American Power Conversion 100 VAC User Manual

Size:
584.87 Kb
Download

User’s Manual

English

APC Smart-UPS

1400 VA 2U Rack Mount

Uninterruptible Power Supply

100 Vac

990-7096,Revision 2

TABLE OFCONTENTS

ENGLISH

Chapter 1: Safety Information...................................................................

1

Conventions Used in this Manual.................................................................................................

1

Handling Safety ............................................................................................................................

1

Electrical Safety............................................................................................................................

1

Deenergizing Safety .....................................................................................................................

2

Battery Safety ...............................................................................................................................

2

Recycling of Batteries ..................................................................................................................

2

Chapter 2: Basics.......................................................................................................

3

About APC ...................................................................................................................................

3

About Your New UPS ..................................................................................................................

3

How to Contact APC ....................................................................................................................

3

Chapter 3: Installation........................................................................................

4

Unpacking.....................................................................................................................................

4

Inspection..................................................................................................................................

4

Contents ....................................................................................................................................

4

Placement..................................................................................................................................

4

How to Install Your Smart-UPS ...................................................................................................

4

Mount the UPS in the Rack.......................................................................................................

5

Connect the Battery and Attach the Front Panel Bezel.............................................................

6

Connect Power and Equipment to the UPS ..............................................................................

7

Chapter 4: Operation............................................................................................

9

Front Panel....................................................................................................................................

9

Operation...................................................................................................................................

9

Self-Test....................................................................................................................................

9

Utility Power...........................................................................................................................

10

Battery Power..........................................................................................................................

11

Rear Panel...................................................................................................................................

12

On-BatteryOperation .................................................................................................................

13

User Configuration Items ...........................................................................................................

14

990-7096,Revision 2

Chapter 5: Maintenance and Troubleshooting......................

15

Storage........................................................................................................................................

15

Storage Conditions..................................................................................................................

15

Extended Storage ....................................................................................................................

15

Replacing the Battery .................................................................................................................

15

Troubleshooting..........................................................................................................................

17

Service ........................................................................................................................................

19

Regulatory Agency Approvals ...................................................................................................

20

On-BatteryRun Time .................................................................................................................

20

CHAPTER1: SAFETYINFORMATION

This Safety Guide contains important instructions that should be followed during installation and maintenance of the APC equipment and batteries. It is intended for APC customers who setup, install, relocate, or maintain APC equipment.

Conventions Used in this Manual

This section defines the symbols used throughout this manual. Carefully read all information boxes and abide by the instructions.

The WARNING sign denotes a serious hazard. It calls attention to a procedure, practice, condition, or the like, which, if not correctly performed or adhered to, could result in injury to personnel.

The CAUTION sign denotes a hazard. It calls attention to an operating procedure, practice, or the like, which, if not correctly performed or adhered to, could result in damage to or destruction of all or part of the product.

The NOTE sign denotes important information. It calls attention to a procedure, practice, condition, or the like, which is essential to highlight.

Handling Safety

Be careful. Do not lift heavy loads without assistance.

18 – 32 kg (40 – 70 lb.)

This equipment is intended for installation in a temperature-controlledindoor area (see theSpecifications at the APC web site for exact temperature range), free of conductive contaminants.

Electrical Safety

To reduce the risk of fire, connect only to a circuit provided with a 20 A maximum branch circuit overcurrent protection in accordance with the National Electrical Code ANSI/NFPA.

Do not work alone under hazardous conditions.

Check that the power cord(s), plug(s), and sockets are in good condition.

1

990-7096Rev. 2

Deenergizing Safety

This UPS has an internal energy source (the battery), the output may be energized when the unit is not connected to an AC power outlet.

To deenergize the UPS: first press the Off button to switch the outputs off. Next disconnect the UPS from the AC power outlet, then, disconnect the battery and finally, press the ON button to ensure that the internal capacitors are discharged.

The UPS includes a protective earth conductor which carries the leakage current from the load devices (computer equipment). Total leakage current must not exceed 3.5 mA.

Use of this equipment in life support applications where failure of this equipment can reasonably be expected to cause the failure of the life support equipment or to significantly effect its safety or effectiveness is not recommended.

Battery Safety

This equipment contains potentially hazardous voltages. Do not attempt to disassemble the unit. The only exception is for battery replacement using the procedures below. Except for the battery, the unit contains no user serviceable parts. Repairs are performed only by factory trained service personnel.

Do not dispose of batteries in a fire. The batteries may explode.

Do not open or mutilate batteries. They contain an electrolyte which is toxic and harmful to the skin and eyes.

To avoid personal injury due to energy hazard, remove wrist watches and jewelry such as rings when replacing the batteries. Use tools with insulated handles.

Replace batteries with the same number and type of batteries as originally installed in the equipment.

Recycling of Batteries

Return the battery tray to APC using the package in which your replacement tray shipped. (See How to Contact APC, page 3, for details.) The battery replacement kit includes a new battery tray. See your dealer orReplacing the Battery, page 16, for information on replacement battery kits.

