AEG 1000 User Manual

Size:
2.21 Mb
Download

Alarm

Possible cause

Remark/ Action

 

 

 

 

 

 

 

Input AC Under

The utility power

The uninterruptible

 

 

Voltage

voltage is below the

power supply

 

 

(Alarm #7)

minimum operating

transfers to Battery

 

 

range.

mode if supporting

 

 

Intermittent Alarm

 

 

 

load.

 

 

 

 

 

 

 

 

 

 

 

Input Under/Over

The utility power

The UPS transfers to

 

 

Frequency

frequency is out of

Battery mode if

 

 

(Alarm #8)

usable frequency

supporting load.

 

 

range.

 

 

 

Intermittent Alarm

 

 

 

 

 

 

 

 

 

 

 

 

Site Wiring Fault

An alarm triggers

Have a qualified

 

 

(Alarm #194)

when the difference

electrician correct the

 

 

between the ground

wiring problem. If the

 

 

Intermittent Alarm

 

 

and neutral voltage

uninterruptible power

 

 

 

 

 

 

>15 V.

supply is not wired

 

 

 

 

with a neutral wire,

 

 

 

 

change the

 

 

 

 

Site Fault to “disabled”

 

 

 

 

in the Settings menu.

 

 

 

 

 

 

 

Remote Emergency

The external contacts

The UPS deenergizes

 

 

Power Off

in the rear of the

the load and enters

 

EN

(Alarm #12)

uninterruptible power

Standby mode. For

 

Intermittent Alarm

supply are configured

more information, see

 

 

for remote emergency

“EPO (Emergency

 

 

 

 

 

 

power-offoperation

PowerOff)” in

 

 

 

and they are

Chapter 8.4 on pg. 57.

 

 

 

activated.

 

 

 

 

 

 

 

 

Output Overload

The load level is at

The UPS can support

 

 

(Alarm #25)

or has exceeded the

the load indefinitely at

 

 

configurable threshold

this load level.

 

 

Intermittent Alarm

 

 

limit for a Overload

The alarm clears when

 

 

 

 

 

 

condition.

 

 

 

the load drops below

 

 

 

 

5% of the set point.

 

 

 

 

 

 

 

Battery DC Over

The battery voltage

The uninterruptible

 

 

Voltage

level has exceeded

power supply turns off

 

 

(Alarm #68)

the maximum

the charger until the

 

 

allowable limits.

next power recycle.

 

 

Intermittent Alarm

 

 

 

Contact your service

 

 

 

 

 

 

 

 

representative.

 

 

 

 

 

 

 

61

Alarm

Possible cause

Remark/ Action

 

 

 

Charger Failure

A battery charger fault

The UPS turns off the

(Alarm #34)

has been detected.

charger until the next

 

power recycle.

Continuous Alarm

 

 

Contact your service

 

 

 

 

representative.

 

 

 

Output Short Circuit

The uninterruptible

The uninterruptible

(Alarm #58)

power supply has

power supply operates

detected abnormal

as a constant-current

Intermittent Alarm

low impedance that

source (4.4 x IN) and

 

 

placed on its output

shuts down after five

 

and considers it a

cycles (100ms).

 

short circuit.

 

 

 

 

Heat sink Over

The uninterruptible

Make sure that the

Temperature

power supply has

fans are spinning and

(Alarm #73)

detected that one of

that the air intake

its heat sinks has

vents on the

Intermittent Alarm

exceeded the

uninterruptible power

 

 

maximum defined

supply are not

 

operating

blocked. After the

 

temperature.

maximum

 

Possible fan failure

temperature is

 

reached, the

 

(see below).

 

uninterruptible power

 

 

 

 

supply shuts down.

 

 

 

Fan Failure

The uninterruptible

This is an alarm only.

(Alarm #193)

power supply has

Contact your service

detected that one or

representative

Continuous Alarm

more fans are not

immediately and

 

 

functioning correctly.

remove the load.

 

 

 

Fatal EEPROM Fault

There is EEPROM

Contact your service

(Alarm #53)

data corruption due

representative.

to a failed device or

 

Continuous Alarm

 

incorrect flash upgrade.

