3. Web Server Quick Guide

 

 

Item

Unit

View

 

Description

 

 

 

 

Plant

Inverter

 

 

 

 

 

and

 

 

 

 

 

 

Group

 

 

 

 

Overall plant sta-

-

x

 

Red: Plant PR <50%, or:

 

 

tus

 

 

 

Any inverter in the network

 

 

 

 

 

 

- in fail safe mode, or

 

 

 

 

 

 

- missing from the scan list, no contact with the master

 

 

 

 

 

 

3

 

 

 

 

 

Yellow: Any inverter in the network

 

 

 

 

 

- with PR<70%, or

 

 

 

 

 

- in Connectingor Off gridmode

 

 

 

 

 

 

Green: Plant PR ≥ 70%, and

 

 

 

 

 

 

 

 

 

 

 

 

- all inverters with PR≥ 70%, and

 

 

 

 

 

 

- all inverters in On grid mode

 

 

 

 

 

x

Red: Inverter PR<50%, or inverter has an error

 

 

 

 

 

 

Yellow: Inverter PR between 51% and 70%, or inverter

 

 

 

 

 

 

in Connectingmode

 

 

 

 

 

 

Green: No errors, and

 

 

 

 

 

 

- inverter PR≥70%, and

 

 

 

 

 

 

- inverter in "on grid" mode

 

 

Current production

kW

x

x

Real time energy production level

 

 

Yield today

kWh

x

x

Cumulative yield for the day

 

 

Total revenue

Euro

x

x

Cumulative revenue earned since initial startup

 

 

Total CO2 saving

kg

x

x

Cumulative CO2 saved since initial startup

 

 

Performance ratio

%

x

x

Real time performance ratio

 

 

Total yield

kWh

x

x

Cumulative yield since initial startup

 

 

Power limit adjust-

%

 

x

Maximum power limit as % of nominal inverter AC output

 

 

ment

 

 

 

rating

Note:

To calculate performance ratio PR, an irradiation sensor is required, see [Setup → Calibration].

3.5. Additional Information

Refer to the Web Server User Manual to learn more about:

Inverter start-upand check of settings

Messaging

Graphs

Remote access

Web portal upload

Logging capacity and changing the logging interval

Settings backup and restore

20

8000038784_00_BAL_en / L00410565-01_02

4. Troubleshooting

4. Troubleshooting

4.1. Troubleshooting

Only trained and authorised personnel familiar with electrical systems and safety

issues may work on inverters and electrical installations.

4

Should the inverter not supply energy as expected, go through the checklist before calling service.

1.Check that the grid is properly connected to the inverter and that the mains switch is not switched off.

2.Check that there is sufficient solar radiation to generate power. UPV >250 V

3.Check for shading and loose cables/connections in the PV system.

4.Check whether the voltage of the PV modules are within the expected values. If not go to point 7.

5.Check whether the voltage values of the grid lie within the threshold values. If this is not the case please contact your public utility for technical assistance.

6.If the above-mentionedpoints are OK, wait 15 minutes to find out whether there is a permanent failure.

7.If the PV system still supplies no power to the grid, check the display for:

-PV module voltage, current and power

-grid voltage, current and power

-event text, see log area

Then call service.

In the event of a failure, the red LED will flash and the display will show an event. Refer to the table for event descriptions and recommended actions.

Event text

Description

Remedy

Grid

Grid values are out of range

Check the voltage and frequency values in the display. If values

 

 

are zero, check the circuit-breaker(fuses) and cables. If values

 

 

are outside the applied limits, request technical service from in-

 

 

staller/energy company.

PV

The PV isolation resistance is too

Make a visual inspection of all PV cables and modules. If the event

 

low

occurs frequently, request technical service.

Internal

An internal event has occurred

Make sure airflow over the heat sink is not obstructed. Wait 5 mi-

 

 

nutes. If the inverter does not reconnect (although sufficient irra-

 

 

diance is available) or the event occurs regularly, action must be

 

 

taken. Service inverter.

Fail Safe

Internal or AC installation error

Turn off both AC and DC (PV) power to the inverter. Make a visual

 

 

inspection of the PV installation, if everything is in order, wait 5

 

 

minutes and re-applyAC and DC (PV) power. If the inverter re-

 

 

sumes fail safe operation, action must be taken. Service inverter.

Table 4.1: Events

Note:

For more event descriptions, refer to the Protect PV Reference Manual in the download area at: www.aegps.com/solarinverters

8000038784_00_BAL_en / L00410565-01_02

21

5.Maintenance

5.Maintenance

5.1. Maintenance

Normally, the inverter needs no maintenance or calibration.

Ensure the heatsink at the rear of the inverter is not covered.

5

Clean the contacts of the PV load switch once per year. Perform cleaning by cycling the switch to on and off positions ten times.The PV load switch is located at the base of the inverter.

5.1.1. Cleaning the Cabinet

Clean the inverter cabinet using pressurised air, a soft cloth or a brush.

5.1.2. Cleaning the Heatsink

Clean the heatsink using pressurised air, a soft cloth or a brush.

For correct operation and long service life, ensure free air circulation

-around the heatsink at the rear of the inverter

-to the fan at the inverter base

Do not touch the heatsink during operation.

Temperature can exceed 70°C.

Note:

Do not cover the inverter.

Do not use a water hose, aggressive chemicals, cleaning solvents or strong detergents to clean the inverter.

22

8000038784_00_BAL_en / L00410565-01_02

 

 

 

 

 

Czech Republic

France & Africa

Italy

 

AEG Power Solutions

AEG Power Solutions

AEG Power Solutions spol. s r.o.

ZI 10 rue Jean Perrin

Via Trento 30

Na vlastní pude 6/1368

37173 Chambray-lès-Tours

20059 Vimercate – Milan

102 00 PRAHA 15 Hostivar

Tel:

+ 332 47 80 88 96

Tél :

+39 0 39 686 3837

Tel:

+ 420 602 316 314

Fax:

+ 332 47 80 88 38

Fax :

+39 0 39 686 3847

Fax:

+ 420 274 773 265

Email:

service.fr@aegps.com

Email:

service.it@aegps.com

Email:

service.cz@aegps.com

Germany

AEG Power Solutions

Emil-SiepmannStr.32

D-59581Warstein/Belecke

Tel:

+ 49 2902 763 100

Fax:

+ 49 2902 763 645

Email: service.de@aegps.com

United Kingdom

AEG Power Solutions Ltd.

Vision 25

Innova Park

Enfield EN3 7XY

Tel:

+44 (0) 1992 719 200

Fax:

+44 (0) 1992 702 151

Email:

service.uk@aegps.com

Spain

AEG Power Solutions, SL Parque Tecnologico de Alava C/Albert Einstein 31

01510 Minano – Alava

Tél:

+ 34 66 990 31 12

Fax:

+34 945 21 41 11

Email:

service.es@aegps.com

Netherlands

AEG Power Solutions

Weerenweg 29

1161 AH Zwanenburg

Tel:

+ 31 20 40 77 818 / 821

Tel.outside office hours

 

+ 31 20 40 77 866

Fax:

+ 31 20 40 77 801

Email:

service.nl@aegps.com

Lit. No. L00410565-01_02Rev. date2011-05-25