AEG-Electrolux 125D-W User Manual

Size:
212.14 Kb
Download

125 D

ExtractorHood

InstallationandOperatingInstructions

Contents

Introduction

3

Extraction mode

3

 

 

Recirculation mode

4

 

 

Electrical connection for UK

5

Technical details

6

Installation

7

Safety warnings for kitchen unit installer

7

 

 

Wall mounting

9

 

 

Hood operation

11

Safety warnings for user

12

 

 

Maintenance and care

13

Opening the grid

13

 

 

Grease filter

13

 

 

Carbon filter

14

 

 

Changing the light bulb

15

 

 

Cleaning

15

Accessories

16

What to do if

17

Service & Spare Parts

18

Printed on recycled paper.

AEG – putting words into action.

2

Introduction

Extraction mode

The hood is supplied as an extractor unit and can also be used as a filtered function (recirculation) by fitting activated carbon filters (availableasanaccessory).

The unit features two outlet holes, one of which A is located on the top of the unit while the other B is located on the rear.

To connect up the hose, you should first fit the bayonet-mountingflange C (Ø100-120mm) on the outlet required (if using the top outlet, fix the flange in place using the screw supplied as shown in

Fig. 1).

Close off the unused hole using the bayonet fitting caps D.

 

D

 

A

 

B

1

C

C

A

B

D

● Important! To use the back hole B, remove switch F from the top hole. — Fig 2.

2

3

● Move the lever L to position A — Fig. 3.

L

3

L

When connecting the hood using a telescopic wall pipe, you should use a non-inflammableoutlet hose ABS 120 (120 mm Ø)

E-Nr.942 118 611 from our range of special accessories.

Recirculation mode

The air is filtered and recirculated through the front grid.

Move the lever L to position F — Fig. 3.

You will need an original KFF activated carbon filter. (See accessories).

Summer/Winter Hood Conversion

To avoid excessive heat loss during the winter months, we recommend that the hood be converted from extraction mode to recirculation.

In order to convert the hood, a charcoal filter (available as an accessory) is required. Follow the instructions for operating the hood to recycle air.

When the temperature outdoors becomes more mild (spring), the filter can be removed and the hood converted once again to extraction. Please consult the assembly instructions for operating the hood in extraction mode.

4

Electrical connection for the UK

Appliances with 2 wires

WARNING: DOUBLE INSULATED - DO NOT EARTH

The appliance must be connected to fixed wiring with a double pole switched fused spur outlet with or without pilot lamp.

We strongly recommend the appliance to be connected only by a qualified electrician who is a member of the NICEIC who will complywiththeIEEandanylocalregulations.

NOTE:

Theterminology“DOUBLEPOLE”meansthatboththeliveandthe neutralsuppliesareswitchedanddisconnectedatthesametime. The terminations labelled SUPPLY are for the connection for the internalhousewiringandtheterminationslabelledLOADareforthe appliance.

IMPORTANT

The wires of the mains lead supplied with this appliance are coloured in accordance with the following code:

Blue-Neutral

Brown-Live

As the colours of the flexible cord of this appliance may not correspond with the coloured markings identifying the terminals in the plug, proceed as follows: The wire which is coloured brown must be connected to the terminal which is marked with the letter L or coloured red.

The wire which is coloured blue must be connected to the terminal which is marked with the letter N or coloured black.

 

BLUE

BROWN

 

(NEUTRAL)

(LIVE)

 

 

L

 

 

LOAD

 

N

L

 

SUPPLY

 

LOAD

FUSE

ON

DP 13A, 250V

 

 

 

N SUPPLY

5

Technical details

Dimensions

Height x Width x Depth (in cm)

69-113x 59.9 x 51

 

 

 

 

Weight

 

Net:

11,5 kg

Gross:

12,6 kg

 

 

Maximum absorbed power:

205 W

Motor absorption

1 x 125 W

 

 

Lighting:

2 x 40 W

 

 

Length of the cable:

110 cm

 

Fan powers (speed), speed in compliance with DIN 44971

Extraction mode

 

1

115 m3/h

2

152 m3/h

3

210 m3/h

Recirculation mode

 

1

110 m3/h

2

129 m3/h

3

145 m3/h

Flange:100-120mm Ø

 

 

 

6

Installation

Safety warnings for kitchen unit installer

When used as an extractor unit, the hood must be fitted with a 100 or120mm diameter hose.

