American Power Conversion 3000 VA User Manual

Size:
861.78 Kb
Download

User Manual

English

APC Smart-UPSXL

2200/3000 VA 120/230 VAC

Rack Mount 3U

Uninterruptible Power Supply

990-2404

06/2005

Introduction

Introduction

About this UPS

The APC Uninterruptible Power Supply (UPS) provides protection for electronic equipment from utility power blackouts, brownouts, sags and surges. The UPS filters small utility line fluctuations and isolates electronic equipment from large disturbances by internally disconnecting from utility line power. The UPS provides continuous power from the internal battery until utility power returns to safe levels or the battery is fully discharged.

Unpack

Read the Safety Guide before installing the UPS. The User Manual and Safety Guide are accessible on the supplied User Manuals CD and on the APC Web site, www.apc.com.

Inspect the UPS upon receipt. Notify the carrier and dealer if there is damage. The packaging is recyclable; save it for reuse or dispose of it properly.

Check the package contents:

UPS

Front bezel

Rail kit

EPO connector

UPS literature kit containing:

Two mounting brackets

Eight flathead screws

Product documentation

Smart-UPS®User Manuals CD

PowerChute® CD

Serial and USB communication cables

Safety information

Warranty information

230V Models Only: UPS literature kit additional contents:

Input power cord

Alternate input power cord (UK customers)

Utility connector plug

IEC jumper cables

The model and serial numbers for all units are located on the rear panel. See the small label with numbers and bar codes.

Specifications

Temperature

32° to 104° F (0° to 40° C)

This unit is designed for indoor

Operating

use only. Select a location sturdy

Storage

5° to 86° F(-15° to 30° C) charge the UPS battery every six months

enough to handle the weight.

 

86° to 113° F (30° to 45° C) charge the UPS battery every three months

Do not operate the UPS where

Maximum

 

there is excessive dust or the

Elevation

 

temperature or humidity are

Operating

10,000 ft (3,000 m)

outside the specified limits.

Storage

50,000 ft (15,240 m)

 

 

 

 

Humidity

0 to 95% relative humidity, non-condensing

 

 

 

 

Weight

135 lbs (61 kg) with battery module

135 lbs (61 kg)

 

80 lbs (36 kg) without battery module

 

 

 

 

Maximum Number of External Battery Packs Supported by the

10

Smart-UPSXL

 

 

 

 

Smart-UPSXL 2200/3000 VA 120/230 VAC 3U Rack Mount User Manual

3

Installation

Installation

Your UPS model may vary from the examples depicted in this manual.

The UPS and the battery module are heavy. Remove the battery module to lighten the UPS during installation.

Install the Rails in the Rack

For details on rail installation refer to the instructions in the rail kit.

Install the UPS in the Rack and Connect the Battery Module

4x

4x

 

 

4

Smart-UPSXL 2200/3000 VA 120/230 VAC 3U Rack Mount User Manual

Start Up

Accessories

This UPS is equipped with an accessory SmartSlot. Refer to the APC Web site, www.apc.com for available accessories.

If a standard accessory, such as a SNMP card is installed on this UPS, refer to the Utility CD for user documentation.

Install accessories prior to connecting power to the UPS.

Start Up

Connect Equipment and Power to the UPS

1.The UPS features a transient voltage surge-suppression(TVSS) screwlocated on the rear panel, for connecting the ground lead on surge suppression devices such as telephone and network line protectors.

Prior to connecting the grounding cable, ensure that the UPS is NOT connected to utility or battery power.

2. Connect equipment to the UPS.

NOTE: This UPS is equiped with an external battery connector on the rear panel of the unit.

Where appropriate use an APC extension battery cable. For ordering details contact your dealer or APC through the Web site www.apc.com.

3.Add optional accessories to the SmartSlot located on the rear panel.

4.Plug the UPS into a two-pole,three-wire,grounded receptacle only. Avoid using extension cords.

230 V models: The utility power cord is supplied in the UPS literature kit. Prior to connecting the utility power, connect the ground lead (optional) to the TVSS screw.

5.120 V models: Check theSITE WIRING FAULT LEDlocated on the rear panel. The LED will be illuminated if the UPS is plugged into an improperly wired utility power outlet, (seeTroubleshooting).

6.To use the UPS as a master on/off switch be sure all connected equipment is switched on.

Rear Panels

120 VAC

230 VAC

Smart-UPSXL 2200/3000 VA 120/230 VAC 3U Rack Mount User Manual

5

Start Up

Start the UPS

1.Press the button on the front panel to start the UPS.

The battery charges to 90% capacity during the first four hours of normal operation. Do not expect full battery run capability during this initial charge period.

Refer to the APC Web site, www.apc.com for battery runtimes.

