APC Smart-UPS® RT

8000/10000 VA 200-240VAC

Tower/Rack-Mount6U

Uninterruptible Power Supply

990-2689C04/2006

Introduction

The APC Smart-UPS®RT is ahigh-performance,uninterruptible power supply (UPS) that provides protection for electronic equipment from utility power blackouts, brownouts, sags and surges. The UPS filters small utility line fluctuations and isolates electronic equipment from large disturbances by internally disconnecting from utility line power. The UPS provides continuous power from the internal battery until utility power returns to safe levels or the battery is fully discharged.

INSTALLATION

Read the safety information sheet before installation.

Unpacking

Inspect the UPS upon receipt. Notify the carrier

Literature kit containing:

and dealer if there is damage.

 

XLT/XLTW models only: Software CD

The packaging is recyclable; save it for reuse or

 

Smart-UPSUser Manuals CD

dispose of it properly.

XLI model only: Six output power cords

Check the package contents:

 

Serial cable

UPS (with batteries disconnected)

Product documentation, safety and

Two front bezels

 

warranty information

 

 

Network Management Card

 

 

documentation

Removing the Batteries

The unit is heavy. To lighten the unit, remove the batteries. Refer to the unpacking instructions on the carton in which the unit is shipped.

Specifications

TEMPERATURE

32° to 104° F (0° to 40° C)

This unit is intended for

OPERATING

indoor use only. Select a

STORAGE

5° to 113° F(-15to 45° C) charge UPS battery every six months

location sturdy enough to

 

 

handle the weight.

MAXIMUM

 

 

Do not operate the UPS where

ELEVATION

 

OPERATING

10,000 ft (3,000 m)

there is excessive dust or the

STORAGE

50,000 ft (15,000 m)

temperature and humidity are

 

 

outside the specified limits.

HUMIDITY

0% to 95% relative humidity, non-condensing

Ensure the air vents on the

 

 

 

 

front and rear of the UPS

 

 

are not blocked.

 

 

 

WEIGHT

244 lbs (111 kg)

 

UPS

 

UPS WITH

284 lbs (129 kg)

 

PACKAGING

 

 

1

Hardwiring

Wiring must be performed by a qualified electrician.

1.Install a utility circuit breaker in accordance with local electrical codes (see tables below) for input wiring.

2.Switch the UPS input circuit breaker (see A) and utility circuit breakers OFF.

3.Remove the access panel (see B).

4.Remove circular knockouts.

5.Run wires through access panel to terminal blocks. Wire to ground block first. Adhere to all national and local electrical codes. (See tables and graphics.)

6.Use appropriate glands to achieve strain-reliefon the hardwired input and output power cables.

XLT, XLJ, AND XLTW MODELS

Input Connection

 

 

 

 

 

 

 

 

 

 

 

 

 

Output Connection (optional)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Wire to L1, L2, and

 

 

.

 

 

 

 

 

 

 

 

 

Wire to L1A, L2A, and

 

 

 

.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

System

 

 

Wiring

 

 

 

Voltage

Current

 

External Input Circuit

 

Wire Size

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Full Load

 

Breaker (typical)

 

(typical)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(Nominal)

 

 

 

 

 

 

 

 

 

SURT8000XLJ,

 

 

Input &

 

 

 

200/208/220/240 V

40 A

 

 

50 A / 2-pole

 

10mm2

SURT8000XLT,

 

 

Output

 

 

 

 

 

 

 

 

 

 

 

for Input Wiring only

 

#8 AWG

SURT8000XLTW

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SURT10000XLJ,

 

 

Input &

 

 

 

200/208/220/240 V

XLJ-50A

 

60 A or 63 A / 2-pole

 

16mm2

SURT10000XLT,

 

 

Output

 

 

 

 

 

 

 

XLT-48A

 

for Input Wiring only

 

#6 AWG

SURT10000XLTW

 

 

 

 

 

 

 

 

 

 

 

 

XLTW-48A

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

XLI MODELS

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Input Connections

 

 

 

 

 

 

 

 

 

 

 

 

 

Output Connection (optional)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Single-Phase:Wire to L1, N, and

 

 

.