If the fumes must be forced out through the wall, you must obtain a MKZ sizable wall exhaust pipe (with external exhaust and air intake), E-Nr.-610 899 004 (Ø 120 mm) which is one of our optional parts.

When installing the hood, make sure you respect the following minimum distance from the top edge of the cooking hob/ring surfaces:

Electrical

650 mm

Gas hob

700 mm

Electric cooker

685 mm

Gas cooker

787 mm

The hood cannot be connected to flues of other appliances that run on energy sources other than electricity.

The air outlet must not be connected to chimney flues or combustion gas ducts. The air outlet must under no circumstances be connected to ventilation ducts for rooms in which fuel-burningappliances are installed.

It is advisable to apply for authorization from the relevant controlling authority when connecting the outlet to an unused chimney flue or combustion gas duct.

The air outlet installation must comply with the regulations laid down by the relevant authorities.

When the unit is used in its extractor version, a sufficiently large ventilation hole must be provided, with dimensions that are approximately the same as the outlet hole.

National and regional building regulations impose a number of restrictions on using hoods and fuel-burningappliances connected to a chimney, such as coal or oilroom-heatersand gas fires, in the same room.

7

Regulations on fuel-burningsystems specify a maximum depression of 0.04 bar in such rooms.

Hoods can only be used safely with appliances connected to a chimney if the room and/or flat (air/environment combination) is ventilated from outside using a suitable ventilation hole approximately 500-600cm2 to avoid the possibility of a depression being created during operation of the hood.

If you have any doubts, contact the relevant controlling authority or building inspector’s office.

Since the rule for rooms with fuel burning appliances is “outlet hole of the same size as the ventilation hole”, a hole of 500-600cm2, which is to say a larger hole, could reduce the performance of the extractor hood.

If the hood is used in its filtering function, it will operate simply and safely in the above conditions without the need for any of the aforementioned measures.

When the hood is used in its extractor function, the following rules must be followed to obtain optimal operation:

short and straight outlet hose

keep bends in outlet hose to a minimum

never install the hoses with an acute angle, they must

always follow a gentle curve only

— keep the hose as large as possible (120 mm Ø min.).

Failure to observe these basic rules will drastically reduce the performance and increase the noise levels of the extractor hood.

8

Wall mounting

Fix the drilling template to the wall.

Make 3 Ø 8mm holes in the wall 2 at points I, 1 as desired at points L.

Insert the three Ø 8mm expansion plugs into the wall.

Insert 2 5x45 screws at points I but do not tighten them completely.

Adjust the unit so that it is positioned at a right angle to the wall by turning the two support screws G.

Fit the hood into holes I, tighten the 2 screws.

From inside the hood, insert the third 5x45 screw into hole L. —

Fig. 4.

4

Measure the height between the upper side of the body of the cooker hood and the ceiling (fig. 5).

5

9

Set the chimney according to the measured height and stop its run with the two fixing screws 2,9x6,5 mm supplied (fig. 6).

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

7

6

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Fix the chimney to the aesthetic top with two screws 2,9x6,5 mm supplied (fig. 7).

From the inside of the hood, fix the aesthetic top with four screws M3x6 supplied (Two each side)(fig. 8).

Fix the upper bracket to the wall, close to the ceiling, perpendicularly to the outlet hole of the hood with 2 screws 5x45 mm (fig. 8).

Fix the chimney to the bracket with two screws 2,9x6,5 mm (fig. 8).

8

10