TOTAL ACCESS 4303 PLUS DC POWER SUPPLY

JOBAID

61202335L1-22A

0401

DC SUPPLY

CLEI: SLPOCDBC_ _

DC SUPPLY

PLUS

1202335L1

POWER

TEMP

#61202335L1-22A#

FRONT PANEL LEDs

POWER

Off

Both –48VDC fuses blown, power not supplied to the shelf,

 

 

or incorrect polarity on the voltage supplied to the shelf

 

Green

Power supplied is the correct voltage and polarity; backplane

 

 

and hot insertion voltages correct

 

Amber

–48VDC input and hot insertion voltage present; no back-

 

 

plane voltage

 

Red

–48VDC input present; no backplane voltage and no hot

 

 

insertion voltage

TEMP

Off

Normal

 

Red

Over-temperaturecondition

DESCRIPTION

The Total Access® 4303Plus DC Power Supply is a removable assembly that provides the voltages necessary for proper system operation. The unit features LEDs for overtemperature and DC output, an input fuse, and the ability to behot-swappedwhen used with another DC supply in the same chassis. The supply interfaces to the Total Access backplane through a48-pinconnector. The unit accepts one or two–48VDC inputs from the backplane and supplies–48VDC fused output for use with external input logic, +5 VDC as hot insertion bias voltage for modules, and +2.1 VDC for backplane termination. In addition, the Total Access 4303Plus DC Supply provides alarm relay ouputs when installed in slotPS-A.

The following features are supported on the Total Access 4303 Plus DC Power Supply:

Thermal limit indicator with open collector output

DC status indicator on the 2.1 and 5 volt outputs with open collector output

Short circuit protection

Compatible with existing Total Access DC Power Supplies (P/N 1200335L1)

SPECIFICATIONS

Specifications

Input Voltage

–42VDC to–56VDC

Operating Temperature

–40°Cto +65°C

Storage Temperature

–40°Cto +85°C

Relative Humidity

Up to 95% noncondensing

Over Temperature Indication

90°C ±5%

–48VDC Short Circuit Protection

Fused 1-ampslow blow

Backplane Voltage Short Circuit Protection

Self-mending

Compliance

FCC Part 15, UL 60950, NEBS Level III,

 

GR-1089-CORE

ALARM RELAYS

There are eight alarm relays that provide normally open or normally closed contacts for each of the following alarms:

Visual Critical

Visual Major

Visual Minor

Audible Critical

Audible Major

Audible Minor

Auxiliary 1

Auxiliary 2

POWER SUPPLY 48 PIN CONNECTOR PINOUT

Pin #

Row A Signal

Row B Signal

Row C Signal

1

AUD_CRIT_NO

AUD_CRIT_COM

AUD_CRIT_NC

2

AUD_MAJ_NO

AUD_MAJ_COM

AUD_MAJ_NC

3

AUD_MIN_NO

AUD_MIN_COM

AUD_MIN_NC

4

VIS_CRIT_NO

VIS_CRIT_COM

VIS_CRIT_NC

5

VIS_MAJ_NO

VIS_MAJ_COM

VIS_MAJ_NC

6

VIS_MIN_NO

VIS_MIN_COM

VIS_MIN_NC

7

AUX1_RLY_NO

AUX1_RLY_COM

AUX1_RLY_NC

8

AUX2_RLY_NO

AUX2_RLY_COM

AUX2_RLY_NC

9

–48V_A

PS_OK

PS_TEMP

10

–48V_B

2.1V

PS_PRESENT

11

2.1V

2.1V

2.1V

12

–48V_AB_RTN

2.1V

VCC

13

GND

GND

GND

14

GND

GND

PSRLY_CLK

15

GND

PSRLY_LOAD

PSRLY_DATAIN

16

FR_GND

–48V

PSRLY_DATAOUT

C A U T I O N !

SUBJECT TO ELECTROSTATIC DAMAGE OR DECREASE IN RELIABILITY.

HANDLING PRECAUTIONS REQUIRED.

TOTAL ACCESS 4303 PLUS DC POWER SUPPLY

PRICING AND AVAILABILITY 800.827.0807 TECHNICAL SUPPORT 800.726.8663 RETURN FOR REPAIR 256.963.8722 www.adtran.com 61202335L1-22A

TURNUP STEPS

To install the Total Access 4303 Plus DC Power Supply, perform the following steps:

1

After unpacking the Total Access 4303 Plus DC Power Supply, inspect it for damage. If damage is

2

found, file a claim with the carrier and then contact ADTRAN® Customer Service.

Pull the ejector tab on the bottom of the Total Access 4303 Plus DC Power Supply into the down

 

position.

3

Hold the Total Access 4303 Plus DC Power Supply by the front panel while supporting the bottom

 

edge of the module and align the module edge with the guide groove for slot PS-A orPS-B in the

 

chassis. If using only one Total Access Plus DC Power Supply module, insert the module in slot

 

PS-A in order to use the alarm relay outputs.

4

Gently but firmly push the module into the selected slot. Simultaneous thumb pressure at the top

 

(above the POWER LED) and at the bottom (below the electrostatic caution symbol) of the module

 

will ensure a good seat of the module pins into the backplane connector.

5

Apply power to the shelf and verify that the POWER LED is green. If thePOWER LED does not

 

illuminate, disconnect power, and verify polarity.

6 Push the ejector tab up and closed against the module front panel.

To verify one or both –48VDC supply voltages, use the SCU terminal and navigate to the following path:

System Status/System Alarms/–48VBus

COMPLIANCE

This product is NRTL listed to the applicable UL standards. The Total Access 4303 Plus DC Power

Supply is intended for installation in a type “B” or “E” enclosure in a Restricted Access Only area. The

Total Access 4303 shelf Frame Ground terminal must be connected to an earth ground to ensure that the front panel of the Total Access 4303 Plus DC Power Supply is properly grounded via the backplane connector.

Code

Input

Output

Power Code (PC)

F

C

Telecommunication Code (TC)

X

Installation Code (IC)

A

This device complies with Part 15 of the FCC rules. Operation is subject to the following two conditions: (1) This device may not cause harmful interference, and (2) this device must accept any interference received, including interference that may cause undesired operation.

Changes or modifications not expressly approved by ADTRAN could void the user’s authority to operate this equipment.

WARRANTY

ADTRAN will replace or repair this product within the warranty period if it does not meet its published specifications or fails while in service. Warranty information can be found at www.adtran.com/warranty. U.S. and Canada customer Faxback: 877-457-5007,Document 414.