 

 

 

 

 

 

62

10 Maintenance

The PROTECT D. is constructed using modern, low-wearcomponents. Nevertheless, in order to maintain constant availability and operating reliability, it is advisable to make visual checks (of the battery and the vents in particular) at regular intervals (but at least every 6 months).

CAUTION!

Always make sure to secure the working area and carefully follow all safety instructions!

10.1Charging the battery

The battery is always charged automatically when connected to the mains power supply, regardless of the operating mode. IMPORTANT: The battery charging module must be activated (presetting, also see Chapter 7.3.6 on pg. 49ff).

The total charging time for the battery after it has been discharged for a long period of time can depend on the number of additional external battery units (see Chapter 2.3).

10.2 Maintenance checks

EN

The following maintenance work should be performed:

Activity

Frequency

Described in

Visual check

6 months

Chapter 10.2.1

Battery/ventilator check

6 months

Chap 10.2.2/10.2.3

10.2.1Visual check

When doing visual checks, be sure to check whether ...

there are any mechanical damages or foreign bodies in the system,

there is any conductive dirt or dust accumulation in the device and

dust accumulation impedes the heat input or heat dissipation.

63

CAUTION!

Before performing the next step, make sure to switch off the voltage supply to the PROTECT D.

If a large amount of dust has accumulated, the device should be carefully cleaned with dry compressed air to allow for better heat exchange.

The time intervals of the visual checks to be performed largely depend on where the devices are installed and the environmental conditions at these locations.

10.2.2Battery check

You can tell whether the batteries are getting older by making regular capacity tests. Every six months, make comparative checks with respect to the bridging time possible by, for example, simulating a power outage. The load should always show close to the same power requirements. If the battery time sinks drastically compared to the previous check, please contact our hotline (see pg. 5).

10.2.3Ventilator check

Check the ventilators regularly for dust accumulation and any noticeably irregular noises. If the vents are clogged, they must be cleaned; if the ventilator appears to be unusually loud or is not operating smoothly, please contact our hotline (see pg. 5).

10.3Battery replacement

CAUTION!

A battery can present a risk of electrical shock and can be very dangerous if handled improperly.

The following precautions should be observed before replacing the batteries:

Remove rings, watches and other metal objects.

If the battery replacement kit is damaged in anyway or shows signs of leakage, contact your dealer immediately.

Properly recycle or dispose of used batteries. Do not dispose of batteries in a fire. The batteries may explode.

64

Note:

i The UPS internal batteries are heavy. Use caution when handling the heavy batteries.

The internal batteries are located behind the UPS front cover (behind the LCD control panel). The internal batteries are packaged together as one unit for easier handling.

To replace the batteries in the UPS (use Protect D.1000 picture for reference):

1. Remove the four M6x16 pan-headscrews, see Figure 21.

EN

Fig. 21: Preparatory measures for battery replacement

2.Then unscrew the two centered screws in front panel (2) using a suitable cross-slotscrewdriver (recommended: Phillips PH1).

3.Now reach behind the front panel on the right and the left and pull the UPS approx. 70 mm forward out of the rack (3) so that the silver sticker on the top of the UPS with the safety precautions becomes visible (refer as well to the following fig. 22)

4.Now slide the front panel a few millimeters sideways to the left (4). The lock will be released …

5.… and you can rotate the entire front panel upwards (5). Make sure not to cut the flexible ribbon cable to the LCD display!

Do not use excessive force.

65

This part stays in the rack!

5

4

32

Fig. 22: Removing the UPS front cover

6.Disconnect the internal battery connector and EBM battery connector. If the EBM cable is not connected to an EBM, unclip the EBM cable and move it to the left out of the way, see Figure 23.

7.Remove and retain the two screws on the battery cover plate, see Figure 23.

Fig. 23: Disconnecting the UPS internal batteries; Removal of the battery cover plate

8.Grasp an edge of the battery cover plate and pull it out gently. Remove and retain the battery cover plate. Figure 23 shows the location of the battery cover plate.