2.For optimal computer system security, install PowerChute Smart-UPSmonitoring software.

Communication Ports

SERIAL PORT USB PORT Use only the supplied cable to connect to the serial port. A standard

serial interface cable is incompatible with the UPS.

Serial and USB ports cannot be used simultaneously.

Emergency Power Off

The emergency power off (EPO) feature is user configurable. EPO provides immediate de-energizingof connected equipment from a remote location, without switching to battery operation.

1.Use the EPO connector supplied with the UPS.

2.Use a normally-opencontact to connect the +24 terminal to the IN terminal. External voltage is not required.

3.Wire the four-pinconnector to the EPO system.

EPO PORT

 

EPO

(located on rear panel)

 

Connector

The EPO interface is a Safety Extra Low Voltage (SELV) circuit. Connect it only to other SELV circuits. The EPO interface monitors circuits that have no determined voltage potential. Such closure circuits may be provided by a switch or relay properly isolated from the utility. To avoid damage to the UPS, do not connect the EPO interface to any circuit other than a closure type circuit.

Use one of the following cable types to connect the UPS to the EPO switch.

CL2: Class 2 cable for general use.

CL2P: Plenum cable for use in ducts, plenums, and other spaces used for environmental air.

CL2R: Riser cable for use in a vertical run in a floor-to-floorshaft.

CLEX: Limited use cable for use in dwellings and for use in raceways.

For installation in Canada: Use only CSA certified, type ELC, (extra-lowvoltage control cable).

For installation in other countries: Use standard low-voltagecable in accordance with national and local regulations.

6

Smart-UPSXL 2200/3000 VA 120/230 VAC 3U Rack Mount User Manual

Operation

Operation

Display Panels

120 V models

Load /

230 V models

Battery

 

Charge

Display Panel Indicators and Function Buttons

Indicator

Indicator Title

Description

 

 

 

LED

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

On Line

The UPS is supplying utility power to the connected equipment,

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(see Troubleshooting).

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AVR Trim

The UPS is compensating for a high utility voltage. Refer to the APC Web site,

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

www.apc.com for AVR settings.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AVR Boost

The UPS is compensating for a low utility voltage. Refer to the APC Web site,

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

www.apc.com for AVR settings.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

On Battery

The UPS is supplying battery power to the connected equipment.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Overload

The connected equipment is drawing more than the UPS power rating allows,

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(see Troubleshooting).

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Replace Battery/Battery

The battery is disconnected or must be replaced, (see Troubleshooting).

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Disconnected

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Smart-UPSXL 2200/3000 VA 120/230 VAC 3U Rack Mount User Manual

7

Operation

230V

120V

Diagnostic

Utility Voltage

 

 

Battery

Charge

The UPS has a diagnostic feature that indicates the utility voltage.

The UPS starts a self-testas part of this procedure. Theself-testdoes not affect the voltage display.

Press and hold the button to view the utility voltage bar graph indicator. After

a few seconds, this five-LEDBattery Charge indicator on the right of the display panel will show the utility input voltage.

Refer to the figure on the left for the voltage reading. Values are not listed on the UPS.

The indicator on the UPS shows the voltage is between the displayed value on the list and the next higher value, (see Troubleshooting).

Feature

Feature Title

 

Function

Button

 

 

 

 

 

Power On

Press this button to turn on the UPS. Continue reading for additional

 

 

capabilities.

 

 

Power Off

Press this button to turn off the UPS.

 

Self-Test

Automatic: The UPS performs aself-testautomatically when tuned on, and

 

 

every two weeks thereafter (by default). During the self-test,the UPS

 

 

briefly operates the connected equipment on battery.

 

 

Manual: Press and hold the

button for a few seconds to initiate the

 

 

self-test.

 

 

Cold Start

When there is no utility power and the UPS is off, the cold start feature will

 

 

switch the UPS and connected equipment onto battery power,

 

 

(see Troubleshooting).

 

8

Smart-UPSXL 2200/3000 VA 120/230 VAC 3U Rack Mount User Manual

Configuration

Configuration

UPS settings

Settings are adjusted through PowerChute software or optional SmartSlot accessory cards.

Function

Factory

User Selectable

 

Description

Default

Choices

 

 

 

 

 

Automatic

On startup and

• Every 7 days

Set the interval at which the UPS will execute a

Self-Test

every 14 days

(168 hours)

 

self-test.

 

 

(336 hours)

• On startup and every

 

 

 

there after

14 days (336 hours)

 

 

 

 

there after

 

 

 

 

 

• On startup only

 

 

 

 

• No self-test

 

 

 

 

 

 

 

UPS ID

UPS_IDEN

Up to eight characters

Uniquely identify the UPS, (i.e. server name or

 

 

(alphanumeric)

location) for network management purposes.

