPROTECTED OUTPUTS

Remove cover plates from the unit before cutting holes for power cable access. Metal shavings can cause serious equipment damage. A metal punch can be used to make the holes in the plates.

Failure to follow these instructions can result in injury or equipment damage.

Inrow Installation

Maintain 36” hot aisle spacing.

Hot Aisle

pdx0849a

150/175kw Modular PDU Installation

5

Loading...
+ 19 hidden pages