Carefully pull the handle on the battery tray and slide the battery package slowly out onto a flat, stable surface; use two hands to support the battery package, see Figure 24. Pay attention to the weight of the battery system, especially at the more powerful models.

66

Fig. 24: Pull out the battery pack

Note:

i Verify that the replacement batteries have the same rating as the batteries being replaced.

9.Slide the new battery package into the UPS unit. Push the battery package in firmly.

10.Replace the battery cover plate onto the screw mounts, threading the battery connector through the access slot.

11.Now connect the internal battery system by connecting the

two battery connectors (each consisting of a red and a black

EN

connector) with each other: red in red, black in black.

 

Make sure to press the connectors quickly and

 

firmly into one another (red in red, black in black).

 

 

If you see a small electric arc while doing this, this

 

is no cause for concern.

 

If the EBM cable isn´t connected to an EBM, clip the EBM

 

cable back into its holder on the battery cover plate. See

 

Figure 23.

 

12.Finally close the front panel again slowly and carefully following the directions in reversed order. Make sure that you do not pinch any wires. As the last step, don’t forget to lock the front panel into place using the two screws located in the middle. Then push the UPS completely back into the rack and fasten the UPS on the side using the four M6x16 screws that come with it.

67

i

Replace the EBM battery

If the UPS will be operated with additional external

battery packs we recommend from technical point of

 

view to replace all battery systems at the same time.

 

Replace the EBM battery system same as the UPS

 

replacement, ensure a proper connection.

Disposal of waste batteries (applicable in the European Union and other European countries with separate collection systems)

This symbol on the battery or on the packaging indicates that the battery provided with this product shall not be treated as household waste. On certain batteries this symbol might be used in combination with a chemical symbol. The chemical symbol “Pb” (lead) is added if the battery contains more than 0.4% lead.

By ensuring these batteries are disposed of correctly, you will help prevent potentially negative consequences for the environment and human health which could otherwise be caused by inappropriate waste handling of the battery. The recycling of the materials will help to conserve natural resources.

In case of products that for safety, performance or data integrity reasons require a permanent connection with an incorporated battery, this battery should be replaced by qualified service staff only.

To ensure that the battery will be treated properly, hand over the product at end-of-lifeto the applicable collection point for the recycling of electrical and electronic equipment.

For more detailed information about recycling of this battery, please contact your local Civic Office, your household waste disposal service or the shop where you purchased the product.

68

11 Storage, Dismantling and Disposal

11.1Storage

Long storage times without occasionally recharging or discharging can lead to permanent damage to the battery.

If the battery is stored at room temperature (20°C to 30°C), there will be a spontaneous self-dischargedue to inner reactions of 3 to 6% a month. Please avoid storage at temperatures above room temperature. High storage temperature will lead to the increasedself-dischargeof the battery.

To retain full capacity and service life, batteries stored at room temperature should be recharged every six months.

 

i

Before being put into storage, the PROTECT D.

 

 

should be connected to the power supply to ensure

 

 

that the

battery is

completely charged. For

the

 

 

minimum

charging

time, please refer to

the

 

 

 

information in Chapter 10.1.

 

 

11.2

Dismantling

 

 

 

 

 

 

 

EN

 

To de-installthe UPS, perform the same steps as for

the

 

installation but in reversed order.

 

 

 

11.3

Disposal

 

 

 

 

 

 

 

 

 

 

 

In the interests of environmental protection and recycling, please

 

 

dispose of the individual parts of the device as specified and

 

according to the legal regulations when its service life has ended. Please remember that any violation of these regulations can be interpreted as a breach of the law.

Disposal of old electrical & electronic equipment (applicable in the European Union and other European countries with separate collection systems)

This symbol on the product or on ist packaging indicates that this product shall not be treated as household waste. Instead it shall be handled over the applicable collection point for the recycling of electrical and electronic equipment.

69

By ensuring this product is disposed of correctly, you will help prevent potential negative consequences fort he environment and human health, which could otherwise be caused by inappropriate waste handling of this product. The recycling of materials will help to conserve natural resources.

For more detailed information about recycling of this product, please contact your local Civic Office, your household waste disposal service or the shop where you purchased the product.

70