990-7096Rev. 2

2

CHAPTER2: BASICS

About APC

American Power Conversion Corporation (APC) is the leading national and international manufacturer of state of the art uninterruptible power supplies, redundant switches, power management software, and related equipment. APC products protect hardware, software, and data from the threat of power disturbances in business and government offices throughout the world.

About Your New UPS

This APC Uninterruptible Power Supply (UPS) is designed to prevent blackouts, brownouts, sags and surges from reaching your computer and other valuable electronic equipment. This UPS also filters out small utility line fluctuations and isolates your equipment from large disturbances by internally disconnecting from the utility line, while supplying power from its internal batteries until the utility line returns to safe levels.

The UPS is ready to be mounted in a 46.5 cm (19-inchwide) EIA/IEC rack cabinet.

How to Contact APC

Internet: http://www.apcc.com/support/contact

3

990-7096Rev. 2

CHAPTER3: INSTALLATION

Unpacking

APC has taken care to design robust packaging for your product. However, accidents and damage may occur during shipment.

Inspection

Inspect the UPS upon receipt. Notify the carrier and dealer if there is damage. The packaging is recyclable; save it for reuse or dispose of it properly.

Contents

The shipping package contains the UPS, its front panel bezel (disconnected from the unit), mounting rails, and a literature kit (containing mounting hardware and product documentation).

Placement

Install the UPS in a protected area that is free of excessive dust and has adequate air flow. Do not operate the UPS where the temperature and humidity are outside the specified limits.

Changes or modifications to this unit not expressly approved by the party responsible for compliance could void the warranty.

How to Install Your Smart-UPS

To install the UPS follow these steps:

1.Mount the UPS in the rack.

2.Connect the battery and attach the front panel bezel.

3.Connect power and the equipment to the UPS.

4.Turn on the UPS.

5.Install optional PowerChute® software (sold separately).

This section describes each step in detail.

990-7096Rev. 2

4

Mount the UPS in the Rack

Select a location with adequate air flow that is free from excessive dust. Ensure that the air vents on the front and rear of the UPS are not blocked. Allow at least 2.54 cm (1 inch) of space on both sides.

The UPS requires two people to install due to its weight.

To lighten the UPS, you may remove the batteries while you mount the unit in the rack. Refer to Replacing the Battery, page 15, for instructions on removing the batteries.

The UPS comes with standard 46.5-cm(19-inch)rack mount brackets (ears) and cleats installed and mounting rails for rack mounting included. The rails support the UPS and allow adequate air flow. There are two steps to install the UPS in a rack. This section describes each in detail.

1.Install the mounting rails in the rack (required for four-postracks only).

2.Load the UPS into the rack.

Check the rack to make sure it will not tip after moving the mounting brackets.

Install the Mounting Rails in the Rack (Four-PostRack Installation Only)

Install the mounting rails in the rack. Directions are included with the rail kit.

Load the UPS into the Rack

Due to the weight of the UPS, two people are required to install it in the rack. To lighten the UPS, you may remove the batteries while you mount it in the rack. Refer to Replacing the Battery, page 16, for instructions on how to remove the batteries.

Four-PostRacks

1. Supporting the UPS from both sides, carefully align the unit with the rails.

2. Each side of the UPS has a cleat Πthat must slide into the groove on the rail. Insert each cleat into its groove and slide the UPS into position.

3. Insert the four (4) ornamental screws

Œ

supplied with the UPS through the

 

 

mounting brackets and into the top

 

and bottom holes in the U-space.

5

990-7096Rev. 2

Two-PostRacks

 

 

 

 

1. If the rack holes are not 10-32

 

 

threaded, first attach the backing plate

 

 

supplied (870-1148)Πto the rack.

 

 

2. Support the UPS from the front and

 

 

back. Insert the four (4) ornamental

 

 

screws supplied with the UPS

 

 

through the mounting brackets and

 

 

into the top and bottom holes in the

 

 

U-spaceas shown for theFour-Post

Œ

Œ

Rack. Screw them into the threaded

 

 

holes of the backing plate.

Removing the UPS from the Rack

Due to the weight of the UPS, two people are required to remove it from the rack.

1.Remove the front panel bezel: Face the front of the UPS, and, using both hands, insert each index finger behind the lip of the curved section of the front panel bezel and pull towards you.

2.Unscrew the four ornamental screws (two screws on each mounting bracket).

3.Position one person in front of the rack and the second person either behind or on one side of the UPS for additional support.

4.Using the battery tray handle to support the front of the unit, slide the UPS partially out of the rack.

5.Supporting the UPS from the bottom or rear of the unit, slide the UPS fully out of the rack.

Connect the Battery and Attach the Front Panel Bezel

The UPS is shipped without its battery connected and the front panel bezel installed (it is packaged separately within the main box). You must connect the battery and install the plastic front panel bezel before the installation is complete.

Œ

Ž

1.Facing the front of the UPS, locate the battery cable (in the center of the unit) and remove the tape to expose the cable connector.

2.Locate the UPS battery connector Œ which is to the right of the battery trayand recessed. Connect the battery cable connector to the UPS connector. Press firmly to ensure that the connection is tight. You will hear a “snap” when the connector is properly seated. Also, as a visual indication, the back of the connector should be recessed (~0.64 cm) from the sheet metal

990-7096Rev. 2

6