 

 

 

 

 

Date of Last

Manufacture

mm/dd/yy

 

Reset this date when you replace the battery

Battery

Date

 

 

module.

 

Replacement

 

 

 

 

 

 

 

 

 

 

Minimum Capacity

0 percent

• 0%

• 60%

Specify the percentage to which batteries will

Before Return from

 

• 15%

• 75%

be charged following a low battery shutdown

Shutdown

 

• 30%

• 90%

before powering connected equipment.

 

 

• 45%

 

 

 

 

 

 

 

 

Voltage Sensitivity

High sensitivity

Brightly

 

Adjust by pressing the VOLTAGE SENSITIVIY

The UPS detects

 

illuminated: high

 

 

 

sensitivity

switch

(rear panel). Use a pointed object,

and reacts to line

 

voltage distortions

 

Dimly illuminated:

(such as a pen) to do so.

by transferring to

 

medium sensitivity

Note: In situations of poor power quality, the

battery operation to

 

No illumination:

UPS may frequently transfer to battery

protect the

 

low sensitivity

operation. If the connected equipment can

connected

 

 

 

operate normally under such conditions, reduce

equipment.

 

 

 

the sensitivity setting to conserve battery

 

 

 

 

capacity and service life.

 

 

 

 

Voltage sensitivity levels can be changed

 

 

 

 

through PowerChute software.

 

 

 

 

 

Alarm Delay

Enable

• Enable

 

Mute ongoing alarms or disable all alarms

Control

 

• Mute

 

permanently.

 

 

• Disable

 

 

 

 

 

 

 

 

Shutdown Delay

90 seconds

• 0 s

• 360 s

Set the interval between the time when the UPS

 

 

• 90 s

• 450 s

receives a shutdown command and actual

 

 

• 180 s

• 540 s

shutdown.

 

 

 

• 270 s

• 630 s

 

 

 

 

 

 

 

 

Smart-UPSXL 2200/3000 VA 120/230 VAC 3U Rack Mount User Manual

9

Configuration

 

 

Factory

User Selectable

 

 

 

Function

 

Default

Choices

 

Description

 

 

 

 

 

 

 

Low Battery

 

2 minutes

Brightly

 

The low-batterywarning beeps are continuous

Warning

 

 

illuminated:

when two minutes of run time remain.

PowerChute

 

 

low battery warning

To change the default interval setting, use a

software interface

 

 

level of about

2 minutes

pointed object such as a pen to press the

provides automatic,

 

 

Dimly illuminated:

VOLTAGE SENSITIVIY switch

(rear

unattended

 

 

low battery

shutdown when

 

 

panel), while

 

 

 

 

warning level of about

 

 

approximately two

 

 

 

 

 

 

 

5 minutes

 

 

 

 

minutes of battery

 

 

 

pressing the

button, (front display).

 

 

No illumination:

operated run time

 

 

 

 

Change the low battery warning interval setting

remains.

 

 

low battery warning

 

 

to the time that the operating system or system

 

 

 

level is about 8 minutes

 

 

 

software requires to safely shut down.

 

 

 

 

 

 

 

 

 

 

Synchronized

0 seconds

• 0 s

• 240 s

Specify the time the UPS will wait after the

Turn-onDelay

 

 

• 60 s

• 300 s

return of utility power before start up, (to avoid

 

 

 

• 120 s

• 360 s

branch circuit overload).

 

 

 

 

• 180 s

• 420 s

 

 

 

 

 

 

 

 

 

High Transfer Point

120

V models:

• 127 VAC

• 133 VAC

To avoid unnecessary use of the battery where

 

127

VAC

• 130 VAC

• 136 VAC

utility voltage is chronically high, set the high

 

 

 

 

 

transfer point higher if the connected

 

230

V models:

• 253 VAC

• 261 VAC

equipment can tolerate this condition.

 

 

 

 

 

253

VAC

• 257 VAC

• 265 VAC

 

 

 

 

 

 

 

 

 

Low Transfer Point

120

V models:

• 97 VAC

• 103 VAC

To avoid unnecessary use of the battery where

 

106

VAC

• 100 VAC

• 106 VAC

utility voltage is chronically low, set the low

 

 

 

 

 

transfer point lower if the connected equipment

 

230

V models:

• 196 VAC

• 204 VAC

can tolerate this condition.

 

 

 

 

 

 

208 VAC

• 200 VAC

• 208 VAC

 

 

 

 

 

 

 

 

 

Output Voltage

 

 

 

 

230 V models only: Sets the output voltage of

230 V models

230

VAC

• 220 VAC

• 240 VAC

the UPS.

 

 

 

 

 

 

 

 

 

 

10

Smart-UPSXL 2200/3000 VA 120/230 VAC 3U Rack Mount User Manual