 

 

 

 

Wire to L1A, N1, and

 

 

 

.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Three-Phase:Wire to L1, L2, L3, N, and

 

 

.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

System

 

Wiring

 

Number

 

Voltage

 

Current

 

 

 

External Input

 

Wire Size

 

 

 

 

 

 

 

of

 

 

 

 

Full Load

 

 

 

Circuit Breaker

 

(typical)

 

 

 

 

 

 

 

Phases

 

 

 

 

(Nominal)

 

 

 

(typical)

 

 

SURT8000XLI

 

Input

 

1

 

 

 

 

220/230/240 V

 

40 A

 

 

 

50 A / 2-pole

 

10mm2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Input

 

3+

 

 

 

380/400/415 V

 

15

A / phase when

 

 

 

50 A / 4-pole

 

10mm2

 

 

 

 

 

 

 

Neutral

 

 

 

 

online

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

40

A on L1 in bypass

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Output

 

1

 

 

 

 

220/230/240 V

 

40

A

 

 

 

(not required)

 

10mm2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SURT10000XLI

 

Input

 

1

 

 

 

 

220/230/240 V

 

50 A

 

 

 

63 A / 2-pole

 

16mm2

 

 

Input

 

3+

 

 

 

380/400/415 V

 

18

A / phase when

 

 

 

63 A / 4-pole

 

16mm2

 

 

 

 

 

 

 

Neutral

 

 

 

 

online

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

50

A on L1 in bypass

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Output

 

1

 

 

 

 

220/230/240 V

 

50

A

 

 

 

(not required)

 

16mm2

2

7.XLI model only: Forthree-phaseinput, set the Input Phase Selector switch (seeC) to ‘3’. Forsingle-phaseinput, leave switch in default position of ‘1’.

XLT/XLJ/XLTW MODELS

OUTPUT

L1A

L2A

INPUT

L1

L2

A B

XLI MODEL

A

8.Switch the circuit breakers ON.

9.Check line voltages.

10.Replace the access panel.

3

OUTPUT

L1A

N1

INPUT

L1

L2

L3

N

C

B

Installing and Connecting the Batteries and Attaching the Front Bezel

n

o

 

 

 

 

 

 

 

 

 

p

q

 

 

 

 

r

s

 

 

 

 

 

 

 

 

 

4

CONNECTINGPOWER ANDEQUIPMENT TO THEUPS

1.Hardwire the UPS (see Hardwiring).

2.Connect equipment to the UPS (cables not included for XLT/XLJ/XLTW models).

3.Turn on all connected equipment. To use the UPS as a master on/off switch, be sure that all connected equipment is switched ON.

4.Press the button on the front panel to power up the UPS.

The battery charges to 90% capacity during the first three hours of normal operation. Do not expect full battery run capability during this initial charge period.

5.Configure the Network Management Card (optional).

OPTIONS

Refer to the APC Web site, www.apc.com for available accessories.

External Battery Pack SURT192XLBP

Rail Kit SURTRK2

Isolation Transformer

Service Bypass Panel

CIRCUITBREAKERS

 

Input Circuit Breaker

The UPS is protected from extreme overloads when in ON position.

 

8000/10000 VA

The breaker must be on for the UPS to operate.

 

 

XLI/XLJ/XLT/XLTW

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Output Circuit Breaker

 

 

 

 

 

 

8000/10000 VA

 

 

 

XLJ/XLT/XLTW

 

 

 

 

 

 

 

 

L6-20

 

L6-30

 

 

 

 

 

250V 20A

 

250V 30A

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Output Circuit Breaker

 

 

 

8000/10000 VA XLI

 

 

 

 

 

 

 

 

 

 

IEC 320-C19

 

 

 

 

 

IEC 320-C13

16A for each

 

 

 

 

 

 

 

 

 

 

receptacle

 

 

 

 

 

10 A total

 

 

 

 

 

 

 

 

 

 

 

current from four

 

 

 

 

 

 

receptacles

 

 

 

 

 

 

5

 

BASICCONNECTORS

 

 

 

 

 

Power management software and interface kits can be used with the

Serial Port

UPS.

Use only interface kits supplied or approved by APC.

 

 

 

 

 

 

 

 

 

 

 

Connect the UPS to the network.

 

 

 

 

 

 

 

 

 

 

(Located on the Network Management Card.)

Ethernet Port

 

 

 

 

 

 

 

 

 

 

 

 

The optional Emergency Power Off (EPO) feature allows connected

 

 

 

 

 

 

 

 

 

 

loads to be immediately de-energizedfrom a remote location, without

EPO Terminal

switching to battery operation (see EPO Option).

 

 

 

 

 

 

 

 

 

 

 

 

The UPS features a transient voltage surge-suppression(TVSS) screw

 

 

 

 

 

 

 

 

 

 

for connecting the ground lead on surge suppression devices such as

 

 

 

 

 

TVSS Screw

telephone and network line protectors.

 

 

 

 

 

When connecting grounding cable, disconnect the unit from the utility

 

 

 

 

 

power outlet.

 

 

 

 

 

Optional external battery packs provide extended runtime during

 

 

 

 

 

 

 

 

 

 

power outages. These units support up to 10 external battery packs.

External Battery Pack

Refer to the APC Web site, www.apc.com for the information on the

Connectors

external battery pack, SURT192XLBP.

6

OPERATION

FRONTDISPLAYPANEL

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Indicator

 

Description

 

 

 

 

 

 

 

Online

 

The UPS is drawing utility power and performing double conversion to supply

 

 

 

 

 

 

power to connected equipment (see Troubleshooting).

 

 

 

 

 

 

 

On Battery

 

The UPS is supplying battery power to the connected equipment.

 

 

 

 

 

Bypass

 

The UPS is in bypass mode, sending utility power directly to connected equipment.

 

 

 

 

 

 

Bypass mode operation is the result of an internal UPS fault, an overload condition

 

 

 

 

 

 

 

 

 

 

 

or a user initiated command either through an accessory or the manual bypass

 

 

 

 

 

 

switch. Battery operation is not available while the UPS is in bypass mode (see

 

 

 

 

 

 

Troubleshooting).

Fault

 

The UPS detects an internal fault (see Troubleshooting).

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Overload

 

The connected loads are drawing more power than the UPS power rating (see

 

 

 

 

 

 

Troubleshooting).

 

 

 

 

Replace

 

The battery is disconnected or must be replaced (see Troubleshooting).

Battery

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Feature

 

Function

 

 

 

Power On

 

Press this button to turn on the UPS. (Read on for additional capabilities.)

 

 

 

 

 

 

 

 

 

 

 

Power Off

 

Press this button to turn off the UPS.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

7

 

 

 

 

Feature

Function

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Normal /Bypass

Manually switch connected equipment to bypass mode, so that utility power is

 

 

 

 

sent directly to connected equipment. Battery operation is not available while

 

 

 

 

 

 

 

 

the UPS is in bypass mode. (See Troubleshooting.)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Cold Start

This is not a normal condition.

 

 

 

 

 

 

 

 

 

Supply immediate battery power to the UPS and connected equipment (see

 

 

 

 

Troubleshooting). Press and hold the

 

button to power up the UPS and

 

 

 

 

 

 

 

 

 

connected equipment. The UPS will emit two beeps. During the second beep,

 

 

 

 

release the button.

 

 

 

 

 

 

 

 

Self-Test

Automatic: The UPS performs aself-testautomatically when turned on, and

 

 

 

 

every two weeks thereafter (by default). During the self-test,the UPS briefly

 

 

 

 

operates the connected equipment on battery.

 

 

 

 

 

 

Manual: Press and hold the

 

button for a few seconds to initiate the self-

 

 

 

 

 

 

 

 

 

test.

 

 

 

 

 

 

 

 

 

 

 

Diagnostic Utility

The UPS has a diagnostic feature that displays the utility voltage. Plug the UPS

 

Voltage

into the normal utility power.

 

 

 

 

 

 

 

 

 

The UPS starts a self-testas part of this procedure. Theself-testdoes not

 

 

 

 

 

 

 

 

affect the voltage display.

 

 

 

 

 

 

 

 

 

Press and hold the

 

button to view the utility voltage bar graph display.

 

 

 

 

 

 

 

 

 

After a few seconds the five-LED,Battery Charge

 

display on the right of

 

 

 

 

 

 

 

 

 

the front panel shows the utility input voltage.

 

 

 

 

 

 

Refer to the figure at left for the voltage reading (values are not listed on the

 

 

 

 

UPS).

 

 

 

 

 

 

 

 

 

 

 

The display indicates the voltage is between the displayed value on the list and

 

 

 

 

the next higher value.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

On Battery Operation

The UPS switches to battery operation automatically if the utility power fails. While running on battery, an alarm beeps four times every 30 seconds.

Press the button to silence this alarm. If the utility power does not return, the UPS continues to supply power to the connected equipment until the battery is fully discharged.

When two minutes of runtime remain the UPS emits a continuous beep. If PowerChute or the Network Management Card is not being used, files must be manually saved and the computer must be properly shut down before the UPS fully discharges the battery.

The UPS battery life differs based on usage and environment.

Refer to the APC Web site, www.apc.com for on battery runtimes.